| Plan Review Stops For Permit 06090999 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2007-09-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-09-25 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-09-25 |
Time |
15:26 |
Sent To |
|
|
| Notes |
| 2007-09-25 15:27:19 | REVISION 9/12, SHEETS CS, A1, A2 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2007-09-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-09-25 |
Time |
08:16 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-09-25 |
Time |
08:16 |
Sent To |
|
|
| Notes |
| 2007-09-25 08:16:52 | REVISION 8/30 | | | CS, A7 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2007-08-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-08-30 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-08-30 |
Time |
13:55 |
Sent To |
|
|
| Notes |
| 2007-08-30 13:56:33 | REVISION CS, A2 AND SPEC BOOK, DATED 7/20 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-04-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-04-03 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-04-03 |
Time |
16:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-02-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-02-05 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-02-05 |
Time |
09:21 |
Sent To |
|
|
| Notes |
| 2007-02-05 09:24:26 | ****CORRECTIONS**** | | | ****PLAN CHECK**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE | | | FBC2004 | | | | | | 1.)THIS IS A PLAN CHECK ONLY.PLEASE APPLY FOR | | | PERMIT. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-11-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-11-07 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-11-07 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2006-11-07 15:11:33 | ****CORRECTIONS**** | | | ****PLAN CHECK**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE | | | FBC2004 | | | | | | 1.)DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3. | | | | | | 2.)THE AHJ IS CITY OF WEST PALM BEACH, NOT PBC, | | | REVISE CS NOTES. | | | | | | 3.)SHEET CS, TYPE OF CONSTRUCTION, DECLARE A OR B, | | | FBC 6. | | | | | | 4.)EACH SHEET SHOULD HAVE ALL INFORMATION REQUIRED BY | | | FAC61G16-23.002, 003 (ARCHITECTS) AND FAC61G15-23.002 | | | (ENGINEERS). | | | | | | 5.)PROVIDE DESIGN LOAD INFORMATION FOR THE ROOF | | | MOUNTED EF1 SHOWN ON MP1; ADDRESS THE ADDITIONAL DEAD | | | LOAD ON THE ROOF ON THE PLAN. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2007-10-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-10-04 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-10-04 |
Time |
10:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2007-08-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-23 |
Time |
18:30 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-23 |
Time |
18:26 |
Sent To |
|
|
| Notes |
| 2007-08-23 18:30:58 | REV FOR E-1 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2007-03-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-03-30 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-03-30 |
Time |
08:51 |
Sent To |
|
|
| Notes |
| 2007-03-30 08:51:33 | FEES PAID |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-03-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-03-18 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-03-18 |
Time |
14:22 |
Sent To |
|
|
| Notes |
| 2007-03-18 14:52:03 | ** UNSAT ** | | | | | | 1) NOTE: PERMIT APPLICATION FEES WERE NOT PAID WHEN | | | APPLIED. | | | PLEASE KNOW FEES MUST BE PAID AT THE TIME OF | | | APPLICATION. | | | | | | ** PLANS WILL BE PLACED INTO A HOLD STATUS UNTIL FEES | | | ARE PAID. | | | FBC ADMIN SECTION 108.2 | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | A CALL WILL BE PLACED TO THE CONTRACTOR ON THE NEXT | | | BUSINESS DAY. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-01-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-01-13 |
Time |
18:26 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-01-13 |
Time |
17:45 |
Sent To |
|
|
| Notes |
