| Plan Review Stops For Permit 06090449 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2006-09-14 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2006-09-14 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2006-09-14 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2006-09-14 00:00:00 | NEED AN EXTENSION FOR THIS ADDRESS | | | ATTACH PERMIT TO EXT #009 UNIT 104 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2007-08-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-08-29 |
Time |
16:09 |
Rev Time |
2.00 |
| Received By |
jwitmer |
Date |
2007-08-29 |
Time |
14:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-03-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-03-29 |
Time |
15:02 |
Rev Time |
0.66 |
| Received By |
jwitmer |
Date |
2007-03-29 |
Time |
15:01 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-12-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-12-07 |
Time |
14:02 |
Rev Time |
1.77 |
| Received By |
jwitmer |
Date |
2006-12-07 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2006-12-07 14:03:51 | PERMIT: 06090449 | | | ADD: 2247 PALM BEACH LAKES BLVD., SUITE 104 | | | CONT: TROPIC BUILDERS | | | TEL: (561)271-8723 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1STREVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATETHE REVISION & | | | REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF | | | THE COURT BEFORE A | | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) IF THE WORK | | | DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT ACTUALLY | | | COMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE | | | IS NULL & VOID. | | | | | | 3) COMPLIED. | | | | | | 4) COMPLIED. | | | | | | 5) COMPLIED. | | | | | | 6) 2ND REQUEST,PLANS INDICATE DOOR# 101 ARE MISSING | | | THE REQUIRED 18" ON THE PULL SIDE OF DOOR. 11-4.13.6 | | | MANEUVERING CLEARENCES | | | AT DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS THAT | | | ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN | | | IN | | | FIG. 25. THE FLOOR OR GROUND AREA WITH IN THE REQUIRED | | | CLEARANCES SHALL BE CLEAR & LEVEL. | | | 1003.3.3 HORIZONTAL PROJECTIONS . | | | ELEMENTS CANNOT PROJECT OVER A WALKING SURFACE MORE | | | THAN 4 INCHES (102 MM) WHEN THEY ARE LOCATED BETWEEN 27 | | | AND 80 INCHES (686 AND 2032 MM) ABOVE THE FLOOR. | | | HANDRAILS CAN PROJECT UP TO 4" INCHES (114 MM) FROM THE | | | WALL. | | | | | | 7) THE ARCHITECTS NAME LESLAW A. CZACZYK INTHE | | | TITLEBLOCK | | | IS STAMPED SIGNATURE NOT AN ORIGINAL AS REQUIRED BY: | | | PLANS, SPECIFICATIONS, REPORTS OR | | | OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND | | | BEING FILED FOR PUBLIC | | | RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | | TO THE DOCUMENT. | | | FL STATE STAT: 61G15-23.002 ENGINEERS | | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-10-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-10-10 |
Time |
07:33 |
Rev Time |
1.11 |
| Received By |
jwitmer |
Date |
2006-10-10 |
Time |
07:33 |
Sent To |
|
|
| Notes |
| 2006-10-10 07:46:55 | BUILDING PLAN REVIEW | | | PERMIT: 06090449 | | | ADD: 2247 PALM BEACH LAKES BLVD., SUITE 104 | | | CONT: TROPIC BUILDERS | | | TEL: (561)271-8723 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1STREVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATETHE REVISION & | | | REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF | | | THE COURT BEFORE A | | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) IF THE WORK | | | DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT ACTUALLY | | | COMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE | | | IS NULL & VOID. | | | | | | 3) THE ARCHITECT OF RECORD IS MISSING THEIR PRINTED | | | NAME IN THE TITLEBLOCK. FSS 481.221. | | | | | | 4) T.1 CODE NOTE # 8 TO INDICATE THE CURRENT FLORIDA | | | ACCESSIBILITY CODE 2004 FLORIDA BUILDING CODE, | | | BUILDING- CHAPTER 11. | | | | | | 5)T.1 IS MISSING IN THE PROJECT DATA : | | | 5A) 2004 FLORIDA EXISTING BUILDING CODE | | | 5B) LEVEL OF ALTERATION | | | 5C) TOTAL SQ. FOOTAGE /FLOOR | | | 5D) HEIGHT OF BLDG. & STORIES. | | | | | | 6) PLANS INDICATE THE FRONT ENTRY DOOR & DOOR# 101 ARE | | | MISSING THE REQUIRED 18" ON THE PULL SIDE OF DOOR. | | | 11-4.13.6 MANEUVERING CLEARENCES | | | AT DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS THAT | | | ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN | | | IN | | | FIG. 25. THE FLOOR OR GROUND AREA WITH IN THE REQUIRED | | | CLEARANCES SHALL BE CLEAR & LEVEL. BUILDING PLAN | | | REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2007-08-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-01 |
