Plan Review Details - Permit 06091064
Plan Review Stops For Permit 06091064
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-04-01 Cont ID  
Sent By lmartine Date 2008-04-01 Time 18:16 Rev Time 0.00
Received By lmartine Date 2008-04-01 Time 18:16 Sent To  
Notes
2008-04-01 18:17:38REVISION TO REPAIR ROOF AND SIDINGOKLM

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-02-01 Cont ID  
Sent By lmartine Date 2008-02-01 Time 13:31 Rev Time 0.00
Received By lmartine Date 2008-02-01 Time 13:31 Sent To  
Notes
2008-02-01 13:33:11REVISION FOR REAR STEPS AND FLOOR CHANGE AT LAUNDRY
 AREA OKLM

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-07-25 Cont ID  
Sent By lmartine Date 2007-07-25 Time 14:35 Rev Time 0.00
Received By lmartine Date 2007-07-25 Time 14:35 Sent To  
Notes
2007-07-25 14:36:07REVISION FOR FOUNDATION APPROVED

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-04-13 Cont ID  
Sent By lmartine Date 2007-04-13 Time 19:01 Rev Time 0.00
Received By lmartine Date 2007-04-13 Time 19:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-24 Cont ID  
Sent By alange Date 2006-10-24 Time 13:06 Rev Time 0.00
Received By alange Date 2006-10-24 Time 13:06 Sent To  
Notes
2006-10-24 13:11:27DENIED
  
  
 1.SUBMIT TWO ORIGINAL SIGNED AND SEALED SURVEYS.FS
 472.025
  
 2.SHOW THE TYPE OF LAP SIDING USED.
  
 3.SHOW ROOF SHEATHING NAILING SCHEDULE.FBC 2304.9.1
 TABLE 31
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS PER 2004 FBC.
  
 5.DOOR STATE PRODUCT APPROVAL MISSING EVALUATION
 REPORT.ROOF PRODUCT APPROVAL MISSING STATE PRODUCT
 APPROVAL.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE FOLLOWING STATE
 APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL SHEETS THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM THE STATE. IF
 THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT AN
 APPLICATION FOR LOCAL PRODUCT APPROVAL OR SITE SPECIFIC
 FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 6.THOSE PRODUCT APPROVALS WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.WPB AMENDMENT TO FBC 106.3.3.
  
  
 7.SUBMIT TWO SETS OF TRUSS DRAWINGS FOR REVIEW PER
 2004 FBC R-802.10.1TRUSS DRAWING REQUIRED TO BE
 APPROVED PRIOR TO INSTALLATION.
  
 8.A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR
 A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.SHOW HOW PLANS
 WILL COMPLY WITH THE SECTION(S) SELECTED.2004 FBC
 EXISTING BUILDING 301.5
  
 9.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHESWITHIN THE FIRST 10 FEET.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. SUBMIT ONE
 COPY OF OLD PAGES FOR REFERENCE . A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DEPARTMENT
 561-805-6672
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-03-20 Cont ID  
Sent By dpalmer Date 2008-03-20 Time 08:49 Rev Time 0.00
Received By dpalmer Date 2008-03-20 Time 08:49 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-03-07 Cont ID  
Sent By dpalmer Date 2008-03-07 Time 12:25 Rev Time 0.00
Received By dpalmer Date 2008-03-07 Time 12:25 Sent To PC
Notes
2008-03-07 12:26:09** DENIED REVIEWFOR REVISION **
  
 ** PLEASE SEE SEVERAL ITEMS FROM ORIGINAL *PROVISO*
 GIVEN ON 5/8/07 HAVE NOT BEEN ADDRESSED.
  
 1) NOTE: PLEASE SEE MISSING REQUIRED FOOTER STEEL AS
 PART OF THE GROUNDING ELECTRODE SYSTEM.
 250.50
  
 2) NOTE: PLEASE SEE MISSING REFLECTED CODES TO BE
 STATED ON PLANS.
 2005 NFPA-70
 2004 FBC W/2006 REVISIONS
 2002 NFPA-72
  
 3) NOTE: PLEASE SEE THE CIRCUITING FOR DINING ROOM
 RECEPTACLES ARE STILL SHOWING #14 AWG AND 15AMP
 BREAKERS WHEN THE CODE SPECIFICALLY REQUIRE THE MINIMUM
 OF 20AMP AND #12 AWG.
 THIS WAS REDLINED ON PREVIOUS PLANS ISSUED FOR PERMIT
 AND STILL HAS NOT BEEN CHANGED.
  
