Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-17 Cont ID  
Sent By jgomez Date 2006-10-17 Time 17:44 Rev Time 3.00
Received By jgomez Date 2006-10-17 Time 17:44 Sent To  
Notes
2006-10-17 18:01:29BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2-AFTER ALL DRAWINGS ARE REVISED, PAY PALM BEACH
 COUNTY IMPACT FEES. BRING BACK STAMPED DRAWINGS AND
 COPY OF THE PAID RECEIPT.
  
 3-A)ENGINEER NEEDS TO PROVIDE ALL HIS INFORMATION
 IN ALL DRAWINGS AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTES AND FLORIDA ADMINISTRATIVE CODE SEC.
 61G15-23.002.
 B)ENGINEER NEEDS TO SIGN AND SEAL ALL DRAWINGS.
  
  
 4-WHY ARE BOTH DRAWINGS LABELED A-101. REVISE AS
 REQUIRED.
  
 5-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY CHAPTER
 13 FBC 2004.
  
 6-ENGINEER TO SPECIFY HOW MUCH AREA IS ADDED TO THE
 HOUSE TO DETERMINE PERMIT VALUATION AS REQUIRED BY SEC.
 108.3 CITY AMENDMENTS TO FBC 2004.
  
 7-ENGINEER TO SPECIFY SPECIFIC BUILDING CODE AND ALL
 THE DESIGN CRITERIA AS REQUIRED BY SEC. R301 2004
 FLORIDA RESIDENTIAL CODE.
  
 8-ENGINEER TO PROVIDE COMPLETE ENGINEERING ANALYSIS
 SHOWING HOW CAN THE 2"X10" FLOOR JOISTS EXPAND UP TO
 24'-0".SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 9- DRAWINGS TO PROVIDE COMPLETE SPECS SHOWING
 COMPLIANCE WITH WOOD PROTECTION AGAINST DECAY. SEE SEC.
 R319 2004 FLORIDA RESIDENTIAL CODE.
  
 10-PROVIDE COMPLETE EXTERIOR ELEVATIONS. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 11-CLARIFY IF HOME IS GOING TO HAVE MECHANICAL
 VENTILATION. OTHERWISE, PROVIDE VENTILATION AS REQUIRED
 BY SEC. R303.1 2004 FLORIDA RESIDENTIAL CODE.
  
 12-SPECIFY WINDOW TYPES AND SIZES TO VERIFY
 COMPLIANCE WITH EGRESS REQUIREMENTS SEC. R310 2004
 FLORIDA RESIDENTIAL CODE.
  
 13-SPECIFY SAFETY GLASS FOR BATHROOM WINDOW. SEC.
 R308.4 2004 FLORIDA RESIDENTIAL CODE.
  
 14-PROVIDE COMPLETE SPECIFICATIONS FOR FOOTINGS. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 15-PROVIDE COMPLETE SPECIFICATIONS FOR ATTACHMENT OF
 NEW FOOTING TO EXISTING. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004
  
 16-PROVIDE COMPLETE DRAWINGS AND SPECIFICATIONS FOR
 CRAWL SPACE TO COMPLY WITH SEC. R408 2004 FLORIDA
 RESIDENTIAL CODE.
  
 17-SECTION A-A:
 A)PROVIDE COMPLETE SPECIFICATIONS. SPECIFY ALL
 CONNECTORS, ROOF VENTILATION, STUCCO THICKNESS, WALL
 SHEATHING FASTENING, CONNECTION OF WALL TO FOUNDATION
 AND ROOF,THICNESS OF VAPOR BARRIER, TERMITE
 PROTECTION,DIMENSIONS FOR FOOTING EMBEDMENT INTO
 GRADE,CONSTRUCTION MATERIALS UNDERSIDE OF FLOOR
 FRAMING, ETC. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 B)R19 INSULATION DOESN'T FIT IN 2X4 STUDS. REVISE
 AS REQUIRED.
 C) CLARIFY WHY 2" INSULATION ON FOUNDATION AND
 PROVIDE COMPLETE SPECS AND LOCATION FOR SUCH
 INSULATION. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
 D) REVISE ROOF FRAMING DETAIL TO MATCH ACTUAL ROOF
 FRAMING PLAN.
  