Time |
17:47 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-01 |
Time |
17:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2007-04-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-04-08 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-04-08 |
Time |
09:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-03-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-03-02 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-03-01 |
Time |
17:53 |
Sent To |
|
|
| Notes |
| 2007-03-02 09:16:36 | *** UNSAT *** | | | | | | 1) NOTE: PLEASE SEE THE LIGHTING POWER DENSITIES AND | | | THE LIGHTING FIXTURES ON PLANS AND FIXTURE LEGEND DO | | | NOT CORRELATE. | | | PLEASE SEE THERE ARE SEVERAL AREAS/ROOMS WHICH THE | | | LIGHTING WATTAGE EXCEEDS THAT OF THE TABLES AND | | | ALLOWANCES PERMITTED BY THE TABLES AND THE FBC ENERGY | | | CODE. | | | 13-415.2. | | | PLEASE SEE 13-415.1AB.1.1 AND SEE ENERGY CALCULATIONS | | | FOR USE. | | | PLEASE SEE THE TABLES FOR MAX LIGHTING ALLOWANCES. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | 2007-03-01 17:53:14 | IN ELEC FOR REVIEW |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-12-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-12-03 |
Time |
20:10 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-12-03 |
Time |
19:30 |
Sent To |
|
|
| Notes |
| 2006-12-03 20:12:58 | *** UNSAT 2ND REVIEW**** | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND NEW | | | NOTES DUE TO THE PLANS SUBMITTED. | | | THE NOTES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS REVIEW | | | AND INDICATE A "NO OR OK". IF A "NO" IS SHOWN FURTHER | | | EXPLANATION/NOTES MAY BE PRESENT. | | | ** PLEASE SEE ANY NEW NOTES ARE BEING ADDED TO THE | | | BOTTOM OF FIRST REVIEW NOTES. | | | | | | ** PLEASE KNOW A RESPONSE LETTER FROM THE DESIGN | | | PROFESSIONAL EXPLAINS HOW EACH COMMENT WAS ADDRESSED OR | | | A RESPONSE ON THE COMMENT ITSELF IS MOST HELPFUL IN THE | | | REVIEW PROCESS. | | | | | | 1) NOTE: OK, HOWEVER SEE NEW NOTES. | | | | | | 2) NOTE: OK. | | | | | | 3) NOTE:NO, IT IS UNCLEAR WHERE THIS DETAIL IS ON | | | PLANS. DETAIL FOR THE REDUNDANT GROUNDING IS REQUIRED. | | | WHICH METHOD WILL BE USED. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE THAT NEC 517, 517.13 DETAILS IS SHOWN ON | | | PLANS. | | | PLEASE SEE NOTE BELOW RISER DENOTING GROUND BOND PER | | | NEC MAY NOT USED IN LIEU OF DETAIL REQUIRED. | | | FBC 106.1.2 ADMIN SECT AS ADOPTED BY THE | | | CITY OF WEST PALM BEACH. | | | | | | 4) NOTE:NO, PLEASE SEE PLANS NOW INDICATE "OC SENSOR" | | | TYPE DEVICES AT ALL LOCATIONS. PLEASE SEE THAT THE | | | EMERGENCY LIGHTS AND EXIT LIGHTS SHALL BE SHOWN AHEAD | | | OF ANY LIGHTING CONTROL DEVICE. PLEASE SEE SOME EXT LTS | | | DO NOT INDICATE CIRCUITING. PLEASE SEE 700.12E. | | | PLEASE SEE LIGHTING POWER DENSITIES COULD NOT BE | | | LOCATED ON PLANS. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1, .1.2 AND | | | .1.3. | | | PLEASE PROVIDE LIGHTING CONTROL(S), STATED DEVICES, AND | | | LOCATIONS OF OVER RIDES AND DEVICES. PLEASE INDICATE | | | THE MAX TIMES ON OVER RIDES. (FYI, TIMER TYPE | | | 4HRS MAX, OCCUPANT TYPE 30MINS MAX). | | | PLEASE INDICATE THE MAX LPD(LIGHTING POWER DENSITIES). | | | PER 13-415.2.ABC.1, TABLES 415. | | | | | | 5) NOTE: NO, SAME NOTE. | | | | | | ** PREVIOUS REVIEW NOTE** | | | PLEASE INDICATE ALL ROOM/AREAS DESIGNATIONS ON PLANS | | | AND CORRELATE PANEL SCHEDULE WHICH IS TO BE SPECIFIC TO | | | AREAS BEING FED. | | | 408.4, | | | | | | 6) NOTE: OK. MEETS EXCEPTION. | | | | | | 7) NOTE: OK? PLEASE SEE RISER SEEMS TO BE OK, HOWEVER A | | | QUESTION ON THE DESIGNATION OF MULTIPLE BREAKERS IN THE | | | MDP WHICH MENTIONS DESIGNATIONS TO OTHER PANEL "A'S?? | | | PLEASE CLARIFY IN RESPONSE/PLANS THE OTHER BREAKERS. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE RISER SHOW THE MAIN PANEL IN SPACE AS 400 | | | MCB. PLEASE SEE THIS APPEARS TO BE A MISPRINT AS THE | | | SCHEDULE AND SERVICE PROVIDED MENTIONS 300A. | | | (POSSIBLE, 400MLO/300MCB. | | | FBC 106.1.2 ADMIN SECT. | | | | | | 8) NOTE: OK. | | | | | | 9) NOTE: NO, PLEASE SHOW, HOW WATTS PER SQ FT, HOW MANY | | | RECEPTS AND VA PER RECEPT AND HOW THE CONNECTED LOADS | | | SHOWN ARE BEING DERIVED. