Plan Review Details - Permit 06090700
Plan Review Stops For Permit 06090700
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-10-02 Cont ID  
Sent By lursu Date 2006-10-02 Time 12:38 Rev Time 0.00
Received By lursu Date 2006-10-02 Time 12:37 Sent To  
Notes
2006-10-02 00:00:00EXT #0020 WAS CREATED FOR UNIT 1203
2006-09-30 00:00:00NEEDS FOR NEW SPACE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-04-02 Cont ID  
Sent By rmcdouga Date 2007-04-02 Time 08:23 Rev Time 0.00
Received By rmcdouga Date 2007-04-02 Time 08:22 Sent To FIRE
Notes
2007-04-02 08:24:35REVISED SHEETS A1 AND LS1 ARE OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-02-02 Cont ID  
Sent By rmcdouga Date 2007-02-02 Time 15:00 Rev Time 0.00
Received By rmcdouga Date 2007-02-02 Time 15:00 Sent To  
Notes
2007-02-02 15:02:00REVISED PAGES A1, A2, LS1 ARE OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-12-12 Cont ID  
Sent By rmcdouga Date 2006-12-12 Time 16:19 Rev Time 0.00
Received By rmcdouga Date 2006-12-12 Time 16:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-03 Cont ID  
Sent By rmcdouga Date 2006-11-03 Time 11:45 Rev Time 0.00
Received By rmcdouga Date 2006-11-03 Time 11:45 Sent To  
Notes
2006-11-03 15:11:39 
 DENIED BY BUILDING
  
 1) THE LEVEL OF ALTERATION FOR THIS PROJECT IS LEVEL 2,
 NOT LEVEL 1. PLEASE CORRECT ON SHEET A.0. SEE 2004 FBC
 EXISTING BUILDING CODE SECTION 304.
  
 2) ON SHEET LS.1, THE CONSTRUCTION TYPE IS INCORRECTLY
 SPECIFIED AS TYPE V-B. THE CONSTRUCTION TYPE LISTED ON
 SHEET A.0 IS TYPE I-A. PLEASE CORRECT.
  
 3) ON LS.1, THE OCCUPANT LOAD CALCULATIONS ARE
 INCORRECT. THE OCCUPANCY IS BUSINESS NOT MERCANTILE.
 THE FLOOR AREA FOR OCCUPANT IS 100 GROSS. SEE FBC TABLE
 1004.1.2. PLEASE CORRECT.
 AREA IS 3000 SQFT DIVIDED BY 100 WHICH EQUALS 30
 PERSONS.
  
 4) THE REQUIRED EGRESS WIDTH IS 30 TIMES 0.2EQUALS 6
 INCHES. HOWEVER, FBC 1008.1.1 REQUIRES EGRESS DOORS TO
 HAVE A MINIMUM CLEAR WIDTH OF 32 INCHES. SEE NOTATIONS
 ON SHEET LS.1 OF ONE OF THE PLAN SETS.
  
 5)ON SHEETS ET.1 AND D.1 PORTIONS OF THE EXISTING
 WALLS APPEAR TO BE MISSING. PLEASE CORRECT.
  
 6)SPECIFY THE FIRE RATING OF THE NEW WALLS THAT ARE
 PART OF THE EXISTING FIRE RATED CORRIDOR. INDICATE
 THESE WALLS ON THE PLANS. PROVIDE WALL SECTIONS AND
 ASSEMBLY NUMBERS.
  
 7) SPECIFY THE REQUIRED FIRE RATING OF THE TWO NEW
 EGRESS DOORS IN THE FIRE RATED CORRIDOR. PROVIDE ID
 TAGS FOR THE DOORS THAT WILL TIE THEM TO THE DOOR
 SCHEDULE ON SHEET A.4.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-28 Cont ID  
Sent By rmcdouga Date 2006-09-28 Time 12:47 Rev Time 0.00
Received By rmcdouga Date 2006-09-28 Time 07:07 Sent To  
Notes
2006-09-28 00:00:00DENIED BY BUILDING
  
 1) SPECIFY THE LEVEL OF ALTERATION FOR
 THE WORK AS SPECIFIED IN THE 2004 FBC
 EXISTING BUILDING CODE.
  
