Plan Review Details - Permit 06090766
Plan Review Stops For Permit 06090766
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-12-23 Cont ID  
Sent By mjacobs Date 2006-12-23 Time 13:21 Rev Time 0.00
Received By mjacobs Date 2006-12-23 Time 12:43 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-09 Cont ID  
Sent By mjacobs Date 2006-11-09 Time 14:45 Rev Time 0.00
Received By mjacobs Date 2006-11-08 Time 16:48 Sent To PC
Notes
2006-11-08 18:34:29BUILDING PLAN REVIEW
 PERMIT: 06090766
 ADD: 615 MONROE DR
 CONT:MTC REMODELING INC.
 TEL: (561)655-5956
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW2ND
 ACTION: DENIED
  
 1) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
  
 2)FBC. 1609.1.4STRUCTURAL MEMBERS AND SYSTEMS AND
 COMPONENTS AND CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED OVERTURNING,
 UPLIFT AND SLIDING AND TO PROVIDE CONTINOUS LOAD PATHS
 FOR THESE FORCES TO THE FOUNDATION.HOW WILL THE
 PRECAST CONCRETE BE ANCHORED IN THE GROUND?IF THE
 PRECAST CONCRETE WILL BE PLACE ON GRADE PROVIDE THE
 ENGINEERING DRAWINGS WHIC STATE THAT THIS DESIGW WILL
 MEET THE 140MPH 3SEC WIND GUST.
  
 3)ONCEAGAIN THE DRAWINGS SUBMITTED ARE NOT CLEAR.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVENT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. FBC. 106.1.1
  
 4)SHOW THE FRONT/ LEFT AND RIGHT ELEVATIONS OF THE
 PROJECT. THE DRAWINGS PROVIDEDARE NOT DRAWN TO THE
 SCALE SPECIFIED. THE DETAIL DRAWINGS ON THE SHEET ARE
 INSUFFICIENT. INDICATE THE LOAD OF THE DECK ACCORDING
 TO TABLE 1607.1
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-18 Cont ID  
Sent By mjacobs Date 2006-10-18 Time 11:27 Rev Time 0.00
Received By mjacobs Date 2006-10-18 Time 07:42 Sent To PC
Notes
2006-10-18 11:27:19BUILDING PLAN REVIEW
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1) W.P.B. AMENDMENTS106.1.3.BUILDING PLANS SHALL BE
 DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL
 PAPER. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUED SUCH
 THINGS AS MINIMUM SIZE SHAPE,CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
  
 2) THE DRAWINGS FOR THE FOOTERS AND THE STEPS ARE NOT
 CLEAR. SUBMIT CLEAR DETAILS OF THE FOOTERS AND STEPS.
 IF THE DECK WILL BE COVERED, A ROOFING DETAIL WILL BE
 REQUIRED SHOWING THE SLOPE OF THE ROOF AND ALL
 MATERIALS WHICH WILL BE USED ON THE ROOF. SUBMIT THE
 FRONT REAR AND SIDE ELEVATIONS OF THIS PROJECT FOR
 CLARITY.
  
 3) R312.1 GUARDS REQUIRED.
 PORCHES, BALCONIES OR RAISED FLOOR SURFACES LOCATED
 MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR OR GRADE
 BELOW SHALL HAVE GUARDS NOT LESS THAN 36 INCHES (914
 MM) IN HEIGHT. OPEN SIDES OF STAIRS WITH A TOTAL RISE
 OF MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR OR
 GRADE BELOW SHALL HAVE GUARDS NOT LESS THAN 34 INCHES
 (864 MM) IN HEIGHT MEASURED VERTICALLY FROM THE NOSING
 OF THE TREADS .
  
 4) IF THE ROOF IS A FLAT DECK, A ROOFING CONTRACTOR
 WILL HAVE TO DO THE WORK. PRODUCT APPROVAL IS REQUIRED
 FOR THE ROOFING MATERIALS.
  
 5) 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVENT LAWS, ORDINANCES,RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-12-19 Cont ID  
Sent By adarroug Date 2006-12-19 Time 10:08 Rev Time 0.00
Received By adarroug Date 2006-12-19 Time 10:08 Sent To B
Notes
2006-12-19 10:09:05TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-08 Cont ID  
Sent By adarroug Date 2006-11-08 Time 13:32 Rev Time 0.00
Received By adarroug Date 2006-11-08 Time 13:32 Sent To B
Notes
2006-11-08 13:32:42TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-26 Cont ID  
Sent By adarroug Date 2006-10-26 Time 09:23 Rev Time 0.00
Received By adarroug Date 2006-10-26 Time 09:23 Sent To Z
Notes
2006-10-26 09:23:58TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-10-18 Time   Rev Time 0.00
Received By adarroug Date 2006-09-26 Time 13:30 Sent To  
Notes
2006-09-26 00:00:00TO "MISC" BOX#2

Review Stop Z ZONING
Rev No 2 Status P Date 2006-11-04 Cont ID  
Sent By mmclean Date 2006-11-04 Time 13:47 Rev Time 0.00
Received By mmclean Date 2006-11-04 Time 13:47 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-09-25 Cont ID  
Sent By mmclean Date 2006-09-25 Time 16:42 Rev Time 0.00
Received By mmclean Date 2006-09-25 Time 16:42 Sent To I
Notes
2006-09-25 00:00:00DENIED,
 1. PLEASE SHOW THE PROPOSED WORK CLEARLY
 ON THE TWO COPIES OF SURVEYS.
 2. NEED TO KNOW THE SIDE SETBACK (HOW
 FAR THE DECK WILL BE FROM THE SIDE
 PROPERTY LINE.
 3. PLEASE INDICATE IF THERE WILL BE A
 FUTURE ROOF ON THE PROPOSED DECK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720