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE INDICATE WHERE THE CONNECTED LOADS ARE BEING | | | DERIVED. | | | PLEASE INDICATE A LOAD SUMMARY FOR SPACE. PLEASE ALSO | | | INDICATE ALL CONTINUOUS LOADS AT 125% (3OR MORE HRS). | | | 220.3,220.10,220.11,220.13,215.3, 230.42 | | | ETC. | | | | | | 10) NOTE: NO, PLEASE SEE MISSING EQUIPMENT GROUNDING | | | STILL NOT SHOWN FROM PANEL "A" TO "A-1". | | | PREVIOUS NOTE REQUESTED TO SHOW ALL. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE INDICATE "EQUIPMENT GROUNDING" METHOD FROM MAIN | | | MDP TO ALL EQUIPMENT. | | | 250.110, 250.122. | | | ** PLEASE KNOW, IF USING CONDUIT, THERE MUST BE THE NEW | | | CONNECTORS WHICH MUST BE LISTED FOR THIS PURPOSE, | | | OTHERWISE PLEASE INDICATE THE "EQUIPMENT GROUNDING | | | CONDUCTOR" PER 250.122. | | | | | | 11) NOTE: OK, HOWEVER VERIFY A 400A MLO PANEL ONLY | | | BEING 30POLES? THIS DOES NOT NEED TO BE CHANGED ON | | | PLANS. THIS WILL BE VERIFIED IN FIELD. IF PANEL | | | INSTALLED, IS INDEED A 42CIRCUIT PANEL, THEN PLANS WILL | | | BE REQUIRED TO BE REVISED. | | | | | | ** PREVIOUS REVIEW NOTE **PLEASE SEE PANEL "A-1" | | | INDICATES 30POLES, YET SHOWS 42 CIRCUITS/POLES ARE | | | SHOWN ON PANEL.. | | | PLEASE CORRELATE AND ADJUST. | | | 106.1.2 FBC. | | | | | | 12) NOTE: OK. SHOWS 65K FOR BRANCH CIRCUIT BREAKER. | | | | | | | | | | | | *** NEW NOTES FOR SECOND REVIEW*** | | | | | | 1) NOTE: PLEASE SEE BOTH SETS OF NEW REVISED PLANS | | | BEING SUBMITTED CONTAIN A "RUBBER-STAMP" FOR THE | | | REQUIRED ORIGINAL SIGNATURE. PLEASE SEE FLORIDA | | | ADMINISTRATIVE CODE 61G1-16.003, 004 AND FLORIDA | | | STATUTES WHICH REQUIRES AN ORIGINAL SIGNATURE. | | | (EVIDENCE OF AUTHENTICITY). | | | PLEASE KNOW, AT THIS TIME ONE SET OF EACH OF THE PLANS | | | WILL BE RETAINED BY THIS OFFICE, INCLUDING ONE SET OF | | | ORIGINAL SUBMITTED PLANS WHICH WERE SIGNED WITH AN | | | ORIGINAL SIGNATURE. | | | PLEASE KNOW, IF THERE IS ANY VERIFICATION NEEDED FOR | | | SIGNATURE REQUIRED PLEASE CONTACT THE FLORIDA BOARD OF | | | ARCHITECT?S LEGAL COUNSEL. MR. LES SMITH INVESTIGATOR | | | TO THE BOARD OR MR. DAVID MINACCI PROSECUTING | | | ATTORNEY. | | | | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-09-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-09-30 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-09-30 |
Time |
14:19 |
Sent To |
|
|
| Notes |
| 2006-09-30 00:00:00 | *** UNSAT *** | | | | | | 1) NOTE: PLEASE SEE FAC 61G1-16.004, | | | WHICH REQUIRES THE PRINTED NAME OF THE | | | ARCHITECT ON TITLE BLOCKS. | | | PLEASE ALSO SEE THAT THE RAISED SEALS | | | MUST BE CLEAR AND VISABLE WITH ALL | | | INFORMATION AS REQUIRED ON SAID SEAL. | | | PLEASE SEE SEALS ARE NOT EASILY | | | READABLE. | | | FS 481.221, FAC 61G1-16.003 | | | ** THIS IS REQUIRED FOR ALL SHEETS AND | | | FOR ALL TRADES WHETHER OR NOT COMMENT IS | | | MADE BY OTHER REVIEWER(S). | | | | | | 2) NOTE: PLEASE SEE THE FOLLOWING MIN | | | CODES SHALL BE STATED ON PLANS. IMPLY | | | STATING THE "LATEST EDITION" CAN NOT BE | | | USED AS THE LATEST EDITIONS OF SOME | | | CODES ARE OUT AND AVAILABLE YET NOT YET | | | ADOPTED BY THE STATE. | | | PLEASE STATE THE FOLLOWING. | | | 2002 NFPA-70 (NEC), 2002 NFPA-72, 2003 | | | NFPA-101, 2004 FBC. | | | PLEASE KNOW, OTHER CODES RELEVANT MAY BE | | | REQUESTED BY OTHER REVIEWER(S). | | | | | | 3) NOTE: PLEASE SEE THAT NEC 517, 517.13 | | | DETAIL IS SHOWN ON PLANS. | | | PLEASE SEE NOTE BELOW RISER DENOTING | | | GROUND BOND PER NEC MAY NOT USED IN LEIU | | | OF DETAIL REQUIRED. | | | FBC 106.1.2 ADMIN SECT AS ADOPTED BY THE | | | CITY OF WEST PALM BEACH. | | | | | | 4) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1, | | | .1.2 AND .1.3. | | | PLEASE PROVIDE LIGHTING CONTROL(S), | | | STATED DEVICES, LOCATIONS OF OVER RIDES | | | AND EVICES. PLEASE INDICATE THE MAX | | | TIMES ON OVER RIDES. (FYI, TIMER TYPE | | | 4HRS MAX, OCCUPANT TYPE 30MINS MAX). | | | PLEASE INDICATE THE MAX LPD(LIGHTING | | | POWER DENSITIES). PER 13-415.2.ABC.1, | | | TABLES 415. | | | | | | 5) NOTE: PLEASE INDICATE ALL ROOM/AREAS DESIGNATIONS ON | | | PLANS AND CORRELATE | | | PANEL SCHEDULE WHICH IS TO BE SPECIFIC | | | TO AREAS BEING FED. | | | 408.4, | | | | | | 