Plan Review Details - Permit 06090569
Plan Review Stops For Permit 06090569
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-25 Cont ID  
Sent By rmcdouga Date 2006-09-25 Time 10:33 Rev Time 0.00
Received By rmcdouga Date 2006-09-25 Time 10:33 Sent To  
Notes
2006-09-25 00:00:00DENIED BY BUILDING
  
 1) SPECIFY THE LEVEL OF ALTERATION FOR
 THE WORK PER THE 2004 FBC EXISTING
 BUILDING CODE.
  
 2) SPECIFY THE CONSTRUCTION TYPE, NUMBER
 OF FLOORS, SPRINKLERED BUILDING, ETC.
 FOR THE BUILDING.
  
 3) PROVIDE A DETAIL OF THE NEW PARTITION
 WALLS. SPECIFY WALL TYPE.
  
 4) FBC 603.1 LIMITS THE APPLICATION OF
 COMBUSTIBLE MATERIALS IN BUILDINGS OF
 TYPE I OR II CONSTRUCTION. SHOW
 COMPLIANCE.
  
 5) THE NEW POWDER ROOM MUST COMPLY WITH
 THE FAIR HOUSING ACT DESIGN MANUAL FOR
 THE FOLLOWING. (REQUIREMENT 3) A USABLE
 DOOR WITH A NOMINAL 32" CLEAR OPENING IS
 REQUIRED, (REQUIREMENT 4) AN ACCESSIBLE
 ROUTE TO AND INTO THE POWDER ROOM IS
 REQUIRED AND (REQUIREMENT 5) A
 RECEPTACLE IN AN ACCESSIBLE LOCATION.
 SEE PAGE 7.38 OF DESIGN MANUAL.
  
 6) FAC 61G1-16.004 REQUIRES THE
 ARCHITECTURAL FIRM'S LICENSE NUMBER IN
 THE TITLE BLOCK.
  
 7) FAC 61G-16.003 REQUIRES THE ARCHITECT
 TO DATE EACH SHEET THAT THEY SIGN AND
 SEAL.
  
 8) ADDRESS COMMENTS FROM OTHER TRADES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-07-30 Cont ID  
Sent By dpalmer Date 2007-07-30 Time 14:12 Rev Time 0.00
Received By dpalmer Date   Time   Sent To PC
Notes
2007-07-30 14:14:04*** PLANS SENT BACK AS PERMIT APPLICATION TIME HAS
 EXPIRED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-24 Cont ID  
Sent By dpalmer Date 2006-09-24 Time 15:28 Rev Time 0.00
Received By dpalmer Date 2006-09-24 Time 15:18 Sent To  
Notes
2006-09-24 00:00:00***UNSAT ***
  
 1)NOTE: PLEASE SEE MISSING LICENSE
 INFORMATION REQUIRED ON TITLE BLOCKS AS
 REQUIRED PER FAC 61G1-16.004, FS 481.219
 PLEASE SEE MISSING FIRM # AKA,
 CERTIFICATE OF AUTHORIZATION NUMBER.
 THIS IS REQUIRED FOR ALL TRADES AND FOR
 ALL SHEETS WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-03 Cont ID  
Sent By mawillia Date 2006-10-03 Time 09:54 Rev Time 0.00
Received By mawillia Date 2006-10-03 Time 09:44 Sent To  
Notes
2006-10-03 00:00:00*****DENIED*****
  
  
  
 1.) ALL OTHER PLAN REVIEWER'S ISSUES
 MUST BE ADDRESSED AND/OR RECTIFIED.
  
 2.) STRUCTURES UNDERGOING CONSTRUCTION,
 ALTERTION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.
  
 3.) ACCUMULATIONS OF COMBUSTIBLE WASTE
 MATERIAL AND DUST DEBRIS SHALL BE
 REMOVED FROM THE STRUCTURE AND ITS
 IMMEDIATE VICINITY AT THE END OF THE
 SHIFT OR MORE FREQUENTLY AS NECESSARY
 FOR SAFE OPERATIONS.
  
 4.) ENTRANCES, CORRIDORS, AND EXITS ARE
 NOT BE HINDERED OR COMPROMISED BY THE
 STOCKING AND/OR DISPOSAL OF BUILDING
 MATERIALS.
  
 5.) IF THE SCOPE OF THE INTERIOR
 BUILDOUT REQUIRES MODIFICATION OF THE
 FIRE PROTECTION SYSTEM, PROVIDE SEPARATE
 PERMIT AND PLANS.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-18 Cont ID  
Sent By adarroug Date 2007-07-18 Time 08:30 Rev Time 0.00
Received By adarroug Date 2007-07-18 Time 08:30 Sent To  
Notes
2007-07-26 14:10:58TO "BOB"#8
2007-07-18 08:33:01WAITING FOR "BOB" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-03 Cont ID  
Sent By mawillia Date 2006-10-03 Time 09:54 Rev Time 0.00
Received By mawillia Date 2006-09-18 Time 14:59 Sent To  
Notes
2006-09-23 00:00:00TO "BOB"#1
2006-09-18 00:00:00WAITING FOR "BOB"

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-09-27 Cont ID  
Sent By kstevens Date 2006-09-27 Time 13:04 Rev Time 0.00
Received By kstevens Date 2006-09-27 Time 13:04 Sent To  
Notes
2006-09-27 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
  
 1. SHT A101 PER FAC 61G1-16.004(2) THE
 FIRM LICENSE NUMBER IS REQUIRED IN THE
 TITLE BLOCK. ARCHITECTS LICENSE NUMBER
 IS SHOWN. NO LICENSE NUMBER FOR EDRC
 ARCHITECTS. FS 481.219.
  
 2. THE SANITARY SYSTEM IS AN ENGINEERED
 SYSTEM, (SOVENT). CHANGE TO AN
 ENGINEERED SYSTEM SHALL BE SUBMITTED BY
 AN ENGINEER AND EXISTING RISERS SHALL BE
 SHOWN, WITH CHANGES INDICATED. SHOW ALL
 PIPE SIZES AND VENTING IF REQUIRED.
 SECTION 106.3.5.1.3.
  
 3. SUBMIT A WATER RISER DIAGRAM
 ISOMETRIC SHOWING ALL PIPE SIZES,
 VALVES, AND WATER HAMMER ARRESTORS
 REQUIRED BY SECTION 604.9. WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE
 FIXTURE IN AN, "EFFECTIVE RANGE", NOT IN
 THE CEILING. WH-PDI 201 AND MANUF.
 INSTALLATION INSTRUCTIONS.
  
 4. SHT A101 STAFF TOILET PLUMBING PLAN
 SHOWS 1-1/2" SANT. PIPING TO THE WASH
 MACHINE. PER TABLE 709.1, MINIMUM 2"
 TRAP IS REQUIRED.
  
 5. SUBMIT MANUF. SPECIFICATIONS FOR THE
 LAV AND THE W/C. PER FIGURE 405.3.1 THE
 MINIMUM CLEARNACE BETWEEN THE W/C AND
 THE LAV IS 21". PLANS INDICATE 57-1/4"
 OPENING IN ROOM AND SCALES OUT LESS THAN
 REQUIRED CLEARANCE. SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]