Plan Review Details - Permit 06090447
Plan Review Stops For Permit 06090447
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-09-14 Cont ID  
Sent By lursu Date 2006-09-14 Time 15:09 Rev Time 0.00
Received By lursu Date 2006-09-14 Time 11:24 Sent To  
Notes
2006-09-14 00:00:00ADDRESS ON APP READS 611 21ST ST/PAPA
 READS 608 23RD ST
 ADDRESS HAD BEEN CORRECTED

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2007-09-26 Cont ID  
Sent By rmcdouga Date 2007-09-26 Time 18:57 Rev Time 0.00
Received By rmcdouga Date 2007-09-26 Time 18:57 Sent To  
Notes
2007-09-26 18:58:12REVISIONS TO SHEETS D1, A1, A2,A3, A5 AND A6 HAVE BEEN
 REVIEWED FOR CODE COMPLIANCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2007-07-19 Cont ID  
Sent By rmcdouga Date 2007-07-19 Time 10:21 Rev Time 0.00
Received By rmcdouga Date 2007-07-19 Time 10:21 Sent To  
Notes
2007-07-19 10:30:48REVISIONS TO SHEETS A1, A2, A3, A5, A6 ARE DENIED.
  
 1) ON SHEET A1 THE WINDOW NOTES SPECIFY PGT WINDGUARD
 WINDOWS. THE CONTRACTOR HAS REVISED THE WINDOW PRODUCT
 APPROVALS TO IMPACT RATED KDWINDOWS. PLEASE REVISE.
  
 2) THE WINDOWS SIZES SHOWN ON THE ELEVATIONS AND FLOOR
 PLAN DO NOT CORRESPOND WITH THE DIMENSIONS IN THE
 WINDOW SCHEDULE ON A1 FOR THE KITCHEN AND BATHROOM
 WINDOWS.
  
 3) PROVIDE A DETAIL OF THE IN FILL FRAMING AT THE
 BATHROOMWINDOWS.
  
 4) THE REAR ELEVATION ON A3 HAS THE WRONG DETAIL TAG
 FOR THE IN FILL FRAMING. IT SHOULD BE 1 ON A6.
  
 5) THE OPENING WIDTH DIMENSION IN DETAIL 1 ON A5 IS TOO
 SMALL FOR THE WINDOWS SPECIFIED IN THE SCHEDULE ON A1.
 PLEASE REVISE.
  
 6) THE OPENING WIDTH DIMENSION IN DETAIL 1 ON A6 IS TOO
 SMALL FOR THE WINDOWS SPECIFIED IN THE SCHEDULE ON A1.
 PLEASE REVISE.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-07-18 Cont ID  
Sent By rmcdouga Date 2007-07-18 Time 18:59 Rev Time 0.00
Received By rmcdouga Date 2007-07-18 Time 18:59 Sent To  
Notes
2007-07-18 18:44:58REVISED PRODUCT APPROVALS FOR SINGLE HUNG WINDOWS,
 MULLIONS AND CASEMENT WINDOWS. LETTER FROM ENGINEER
 CERTIFYING PRODUCTS TO THE 2004 FBC.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-06-26 Cont ID  
Sent By rmcdouga Date 2007-06-26 Time 15:32 Rev Time 0.00
Received By rmcdouga Date 2007-06-26 Time 15:32 Sent To  
Notes
2007-06-26 15:33:10REVISED PRODUCT APPROVALS FOR WINDOWS ARE DENIED
  
 1) PLAN SHEET A-1 WILL BE REQUIRED TO BE REVISED TO
 REFLECT THE CHANGES TO THE WINDOW TYPES THAT ARE NOT
 INDICATED IN THE WINDOW SCHEDULE.
  
 2)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 3) THE PRODUCT APPROVAL FOR THE SERIES 455 IS MISSING
 PAGES E-1 AND E-2.
  
 4) THE PRODUCT APPROVALS SUBMITTED FOR THE MULLIONS AND
 CASEMENT WINDOWS DO NOT COMPLY WITH THE 2004 FBC FOR
 NOT ALLOWING A 1/3 STRESS INCREASE OF STEEL FASTENERS,
 BUT HAVE REVISED NOAS THAT DO COMPLY. SUBMIT THE LATEST
 NOAS.
  