6) NOTE: PLEASE PROVIDE EITHER NEW OR | | | EXISTING SIGN CIRCUIT LOCATION PER | | | 600.5. IT IS UNCLEAR AT THIS TIME. | | | | | | 7) NOTE: PLEASE SEE RISER SHOW THE MAIN | | | PANEL IN SPACE AS 400 MCB. PLEASE SEE | | | THIS APPEARS TO BE A MISPRINT AS THE | | | SCHEDULE AND SERVICE PROVIDED MENTIONS | | | 300A. | | | POSSIBLE, 400MLO/300MCB. | | | FBC 106.1.2 ADMIN SECT. | | | | | | 8) NOTE: PLEASE INDICATE IF PANEL "A" | | | CONTAINS "FEED-THRU" LUGS OR IS THERE | | | OCP WHICH FEEDS PANEL"A-1'.?? | | | | | | 9) NOTE: PLEASE INDICATE WHERE THE | | | CONNECTED LOADS ARE BEIGN DERIVED. | | | PLEASE INDICATE A LOAD SUMMARY FOR | | | SPACE. PLEASE ALSO INDICATE ALL | | | CONTINUOUS LOADS AT 125% (3OR MORE HRS). | | | 220.3,220.10,220.11,220.13,215.3, 230.42 | | | ETC. | | | | | | 10) NOTE: PLEASE INDICATE "EQUIPMENT | | | GROUNDING" METHOD FROM MAIN MDP TO ALL | | | EQUIPMENT. | | | 250.110, 250.122. | | | ** PLEASE KNOW, IF USINGCONDUIT, THERE | | | MUST BE THE NEW CONNECTORS WHICH MUST BE | | | LSTED FOR THIS PURPOSE, OTHERWISE PLEASE | | | INDICATE THE "EQUIPMENT GROUNDING | | | CONDUCTOR" PER 250.122. | | | | | | 11) NOTE; PLEASE SEE PANEL "A-1" | | | INDICATES 30POLES, YET SHOWS 42 | | | CIRCUITS/POLES ARE SHOWN ON PANEL.. | | | PLEASE CORRELATE AND ADJUST. | | | 106.1.2 FBC. | | | | | | 12) NOTE; PLEASE PROVIDE THE AIC RATING | | | FOR THE NEW MB FROM MDP TO NEW TENANT | | | SPACE. | | | PLEASE ALSO SEE THE AIC RATING FOR EACH | | | OF THE TENANT PANELS IS BEING SHOWN AT | | | 22K, WHICH SEEMS HIGH FOR BRANCH BRKRS?? | | | ** THIS IS OK, HOWEVER PLEASE KNOW, IF | | | SHOWN, THEN 22K RATED BRNACH BRKRS WILL | | | BE REQUIRED. | | | 110.9, | | | FBC 106.1.2 ADMIN SECT. | | | 106.3.5.1.2 | | | | | | ** PLEASE SEE ANY COMMENTS FROM OTHER | | | TRADES WHICH MAY AFFECT THE ELECTRICAL PLANS/DEISGN. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2007-08-30 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-08-30 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-08-30 |
Time |
15:43 |
Sent To |
|
|
| Notes |
| 2007-08-30 15:53:05 | *****APPROVED***** | | | | | | | | | | | | REVISED PLAN SHEETS A.1AND E.2 WERE STAMPED, INITIALED, | | | AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2007-04-12 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-04-12 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-04-12 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2007-04-12 14:55:50 | *****APPROVED***** | | | | | | | | | | | | PLAN SHEETS A.1, A.2, AND E.2 WERE STAMPED, INITIALED, | | | AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-03-22 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-03-22 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-03-22 |
Time |
09:24 |
Sent To |
|
|
| Notes |
| 2007-03-22 10:07:52 | ****PROVISO***** | | | | | | | | | ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | | BEEN ADDRESSED;APPROPIATE PLAN SHEET(S) WILL BE | | | STAMPED ONCE OTHER PLAN REVIEWS HAVE BEEN SATISFIED. | | | | | | | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2006-12-22 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-12-22 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-12-22 |
Time |
11:58 |
Sent To |
|
|
| Notes |
| 2006-12-22 12:04:45 | *****DENIED***** | | | | | | THE FOLLOWING COMMENTS WERE TAKEN FROM THE PREVIOUS | | | FIRE PLAN REVIEW: | | | | | | | | | | | | 1.)IN ADDTION TO NFPA 101 (2003 EDITION), THE FLORIDA | | | FIRE PREVENTION CODE (2004 EDITION) SHALL BE | | | REFERENCED. | | | | | | 2.)STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3.)CONSTRUCTION, AND/OR DEMOLITION OPERATIONS SHALL | | | NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID | | | PROPERTY AND THE VICINITY THEREOF (INCLUDING FIRE | | | LANES). | | | | | | 4.) ALL EXITS AND EXIT CORRIDORS ARE TO REMAIN CLEAR | | | AND UNOBSTRUCTED DURING CONSTRUCTION OPERATIONS. | | | | | | 5.)ON SHEET A.1 IT SHOWS THAT ACCESS TO THE FIRE | | | EXTINGUISHER(S) WILL BE OBSTRUCTED WHEN THE DOOR IS/ARE | | | OPENED.OK!! | | | | | | 6.)PLANS OR INFORMATION DOES NOT INDICATE IF THE | | | EXISTING BUILDING HAS A FIRE ALARM SYSTEM.IF SO, | | | PLEASE SHOW A LAYOUT OF THE DEVICES IN THE EXISTING/NEW | | | TENANT SPACE. | | | | | | 7.)IF THE SCOPE OF THE INTERIOR BUILDOUT REQUIRES | | | MODIFICATION OF THE FIRE ALARM OR FIRE SPRINKLER | | | SYSTEM, SEPARATE PERMIT AND DRAWINGS ARE TO SUBMITTED | | | FOR REVIEW. | | | | | | 8.)THE FIRE DEPARTMENT WILL BE NOTIFIED WHEN A FIRE | | | PROTECTION SYSTEM IS SHUT DOWN AND WHEN IT IS RETURNED | | | TO SERVICE. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-10-25 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-10-25 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-10-25 |