 2) SPECIFY THE BUILDING HEIGHT AND
 NUMBER OF STORIES.
  
 3) THE CONSTRUCTION TYPE SPECIFIED FOR
 THIS BUILDING IS INCORRECT. SEE 2004 FBC
 TABLE 503 FOR ALLOWABLE HEIGHTS AND
 AREAS.
  
 4) ON SHEET LS.1, THE OCCUPANCY TYPE AND
 OCCUPANT LOAD ARE INCORRECT. SEE FBC 302
 AND TABLE 1004.1.2.
  
 5) SUBMIT A DEMOLITION PLAN OR FLOOR
 PLAN SHOWING THE EXISTING CONDITION OF
 THE SPACE PRIOR TO THE PROPOSED
 CONSTRUCTION.
  
 6) ON SHEET LS.1 THE MAXIMUM DEAD END
 CORRIDOR IS INCORRECTLY SPECIFIED AS 5'.
 SEE FBC 1016.3 EXCEPTION (2) WHICH
 ALLOWS 50' MAX DEAD END CORRIDOR LENGTH
 IN FULLY SPRINKLERED BUSINESS
 OCCUPANCIES.
  
 7) FBC TABLE 803.5 REQUIRES INTERIOR
 WALL AND CEILING FINISHES TO BE CLASS B
 IN VERTICAL EXITS AND EXIT PASSAGEWAYS.
 PLEASE REVISE ON SHEET A.1.
  
 8) THE DOOR AT THE SHOWER ROOM CAN NOT
 SWING INTO THE REQUIRED FLOOR SPACE FOR
 THE LAVATORY. SEE FBC 11-4.23.2.
  
 9) THE BREAKROOM CABINET ELEVATION ON
 LS.1 SPECIFIES THE 2001 FBC. PLEASE
 UPDATE TO 2004 FBC.
  
 10) ON LS.1 THE BREAKROOM CABINET
 ELEVATION DOES NOT CORRESPOND TO THE
 FLOOR PLANS. PLEASE CORRECT. THE DOOR
 ALSO SWINGS INTO THE CLEAR FLOOR SPACE
 AT THE SINK.
  
 11) FBC 11-4.24.4 LIMITS SINKS TO A
 MAXIMUM DEPTH OF 6-1/2 INCHES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-02-21 Cont ID  
Sent By dpalmer Date 2007-02-21 Time 18:43 Rev Time 0.00
Received By dpalmer Date 2007-02-21 Time 18:20 Sent To PC
Notes
2007-02-21 18:44:06REV'S OK, STAMPED

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-01-08 Cont ID  
Sent By dpalmer Date 2007-01-08 Time 07:19 Rev Time 0.00
Received By dpalmer Date 2007-01-07 Time 19:54 Sent To PC
Notes
2007-01-08 07:19:52STAMPED, AND WILL NEED NEW NOC, AS THE NOC FROM SEPT
 HAS EXPIRED. FS 713.13(2).
2007-01-07 19:55:532007-01-07 19:55:53
 REMOVED FROM INCOMING. IN ELEC FOR REVIEW.
  
 **PREVIOUS STAMPED PLUMING SHEETS INSERTED IN SETSAND
 REMOVED REVISED SHEETS ON 1/5 BY CONTRACTOR.. WILL
 SUBMIT REVISED PLUMBING AFTER PERMIT IS ISSUED.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-12-08 Cont ID  
Sent By dpalmer Date 2006-12-08 Time 07:24 Rev Time 0.00
Received By dpalmer Date 2006-12-07 Time 20:25 Sent To  
Notes
2006-12-08 07:53:38****UNSAT 3RD REIVEW *****
  
 *** PLEASE KNOW AS SOME ITEMS WERE ADDRESSED FOR THE
 MOST PART HOWEVER THERE ARE SOME ITEMS WHICH DO NOT
 CORRELATE OR NOT CLEAR FROM PREVIOUS REVIEW.
  