 4) NOTE: PLEASE SEE THE LOADS WHICH ARE REQUIRED TO BE
 FIGURED INTO LOAD CALCULATIONS FOR DINING ROOM CIRCUITS
 SHALL BE PER 220.52, 210.11C1 AND 210.52B1
 ** MINIMUM 1500VA FOR EACH AND THIS LOAD SHALL BE IN
 ADDITION TO ANY OTHER SMALL APPLIANCE CIRCUITS.
 ON PREVIOUS REVIEW AND REDLINED ON PLANS WITH
 PROVISO*.
  
 5) NOTE: PLEASE SEE THE REFRIGERATOR CIRCUIT WHICH
 STILL SHOWS #14 AWG WITH 20AMP BREAKER WHICH IS NOT
 PERMITTED.
 240.4, 310.16 ETC
 ** NOTED ON PREVIOUS REVIEW AND REDLINED ON PLANS ALONG
 WITH PROVISO.
  
 6) NOTE: PLEASE SHOW THE LOCATION OF ALL SERVICE
 EQUIPMENT ON PLANS MEETING 110.26, 240.24 PLEASE
 INDICATE THE EXISTING MAIN AS PART OF THE SERVICE. THE
 LOAD CALCULATIONS STATE *PROPOSED SERVICE* YET THE
 RISER SHOWS *EXISTING*?
 FOR EXAMPLE: PLEASE SEE THE SERVICE PANEL OUTSIDE IS
 SHOWN DIRECTLY BEHIND THE CONDENSING UNIT WHICH DOES
 NOT MEET 110.26 AND ONE OR THE TWO ARE REQUIRED TO
 MOVE.
  
 7) NOTE: PLANS APPEAR TO BE MISSING A GFI RECEPTACLE
 ALONG KITCHEN COUNTER SPACE WITHIN 2FT OF THE END PER
 210.52C1.
 PLEASE VERIFY AND ADJUST ON PLANS. BASED ON SCALE SHOWN
 THIS IS MISSING.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-05-08 Cont ID  
Sent By dpalmer Date 2007-05-08 Time 14:31 Rev Time 0.00
Received By dpalmer Date 2007-05-07 Time 17:08 Sent To PC
Notes
2007-05-08 14:31:34*** PROVISO/REVISION ***
  
 ** IMPORTANT**
 THE FOLLOWING ITEMS MUST BE REVISED AND ADDRESSED ALONG
 WITH ANY OTHER CHANGES BEFORE A*ANY* ROUGH ELECTRICAL
 INSPECTION.
 A *HOLD* WILL BE PLACED ON THE ELECTRICAL SUB-PERMIT
 FOR INSPECTIONS.
  
 1) NOTE: PLEASE SEE THE DINING ROOM/BREAKFAST AREA
 LOADS OF 1500 VA ON PANEL SCHEDULE ARE NOT FIGURED INTO
 THE LOAD CALCULATIONS PER 210.11C1, 210.52B1, 220.16
 PLEASE SEE THE OCP AND AWG IS SHOWN AS 15AMP AND #14 ON
 ONE OF THE CIRCUITS WHICH REQUIRES 20AMP AND #12.
 PLEASE REVISE LOAD CALCULATIONS, PANEL SCHEDULE, OCP
 AND AWG.
  