Time |
10:25 |
Sent To |
|
|
| Notes |
| 2006-10-25 13:53:03 | *****DENIED***** | | | | | | | | | | | | 1.)NFPA 101 (2003 EDITION) AND FLORIDA FIRE | | | PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED. | | | | | | 2.)STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3.)CONSTRUCTION, AND/OR DEMOLITION OPERATIONS SHALL | | | NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID | | | PROPERTY AND THE VICINITY THEREOF (INCLUDING FIRE | | | LANES). | | | | | | 4.) ALL EXITS AND EXIT CORRIDORS ARE TO REMAIN CLEAR | | | AND UNOBSTRUCTED DURING CONSTRUCTION OPERATIONS. | | | | | | 5.)ON SHEET A.1 IT SHOWS THAT ACCESS TO THE FIRE | | | EXTINGUISHER(S) WILL BE OBSTRUCTED WHEN THE DOOR IS/ARE | | | OPENED. | | | | | | 6.)PLANS OR INFORMATION DOES NOT INDICATE IF THE | | | EXISTING BUILDING HAS A FIRE ALARM SYSTEM.IF SO, | | | PLEASE SHOW A LAYOUT OF THE DEVICES IN THE EXISTING/NEW | | | TENANT SPACE. | | | | | | 7.)IF THE SCOPE OF THE INTERIOR BUILDOUT REQUIRES | | | MODIFICATION OF THE FIRE ALARM OR FIRE SPRINKLER | | | SYSTEM, SEPARATE PERMIT AND DRAWINGS ARE TO SUBMITTED | | | FOR REVIEW. | | | | | | 8.)THE FIRE DEPARTMENT WILL BE NOTIFIED WHEN A FIRE | | | PROTECTION SYSTEM IS SHUT DOWN AND WHEN IT IS RETURNED | | | TO SERVICE. | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2007-12-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-12-12 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-12-12 |
Time |
10:34 |
Sent To |
FIRE |
|
| Notes |
| 2007-12-12 10:35:27 | TO "F" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2007-10-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-09 |
Time |
13:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-09 |
Time |
13:53 |
Sent To |
M |
|
| Notes |
| 2007-10-09 13:54:11 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-07-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-19 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-19 |
Time |
13:28 |
Sent To |
|
|
| Notes |
| 2007-07-30 09:00:27 | TO "COMM" BD#30 | | 2007-07-19 13:29:22 | WAITING FOR "COMM" BD--REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-03-30 |
|
|
Cont ID |
|
| Sent By |
spalmer |
Date |
2007-03-30 |
Time |
17:38 |
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2007-03-30 |
Time |
17:38 |
Sent To |
|
|
| Notes |
| 2007-03-30 17:38:33 | WAITING FOR COMM BOARD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-02-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-14 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-14 |
Time |
16:26 |
Sent To |
|
|
| Notes |
| 2007-02-26 11:32:45 | TO "COMM" BD#19 | | 2007-02-14 16:26:43 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-11-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-11-29 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-11-29 |
Time |
14:22 |
Sent To |
|
|
| Notes |
| 2006-11-29 14:22:25 | TO COMM BOARD #47 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-11-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-11-16 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-16 |
Time |
13:19 |
Sent To |
B |
|
| Notes |
| 2007-04-02 17:26:11 | TO COMM BOARD # 17 | | 2006-11-16 13:20:10 | WAITING FOR "COMM"BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-10-25 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-10-25 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-09-15 |
Time |
11:13 |
Sent To |
|
|
| Notes |
| 2006-09-30 00:00:00 | TO COMM BOARD #6 | | 2006-09-15 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2007-10-20 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-10-20 |
Time |
19:16 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-10-20 |
Time |
18:41 |
Sent To |
PC |
|
| Notes |
| 2007-10-20 19:16:52 | REV PG M-1 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2007-10-20 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-08-06 |
Time |
18:41 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-08-06 |
Time |
11:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2007-03-17 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-03-17 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-03-17 |
Time |
14:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2006-12-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-12-07 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-12-07 |
Time |
10:07 |
Sent To |
|
|
| Notes |
| 2006-12-07 10:14:04 | DENIED: | | | 1.THE RESUBMITTAL DOES NOT CONTAIN ANY MECHANICAL | | | SHEETS.WAS THIS AN OVERSIGHT OR IS THE MECHANICAL | | | CONTRACTOR TO PROVIDE PLANS WITH THE MECHANICAL PERMIT | | | APPLICATION.PLEASE CLARIFY. | | | | | | 2.PLEASE NOTE, SIGNATURE ON THE RESUBMITTED PLANS IS | | | NOT AN ORIGINAL SIGNATURE IT IS A STAMP AS REQUIRED BY | | | THE FLORIDA ADMINSTRATIVE CODE 61G1-16.003 & 004. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | | AT (561)805-6719 OR E-MAIL [email protected]. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-10-17 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-10-17 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-10-17 |
Time |
16:11 |
Sent To |
|
|
| Notes |
| 2006-10-17 16:32:49 | DENIED: | | | ARCHITECTS SEAL IS NOT LEGIBLE, PLEASE ALSO PROVIDE | | | PRINTED NAME OF SAID ARCHITECT IN ACCORDANCE WITH FS | | | 481.221, FAC 61G1-16.003, 61G1-16.004. | | | | | | PLANS ARE OTHERWISE CODE COMPLIANT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | | AT (561)805-6719. |
|
|
| Review Stop |
MEDGAS |
MEDICAL GAS |
| Rev No |
3 |
Status |
P |
Date |
2007-03-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-03-09 |
Time |
07:56 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-03-07 |
Time |
18:58 |
Sent To |
|
|
| Notes |
| 2007-05-15 10:47:27 | PICTURE CERTIFICATIONS REQUIRED AT THE TIME OF | | | APPLICATION |
|
|
| Review Stop |
MEDGAS |
MEDICAL GAS |
| Rev No |
2 |
Status |
F |
Date |
2007-01-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-01-10 |
Time |
07:12 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-01-09 |
Time |
18:56 |
Sent To |
|
|
| Notes |
| 2007-01-10 07:34:36 | DENIED | | | REFERENCE: NFPA 99C | | | | | | FROM PREVIOUS REVIEW: | | | | | | 15. A SEPARATE MED-GAS PERMIT IS REQUIRED FOR THE | | | VACUUM AND COMPRESSED AIR SYSTEMS. CERTIFICATION FOR | | | THE CONTRACTOR, INSTALLER AND/OR BRAZER WITH PICTURE | | | IDENTIFICATION IS REQUIRED AT THE TIME OF APPLICATION. | | | (INFORMATIONAL ONLY). | | | | | | *************NEW COMMENT************* | | | | | | 1B. THE PERSONAL SIGNATURE OF THE ARCHITECT SHALL | | | APPEAR ON ALL ARCHITECTURAL DOCUMENTS. 61G1-16.003 & FS | | | 481.2055. THE SEAL IS STAMPED WITH A SIGNATURE STAMP. | | | THIS IS NOT APPROVED. PLEASE SIGN EACH SHEET. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
MEDGAS |
MEDICAL GAS |
| Rev No |
1 |
Status |
F |
Date |
2006-10-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-10-16 |
Time |
18:50 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-10-14 |
Time |
19:01 |
Sent To |
|
|
| Notes |
| 2006-10-16 18:52:53 | DENIED | | | REFERENCE:NFPA 99C 2002 | | | | | | 1. A SEPARATE MED-GAS PERMIT IS REQUIRED FOR THE VACUUM | | | AND COMPRESSED AIR SYSTEMS. CERTIFICATION FOR THE | | | CONTRACTOR, INSTALLER AND/OR BRAZER WITH PICTURE | | | IDENTIFICATION IS REQUIRED AT THE TIME OF APPLICATION. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2007-08-30 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-08-30 |
Time |
12:42 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-08-30 |
Time |
12:42 |
Sent To |
|
|
| Notes |
| 2007-08-30 12:43:13 | | | | | | | REVISION OK - SHTS P-1, P-2 & P-3 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2007-04-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-04-10 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-04-10 |
Time |
10:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2007-03-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-03-09 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-03-07 |
Time |
18:58 |
Sent To |
|
|
| Notes |