 5) THE PRODUCT APPROVALS FOR THE FIXED WINDOW AND THE
 SINGLE HUNG WINDOW DO NOT COMPLY WITH THE 2004 FBC FOR
 THE REASON STATED ABOVE.
  
 6) ADDITIONAL FEES ARE DUE. 5 PRODUCT APPROVALS WERE
 SUBMITTED AND THE FEE WAS ASSESSED FOR ONE. AN
 ADDITIONAL $40.00 IS DUE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-04-25 Cont ID  
Sent By rmcdouga Date 2007-04-25 Time 16:08 Rev Time 0.00
Received By rmcdouga Date 2007-04-25 Time 16:08 Sent To  
Notes
2007-04-25 16:12:56REVISED DOOR PRODUCT APPROVAL IS OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-01-09 Cont ID  
Sent By rmcdouga Date 2007-01-09 Time 15:55 Rev Time 0.00
Received By rmcdouga Date 2007-01-09 Time 15:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-16 Cont ID  
Sent By rmcdouga Date 2006-11-16 Time 08:05 Rev Time 0.00
Received By rmcdouga Date 2006-11-16 Time 07:30 Sent To  
Notes
2006-11-16 08:04:52DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SPECIFY THE STUD SPACING IN THE WALL SECTION ON
 SHEET A-5.
  
 3) ASTM C926REQUIRES STUCCO APPLIED VERTICALLY OVER
 METAL LATH WITH A SOLID BASE TO HAVE A MINIMUM
 THICKNESS OF 7/8". SEE FBC 2510.3. PLEASE CORRECT WALL
 SECTION ON A-5.
  
 4)FBC 2510.6 REQUIRES A WEATHER RESISTANT BARRIER
 OVER THE PLYWOOD BACKING BEHIND THE LATH AND STUCCO.
 PLEASE SPECIFY ON WALL SECTION ON A-5.
  
 5) THE WINDOW SCHEDULE ON A-1 STILL HAS ERRORS. THERE
 ARE MASONRY OPENINGS SPECIFIED THAT ARE THE SAME SIZE
 OR SMALLER THAN THE WINDOW SIZES. THE SIZE CODE FOR
 CASEMENT WINDOWS D, O, V & GG ARE NOT CORRECT. PLEASE
 CORRECT.
  
 6) PLEASE SUBMIT PRODUCT APPROVALS ( APPROVED BY THE
 D.O.R.) FOR THE STRUCTURAL WINDOW MULLIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-19 Cont ID  
Sent By rmcdouga Date 2006-09-19 Time 10:44 Rev Time 0.00
Received By rmcdouga Date 2006-09-19 Time 09:10 Sent To  
Notes
2006-09-19 00:00:00DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SPECIFY THE LEVEL OF ALTERATION FOR
 THE PROJECT. SEE 2004 FBC EXISTING
 BUILDING CODE CHAPTER 3.
  
 3) BEDROOM WINDOWS MUST COMPLY WITH
 EMERGENCY EGRESS REQUIREMENTS OF FBC
 1025.
  
 4) THE NOTE ON SHEET A5 STATES TO FASTEN
 P.T. TO CONC. W/ 1/4" DIA.X 3/4"CONC.
 SCEWS @ 16" O.C. THAT LENGTH FASTENER
 WILL NOT BE SUFFICENT TO ATTACH THE
 2X8S. PLEASE CORRECT.
  
 5) THE TAGS FOR DETAIL 1/SK IS SPECIFIED
 ON SHEET A-3. IN ORDER TO BETTER LOCATE
 THESE DETAILS, PLEASE SPECIFY THE SHEET
 ON WHICH THE DETAIL IS LOCATED AS THE
 BOTTOM CHARACTERS OF THE ID TAG.
  
 6) PLEASE SPECIFY THE REPAIRS THAT WILL
 BE DONE TO THE BALCONIES. "REPAIR AS
 NEEDED" IS TOO GENERAL. SEE CITY
 AMENDMENTS TO FBC 106.1.1.
  
 7) ON SHEET A3 THE KITCHEN DOORS ARE
 SHOWN ON THE SOUTH ELEVATION WITH
 WINDOWS. SUBMIT PRODUCT APPROVALS FOR
 DOORS WITH WINDOWS AS INDICATED BY
 PLANS.
  
