Plan Review Details - Permit 06091036
Plan Review Stops For Permit 06091036
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-23 Cont ID  
Sent By alange Date 2006-10-23 Time 08:30 Rev Time 0.00
Received By alange Date 2006-10-23 Time 08:30 Sent To  
Notes
2006-10-23 08:30:50DENIED
  
 SHOW GENERATOR SLAB DETAIL AND METHOD OF ATTACHMENT TO
 SLAB.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-10-18 Cont ID  
Sent By btrobaug Date 2006-10-18 Time 09:00 Rev Time 0.50
Received By btrobaug Date 2006-10-18 Time 08:45 Sent To M
Notes
2006-10-18 09:00:32 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE
 PLAN/DRAWINGS, SHALL PRINT AND SIGN THEIR NAME ON THE
 SHEETS THEY DRAW. PLEASE DO THIS PRIOR TO
 RESUBMITTING.
  
 2} PROVIDE MANUFACTURERS SPECIFICATIONS AND
 RECOMMENDATION, REGARDING CLEARANCES FOR THE
 GENERATOR.
  
 3} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
 DO THIS ON A SITE PLAN, NOT ON THE SURVEY, 106.1.3FBC.
  
 4} PROVIDE SPECIFICATIONS FOR THE TRANSFER SWITCH.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-10-20 Cont ID  
Sent By mperson Date 2006-10-20 Time 11:42 Rev Time 0.45
Received By mperson Date 2006-10-20 Time 11:42 Sent To B
Notes
2006-10-20 11:56:32UNSAT
 REFERENCE: FBC-2004 FUEL GAS AND FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED FOR GAS PLAN
 REVIEW ON THE ISOMETRIC DRAWING:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL)
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT (2LB REGULATORS AND GENERATOR) TO VERIFY
 COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
  
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 12. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-10 Cont ID  
Sent By adarroug Date 2006-10-10 Time 08:56 Rev Time 0.00
Received By adarroug Date 2006-10-10 Time 08:56 Sent To E
Notes
2006-10-10 08:57:03TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-23 Cont ID  
Sent By alange Date 2006-10-23 Time 08:31 Rev Time 0.00
Received By alange Date 2006-09-29 Time 16:10 Sent To  
Notes
2006-09-29 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-19 Cont ID  
Sent By tgordon Date 2006-10-19 Time 11:35 Rev Time 0.45
Received By tgordon Date 2006-10-19 Time 11:35 Sent To P
Notes
2006-10-19 11:37:33*** DENIED ***
 1) SEE ZONING REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-10-05 Cont ID  
Sent By kdfreema Date 2006-10-05 Time 12:41 Rev Time 0.00
Received By kdfreema Date 2006-10-05 Time 12:41 Sent To  
Notes
2006-10-05 00:00:00**FAILED**
  
 GENERATOR MAY BE INSTALLED NO FURTHER
 THAT 4 FEET INTO A REQUIRED SIDE
 SETBACK. PLEASE SHOW DISTANCE BETWEEN
 GENERATOR AND PROPERTY LINE AS WELL AS
 DISTANCE BETWEEN THE GENERATOR AND THE
 HOUSE.
  
 INSTALLATION INSTRUCTIONS INCLUDING THE
 MFG RECOMMENDED SEPARATION DISTANCES
 MUST BE SUBMITTED AT THE TIME OF PERMIT.

Review Stop Z ZONING
Rev No 1 Status   Date 2006-10-05 Cont ID  
Sent By kdfreema Date 2006-10-05 Time 12:40 Rev Time 0.00
Received By kdfreema Date 2006-10-05 Time 12:39 Sent To  
Notes
***NONE***