Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-10-30 Cont ID  
Sent By mawillia Date 2006-10-30 Time 15:38 Rev Time 0.00
Received By mawillia Date 2006-10-30 Time 15:38 Sent To  
Notes
2006-10-30 15:44:02*****APPROVED*****
  
  
 AS PER ADA,ROOMS IDENTIFIED AS
 HEARING IMPAIRED (HI) SHALL HAVE VISUAL ALARM DEVICES
 (STROBES) IN ADDITION TO AUDILBE.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-19 Cont ID  
Sent By mawillia Date 2006-10-19 Time 12:46 Rev Time 0.00
Received By mawillia Date 2006-10-19 Time 12:46 Sent To  
Notes
2006-10-19 13:21:06*****UNSAT*****
  
  
  
  
 1.)SINCE THE CONTRACT IS GREATER THAN $5000.00, THE
 DOCUMENTS WILL REQUIRE AN ENGINEER'S SEAL THAT HAS BEEN
 SIGNED, DATED, AND STAMPED AS PROVIDED IN SECTION
 471.025, FLORIDA STATUTES.
  
 2.)AS PER WPB FIRE PREVENTION, DUCT SMOKE DETECTORS
 SHALL INTIATE A GENERAL ALARM.
  
 3.)WATERFLOW TO ACTIVATE GENERAL ALARM WITHIN 45 TO
 60 SECONDS.
  
 4.)THE SILENCING OF THE FIRE ALARM SYSTEM SHALL IN NO
 WAY DEACTIVATE VISUAL/STROBE DEVICES.
  
 5.)UL CERTIFICATE FOR CENTAL STATION SERVICE TO BE AT
 THE FACP AND A COPY SUBMITTED TO WPB FIRE PREVENTION BY
 FINAL FIRE ALARM INSPECTION.
  
 6.)COORDINATE WITH THE GENERAL CONTRACTOR AND/OR THE
 SPRINKLER CONTRACTOR THAT THE DOUBLE DETECTOR CHECK
 VALVE BE CHAINED AND LOCKED AT THE COMPLETION OF FIRE
 ALARM/SPRINKLER FINAL.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-25 Cont ID  
Sent By adarroug Date 2006-10-25 Time 19:20 Rev Time 0.00
Received By adarroug Date 2006-10-25 Time 19:20 Sent To FIRE
Notes
2006-10-25 19:21:05TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-19 Cont ID  
Sent By mawillia Date 2006-10-19 Time 12:46 Rev Time 0.00
Received By mawillia Date 2006-10-02 Time 10:02 Sent To  
Notes
2006-10-02 00:00:00TO "F" BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved