Plan Review Details - Permit 06090551
Plan Review Stops For Permit 06090551
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-12-28 Cont ID  
Sent By mjacobs Date 2006-12-28 Time 07:13 Rev Time 0.00
Received By mjacobs Date 2006-12-28 Time 05:53 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-13 Cont ID  
Sent By mjacobs Date 2006-10-13 Time 16:26 Rev Time 0.00
Received By mjacobs Date 2006-10-13 Time 11:11 Sent To PC
Notes
2006-10-13 16:26:00BUILDING PLAN REVIEW
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1) 2107.2.3 ACI 530/ASCE 5/TMS 402, SECTION
 2.1.10.6.1.1, LAP SPLICES .
 THE MINIMUM LENGTH OF LAP SPLICES FOR REINFORCING BARS
 IN TENSION OR COMPRESSION, L L D , SHALL BE CALCULATED
 BY EQUATION 21-2, BUT SHALL NOT BE LESS THAN 15 INCHES
 (380 MM).INDICATE THE EMBEDMENT DIMENTION OF THE
 JDOWELS AND THE LAP SPLICES.SHOW THE AREA OF THE NEW
 SITE WALL ON THE PLANS.
  
 2) THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*.
  
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-12-26 Cont ID  
Sent By adarroug Date 2006-12-26 Time 16:47 Rev Time 0.00
Received By adarroug Date 2006-12-26 Time 16:47 Sent To B
Notes
2006-12-26 16:47:39TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-18 Cont ID  
Sent By adarroug Date 2006-12-18 Time 11:40 Rev Time 0.00
Received By adarroug Date 2006-12-18 Time 11:40 Sent To Z
Notes
2006-12-18 11:41:01TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-23 Cont ID  
Sent By adarroug Date 2006-09-23 Time 15:11 Rev Time 0.00
Received By adarroug Date 2006-09-23 Time 15:11 Sent To B
Notes
2006-09-23 00:00:00TO "MISC" BOX#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-10-13 Time   Rev Time 0.00
Received By adarroug Date 2006-09-15 Time 16:13 Sent To  
Notes
2006-09-15 00:00:00TO "Z" BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2006-12-26 Cont ID  
Sent By mmclean Date 2006-12-26 Time 08:28 Rev Time 0.00
Received By mmclean Date 2006-12-26 Time 08:28 Sent To I
Notes
2006-12-26 08:29:42MAXIMUM HEIGHT ALLOWED WITHIN THE 25FT FRONT SETBACK IS
 4FT.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-09-21 Cont ID  
Sent By mmclean Date 2006-09-21 Time 08:22 Rev Time 0.00
Received By mmclean Date 2006-09-21 Time 08:22 Sent To I
Notes
2006-09-21 00:00:00DENIED,
 1. PLEASE SUBMIT THE EASEMENT APPROVAL
 FROM THE CITY OF WEST PALM BEACH UTILITY
 DEPT.
  
 NOTE:THE COLUMNS AND WALL CAN ONLY BE A
 MAXIMUM HEIGHT OF 4FT WITHIN THE 25FT
 FRONT SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720