  
 1) NOTE: PLEASE SHOW THE ATTACHMENT POINT FOR THE
 TRANSFORMER. BLDG STEEL, EXISTING GROUNDING ELECTRODE
 SYSTEM/RISER IN BLDG ELECTRICAL ROOM?
 250.30, 250.50, 250.58
 BY PLACING THE CONDUCTOR SIZE ON RISER THIS DOES
 INDICATE THE ATTACHMENT LOCATION AS PREVIOUSLY
 REQUESTED.
  
 2) NOTE: PLEASE CORRELATE RISER AND PANEL SCHEDULE FOR
 FEEDERS TO THE TRANSFORMER.
 PLEASE SEE RISER SHOWS #6'S AND THE PANEL SCHEDULE
 SHOWS #8'S.
 FBC 106.1.2,
 310.16
  
 3) NOTE: PLEASE SEE LIGHTING POWER DENSITIES ARE NOT
 COMPLETED AND SHALL BE INDICATE BY THE DESIGNER. THE
 "BLOCK" SHOWING LPD'S PERMITTED IS NOT COMPLETE AT THIS
 TIME.
 13-415.2, 13-415.2.ABC.1
  
 4) NOTE: PLEASE SEE THERE IS NO LIGHTING CONTACTOR
 DETAIL, SCHEDULE SHOWN AS STATED IN NOTE #3 OF THE KEY
 NOTES.
 PLEASE SEE NO LCP/LCC IS SHOWN NEXT TO ELECTRICAL PANEL
 AS STATED IN NOTE ALSO.
 AS STATED IN THE PREVIOUS REVIEW, PLEASE PROVIDE DETAIL
 FOR THIS. PLEASE KNOW, ON THIS DETAIL THE EM/EXT LTS
 WILL BE SHOWN WIRED AHEAD OF ANY LIGHTING CONTROL PANEL
 OR CONTACTOR, AS NOTED IN NOTE #4 OF KEY NOTES PER
 700.12E
  
 **** ONCE ALL REVIEWS ARE DONE, AND "IF" ALL THE OTHER
 REVIEWS HAVE PASSED PLEASE HAVE THE GENERAL CONTRACTOR
 CONTACT THIS REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-12-08 06:57:46IN PROGRESS
2006-12-07 20:26:11REMOVED FROM INCOMING, IN ELECTRIC FOR REVIEW. WILL BE
 SENT BACK TO INCOMING ONCE REVIEW IS DONE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-10-28 Cont ID  
Sent By dpalmer Date 2006-10-28 Time 11:42 Rev Time 0.00
Received By dpalmer Date 2006-10-27 Time 21:13 Sent To  
Notes
2006-10-28 11:42:55*** UNSAT 2ND REVIEW***
  
 ** PLEASE SEE SOME NOTE SNOTES FROM PREVIOUS REVIEW AND
 SEE NEW NOTE ADDED TO THE BOTTOM OF NOTES.
 PLEASE SEE NOTES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS
 REVIEW.
 PLEASE SEE NEW NOTE DUE TO CHANGES IN RISER FROM
 PREVIOUS REVIEW.
  
  
 1)A) NOTE: NO, PLEASE SEE NOW SOME SHEETS SHOW #
 1101??
 PLEASE CORRELATE AND BE SURE WORK AND SCOPE OF WORK IS
 LOCATED IN ONE AREA. PLEASE ADJUST PERMIT APPLICATION
 IF NEEDED AND PLEASE BE SURE TO CORRELATE PLANS. PLEASE
 SEE PLANS SHOWS 1203 ON SOME SHEETS AND 1101 ON
 OTHERS???
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE SUITE/UNIT # STILL
 NEEDS TO BE VERIFIED. PLEASE KNOW, ONCE
 THE SUITE CORRELATES, THEN PLEASE
 ADJUST. PLEASE SEE PLANS INDICATE 1201,
 THE PERMIT APPLICATION MENTIONS 1203.
 COPY OF PERMIT APPLICATION HAS BEEN SENT
 TO ADDRESSING.
  