| 2007-03-09 08:01:37 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 BUILDING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE FLORIDA | | | STATUTES | | | NFPA 99C 2002 | | | | | | FROM PREVIOUS REVIEW: | | | | | | 1. OK | | | 2. OK | | | 3. OK | | | 4. OK | | | 5. OK | | | 6. OK | | | 7. OK | | | 8. OK | | | | | | 9. SHT P.2 PLUMBING LEGEND #2 AND DETAIL #3 WATER | | | FILTER SYSTEM. FILTER SHALL COMPLY WITH NSF 42. SUBMIT | | | MANUF. SPECIFICATION. SECTION 611.1. | | | ****NO RESPONSE - NOT ADDRESSED. | | | ******RESPONSE NOTED, AND INDICATES THE FILTERED WATER | | | SYSTEM HAS BEEN DELETED, BUT THE PLANS STILL SHOW | | | "FILTERED C.W. TYP. BRANCH"ON THE VAC. AIR & FILTERED | | | WATER DIAGRAM. PLEASE CLARIFY. SECTION 106.1.1. | | | | | | 10. SUBMIT RISER ISOMETRICS FOR THE FOLLOWING. THE | | | WATER SYSTEM, SHOWING ALL PIPE SIZES, VALVES, AND WATER | | | HAMMER ARRESTORS REQUIRE BY SECTION 604.9. THE VACUUM | | | SYSTEM SHOWING ALL PIPE SIZES, VALVES, ETC. THE | | | COMPRESSED AIR SYSTEM, SHOWING ALL PIPE SIZES, VALVES | | | ETC. SECTION 106.3.5.1.3, AND FIGURES 4.5.2.1.3(A) OR | | | 4.5.2.1.3(B) FOR THE VACUUM SYSTEM. | | | ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN, | | | AND THE FULL OPEN VALVES ON ALL WATER DOWN-FEED LINES | | | REQUIRED BY SECTION 606.1(4) ARE NOT SHOWN ON THE WATER | | | RISER ISOMETRIC. | | | ******RESPONSE NOTED, BUT THE WATER HAMMER ARRESTORS | | | SHALL BE LOCATED IN AN "EFFECTIVE RANGE" NEAR THE | | | FIXTURES, NOT IN THE CEILING. PDI-WH 201 & MANUF. | | | INSTALLATION INSTRUCTIONS. | | | | | | 11. OK | | | 12. OK | | | 13. OK | | | 14. OK | | | 15. OK | | | | | | *************NEW COMMENT************* | | | | | | 1B. OK | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-01-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-01-10 |
Time |
07:12 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-01-09 |
Time |
18:56 |
Sent To |
|
|
| Notes |
| 2007-01-10 07:23:35 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 BUILDING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE FLORIDA | | | STATUTES | | | NFPA 99C 2002 | | | | | | FROM PREVIOUS REVIEW: | | | | | | 1. OK | | | 2. OK | | | 3. OK | | | | | | 4. SHT A.1 TOILET ROOM 115 ADAPTABLE RESTROOM. SHOW THE | | | W/C TO BE 1'6" OFF THE WALL TO THE CENTERLINE OF THE | | | FIXTURE. FIGURE 28.SHOW A 5' TURNING AREA PER SECTION | | | 11-4.22.3. | | | ****RESPONSE NOTED, BUT THE DOOR SWING SHALL SWING OUT | | | OF THE TOILET ROOM FOR THE ROOM TO BE ADAPTABLE. | | | | | | 5. SHT A.1 FINISH SCHEDULE. INDICATE HOW PAINTED GWB | | | MEETS THE REQUIREMENTS OF A "SMOOTH, HARD, NONABSORBENT | | | SURFACE" AS REQUIRED IN SECTION 1210.2. TOILET ROOMS | | | 104 & 111. | | | ****RESPONSE NOTED, BUT EPOXY PAINT DOES NOT COMPLY | | | WITH THE REQUIREMENT FOR A HARD SURFACE. | | | | | | 6. SHT A.4 DETAIL 9/A.4 SECTION REQUIRES A KNEE | | | CLEARANCE THAT IS 27" HIGH, 30" WIDE, AND 19" DEEP | | | SHALL BE PROVIDED UNDERNEATH THE SINKS. UNDERLAVATORY | | | ENCLOSURE IS NOT APPROVED. DELETE FROM THE DETAIL. SHOW | | | COMPLIANCE WITH THE FOLLOWING: | | | A. OK | | | B. OK | | | C. 11-4.24.6 EXPOSED PIPES & SURFACES - NOT | | | ADDRESSED. | | | D. OK | | | | | | 7. OK | | | 8. OK | | | | | | 9. SHT P.2 PLUMBING LEGEND #2 AND DETAIL #3 WATER | | | FILTER SYSTEM. FILTER SHALL COMPLY WITH NSF 42. SUBMIT | | | MANUF. SPECIFICATION. SECTION 611.1. | | | ****NO RESPONSE - NOT ADDRESSED. | | | | | | 10. SUBMIT RISER ISOMETRICS FOR THE FOLLOWING. THE | | | WATER SYSTEM, SHOWING ALL PIPE SIZES, VALVES, AND WATER | | | HAMMER ARRESTORS REQUIRE BY SECTION 604.9. THE VACUUM | | | SYSTEM SHOWING ALL PIPE SIZES, VALVES, ETC. THE | | | COMPRESSED AIR SYSTEM, SHOWING ALL PIPE SIZES, VALVES | | | ETC. SECTION 106.3.5.1.3, AND FIGURES 4.5.2.1.3(A) OR | | | 4.5.2.1.3(B) FOR THE VACUUM SYSTEM. | | | ****RESPONSE NOTED, BUT ALL PIPE SIZES ARE NOT SHOWN, | | | AND THE FULL OPEN VALVES ON ALL WATER DOWN-FEED LINES | | | REQUIRED BY SECTION 606.1(4) ARE NOT SHOWN ON THE WATER | | | RISER ISOMETRIC. | | | | | | 11. OK | | | 12. OK | | | 13. OK | | | 14. OK | | | 15. A SEPARATE MED-GAS PERMIT IS REQUIRED FOR THE | | | VACUUM AND COMPRESSED AIR SYSTEMS. CERTIFICATION FOR | | | THE CONTRACTOR, INSTALLER AND/OR BRAZER WITH PICTURE | | | IDENTIFICATION IS REQUIRED AT THE TIME OF APPLICATION. | | | (INFORMATIONAL ONLY). | | | | | | *************NEW COMMENT************* | | | | | | 1B. THE PERSONAL SIGNATURE OF THE ARCHITECT SHALL | | | APPEAR ON ALL ARCHITECTURAL DOCUMENTS. 61G1-16.003 & FS | | | 481.2055. THE SEAL IS STAMPED WITH A SIGNATURE STAMP. | | | THIS IS NOT APPROVED. PLEASE SIGN EACH SHEET. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-10-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-10-16 |