 2) NOTE: PLEASE INDICATE THE FOLLOWING CODES ON PLANS
 AS REQUESTED ON PREVIOUS REVIEW AS FOLLOWS:
 2002 NFPA-70
 2002 NFPA-72
  
 3) NOTE: PLEASE SEE THE LOAD ON THE PANEL SCHEDULE FOR
 THE WATER HEATER IS SHOWN LARGER THAN THE LOAD ON THE
 LOAD CALCULATIONS.
 THE OCP IS BASED ON THE 125% OF THE NAMEPLATE LOAD AND
 THE LOAD FIGURED IN FOR THE SERVICE CALCULATIONS IS
 BASED ON THE 125%.IF THE NAMEPLATE LOAD IS HIGHER
 THAN THE 4.5KW (SHOWN ON LOAD CALCULATIONS ) THEN THE
 OCP WOULD BE REQUIRED TO BE HIGHER THAN THE 2-POLE
 25AMP BREAKER ON PANEL SCHEDULE.
 PLEASE SEE 422.13, 240.4, 310.16
  
 4) NOTE: PLEASE SEE THE REFRIGERATOR CIRCUIT WHICH
 SHOWS A 20AMP BREAKER ON #14 AWG.
 PLEASE CORRECT.
 240.4, 310.16
  
 5) NOTE: PLEASE SEE THE STEEL LISTED PART THE GROUNDING
 ELECTRODE SYSTEM IS TO INCLUDE *FOOTER* STEEL AS
 REQUIRED PER 250.50
  
 ** PLEASE SEE THAT THE ABOVE CORRECTIONS ARE MADE ALONG
 WITH ANY OTHER ELECTRICAL REVISIONS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
2007-05-07 17:08:51IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-03-21 Cont ID  
Sent By dpalmer Date 2007-03-21 Time 19:46 Rev Time 0.00
Received By dpalmer Date 2007-03-21 Time 19:09 Sent To M
Notes
2007-03-21 19:47:15 
  
 ****** UNSAT2ND REVIEW ******
  
 ** PLEASE SEE THERE ARE MANY ITEMS FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING ALONG WITH NEW
 COMMENTS BASED ON CHANGES IN PLANS, OR NEW ITEMS SHOWN
 WHICH WERE NOT ON PREVIOUS PLANS.
  
 1) NOTE: PLEASE BE SURE THE PLANS REFLECT THE FOLLOWING
 RELEVANT CODES 2002 NFPA-70 (NEC), 2002 NFPA-72. SAME
 NOTE FROM PREVIOUS REVIEW.
  
 2) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULE NOW SUBMITTED. PLEASE
 SEE SMOKE ALARMS WHICH ARE MISSING CIRCUITING. PLEASE
 BE SURE TO ALSO SEE 210.12 FOR AFCI PROTECTION
 REQUIRED.
 310.16, 240.4, 408.4
  
 3) NOTE: PLEASE SEE A RISER DIAGRAM IS NOW SHOWN AND
 SHOWS THE SERVICE AS EXISTING, YET THE PANEL WHICH IS
 NOTED ON RISER IS NOT SHOWN ON PLANS FOR LOCATION.
 PLEASE SEE 110.26, 408.7 AND 240.24.
  
 4)NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING
 KITCHEN COUNTER SPACE ARE REQUIRED TO BE GFI/GFI
 PROTECTED. SAME NOTE ON PREVIOUS REVIEW.
  
 5) NOTE: PLEASE SEE 250.50 AS THE NEW FOOTER STEEL IS
 REQUIRED ON THE RISER FOR THE GROUNDING ELECTRODE
 SYSTEM.
  
 6) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.16 FOR
 DINING ROOM. PLEASE SEE THE LOAD IS BEING SHOWN AT
 1200VA.
 PLEASE ALSO SEE THESE SAME SECTIONS OF THE CODE AS THE
 LOAD FOR THE SMALL APPLIANCE CIRCUITS ARE BEING SHOWN
 WITH THE SAME 1200VA.
 NOTED ON PREVIOUS REVIEW.
  