 1) NOTE: OK.
  
 2) NOTE:NO, QUOTING THE SAME CODE GIVEN IN NOTES IN
 LIEU OF TECHNICAL DETAIL OR INFORMATION IS NOT
 PERMITTED.
 PLEASE SEE RISER IS STILL SHOWING A NEUTRAL FROM THE
 PANEL "HP" TO TRANSFORMER.
 SEE NEW NOTES FOR CONDUCTORS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE THE GROUNDING
 ELECTRODE CONDUCTOR AND ATTACHMENT FOR
 THE NEW TRANSFORMER. PER 250.66,250.24,
 250.30, 250.20 ETC.
  
 3) NOTE: OK SEEMS DOORS ARE REMOVED HOWEVER SEE THE
 NEXT COMMENT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE TRANSFORMER LOCATION
 MAY NOT BE LOCATED IN A STORAGE CLOSET.
 PLEASE SEE MIN CLEARANCES PER
 450.9,450.13, 110.26 ETC.
  
 4) NOTE: NO, THIS IS THE SAME NOTE. PLEASE SEE THE
 LENGTH OF TAPPED CONDUCTORS FROM TRANSFORMER DOES NOT
 MEET PREVIOUS NOTE .
 PLEASE SEE 240.21, THE MCB WAS ADDED TO "LP1" HOWEVER
 THE LENGHT OF CONDUCTORS WOULD FARTHER THAN 10FT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE ALSO SEE 240.21 AS THE
 DISTANCE OF THE TAPPED CONDUCTORS FROM
 THE SECONDARY SIDE OF THE TRANSFORMER
 DOES NOT SEEM TO MEET CODE. PLEASE SEE
 10FT OF CONDUCTOR TAP RULE.
 PLEASE SEE IT IS UNCLEAR OF THE PANEL
 LP1 CONTAINS A MCB WITH OCP??
 408.16, 240.21
  
 5) NOTE: OK.
  
 6) NOTE:NO, NO INFORMATION SHOWN FOR NOTE #3 OF KEY
 NOTES ON LIGHTING PLAN.??
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE MINIMUM LIGHTING
 CONTROL SYSTEM AS PROPOSED IN NOTE #3 OF
 KEY NOTES, NEEDS TO BE SHOWN. PLEASE
 ALSO SEE SOME AREAS OF INGRESS AND
 EGRESS SPACE REQUIRES THE OVER-RIDE
 DEVICES SO THAT THE OCCUPANT CAN SEE THE
 LIGHTING WHICH IS BEING OVER-RIDDEN.
 PLEASE PROVIDE THESE DEVICES AT THE
 LOCATION(S) AS MENTIONED.
 PLEASE VERIFY THE RECEPT/WORK OFFICE
 STATION AREA, AS THIS AREA SEEM TO HAVE
 ONE OCCUPANT SENSOR TYPE DEVICE WHICH
 OPERATES LT'S IN ANOTHER ARE. THIS WAS
 RED-LINED ON PLANS.
 PLEASE PROVIDE MIN LIGHTING DENSITIES
 BEING AS SHOWN .
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND
 .1.3.
 PLEASE SEE 13-415.2.ABC.1, AND TABLES.
  
 7) NOTE:NO, AND PLEASE SEE NEW NOTES AS MAIN HAS
 CHANGED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE STATE THE AIC RATING TO
 NEW MAIN DISCONNECT. 110.9., 240.12
  
 *** NEW NOTE ***
  
 8) NOTE: PLEASE SEE NOTE BELOW WHICH WAS AS***
 IMPORTANT*** HOWEVER THIS WAS NOT DONE. PLEASE KNOW IF
 PLANS COME BACK WITH THE OLD/VOIDED SHEETS IN SETS,
 PLANS WILL BE PLACED OUT FRONT FOR PICK UP UNTIL THIS
 IS DONE.
 PLEASE KNOW AS PREVIOUSLY MENTIONED, THIS ONLY DELAYS
 THE REVIEW PROCESS AND ISSUANCE OF PERMIT.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 9) NOTE: PLEASE SEE RISER HAS NOW CHANGED TO 150A'S,
 YET PANEL "H" REMAINS 100A'S??
 PLEASE SEE PREVIOUS PLANS SHOWED 100A MAIN.
 PLEASE CORRELATE, RISER PANEL SCHEDULE CONDUCTORS ETC
 ETC.
  
