Plan Review Details - Permit 06090476
Plan Review Stops For Permit 06090476
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2006-11-07 Cont ID  
Sent By lursu Date 2006-11-07 Time 09:57 Rev Time 0.00
Received By lursu Date 2006-11-07 Time 09:57 Sent To  
Notes
2006-11-07 09:58:13PERMIT WAS ATTACHED TO THE CORRECT SITE ADDRESS: 307
 EVERNIA ST

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-09-21 Cont ID  
Sent By lursu Date 2006-09-21 Time 14:41 Rev Time 0.00
Received By lursu Date 2006-09-14 Time 15:05 Sent To  
Notes
2006-09-21 00:00:00PROJECT UNDRE REVIEW. PCN IS INCORRECT.
2006-09-14 00:00:00NUMERICAL # IS INCORRECT PER CONTRACTOR
 COPY SENT TO LILY

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-04-19 Cont ID  
Sent By mawillia Date 2007-04-19 Time 12:27 Rev Time 0.00
Received By mawillia Date 2007-04-19 Time 12:12 Sent To  
Notes
2007-04-19 12:21:14*****REVISION APPROVED*****
  
  
  
 REVISION OF 03/26/07 APPROVED;PLAN SHEET FA2.1
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-11-07 Cont ID  
Sent By mawillia Date 2006-11-07 Time 09:37 Rev Time 0.00
Received By mawillia Date 2006-11-07 Time 09:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-09-25 Cont ID  
Sent By mawillia Date 2006-09-25 Time 12:37 Rev Time 0.00
Received By mawillia Date 2006-09-25 Time 12:37 Sent To  
Notes
2006-09-25 00:00:00*****UNSAT*****
  
  
  
  
  
 1.) THE PERMIT AND PLANS SHOULD REFLECT
 THE LOCALE WHERE THE ACTUAL WORK IS
 BEING DONE; WHICH IS 307 EVERNIA STREET
 NOT 310 EVERNIA STREET.
  
 2.) SINCE THE CONTRACT IS GREATER THAN
 $2500.00, THE APPLICANT SHALL FILE WITH
 THE AHJ EITHER A RECORDED NOTICE OF
 COMMENCEMENT OR A NOTORIZED STATEMENT
 THAT THE NOTICE HAS BEEN FILED FOR
 RECORDING, ALONG WITH A COPY THEREOF.
  
 3.) SINCE THE SCOPE OF THE WORK IS
 GREATER THAN $5,000.00, AS PER FLORIDA ADMINISTRATIVE
 CODES, A PROFESSIONAL
 ENGINEER SHALL SIGN HIS SEAL TO ALL
 PLANS, SPECIFICATIONS, ETC TO BE FILED
 FOR PUBLIC RECORD. THE STAMPED
 ENGINEERED SEAL SHALL HAVE THE WORDING
 "LICENSE" IN LIEU OF "CERTICATE".
  
 4.) FIRE ALARM SYSTEM TO BE FULLY
 ADDRESSABLE.
  
 5.) DUCT SMOKE DETECTORS SHALL INITIATE
 A GENERAL ALARM.
  
 6.) FIRE ALARM SYSTEM IN CONJUNCTION
 WITH FIRE SPRINKLER SYSTEM TO BE
 MONITORED.
  
 7.) WATERFLOW TO ACTIVATE GENERAL FIRE
 ALARM WITHIN 45 TO 60 SECONDS.
  
 8.) FIRE ALARM SYSTEM SHALL BE UL
 CERTIFIED FOR CENTRAL STATION. INSTALL
 UL CERTIFICATE AT THE FIRE ALARM CONTROL
 PANEL AND PROVIDE A COPY TO WPBFR BY
 FINAL FIRE ALARM INSPECTION.
  
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-09-25 Cont ID  
Sent By rbrown Date 2006-09-25 Time 12:33 Rev Time 0.00
Received By rbrown Date 2006-09-14 Time 16:57 Sent To  
Notes
2006-09-25 00:00:00INCOMING NOTES ENTERED IN FIRE REVIEW IN
 ERROR
2006-09-14 00:00:00TO "F" BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-16 Cont ID  
Sent By adarroug Date 2007-04-16 Time 13:59 Rev Time 0.00
Received By adarroug Date 2007-04-16 Time 13:59 Sent To FIRE
Notes
2007-04-16 13:59:39TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-27 Cont ID  
Sent By adarroug Date 2006-10-27 Time 16:48 Rev Time 0.00
Received By adarroug Date 2006-10-27 Time 16:48 Sent To FIRE
Notes
2006-10-27 16:48:58TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-25 Cont ID  
Sent By mawillia Date 2006-09-25 Time 12:36 Rev Time 0.00
Received By mawillia Date 2006-09-14 Time 12:31 Sent To  
Notes
2006-09-25 00:00:00TO FIRE IN-BOX