 7) NOTE: PLEASE SEE 210.8A1 FOR RECEPTACLES IN BATH
 ROOMS WHICH ARE REQUIRED TO BE GFI.
 PLEASE ALSO SEE EXISTING BATHROOMS.
 PLEASE ALSO SEE THE MISSING GFI RECEPTACLE REQUIRED IN
 POWDER RM.
 210.52D, 210.11C1
  
 8) NOTE: PLEASE SEE WATER HEATER SHOWN WITHOUT THE
 REQUIRED DISCONNECT PER 422.30, 422.31.
  
 9) NOTE: PLEASE SHOW LOAD CALCULATIONS FOR HOUSE PER
 220.31B.
 SAME NOTE ON PREVIOUS REVIEW.
  
 10) NOTE: PLEASE SEE RISER NOW SHOWS A 2-POLE BREAKER
 FOR GFI CIRCUIT? PLEASE ALSO SEE RISER ALSO SHOWS A
 2-POLE 60AMP CIRCUIT TO POOL EQUIPMENT; HOWEVER POOL
 EQUIPMENT WOULD MEAN A POOL PANEL AS CIRCUITED. IF THIS
 IS THE CASE PLEASE INCLUDE PANEL ON RISER, FEEDERS
 ETC.
  
 IF THERE IS NO PANEL, THEN THIS WOULD NOT BE A 60AMP
 BREAKER FOR GENERAL POOL EQUIPMENT.
 PLEASE CLARIFY THIS INFORMATION.
 240.4, 310.16,
 FBC 106.1.2, 106.3.5.4
  
 11) NOTE: PLEASE SHOW THE LOCATION OF THE A/C EQUIPMENT
 REQUIRED DISCONNECTS PER 440.11.
  
 12) NOTE: PLEASE SEE NOW NOTE #24 ON PLANS; THIS HAS
 CHANGED FROM PREVIOUS PLANS WHICH WAS NOTE #22. PLEASE
 SEE THIS AS IT REFERENCES CODES FROM THE 1996 NFPA-72.
 PLEASE SEE AT PRESENT WITH THE 2002 NFPA-72, 11.5.1.1,
 AND 11.8.3 IS THE CURRENT SECTIONS FOR INSTALLATIONS OF
 SMOKE ALARMS. PLEASE SEE PLAN NOTE MENTIONS SD'S IS
 SMOKE DETECTORS. PLEASE SEE PLANS NOW SHOW SA FOR SMOKE
 ALARMS. PLEASE SEE 11.8.3 AS THE SA SHOWN OUTSIDE
 BEDROOM #2 AND #3 IS SHOWN TOO CLOSE TO THE BATHROOM
 DOOR. MUST BE AT LEAST 3FT FROM DOOR OPENING.
 PART OF THIS IS STILL FROM PREVIOUS REVIEW NOTES WITH
 RESPECT TO OLD CODE BEING REFERENCED.
  
 13) NOTE: PLEASE CLARIFY THE FIXTURES SHOWN IN CLOSETS
 TO MEET 410.8. PLEASE KNOW AN ASSUMED 12" SHELF SHALL
 BE DETERMINED.
  
 14) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE
 COMPLIANCE.
  
 15) NOTE: PLEASE SEE THE RISER WHICH DOES NOT INCLUDE
 ANY EXISTING OR NEW MAIN. HOW IS THIS PANEL WHICH IS
 BEING NOTED AS EXISTING 200AMP PANEL BEING FED? PLEASE
 ELABORATE ON RISER AND PROVIDE COMPLETED INFORMATION ON
 RISER AS NOTED.
 215.5, 230.2, 230.70, 230.71, 230.72, 240.4, 310.16
 ETC.
 FBC 106.1.2, 106.3.5.4
  