| 2007-01-13 18:26:49 | ** UNSAT ** | | | | | | 1) NOTE: PLEASE SEE PREVIOUS REVIEW AS THE COMMENT | | | MENTIONED THIS WAS ONLY SUBMITTED FOR PLAN REVIEW AND | | | WAS NOT SUBMITTED FOR PERMIT APPLICATION. | | | PLEASE KNOW AS OF DECEMBER 8TH, 2006 THE STATE OF | | | FLORIDA ADOPTED NEW CODES WITH RESPECT TO THE 2005 | | | NFPA-70 (NEC) AND THE 2006 REVISIONS TO THE 2004 FBC. | | | PLEASE ADJUST PLANS AND PLEASE KNOW THAT AS OF THIS | | | REVIEW NO PERMIT APPLICATION HAS YET BEEN MADE. | | | | | | 2) NOTE: PREVIOUS REVIEW NOTE: | | | PLEASE SEE MISSING INFORMATION REQUIRED ON TITLE | | | BLOCKS FOR ENGINEERING FIRM AS REQUIRED PER FAC | | | 61G15-23.002 AND FLORIDA STATUTES 471.023. | | | PLEASE SEE THE PLANS ARE STILL MISSING THE CERTIFICATE | | | OF AUTHORIZATION NUMBER AS REQUIRED PER SECTIONS GIVEN. | | | THIS IS REQUIRED FOR ALL TRADES AND FOR ALL APPLICABLE | | | SHEETS ETC. | | | ** PLEASE KNOW THE ABOVE TWO NOTES ARE REQUIRED FOR ALL | | | SHEETS AND FOR ALL TRADES WHETHER OR NOT COMMENT IS | | | MADE BY OTHER REVIEWER(S). | | | | | | 3) NOTE: PLEASE SUBMIT THE PANEL SCHEDULE FOR ALL NEW | | | ELECTRICAL. | | | 408.4, 310.16. | | | FBC 106.3.5.1.2 ADMIN SECTION. | | | | | | 4) NOTE: PLEASE CLARIFY OR NOTE THE NEW OR EXITING | | | EMERGENCY LIGHTING WIRED AHEAD OF THESE DEVICES. | | | (700.12E). PLEASE KNOW THAT IF NO EXISTING EMERGENCY | | | BATTERY BACK UP FIXTURE(S) OF SOME KIND ARE PRESENT, | | | NEW ONES WILL BE REQUIRED. | | | NFPA-101 7.8, 7.9 | | | | | | | | | ** ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-10-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-25 |
Time |
07:08 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-24 |
Time |
20:30 |
Sent To |
|
|
| Notes |
| 2006-10-25 07:18:39 | *** UNSAT *** | | | | | | ** PLEASE KNOW THAT PLANS AHVE ONLY BEEN SUBMITTED FOR | | | "PLAN REVIEW" ONLY AND HAVE NOT BEEN SUBMITTED FOR | | | PERMIT. | | | PLANS CAN NOT BE STAMPED OR PASSED EVEN IF PLANS ARE | | | CODE COMPLIANT. | | | | | | 1) NOTE: PLEASE SEE MISSING INFORMATION AS REQUIRED | | | TITLE BLOCKS FOR ARCHITECT PER FLORIDA ADMINISTRATIVE | | | CODE 61G1-16.004. | | | | | | 2) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON | | | TITLE BLOCKS FOR ENGINEERING FIRM AS REQUIRED PER FAC | | | 61G15-23.002 AND FLORIDA STATUTES 471.023. PLEASE SEE | | | MISSING THE REQUIRED PRINTED NAME AND LICENSE NUMBER OF | | | SAID ENGINEER. PLEASE SEE MISSING CERTIFICATE OF | | | AUTHORIZATION NUMBER ETC. | | | ** PLEASE KNOW THE ABOVE TWO NOTES ARE REQUIRED FOR ALL | | | SHEETS AND FOR ALL TRADES WHETHER OR NOT COMMENT IS | | | MADE BY OTHER REVIEWER(S). | | | | | | 3) NOTE: PLEASE INDICATE THE TYPE OF OCC SENSOR DEVICE | | | WHICH WILL BE INSTALLED.(MOTION/HEAT/SOUND??) PLEASE | | | ALSO INDICATE THE MAXIMUM TIME PERMITTED AFTER THE LAST | | | SENSING . (30MINS) FBC 2004 13-415.1.ABC.1 | | | | | | 4) NOTE: PLEASE SEE FRONT COVER SHEET MENTIONS "PBC" | | | AMENDMENTS TO ALMOST ALL CODES. PLEASE KNOW THIS | | | PROJECT IS LOCATED IN THE "CITY OF WEST PALM BEACH AND | | | NOT IN "PALM BEACH COUNTY" JURISDICTION. PLEASE ALSO | | | KNOW UNDER THE CITY THERE IS ONLY LOCAL AMENDMENTS TO | | | THE ADMINISTRATIVE SECTION OF THE 2004 FBC. ( CHAPTER | | | 1). | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | 2006-10-24 20:30:15 | IN ELEC FOR REVIEW. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
P |
Date |
2007-11-01 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-11-01 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-11-01 |
Time |
16:26 |
Sent To |
|
|
| Notes |
| 2007-11-01 16:32:39 | *****APPROVED REVISION DATED 09/12/07***** | | | | | | | | | REVISED PLAN SHEET E1 STAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2007-10-02 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-02 |
Time |
22:45 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-10-02 |
Time |
22:41 |
Sent To |
|
|
| Notes |
| 2007-10-02 22:45:08 | *****APPROVED***** | | | | | | | | | REVISED PLAN SHEETS CS AND A7 WERE REVIEWED BUT NO | | | FIRE-STAMPING NECESSARY. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2007-09-17 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-09-17 |