Time |
17:51 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-10-14 |
Time |
19:01 |
Sent To |
|
|
| Notes |
| 2006-12-03 20:15:03 | ATTACHED SHEET WITH REFERENCE TO FS 553.80(2)B), ONLY A | | | NOTICE FOR INFORMATIONAL PURPOSE AT THIS TIME. | | 2006-10-16 18:48:33 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 BUILDING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | NFPA 99C 2002 | | | | | | 1. SHT T.1 CODE NOTES #8 ACCESSIBILITY TO BE PER | | | FBC-2004 CHAPTER 11. CORRECT REFERENCE. | | | | | | 2. ALL SHEETS. SEAL SHALL IMPRESS INFORMATION REQUIRED | | | BY FAC 61G1-16.002(1) & FS 481.221. PRINTED NAME OF THE | | | PERSON SEALING THE DOCUMENT REQUIRED IN THE TITLE | | | BLOCK. FAC 61G1-16.004(6) & FS 481.2055. | | | | | | 3. SHT A.0 SHOW COMPLIANCE WITH THE FOLLOWING:FOR | | | W/C'S | | | A. 11-4.16.2 CLEAR FLOOR SPACE | | | B. 11-4.16.5 FLUSH CONTROLS | | | | | | 4. SHT A.1 TOILET ROOM 115 ADAPTABLE RESTROOM. SHOW THE | | | W/C TO BE 1'6" OFF THE WALL TO THE CENTERLINE OF THE | | | FIXTURE. FIGURE 28.SHOW A 5' TURNING AREA PER SECTION | | | 11-4.22.3. | | | | | | 5. SHT A.1 FINISH SCHEDULE. INDICATE HOW PAINTED GWB | | | MEETS THE REQUIREMENTS OF A "SMOOTH, HARD, NONABSORBENT | | | SURFACE" AS REQUIRED IN SECTION 1210.2. TOILET ROOMS | | | 104 & 111. | | | | | | 6. SHT A.4 DETAIL 9/A.4 SECTION REQUIRES A KNEE | | | CLEARANCE THAT IS 27" HIGH, 30" WIDE, AND 19" DEEP | | | SHALL BE PROVIDED UNDERNEATH THE SINKS. UNDERLAVATORY | | | ENCLOSURE IS NOT APPROVED. DELETE FROM THE DETAIL. SHOW | | | COMPLIANCE WITH THE FOLLOWING: | | | A. 11-4.24.4 SINK DEPTH | | | B. 11-4.24.5 CLEAR FLOOR SPACE (CABINET DOORS ARE NOT | | | APPROVED IN THE CLEAR FLOOR SPACE. DELETE FROM | | | DETAIL). | | | C. 11-4.24.6 EXPOSED PIPES & SURFACES | | | D. 11-4.24.7 FAUCETS | | | | | | 7. SHT P.1 PLUMBING FIXTURE LEGEND SK-2 SINK MODEL NOT | | | APPROVED. (SEE ATTACHED MANUF. SHEET). MAXIMUM DEPTH | | | FOR AN ACCESSIBLE SINK IS 6-1/2" PER SECTION 11-4.24.4. | | | 8" IS INDICATED ON MANUF. SPECIFICATION SHEET. | | | | | | 8. SHT P.1 EWH & REC. PUMP DIAG. SHOWS PVC PIPE FOR P/T | | | DISCHARGE LINE & EMERGENCY PAN DRAIN LINE. THIS IS NOT | | | APPROVED. SECTION 504.6.2 AND TABLE 605.4. - PAN DRAIN | | | LINE AND P/T DISCHARGE LINE ARE SHOWN AS AIR BREAKS TO | | | THE FLOOR SINK. AIR GAPS ARE REQUIRED. SECTION 802.2 | | | AND DEFINITIONS.- A NOTE INDICATES "TO JAN. SINK BELOW" | | | BUT DETAIL SHOW PIPING TO FLOOR SINK. PLEASE CLARIFY. | | | SECTION 106.1.1. | | | | | | 9. SHT P.2 PLUMBING LEGEND #2 AND DETAIL #3 WATER | | | FILTER SYSTEM. FILTER SHALL COMPLY WITH NSF 42. SUBMIT | | | MANUF. SPECIFICATION. SECTION 611.1. | | | | | | 10. SUBMIT RISER ISOMETRICS FOR THE FOLLOWING. THE | | | WATER SYSTEM, SHOWING ALL PIPE SIZES, VALVES, AND WATER | | | HAMMER ARRESTORS REQUIRE BY SECTION 604.9. THE VACUUM | | | SYSTEM SHOWING ALL PIPE SIZES, VALVES, ETC. THE | | | COMPRESSED AIR SYSTEM, SHOWING ALL PIPE SIZES, VALVES | | | ETC. SECTION 106.3.5.1.3, AND FIGURES 4.5.2.1.3(A) OR | | | 4.5.2.1.3(B) FOR THE VACUUM SYSTEM. | | | | | | 11. SHT P.2 THE COMPRESSOR AIR INTAKE SHALL COMPLY WITH | | | NFPA 99C SECTION 5.1.3.5.13.2. THE MATERIALS FOR THE | | | COMPRESSOR INTAKE PIPING SHALL COMPLY WITH NFPA 99C | | | SECTIONS 5.1.3.5.13.4 & 5.1.10.2.1. | | | | | | 12. SHTS P.1 & P.2 MORE INFORMATION IS REQUIRED FOR | | | ROOM 117. SUBMIT AN ELEVATION FOR THE SOUTH AND EAST | | | WALLS. IT APPEARS THAT THE WATER HEATER AND THE AIR | | | COMPRESSOR ARE LOCATED IN THE SAME SPACE. PLEASE | | | CLARIFY. SECTION 106.1.1. | | | | | | 13. SHT P.2 DETAIL #6 VACUUM TUBES SHALL BE HARD-DRAWN | | | SEAMLESS COPPER PER NFPA 99C SECTION 5.1.10.2.1. DELETE | | | FROM REFERENCE THE OTHER MATERIALS. | | | | | | 14. SHT P.2 DETAIL #1 MORE INFORMATION IS REQUIRED. | | | SUBMIT INFORMATION ON THE DETAIL FOR THE AIR COMPRESSOR | | | INDICATING IF THE AIR INTAKE WILL BE CONNECTED TO THE | | | COMPRESSOR. IF NOT THE FLOOR SINK WILL NOT BE APPROVED | | | IN ROOM 117. SECTION 106.1.1. | | | | | | 15. A SEPARATE MED-GAS PERMIT IS REQUIRED FOR THE | | | VACUUM AND COMPRESSED AIR SYSTEMS. CERTIFICATION FOR | | | THE CONTRACTOR, INSTALLER AND/OR BRAZER WITH PICTURE | | | IDENTIFICATION IS REQUIRED AT THE TIME OF APPLICATION. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|