 10) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2006-10-27 21:16:04*** IN ELECTRICAL FOR REVIEW***
  
  
 ALL OLD/VOIDED SHEETS WHICH WERE REQUESTED TO BE
 REMOVED ON PREVIOUS REVIEW WERE NOT.
 PLEASE KNOW, THIS ONLY CAUSES DELAYS IN REVIEWING AND
 STAMPING OF PLANS AS PREVIOUSLY NOTED.
 THIS WAS NOTED AS** IMPORTANT**.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-30 Cont ID  
Sent By dpalmer Date 2006-09-30 Time 12:38 Rev Time 0.00
Received By dpalmer Date 2006-09-29 Time 20:23 Sent To  
Notes
2006-09-30 00:00:00*** UNSAT ***
  
  
 1)A) NOTE: PLEASE SEE SUITE/UNIT # STILL
 NEEDS TO BE VERIFIED. PLEASE KNOW, ONCE
 THE SUITE CORRELATES, THEN PLEASE
 ADJUST. PLEASE SEE PLANS INDICATE 1201,
 THE PERMIT APPLICATION MENTIONS 1203.
 COPYOF PERMIT APPLICATION HAS BEEN SENT
 TO ADDRESSING.
  
 1) NOTE: PLEASE VERFIFY MISSING
 EQUIPMENT GROUNDING CONUDCTOR FROM
 BUS-TAP DISC TO THE METER. PLEASE ALSO
 INDICATE "FLOATING NEUTRAL" AT THE METER
 AT THIS IS AFTER THE FIRST MEANS OF
 DISCONNECT FOR TRHE BUILDING.
 250.6,250.24., 250.110, 250.122
  
 2) NOTE: PLEASE INDICATE THE GROUNDING
 ELECTRODE CONDUCTOR AND ATTACHMENT FOR
 THE NEW TRANSFORMER. PER 250.66,250.24,
 250.30, 250.20 ETC.
  
 3) NOTE: PLEASE SEE TRANSFORMER LOCATION
 MAY NOT BE LOCATED IN A STROAGE CLOSET.
 PLEASE SEE MIN CLEARENCES PER
 450.9,450.13, 110.26 ETC.
  
 4) NOTE: PLEASE ALSO SEE 240.21 AS THE
 DISTANCE OF THE TAPPED CONDUCTORS FROM
 THE SECONDARY SIDE OF THE TRANSFORMER
 DOES NOT SEEM TO MEET CODE. PLEASE SEE
 10FT OF CONDUCTOR TAP RULE.
 PLEASE SEE IT IS UNCLEAR OF THE PANEL
 LP1 CONTAINS A MCB WITH OCP??
 408.16, 240.21
  
 5) NOTE: PLEASE SEE PLANS FROM A- SHEETS
 TO MEP, SEEM TO INDICATE A "STACKABLE
 WASHER/DRYER UNTI , HOWEVER THE LOAD
 CALCULATIONS AND ELECTRICAL PLANS DO NOT
 SEEM TO CORRELATE WITH THIS. PLEASE
 VERIFY AND ADJUST.
 ** PLEASE KNOW, UNDER THE NEW 2005 CODE
 WHICH IS NOT YERT IN EFFECT, THIS WOULD
 REQUIRE BOTH OF THESE CIRCUITS OR EVEN
 ONE TO BE GFI PROTECTED. THIS IS ONLY
 FOR INFORMATIONAL PURPOSE AS THIS
 PROJECT IS UNDER THE 2002 NEC.
  