Time |
17:47 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-09-17 |
Time |
17:37 |
Sent To |
|
|
| Notes |
| 2007-09-17 17:36:50 | *****APPROVED***** | | | | | | | | | REVISED PLAN SHEET E1 STAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-04-03 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-04-03 |
Time |
16:00 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-04-03 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2007-04-03 15:56:55 | *****APPROVED***** | | | | | | | | | PLAN SHEET E1 STAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-02-07 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-02-07 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-02-07 |
Time |
10:06 |
Sent To |
|
|
| Notes |
| 2007-02-07 10:08:51 | ***PLAN REVIEW ONLY*** | | | | | | 1) PLANS APPEARED TO BE CODE COMPLIANT FROM FIRST | | | REVIEW. NO PERMIT HAS BEEN APPLIED FOR AT THIS TIME. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | (561) 805-6722 OR 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2006-12-05 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-12-05 |
Time |
09:32 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-12-05 |
Time |
09:32 |
Sent To |
|
|
| Notes |
| 2006-12-05 10:09:27 | *****TO BE APPROVED WITH PROVISO***** | | | | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.CONSTRUCTION AND/OR DEMOLITION OPERATIONS IN THE | | | RESTROOM AREA SHALL NOT INTERFERE OR HINDER ACCESS OR | | | EGRESS FROM OTHER AREAS OF THE BUILDING. | | | | | | 3.IF THE FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM | | | IS/ARE MODIFIED DUE TO THE SCOPE OF WORK, SEPARATE | | | PLANS AND PERMIT ARE REQUIRED. | | | | | | 4.THE NUMERICAL ADDRESS OF WHERE THE SCOPE OF WORK IS | | | BEING CONDUCTED SHOULD BE IN THE TITLE BLOCK OF EACH | | | SUBMITTED PLAN SHEET. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2007-09-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-25 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-25 |
Time |
08:54 |
Sent To |
P |
|
| Notes |
| 2007-09-25 08:54:35 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-09-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-13 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-13 |
Time |
15:41 |
Sent To |
|
|
| Notes |
| 2007-09-24 16:28:10 | TO "COMM" BD#41 | | 2007-09-13 15:41:55 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-09-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-04 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-04 |
Time |
11:12 |
Sent To |
B |
|
| Notes |
| 2007-10-04 10:37:39 | TO "COMM" BD#32 | | 2007-09-04 11:13:17 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-07-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-26 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-26 |
Time |
11:05 |
Sent To |
|
|
| Notes |
| 2007-08-07 18:28:09 | TO COMM BOARD #46 | | 2007-07-26 11:06:02 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-03-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-10 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-10 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2007-03-10 13:47:06 | TO "COMM" BD#29 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-12-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-19 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-19 |
Time |
09:34 |
Sent To |
|
|
| Notes |
| 2007-01-11 10:08:04 | TO "COMM" BD#35 | | 2006-12-19 09:34:37 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-12-05 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-12-05 |
Time |
10:17 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-09-28 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2006-09-28 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2007-08-14 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-08-14 |
Time |
17:56 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-08-14 |
Time |
17:56 |
Sent To |
|
|
| Notes |