 16) NOTE: PLEASE SEE THE NOTICE OF COMMENCMENT WHICH
 WAS RECORDED IN 9/06 HAS EXPIED PER FS 713.13(2).
 PLEASE KNOW THAT A NEW RECORDED NOC WILL BE REQUIRED
 BEFORE PICKING UP PERMIT AFTER ISSUANCE. IT IS
 SUGGESTED THAT THE NOC DOES NOT GET RE-RECORDED UNTIL
 PERMIT IS ISSUED.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-16 Cont ID  
Sent By dpalmer Date 2006-10-16 Time 07:50 Rev Time 0.00
Received By dpalmer Date 2006-10-15 Time 20:57 Sent To M
Notes
2006-10-16 07:50:19****** UNSAT *********
  
 1) NOTE: PLEASE BE SURE THE PLANS REFLECT THE FOLLOWING
 RELEVANT CODES 2002 NFPA-70 (NEC), 2002 NFPA-72 .
  
 2) NOTE: PLEASE COMPLETE THE PANEL SCHEDULE INCLUDING
 ALL CONDUCTOR SIZES ALONG WITH THE OCP
 DEVICES/BREAKERS. 310.16, 240.4, 408.4
  
 3) NOTE: PLEASE SEE LOAD CALCS MENTIONS "OVENS" YET
 ONLY ONE SHOWN ON PANEL SCHEDULE AND LOAD CALCS. PLEASE
 CLARIFY AND ADJUST.
 220.31, 408.4 ETC.
  
 4)NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTS SERVING
 KITCHEN COUNTER SPACE ARE REQUIRED TO BE GFI/GFI
 PROTECTED.
  
 5) NOTE: PLEASE BE SUREPANEL SCHEDULE IS SPECIFIC TO
 ROOMS AND AREAS IN WHICH THEY FEED. IE: BEDRM #2
 RECEPTS, BATH RECEPTS, ETC
 408.4, 310.16, 240.4
  
 6) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.16 FOR
 DINING ROOM.(NEW OR EXSITIGN?)
  
 7) NOTE: PLEASE SEE 210.8A1 FOR RECEPTS IN BATH RMS
 WHICH ARE REQUIRED TO BE GFI.
 PLEASE ALSO SEE EXISITING BATHRMS ARE BEING SHOWN AS
 WORK BEING IN THOSE AREAS, PLEASE SEE HOWEVER THERE ARE
 NOT GFI RECEPTS INIDCATED ON PLANS ? ARE THEY GOING TO
 BE NEW OR EXISTING.
 210.52D, 210.11C1
  
 8) NOTE: PLEASE SEE 422.17 FOR WHAT APPEARS TO BE A
 WATER HEATER IN A STORAGE CLOTHES CLOSET WHICH IS NOT
 PERMITTED.
  
 9) NOTE: PLEASE SHOW LOAD CALCULATIONS FOR HOUSE PER
 220.31B.
  
 10) NOTE: PLEASE SHOW LOCATION OF SERVICE ON PLANS.
 PANEL, METER OR MAIN?
 IF THIS GOING TO BE A NEW SERVICE PLEASE SUBMIT A
 COMPLETE RISER DIAGRAM ALONG WITH AIC RATINGS ,
 CONDUCTORS, GROUNDING ETC.
  
 11) NOTE: PLEASE SEE NOTE ON PLANS MENTIONS ALL
 EXISTIGN BEDRMS BEING REWIRED TO CODE, HOWEVER PLEASE
 PROVIDE A LAYOUT FOR EITHER NEW OR EXISTING RECEPTS
 MEETING SPACING REQUIRMENTS PER 210.52.
  
 12) NOTE: PLEASE SHOW THE LOCATION OF THE A/C EQUIPMENT
 AND REQUIRED DISCONNECT'S PER 440.11.
  
