| 2006-09-27 00:00:00 | ******DENIED****** |
| | REFERENCE: FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR GAS PLAN REVIEW ON THE ISOMETRIC |
| | DRAWING. |
| | |
| | 1. PER FBC-2004 CHAPTER 1, SECTION |
| | 106.1, SUBMITTAL DOCUMENTS: CONSTRUCTION |
| | DOCUMENTS SHALL BE SUBMITTED IN TWO OR |
| | MORE SETS. |
| | NOTE: ONLY ONE SET OF DRAWINGS AND |
| | APPLIANCE SUBMITTALS WERE SUBMITTED. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | NOTE: PLEASE CLAIFY WHAT S.S. IS. DO YOU |
| | MEAN CSST? |
| | |
| | 3. TYPE OF GAS, (LP OR NATURAL) |
| | |
| | 4. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | |
| | 5. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | 6. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | |
| | 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2 |
| | NOTE: IF GAS SYSTEM PRESSURE IS 2LB NEED |
| | SHEETS ON MP REGULATORS. |
| | |
| | 8. FBC-2004 CHAPTER 1,SECTION |
| | 106.3.4.2: THE PERSON RESPONSIBLE FOR |
| | THE DESIGN OF THE DRAWING SHALL CLEARLY |
| | PRINT AND SIGN NAME, AND ALSO DATE |
| | DRAWING. PLEASE DO THIS PRIOR TO |
| | RESUBMITTING. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |
| | |
| | |
| | |
| | |