 6) NOTE: PLEASE SEE THE MINIMUM LIGHTING
 CONTROL SYSTEM AS PROPOSED IN NOTE #3 OF
 KEY NOTES, NEEDS TO BE SHOWN. PLEASE
 ALSO SEE SOME AREAS OF INGRESS AND
 EGRESSINTO SPACE REQUIRES THE OVER-RIDE
 DEVICES SO THAT THE OCCUPANT CAN SEE THE
 LIGHTING WHICH IS BEING OVER-RIDEN.
 PLEASE PROVIDE THESE DEVICES AT THE
 LOCATION(S) AS MENTIONED.
 PLEASE VERIFY THE RECEPT/WORK OFFICE
 STATION AREA, AS THIS AREA SEEM TO HAVE
 ONE OCCUPANT SENSOR TYOE DEVICE WHICH
 OPERATES LTS IN ANOTHER ARE. THIS WAS
 REDLINED ON PLANS.
 PLEASE PROVIDE MIN LIGHTING DENSITIES
 BEING AS SHOWN .
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND
 .1.3.
 PLEASE SEE 13-415.2.ABC.1, AND TABLES.
  
 7) NOTE: PLEASE STATE THE AIC RATING TO
 NEW MAIN DISCONNECT. 110.9.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
2006-09-29 00:00:00IN ELEC FOR REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-04-02 Cont ID  
Sent By mawillia Date 2007-04-02 Time 11:27 Rev Time 0.00
Received By mawillia Date 2007-04-02 Time 11:17 Sent To  
Notes
2007-04-02 11:20:28*****REVISIONS OF 03/28/2007 APPROVED*****
  
 SHEET LS.1 WAS STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-02-12 Cont ID  
Sent By mawillia Date 2007-02-12 Time 11:45 Rev Time 0.00
Received By mawillia Date 2007-02-12 Time 11:45 Sent To  
Notes
2007-02-12 11:48:33*****REVISIONS OF 01/30/2007 APPROVED*****
  
 SHEET LS.1 WAS STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-12-12 Cont ID  
Sent By mawillia Date 2006-12-12 Time 14:14 Rev Time 0.00
Received By mawillia Date 2006-12-12 Time 14:14 Sent To  
Notes
2006-12-12 14:16:56*****APPROVED*****
  
  
 TO BE STAMPED WHEN ALL OTHER PLAN REVIEW COMMENTS HAVE
 BEEN ADDRESSED

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-10-30 Cont ID  
Sent By mawillia Date 2006-10-30 Time 10:39 Rev Time 0.00
Received By mawillia Date 2006-10-30 Time 10:39 Sent To  
Notes
2006-10-30 10:56:29*****UNSAT*****
  
  
  
 YOUR RESPONSES TO PREVIOUS FIRE PLAN REVIEW COMMENTS OF
 10/03/06 WERE RECEIVED AS FOLLOWS:
  
  
 1.OK
  
 2.OK
  
 3.OK
  
 4.SO NOTED
  
 5.SO NOTED
  
 6.SO NOTED
  
 7.OK
  
 8.THE ELECTRICAL SHEETS THAT ARE TO BE REFERENCED
 REFLECT SUITE 1101, NOT 1203.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-03 Cont ID  
Sent By mawillia Date 2006-10-03 Time 10:52 Rev Time 0.00
Received By mawillia Date 2006-10-03 Time 10:52 Sent To P
Notes
2006-10-03 00:00:00*****DENIED*****
  
  
  
 1.) VERIFY/RECTIFY THE SUITE NUMBER OF
 WHERE THE SCOPE OF THE WORK IS GOING TO
 BE DONE. THE APPLICATION HAS SUITE 1203,
 WHEREAS THE PLANS HAVE SUITE 1201.
  
 2.) STRUCTURES UNDERGOING CONSTUCTION,
 ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.
  