 13) NOTE: PLEASE SHOW REQUIRED GFI PER 210.63/210.8A2
  
 14) NOTE: PLEASE SEE NOTE #22 ON PLANS AS IT REFERENCES
 CODES FROM THE 1996 NFPA-72.
 PLEASE SEE AT PRESENT WITH THE 2002 NFPA-72, 11.5.1.1,
 AND 11.8.3 ARE THE CURRENT SECTIONS FOR INSTALLATIONS
 OF SMOKE ALARMS. PLEASE SEE PLANS MENTIONS SD'S IS
 SMOKE DETECTORS. PLEASE VERIFY AS IF THESE ARE SMOKE
 DETECTORS, PLEASE VERIFY THE SYSTEM BEING INSTALLED AND
 WHAT DEVICES AND LOCATIONS FOR AUDIBLE SIGNAL WILL BE.
 PLEASE SEE DEFINITIONS AS THIS SEEMS PERHAPS THEY
 SHOULD BE SHOWN AS "SA"'S SMOKE ALARMS.
 PLEASE BE AWARE OF THE OCATIONF OF THE SD/SA SHOWN AT
 AHU LOCATION, 5'MIN AWAY FROM RA GRILLE(ONLY NOTED).
  
 15) NOTE: PLEASE SEE LOAD CALCS MENTIONS
 "FUTURELANSCAPE LTS" YET NO LOADS SHOWN?
  
 16) NOTE: PLEASE CLARFIY THE FIXTURES SHOWNIN CLOSETS
 TO MEET 410.8. PLEASE KNOW AN ASSUMNED 18" SHELF SHALL
 BE DETERMINED.
  
 ** PLEASE KNOW AS THERE IS INFORMATION NOT YET
 SUBMITTED THERE MAY BE FUTURE COMMENTS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
2006-10-15 20:58:46IN ELEC FOR REVIEW , NOTES TO FOLLOW

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2006-09-29 Cont ID  
Sent By ssherman Date 2006-09-29 Time 11:17 Rev Time 0.00
Received By ssherman Date 2006-09-29 Time 11:17 Sent To  
Notes
2006-09-29 00:00:00HISTORICAL APPROVAL PER JILLIAN PAPA

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2008-04-14 Cont ID  
Sent By adarroug Date 2008-04-14 Time 13:51 Rev Time 0.00
Received By adarroug Date 2008-04-14 Time 13:51 Sent To Z
Notes
2008-04-14 13:52:16TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2008-04-09 Cont ID  
Sent By adarroug Date 2008-04-09 Time 08:53 Rev Time 0.00
Received By adarroug Date 2008-04-09 Time 08:53 Sent To Z
Notes
2008-04-09 08:53:42TO "Z" BOX/SUBMITTLAL

