Plan Review Details - Permit 06090951
Plan Review Stops For Permit 06090951
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-11-02 Cont ID  
Sent By mawillia Date 2006-11-02 Time 09:54 Rev Time 0.00
Received By mawillia Date 2006-11-02 Time 09:54 Sent To  
Notes
2006-11-02 09:59:36*****APPROVED*****
  
  
  
  
  
 PLEASE BE ADVISED THAT THE LICENSE / ID BADGE WILL BE
 CHECKED PRIOR TO ANY INSPECTIONS CONDUCTED BY THIS
 OFFICE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-12 Cont ID  
Sent By mawillia Date 2006-10-12 Time 14:57 Rev Time 0.00
Received By mawillia Date 2006-10-12 Time 14:57 Sent To  
Notes
2006-10-12 15:01:25*****UNSAT*****
  
  
  
 1.)PLEASE BE ADVISED THAT NFPA 96, 2004 EDITION SHALL
 BE REFERENCED.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-26 Cont ID  
Sent By adarroug Date 2006-10-26 Time 09:16 Rev Time 0.00
Received By adarroug Date 2006-10-26 Time 09:16 Sent To FIRE
Notes
2006-10-26 09:17:15TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-12 Cont ID  
Sent By mawillia Date 2006-10-12 Time 14:57 Rev Time 0.00
Received By mawillia Date 2006-09-28 Time 13:57 Sent To  
Notes
2006-09-28 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-11-02 Cont ID  
Sent By tgordon Date 2006-11-02 Time 09:26 Rev Time 0.30
Received By tgordon Date 2006-11-02 Time 09:26 Sent To FIRE
Notes
2006-11-02 16:29:53*** PROVISO ***
 1) NO INFORMATION WAS GIVEN AS TO WHAT TYPE OF
 APPLIANCES ARE GOING UNDER THE TYPE II KITCHEN HOOD.
 PIZZA OVENS REQUIRE A TYPE I HOOD, PER 2004 FBC/M
 507.2.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-06 Cont ID  
Sent By tgordon Date 2006-10-06 Time 09:22 Rev Time 0.30
Received By tgordon Date 2006-10-06 Time 09:22 Sent To FIRE
Notes
2006-10-06 00:00:00*** DENIED ***
 1) PLANS FOR THE HOODS HAVE BEED
 SUBMITTED WITH THE BUILDING PLANS. AS
 YOUR PLANS ARE SEALED BY A DIFFERENT
 ENGINEER YOU NEED TO HAVE THE ENGINEER
 ON RECORD (GARY STENLUND P.E.) REVIEW
 THEM AND PUT HIS SHOP DRAWING STAMP ON
 THEM .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.