 3.) ACCUMULATIONS OF COMBUSTIBLE WASTE
 MATERIAL AND DUST DEBRIS SHALL BE
 REMOVED FROM THE STRUCTURE AND ITS
 IMMEDIATE VICINITY AT THE END OF THE
 SHIFT OR MORE FREQUENTLY AS NECESSARY
 FOR SAFE OPERATIONS.
  
 4.) WHERE THE BUILDING IS PROTECTED BY
 FIRE PROTECTION SYSTEMS, SUCH SYSTEMS
 SHALL BE MAINTAINED OPERATIONAL AT ALL
 TIMES DURING ALTERATION.
  
 5.) WHEN IT IS NECESSARY TO SHUT DOWN A
 FIRE PROTECTION SYSTEM, THE FIRE
 DEPARTMENT WILL BE NOTIFIED WHEN THE
 SYSTEM IS SHUT DOWN AND WHEN IT IS
 RETURNED TO SERVICE.
  
 6.) IF THE SCOPE OF THE INTERIOR
 BUILDOUT REQUIRES MODIFICATION OF THE
 FIRE SPRINKLER OR FIRE ALARM SYSTEM,
 SEPARATE PERMIT AND SHOP DRAWINGS/PLANS
 ARE REQUIRED.
  
 7.) INTERIOR FINISH FOR WALLS AND
 CEILINGS IN EXITS AND EGRESS CORRIDORS
 SHALL BE CLASS "A" OR CLASS "B".
  
 8.) INDICATE ON THE PLANS THE LOCATION
 OF FIRE PROTECTION SYSTEMS(I.E.
 SPRINKLER HEADS, SMOKE ALARMS, PULL
 STATIONS, FIRE EXTINGUISHER(S), AUDIO
 AND/OR VISUAL DEVICES, DUCT DETECTORS,
 ETC.) FOR THE EXISTING AS WELL AS THE
 PROPOSED LAYOUT OF THE TENANT SPACE.
  
  
 **PLEASE SUBMIT OR ADDRESS THE ABOVE
 INFORMATION FOR REVIEW.**
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-03-29 Cont ID  
Sent By dpalmer Date 2007-03-29 Time 20:06 Rev Time 0.00
Received By dpalmer Date 2007-03-29 Time 20:06 Sent To B
Notes
2007-03-29 20:06:28TO RMCD DESK

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-02-20 Cont ID  
Sent By adarroug Date 2007-02-20 Time 13:21 Rev Time 0.00
Received By adarroug Date 2007-02-20 Time 13:18 Sent To E
Notes
2007-02-20 13:21:32TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-02-15 Cont ID  
Sent By adarroug Date 2007-02-15 Time 13:06 Rev Time 0.00
Received By adarroug Date 2007-02-15 Time 13:06 Sent To M
Notes
2007-02-15 13:06:52TO "TGORDON" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-02-02 Cont ID  
Sent By adarroug Date 2007-02-02 Time 09:54 Rev Time 0.00
Received By adarroug Date 2007-02-02 Time 09:54 Sent To  
Notes
2007-02-02 09:54:38TO "BOB"#18

