| 2006-10-06 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 2- WIND LOAD SCHEDULE IS NOT REQUIRED |
| | FOR BUILDING WITH MEAN ROOF HEIGHT LESS |
| | THAN 30'-0". CONTRACTOR MAY USE TABLE |
| | 1609.6B OF 2004 FBC TO DETERMINE DESIGN |
| | PRESSURES. IF SUBMITTING ENGINEER'S WIND |
| | LOAD SCHEDULE, THEN ALL COPIES MUST HAVE |
| | ORIGINAL SEAL, SIGNATURE AND DATE AS |
| | REQUIRED BY CHAPTER 471 FL STATUTES. |
| | |
| | 3- STORM PANELS: |
| | A) PROVIDE CLEAR AND LEGIBLE DRAWINGS. |
| | B) FASTENER SPECIFIED ON INSTALLATION |
| | SCHEDULE TO MATCH FASTENER SPECIFIED ON |
| | DRAWINGS. |
| | C) FASTENER SPACING MUST BE REDUCED IF |
| | EDGE DISTANCE IS 2". SEE PAGE 11 OF 17 |
| | OF DRAWINGS AND USE SPECIFIED |
| | MULTIPLIER. |
| | D) PANELS ARE 103" LONG. CONTRACTOR |
| | MARKED INSTALLATION SCHEDULE ON PAGE 10 |
| | OF 17. THIS SCHEDULE IS FOR PANELS UP TO |
| | 8'-0" LONG. MARK CORRECT INSTALLATION |
| | SCHEDULE ON PAGE 11 OF 17. |
| | |
| | 4- ACCORDION SHUTTERS: |
| | A) FLORIDA PRODUCT APPROVAL FL1850-R1 |
| | CALLS FOR DRAWING NO 05-195. DRAWING |
| | SUBMITTED IS 05-196. PROVIDE CORRECT |
| | DRAWING THAT WAS SUBMITTED FOR FLORIDA |
| | PRODUCT APPROVAL. |
| | B) CONTRACTOR MARKED INSTALLATION |
| | SCHEDULE ON PAGE 11 OF 14 FOR SPAN UP TO |
| | 7'-0". PANEL SPAN FOR OPENING #3 IS 91". |
| | REVISE AS REQUIRED. |
| | C) REDUCE FASTENER SPACING AS REQUIRED |
| | WHEN EDGE DISTANCE IS 2". SEE PAGE 11 OF |
| | 14 FOR MULTIPLIER TO BE USED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |