Plan Review Details - Permit 06090554
Plan Review Stops For Permit 06090554
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-12-19 Cont ID  
Sent By mjacobs Date 2006-12-19 Time 08:40 Rev Time 0.00
Received By mjacobs Date 2006-12-19 Time 07:25 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-11-09 Cont ID  
Sent By mjacobs Date 2006-11-09 Time 06:34 Rev Time 0.00
Received By mjacobs Date 2006-11-09 Time 06:12 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-14 Cont ID  
Sent By mjacobs Date 2006-10-14 Time 09:05 Rev Time 0.00
Received By mjacobs Date 2006-10-14 Time 07:08 Sent To PC
Notes
2006-10-14 09:05:03BUILDING PLAN REVIEW
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 3) A SEPERATE PERMIT IS REQUIRED FOR THE BABY FENCE.
 WHEN APPLYING FOR THE FENCE PERMIT ALL REQUIRED
 INFORMATION SHALL BE SUBMITTED.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-11-07 Cont ID  
Sent By btrobaug Date 2006-11-07 Time 16:51 Rev Time 0.33
Received By btrobaug Date 2006-11-07 Time 16:19 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-25 Cont ID  
Sent By btrobaug Date 2006-09-25 Time 11:56 Rev Time 0.33
Received By btrobaug Date 2006-09-25 Time 11:38 Sent To P
Notes
2006-09-25 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 THE SPECIFICATIONS INDICATE A 2HP SPA
 PUMP AND A 1 1/2HP POOL PUMP, THE
 SCHEMATIC INDICATES A POOL PUMP ONLY.
 ALSO THE LIGHT IS LISTED AS 300WATTS IN
 THE SPECS, AND 75/100 WATT LIGHTS.
 PLEASE CORRELATE AND RESUBMIT.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-11-08 Cont ID  
Sent By mperson Date 2006-11-08 Time 15:06 Rev Time 0.00
Received By mperson Date 2006-11-08 Time 15:06 Sent To B
Notes
2006-11-08 15:08:57CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2006-09-15 Cont ID  
Sent By ptjomsto Date 2006-09-15 Time 12:28 Rev Time 0.00
Received By ptjomsto Date 2006-09-15 Time 12:28 Sent To  
Notes
2006-09-15 00:00:00HISTORIC APPROVED BY PAPA

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-12-26 Cont ID  
Sent By adarroug Date 2006-12-26 Time 13:42 Rev Time 0.00
Received By adarroug Date 2006-12-26 Time 13:42 Sent To Z
Notes
2006-12-26 13:42:58TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-12-18 Cont ID  
Sent By adarroug Date 2006-12-18 Time 13:07 Rev Time 0.00
Received By adarroug Date 2006-12-18 Time 13:07 Sent To B
Notes
2006-12-18 13:07:26TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-12-13 Cont ID  
Sent By adarroug Date 2006-12-13 Time 10:24 Rev Time 0.00
Received By adarroug Date 2006-12-13 Time 10:24 Sent To Z
Notes
2006-12-13 10:24:19TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-11-07 Cont ID  
Sent By adarroug Date 2006-11-07 Time 15:03 Rev Time 0.00
Received By adarroug Date 2006-11-07 Time 15:03 Sent To E
Notes
2006-11-07 15:04:19TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-25 Cont ID  
Sent By mmiller Date 2006-10-25 Time 18:16 Rev Time 0.00
Received By mmiller Date 2006-10-25 Time 18:15 Sent To Z
Notes
2006-10-25 18:18:19SENT TO Z BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-23 Cont ID  
Sent By adarroug Date 2006-09-23 Time 15:10 Rev Time 0.00
Received By adarroug Date 2006-09-23 Time 15:10 Sent To E
Notes
2006-09-23 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-10-14 Time   Rev Time 0.00
Received By adarroug Date 2006-09-15 Time 16:23 Sent To  
Notes
2006-09-15 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-11-08 Cont ID  
Sent By mperson Date 2006-11-08 Time 15:05 Rev Time 0.33
Received By mperson Date 2006-11-08 Time 15:05 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-09-27 Cont ID  
Sent By mperson Date 2006-09-27 Time 10:47 Rev Time 0.33
Received By mperson Date 2006-09-27 Time 10:47 Sent To B
Notes
2006-09-27 00:00:00******DENIED******
 REFERENCE: FBC-2004 SEC. 424.2 OR
 FBRC-2003 SEC. 4101 SWIMMING POOLS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW:
  
 1) FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
  
 2) FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
  
 3) FBC-2004 SEC. 424.2.6.6.5, OR
 FBCR-2004 SEC. R4101.6.6.5 WHERE
 PROVIDED, THE VACUUM OR PRESSURE CLEANER
 FITTING SHALL BE LOCATED AT LEAST 6" AND
 NOT GREATER THAN 12" BELOW THE MINIMUM
 OPERATING WATER LEVEL OR AS AN
 ATTACHMENT TO THE SKIMMER.(MANUFACTURE
 SHEETS REQUIRED OR ADD MAKE AND MODEL
 NUMBER TO NOTES)
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2006-12-28 Cont ID  
Sent By mmclean Date 2006-12-28 Time 14:43 Rev Time 0.00
Received By mmclean Date 2006-12-28 Time 14:43 Sent To  
Notes
2006-12-28 14:43:38REVISION: POOL LARGER 2' AND EXPAND DECK 1'

Review Stop Z ZONING
Rev No 3 Status F Date 2006-12-16 Cont ID  
Sent By mmclean Date 2006-12-16 Time 16:20 Rev Time 0.00
Received By mmclean Date 2006-12-16 Time 16:20 Sent To I
Notes
2006-12-16 16:25:40DENIED, REVISION TO MAKE POOL 2' LARGER AND EXPAND DECK
 1'
  
 1. PLEASE SHOW THE SETBACK OF THE POOL FROM WATER'S
 EDGE TO PROPERTY LINE (SIDE). SURVEYS ARE NOT MAKED OF
 THE NEW SETBACK.
 2. PLEASE SHOW THE SETBACK OF THE DECK FROM PROPERTY
 LINE (SIDE). SURVEYS ARE NOT MARKED ON THE NEW SETBACK.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 2 Status P Date 2006-11-01 Cont ID  
Sent By mmclean Date 2006-11-01 Time 18:52 Rev Time 0.00
Received By mmclean Date 2006-11-01 Time 18:52 Sent To I
Notes
2006-11-01 18:54:13NOTE: THE PROPOSED POOL EQUIPMENT SHALL NOT BE CLOSER
 THAN 1.9FT FROM SIDE PROPERTY LINE.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-09-21 Cont ID  
Sent By mmclean Date 2006-09-21 Time 08:48 Rev Time 0.00
Received By mmclean Date 2006-09-21 Time 08:48 Sent To I
Notes
2006-09-21 00:00:00DENIED,
 1. NEED TO SHOW THE LOCATION OF THE POOL
 EQUIPMENT ON TWO COPIES OF SURVEYS.
 2. SURVEY DOES NOT SHOW THE EQUIPMENT
 LOCATION.
 3. THE POOL EQUIPMENT MUST NOT BE
 LOCATED IN THE 5FT RESERVED (U.E.)
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720