 18-SPECIFY ATTIC ACCESS. SEC. R3807 2004 FLORIDA
 RESIDENTIAL CODE.
  
 19-NEED STEPS BY REAR DOOR.SEE SECTIONS R311.5.3
 AND R312 2004 FLORIDA RESIDENTIAL CODE.
  
 20-MIN. HALLWAY DIMENSION IS 3'-0".CLEARANCEIN
 HALLWAY BY WASH AREAIS REDUCED BY PUTTING WASHER AND
 DRYER. REVISE AS REQUIRED. SEC. R311.3 2004 FLORIDA
 RESIDENTIAL CODE.
  
 21-SPECIFY ROOF VENTILATION. SEC. R806 2004 FLORIDA
 RESIDENTIAL CODE.
  
 22-IF INTERIOR WALL CONSTRUCTION IS 2X4'S, THEN WHY
 PROVIDING DETAIL FOR METAL PARTITION.
  
 23-DEPTH OF CLOSETS IN NEW BEDROOMS ARE TOO NARROW.
 CLOTHES DON'T FIT. REVISE AS REQUIRED.
  
 24- PROVIDE DIMENSIONS ON PLOT PLAN.
  
 25- PROVIDE SOIL TEST REPORT.
  
 26-ROOF FRAMING PLAN IS WRONG. PROVIDE COMPLETE ROOF
 FRAMING PLAN INCLUDING ATTACHMENT OF NEW ROOF TO
 EXISTING ROOF. CLARIFY IF USING PREFABRICATED ROOF
 TRUSSES OR CONVENTIONAL FRAMING. PROVIDE COMPLETE SPECS
 FOR EITHER ONE. PROVIDE UPLIFT LOADS AND TRUSS
 CONNECTOR SCHEDULE. SECTION 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 27-SPECIFY NAILING SIZE AND SPACING FOR ROOF
 SHEATHING. SEE TABLE 2304.9.1 2004 FBC 2004.
  
 28-PROVIDE FLORIDA OR LOCAL PRODUCT APPROVAL AS
 REQUIRED BY DCA RULE 9B-72 FOR:
 A) ALL USP OR SIMPSON STRUCTURAL CONNECTORS
 SPECIFIED BY THE ENGINEER ON PLANS AND DETAILS.
  
 29-ENGINEER OF RECORD TO REVIEW AND APPROVE IN
 WRITTING ALL PRODUCT APPROVALS. SEC. 106.3 CITY
 AMENDMENTS TO FBC 2004.
  
 30- STORM SHUTTERS:
 A) PROVIDE CLEAR AND LEGIBLE DRAWINGS.
 B) PROVIDE KEY PLAN AND COMPLETE INSTALLATION
 SCHEDULE.SEE ATTACHED SAMPLE OF INSTALLATION
 SCHEDULE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561) 805-6712

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-05 Cont ID  
Sent By btrobaug Date 2006-10-05 Time 14:21 Rev Time 0.50
Received By btrobaug Date 2006-10-05 Time 14:02 Sent To P
Notes
2006-10-05 00:00:00 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE ENGINEER OF RECORD SHALL INDICATE
 INFORMATION REQUIRED BY 61G15-23.002
 FLORIDA ADMINISTRATIVE CODE. ALSO SEAL
 ALL SHEETS.
  
 2} SUBMIT A PANEL SCHEDULE PER 408.4 NEC
 AND 106.3.5.4(8) FBC.
  
 3} PROVIDE A LOAD CALCULATION PER
 220.31, INCLUDE ADDED LOADS.
  
 4} INDICATE THE RATING OF EXISTING
 SERVICE . 215.5 NEC.
  
