Plan Review Details - Permit 06090456
Plan Review Stops For Permit 06090456
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-09-21 Cont ID  
Sent By mawillia Date 2006-09-21 Time 17:57 Rev Time 0.00
Received By mawillia Date 2006-09-21 Time 17:57 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-09-18 Cont ID  
Sent By mawillia Date 2006-09-18 Time 12:48 Rev Time 0.00
Received By mawillia Date 2006-09-18 Time 12:48 Sent To  
Notes
2006-09-18 00:00:00*****DENIED*****
  
  
  
  
 1.) MECHANICAL PLAN REVIEW COMMENTS MUST
 BE ADDRESSED AND/OR CORRECTED.
  
 2.) IF THERE IS NO BUILDING ALARM, AN
 AUDIBLE (AS WELL AS A VISUAL ALARM) WILL
 BE SOUNDED UPON FIRE SYSTEM ACTUATION.
  
  
  
  
  
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2006-09-14 Cont ID  
Sent By swurafti Date 2006-09-14 Time 12:14 Rev Time 0.00
Received By swurafti Date 2006-09-14 Time 12:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-21 Cont ID  
Sent By adarroug Date 2006-09-21 Time 16:39 Rev Time 0.00
Received By adarroug Date 2006-09-21 Time 16:39 Sent To FIRE
Notes
2006-09-21 00:00:00TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-18 Cont ID  
Sent By mawillia Date 2006-09-18 Time 12:48 Rev Time 0.00
Received By mawillia Date 2006-09-15 Time 10:45 Sent To  
Notes
2006-09-15 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-09-29 Cont ID  
Sent By tgordon Date 2006-09-29 Time 09:58 Rev Time 0.20
Received By tgordon Date 2006-09-29 Time 09:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-09-18 Cont ID  
Sent By tgordon Date 2006-09-18 Time 12:18 Rev Time 0.20
Received By tgordon Date 2006-09-18 Time 12:18 Sent To FIRE
Notes
2006-09-18 00:00:00*** DENIED ***
 1) AS NOTED FOR THE PAST THREE PERMITS
 YOUR COMPANY APPLIED FOR, THE ENGINEER'S
 LICENSE NUMBER MUST APPEAR IN THE TITLE
 BLOCK, PER FAC 61G15-23.002 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.