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-03-17 Cont ID  
Sent By adarroug Date 2008-03-17 Time 14:39 Rev Time 0.00
Received By adarroug Date 2008-03-17 Time 14:39 Sent To E
Notes
2008-03-17 14:39:35TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-03-07 Cont ID  
Sent By adarroug Date 2008-03-07 Time 09:01 Rev Time 0.00
Received By adarroug Date 2008-03-07 Time 09:01 Sent To B
Notes
2008-03-07 09:02:21TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-03-07 Cont ID  
Sent By adarroug Date 2008-03-07 Time 08:43 Rev Time 0.00
Received By adarroug Date 2008-03-07 Time 08:43 Sent To P
Notes
2008-03-07 08:44:20TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-03-04 Cont ID  
Sent By adarroug Date 2008-03-04 Time 09:10 Rev Time 0.00
Received By adarroug Date 2008-03-04 Time 09:10 Sent To M
Notes
2008-03-04 09:11:36TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-03-03 Cont ID  
Sent By adarroug Date 2008-03-03 Time 16:32 Rev Time 0.00
Received By adarroug Date 2008-03-03 Time 16:32 Sent To E
Notes
2008-03-03 16:32:55TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-02-20 Cont ID  
Sent By adarroug Date 2008-02-20 Time 12:05 Rev Time 0.00
Received By adarroug Date 2008-02-20 Time 12:05 Sent To M
Notes
2008-02-20 12:05:42TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-02-20 Cont ID  
Sent By adarroug Date 2008-02-20 Time 11:59 Rev Time 0.00
Received By adarroug Date 2008-02-20 Time 11:59 Sent To P
Notes
2008-02-20 11:59:55TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-01-15 Cont ID  
Sent By adarroug Date 2008-01-15 Time 11:45 Rev Time 0.00
Received By adarroug Date 2008-01-15 Time 11:45 Sent To B
Notes
2008-01-15 11:45:33TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-07-12 Cont ID  
Sent By adarroug Date 2007-07-12 Time 14:06 Rev Time 0.00
Received By adarroug Date 2007-07-12 Time 14:06 Sent To B
Notes
2007-07-12 14:07:11TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-05-03 Cont ID  
Sent By shill Date 2007-05-03 Time 13:06 Rev Time 0.00
Received By shill Date 2007-05-03 Time 13:06 Sent To E
Notes
2007-05-03 13:07:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-20 Cont ID  
Sent By adarroug Date 2007-03-20 Time 11:17 Rev Time 0.00
Received By adarroug Date 2007-03-20 Time 11:17 Sent To E
Notes
2007-03-20 11:17:33TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-10 Cont ID  
Sent By adarroug Date 2006-10-10 Time 09:30 Rev Time 0.00
Received By adarroug Date 2006-10-10 Time 09:30 Sent To E
Notes
2006-10-10 09:30:48TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-24 Cont ID  
Sent By alange Date 2006-10-24 Time 13:11 Rev Time 0.00
Received By alange Date 2006-10-03 Time 14:28 Sent To  
Notes
2006-10-03 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-03-26 Cont ID  
Sent By tgordon Date 2008-03-26 Time 13:39 Rev Time 0.20
Received By tgordon Date 2008-03-26 Time 13:39 Sent To  
Notes
2008-03-26 13:40:11MECH. REVISION TO PLAN HVAC.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-03-04 Cont ID  
Sent By tgordon Date 2008-03-04 Time 15:55 Rev Time 0.30
Received By tgordon Date 2008-03-04 Time 15:55 Sent To  
Notes
2008-03-04 15:56:32REVISION TO MECH. PLAN, ENERGY CAL'S. AND COOLING LOAD
 CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-02-22 Cont ID  
Sent By tgordon Date 2008-02-22 Time 14:41 Rev Time 0.35
Received By tgordon Date 2008-02-22 Time 14:41 Sent To  
Notes
2008-02-22 14:49:21PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** MECHANICAL REVISION TO PLANS **
 *** DENIED ***
 1) COOLING LOAD CALCULATIONS ON FILE ARE CALLING FOR
 32,785 TOTAL COOLING BTU'S, MECHANICAL REVISION IS
 SHOWING TWO SYSTEMS TOTALING 47,600 COOLING BTU'S. THE
 PLANS CAN ONLY CALL FOR 15% MORE THAN THE COOLING LOAD
 CAL'S, SEE 2004 FBC 13-607.1.ABC.1.1. PLEASE CORRECT
 PLANS OR COOLING LOAD CAL'S.
  
 2) PLEASE SHOW THE LOCATION OF CONDENSER UNIT #2 ON
 PLAN.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-03-26 Cont ID  
Sent By tgordon Date 2007-03-26 Time 13:49 Rev Time 0.30
Received By tgordon Date 2007-03-26 Time 13:49 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-16 Cont ID  
Sent By tgordon Date 2006-10-16 Time 08:28 Rev Time 0.30
Received By tgordon Date 2006-10-16 Time 08:28 Sent To P
Notes
2006-10-16 08:36:27*** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS, PER
 2004 FBC 13-101.2.2.
  
 2) PLEASE SHOW LOCATION OF A/C CONDENSER
 UNIT ON MECHANICAL PLANS.
  