 5} SMOKE DETECTORS MUST BE INSTALLED TO
 COMPLY WITH R313.1 RESIDENTIAL FLORIDA
 BUILDING CODE.
  
 6} BATH CIRCUIT REQUIRED TO HAVE A 20
 AMP RECEPTACLE PER 210.11(C)(3), LOCATED
 PER 210.52(D), AND BE GFI PROTECTED PER
 210.8(A)(1). INDICATE SAME ON PLAN.
  
 7} 210.52(E) OUTDOOR OUTLETS. FOR A
 ONE-FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET
 ACCESSIBLE AT GRADE LEVEL AND NOT MORE
 THAN 2.0 M (61/2 FT) ABOVE GRADE SHALL
 BE INSTALLED AT THE FRONT AND BACK OF
 THE DWELLING. SEE 210.8(A)(3).
  
 PLEASE NOTE AN ELECTRICAL PERMIT IS
 REQUIRED FOR THE SCOPE OF WORK PURPOSED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-02 Cont ID  
Sent By adarroug Date 2006-10-02 Time 12:15 Rev Time 0.00
Received By adarroug Date 2006-10-02 Time 12:15 Sent To E
Notes
2006-10-02 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-17 Cont ID  
Sent By jgomez Date 2006-10-17 Time 18:01 Rev Time 0.00
Received By jgomez Date 2006-09-26 Time 11:04 Sent To  
Notes
2006-09-26 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-16 Cont ID  
Sent By tgordon Date 2006-10-16 Time 16:01 Rev Time 0.25
Received By tgordon Date 2006-10-16 Time 16:01 Sent To B
Notes
2006-10-16 16:08:47*** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS, PER
 2004 FBC 13-101.2.2.
  
 2) NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW, PLEASE SUBMITT MECHANICAL PLANS
 FOR REVIEW, PER 2004 FBC /CITY WPB
 AMEND. 106.3.5.4(10) .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-10-16 Cont ID  
Sent By jleech Date 2006-10-16 Time 14:34 Rev Time 0.00
Received By jleech Date 2006-10-16 Time 14:34 Sent To M
Notes
2006-10-16 15:16:29DENIED;
 1. SEE ELECTRICAL PLAN REVIEW NOTE # 1.
 2.RISER DIAGRAM DOES NOT MEET CODE.
 A) NO HOUSE TRAP REQUIRED.
 B) FIRST LAVATORY IS DOUBLE TRAPPED.
 C) VENTS ARE NOTDRAWN TO CODE.
 D) AUTOMATIC CLOTHES WASHER NOT HOOKED TO THE
 DRAINAGE SYSTEM
 AND THE BRANCH DRAIN IS REQUIRED TO BE 3"
 SECTION 406.3.
 E) RAIN LEADER FROM ROOF NOT PERMITED TO DRAIN
 INTO
 THE SEWER SYSTEM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2006-09-29 Cont ID  
Sent By mmclean Date 2006-09-29 Time 14:13 Rev Time 0.00
Received By mmclean Date 2006-09-29 Time 14:13 Sent To I
Notes
2006-09-29 00:00:00DENIED,
 1. THE PROPSED WORK SHOWN ON SITEPLAN
 DOES NOT PROVIDE THE SETBACKS (SIDES)
 2. THE SUBMITTED SITEPLAN DOES NOT
 PROVIDE THE ADDRESS OF THE PROPERTY AND
 SHOW THE FRONT SETBACK OF THE EXISTING
 STRUCTURE FROM PROPERTY LINE.
 3. PLEASE SHOW ON TWO COPIES OF SURVEYS
 THE PROPOSED ADDITION WITH SETBACKS
 (SIDES).
 4. SITEPLAN SUBMITTED DOES NOT PROVIDE
 ALL INFORMATION NEEDED TO DO A COMPLETE
 REVIEW OF THE PROPOSED WORK.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720