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-12-21 Cont ID  
Sent By adarroug Date 2006-12-21 Time 16:23 Rev Time 0.00
Received By adarroug Date 2006-12-21 Time 16:23 Sent To  
Notes
2006-12-21 16:24:24WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-20 Cont ID  
Sent By adarroug Date 2006-11-20 Time 16:54 Rev Time 0.00
Received By adarroug Date 2006-11-20 Time 16:54 Sent To  
Notes
2006-12-09 17:22:07TO BOB #9
2006-11-20 16:54:29WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-18 Cont ID  
Sent By adarroug Date 2006-10-18 Time 16:44 Rev Time 0.00
Received By adarroug Date 2006-10-18 Time 16:44 Sent To  
Notes
2006-10-27 14:25:03TO "BOB"#15
2006-10-18 16:44:42WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-03 Cont ID  
Sent By mawillia Date 2006-10-03 Time 10:52 Rev Time 0.00
Received By mawillia Date 2006-09-22 Time 14:19 Sent To  
Notes
2006-09-23 00:00:00TO "BOB"#15
2006-09-22 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-02-20 Cont ID  
Sent By tgordon Date 2007-02-20 Time 09:39 Rev Time 0.30
Received By tgordon Date 2007-02-20 Time 09:39 Sent To  
Notes
2007-02-20 09:40:53REVISION TO MECH. PLANS PAGE M.1 AND M.2.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-12-12 Cont ID  
Sent By tgordon Date 2006-12-12 Time 16:42 Rev Time 0.30
Received By tgordon Date 2006-12-12 Time 16:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-10-31 Cont ID  
Sent By tgordon Date 2006-10-31 Time 10:21 Rev Time 0.35
Received By tgordon Date 2006-10-31 Time 10:21 Sent To  
Notes
2006-10-31 10:23:27*** DENIED ***
 1) PLEASE SUBMIT A LETTER FROM AN
 ENGINEER THAT'S ASSOCIATED WITH THE
 CLOTHES DRYER MANUFACTURE THAT STATES
 THE USE OF A BOSTER FAN IN THE DRYER
 VENT WILL NOT VOID THE DRYERS WARRANTY.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-09-28 Cont ID  
Sent By tgordon Date 2006-09-28 Time 14:08 Rev Time 0.30
Received By tgordon Date 2006-09-28 Time 14:08 Sent To  
Notes
2006-09-28 00:00:00*** DENIED ***
 1) PLEASE SUBMIT A LETTER FROM AN
 ENGINEER THATS ASSOCIATED WITH THE
 CLOTHES DRYER MANUFACTURE THAT STATES
 THE USE OF A BOSTER FAN IN THE DRYER
 VENT WILL NOT VOID THE DRYERS WARRANTY.
  
 2) PLEASE SUBMIT DETAILED MANUFACTURE'S SPECIFICATION'S
 AND INSTALLATION
 INSTRUCTIONS FOR THE CLOTHES DRYER
 BOSTER FAN.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-02-07 Cont ID  
Sent By jleech Date 2007-02-07 Time 07:29 Rev Time 0.00
Received By jleech Date 2007-02-07 Time 07:29 Sent To  
Notes
2007-02-07 07:32:19REVISION; REDUCED SIZE OF SHOWER ROOM. STILL ADA
 COMPLIANT.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-11-08 Cont ID  
Sent By jleech Date 2006-11-08 Time 07:30 Rev Time 0.00
Received By jleech Date 2006-11-08 Time 07:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-10-03 Cont ID  
Sent By jleech Date 2006-10-03 Time 14:08 Rev Time 0.00
Received By jleech Date 2006-10-03 Time 14:08 Sent To  
Notes
2006-10-03 00:00:00DENIED;
 1.DOOR SWING IN BREAK ROOM AND SHOWER
 ROOM SWINGS INTO THE CLEAR FLOOR SPACE
 OF THE HANDICAP FIXTURES.
 2.SANITARY RISER DIAGRAM; SHOWER IS NOT
 VENTED.
 3.AUTOMATIC CLOTHES WASHER BRANCH DRAIN
 REQUIRED TO BE 3". SEE SECTION406.3.
 4.BREAK SINK NOT IN SAME LOCATION AS
 FLOOR PLAN (DETAIL ON PAGE LS.1 #3)
 5.WATER HEATER DETAIL PAGE P.1 THERMAL
 EXPANTION CONTROL REQUIRED. SECTION
 607.3 SHOW TYPE AND LOCATION.
 6.SHOW TERMINATION POINT OF PAN DRAIN
 AND RELIEF LINE, ALSO SIZE OF PIPE USED.
 7.AIR ADMITTANCE VALVES CAN ONLY BE USED
 ON THE TOP 4 BRANCH INTERVALS. SECTION
 917.3.1 IS THERE 3 FLOORS OR LESS ABOVE
 THE 12 TH FLOOR?
 8.WATER RISER DIAGRAM; SHOW WATER HANNER
 ARRESTORS WHERE REQUIRED ON PLANS AND
 SPEC OUT SIZE AND MANUFACTURE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695