 3) SHOW LOCATION OF BATHROOM EXHAUST
 FAN AND CLOTHES DRYER VENT TERMINATION
 ON MECHANICAL PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-03-10 Cont ID  
Sent By jleech Date 2008-03-10 Time 07:59 Rev Time 0.00
Received By jleech Date 2008-03-10 Time 07:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-02-25 Cont ID  
Sent By jleech Date 2008-02-25 Time 10:21 Rev Time 0.00
Received By jleech Date 2008-02-25 Time 09:52 Sent To  
Notes
2008-02-25 10:29:36DENIED;
 1. AUTOMATIC CLOTHES WASHER SHALL DISCHARGE DOWN STREAM
 OF THE BATHROOM GROUP. SEE FBC PLUMBING SECTION 909.1.
 2. APPROVED "P" PAGE WAS RED LINES, TO EXPEDITE PLANS,
 CHANGES WERE NOT MADE ON NEW REVISION.
 PLANS ARE RED LINED . PLEASE MAKE CHANGES.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-04-02 Cont ID  
Sent By jleech Date 2007-04-02 Time 09:27 Rev Time 0.00
Received By jleech Date 2007-04-02 Time 09:27 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-10-21 Cont ID  
Sent By jleech Date 2006-10-21 Time 12:49 Rev Time 0.00
Received By jleech Date 2006-10-21 Time 12:49 Sent To B
Notes
2006-10-21 13:00:211. AUTOMATIC CLOTHES WASHER BRANCH DRAIN TO BE 3"
 SECTION 406.3 CLEANOUT REQUIRED AT 48" AFF.
 2.W/M TO DISCHARGE DOWN STREAM OF THE BATHROOM GROUP
 SECTION 909.1
 3.SHOWER BATH, SHOWER IS NOT VENTED THE WET VENT FOR
 THE BATHROOM GROUP SHOULD BE THE
 BEFORE THE SHOWER TO RELEAVE THE NEGATIVE PRESSURE
 FROM TOILET.
 4.DISHWASHER TO DISCHARGE INTO THE TAIL PIECE OF THE
 KITCHEN SINK.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2008-04-15 Cont ID  
Sent By choops Date 2008-04-15 Time 11:46 Rev Time 0.00
Received By choops Date 2008-04-15 Time 11:46 Sent To PC
Notes
2008-04-15 11:47:00***APPROVED - LANDSCAPE PLAN SUBMITTAL***

Review Stop Z ZONING
Rev No 2 Status F Date 2008-04-09 Cont ID  
Sent By choops Date 2008-04-09 Time 15:46 Rev Time 0.00
Received By choops Date 2008-04-09 Time 15:46 Sent To  
Notes
2008-04-09 16:06:52***FAILED - SUBMITTAL - LANDSCAPE PLAN***
  
  
 1)TWO (2) COPIES OF ALL PLANS SHALL BE SUBMITTED,
 ONE FOR CITY'S RETENTION AND ONE TO BE POSTED AT
 JOBSITE.PLEASE SUBMIT TWO (2) COPIES OF ALL
 DOCUMENTS.
  
 2)ANYTHING OTHER THAN LANDSCAPING INDICATED ON PLANS
 (SUCH AS FENCES, PATIOS, ETC) SHALL BE REMOVED FROM
 PLANS OR LABELED "TO BE PERMITTED SEPARATELY" AS SOME
 ITEMS SHOWN ARE NOT CODE COMPLIANT.
  
 3)LANDSCAPE PLAN SHALL INDICATE OPEN SPACE AND
 REQUIRED LANDSCAPING CALCULATIONS.
  
 4)LANDSCAPE PLANS SHALL SHOW COMPLIANCE WITH BOTH
 SECTIONS 94-442 AND 94-445 OF THE CITY'S ZONING AND
 LAND DEVELOPMENT REGULATIONS.
  
 INCLUDING, BUT NOT LIMITED TO:
 *PLANT MATERIAL SPECIFICATIONS: PLANT QUALITY.
 *PLANS SHALL INDICATE THAT THE REQUIRED IRRIGATION
 SYSTEM (FOR BOTH THE YARD AND SWALE/PARKWAY AREA) WILL
 BE APPLIED FOR.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720

Review Stop Z ZONING
Rev No 1 Status P Date 2006-10-05 Cont ID  
Sent By kdfreema Date 2006-10-05 Time 16:59 Rev Time 0.00
Received By kdfreema Date 2006-10-05 Time 16:59 Sent To  
Notes
***NONE***