| 2007-08-14 17:56:42 | REVISED PAGE MP 1 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2007-03-30 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-03-30 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-03-30 |
Time |
08:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2007-02-01 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-02-01 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-02-01 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2007-02-01 11:01:04 | ------------------PLAN CHECK----------------- | | | | | | PLAN APPEARS TO BE CODE COMPLIANT. SUBMITTED FOR PLAN | | | CHECK ONLY. NO PERMIT APPLIED FOR AT THIS TIME. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-10-31 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-10-30 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-10-30 |
Time |
15:48 |
Sent To |
|
|
| Notes |
| 2006-10-30 16:31:01 | DENIED:*******PLAN CHECK ONLY****** | | | PLANS THAT ARE SIGNED, SEALED AND DATED BY THE ENGINEER | | | SHALL ALSO LEGIBLY INDICATE THEIR NAME, ADDRESS, AND | | | NUMBER ON EACH SHEET.A TITLE BLOCK WILL SUFFICE. | | | PLEASE ALSO NOTE, IF PRACTICING UNDER A DULY AUTHORIZED | | | ENGINEERING BUSINESS, THE NAME, ADDRESS, AND | | | ENGINEERING BUSINESS NUMBER (CERTIFICATE OF | | | AUTHORIZATION NUMBER). | | | | | | PLANS ARE OTHERWISE CODE COMPLIANT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | | AT (561)805-6719 OR E-MAIL [email protected]. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2007-09-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-09-08 |
Time |
06:57 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-09-08 |
Time |
06:57 |
Sent To |
|
|
| Notes |
| 2007-09-08 07:06:13 | REVISION OK - SHT MP-1 ADDED EW-2 TO FIXTURE INDEX |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2007-03-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-03-22 |
Time |
08:10 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-03-22 |
Time |
08:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-02-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-02-01 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-02-01 |
Time |
16:42 |
Sent To |
|
|
| Notes |
| 2007-02-01 16:48:59 | DENIED - PLAN REVIEW ONLY | | | REFERENCE: | | | FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. OK | | | 2. OK | | | 3. OK | | | | | | 4. SHT MP1 ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME, | | | ADDRESS, AND LICENSE NUMBER, AS WELL AS, THE NAME, | | | ADDRESS, AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE | | | ENGINEERING BUSINESS ON EACH SHEET. 61G15-23.002(2) & | | | FS 471.025.. (REQ'D FOR SHT E1 ALSO). | | | *******RESPONSE NOTED, BUT THE CERTIFICATE OF | | | AUTHORIZATION NUMBER FOR THE ENGINEERING BUSINESS IS | | | STILL REQUIRED. | | | | | | 5. OK | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-11-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-11-01 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-11-01 |
Time |
10:03 |
Sent To |
|
|
| Notes |
| 2006-11-01 10:15:10 | DENIED - PLAN REVIEW ONLY | | | REFERENCE: | | | FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. SHT CS CODE INFORMATION TO READ WEST PALM BEACH, NOT | | | PBC. - PLUMBING CODE REQUIREMENTS SHALL READ FBC-2004 | | | PLUMBING, NOT 2003 IPC. | | | | | | 2. SHT CS CODE REQUIREMENTS. PLUMBING FIXTURES PROVIDED | | | DO NO REFLECT FIXTURES SHOWN ON THE FLOOR PLAN. PLEASE | | | CORRELATE FLOOR PLAN AND PLUMBING CODE REQUIREMENT | | | INFORMATION. | | | | | | 3. SHT A1 DETAIL 3. SHOW THE FOLLOWING FOR COMPLIANCE; | | | 11-4.16.2 CLEAR FLOOR SPACE (IN STALL). - 11-4.19.3 | | | CLEAR FLOOR SPACE (IN STALL). | | | | | | 4. SHT MP1 ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME, | | | ADDRESS, AND LICENSE NUMBER, AS WELL AS, THE NAME, | | | ADDRESS, AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE | | | ENGINEERING BUSINESS ON EACH SHEET. 61G15-23.002(2) & | | | FS 471.025.. (REQ'D FOR SHT E1 ALSO) | | | | | | 5. SUBMIT A SANITARY RISER DIAGRAM ISOMETRIC TO REFLECT | | | THE FLOOR PLAN FOR ALL NEW WORK. SECTION 106.3.5.1.3. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|