 8) SUBMIT PRODUCT APPROVALS FOR THE
 VENTED STORAGE ROOM DOORS AS SHOWN ON A3
 OF PLANS.
  
 9) THE WINDOW SCHEDULE ON A2 CONTAINS
 SEVERAL ERRORS.
 - THE MASONRY OPENING HEIGHTS ARE
 SMALLER THAN THE WINDOW HEIGHTS FOR
 SEVERAL OF THE WINDOWS LISTED.
 - THE WINDOW CODE SIZE FOR SEVERAL OF
 THE ONES LISTED SHOULD BE SH25 OR 25,
 NOT H25 FOR THE SINGLE HUNG WINDOWS.
 PLEASE REVIEW SCHEDULE AND CORRECT.
  
 10) THE STREET HAS BEEN CHANGED IN THE
 TITLE BLOCK OF THE PLANS. ALL CHANGES TO
 SIGNED AND SEALED PLANS ARE REQUIRED TO
 BE MADE BY THE DESIGN PROFESSIONAL THAT
 IS SEALING THEM.
  
 11) CLARIFY THE SCOPE WORK THAT IS
 INDICATED BY DETAIL 1/SK. IS THIS
 EXTERIOR WALL BEING DEMOLISHED AND
 REPLACED WITH A NEW WALL? IF IT IS
 PROVIDE A WALL CROSS-SECTION SPECIFYING
 THE EXTERIOR SUBSTRATE BEHIND THE
 STUCCO, VAPOR BARRIER, THE R-VALUE OF
 THE WALL INSULATION, ETC.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-09-26 Cont ID  
Sent By btrobaug Date 2007-09-26 Time 12:34 Rev Time 0.00
Received By btrobaug Date 2007-09-26 Time 12:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-06-29 Cont ID  
Sent By btrobaug Date 2007-06-27 Time 13:28 Rev Time 0.00
Received By btrobaug Date 2007-06-27 Time 12:14 Sent To  
Notes
2007-06-27 13:30:58 
  
 REVISION DENIED
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE CONDUIT FOR THE SERVICE RISER DOES NOT COMPLY
 WITH TABLE C-8 FOR FILL REQUIREMENT, THIS WAS REDLINED
 ON THE PREVIOUS REVIEW, PLEASE CORRECT ON THE PLAN.
 SHEET E-2.
  
 2} VERIVY CIRCUIT #3 ON THE PANEL SCHEDULE, 20 AMP WITH
 #8 CONDUCTORS, LISTED A SPARE.
  
 3} CLOUD THE REVISIONS ON SHEETS E-3 AND E-4.
  
 4} RELOCATE THE RANGE AND WATER HEATER RECEPTACLES TO
 THEIR RELEVANT LOCATION, OR REMOVE IF NOT BEING
 INSTALLED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-03-02 Cont ID  
Sent By btrobaug Date 2007-03-02 Time 16:40 Rev Time 2.00
Received By btrobaug Date 2007-02-23 Time 16:04 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-01-03 Cont ID  
Sent By btrobaug Date 2007-01-03 Time 18:08 Rev Time 1.00
Received By btrobaug Date 2007-01-03 Time 17:05 Sent To  
Notes
2007-01-03 18:08:26 
 NONCOMPLIANT.
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE PANELS ARE SHOWING THREE PHASE BUSSES (A,,B,C),
 REMOVE "C".
  
 2} THE #8 EQUIPMENT GROUND FROM THE METER TO THE HOUSE
 PANEL IS IN VIOLATION OF 250.6 AND SHALL BE REMOVED.
 THIS WILL BE INSTALLED AFTER THE DISCONNECT WHERE THE
 NEUTRAL WILL BE ISOLATED FROM THE GROUND..
  
 3} THE DISHWASHER STILL APPEARS ON THE PLAN. ADD TO THE
 CALCS OR REMOVE SAME, 220
  
 4} THE BATHROOM CIRCUIT IS LISTED AS 240 VOLTS IN THE
 NOTES SHEET E-1 AND E-2.
  
 5} THE WASHER/DRYER STACK UNITS ARE SHOWN ON THE PLAN
 BUT NOT IN THE CALCS. SOME ARE 240 AND SOME ARE 120
 VOLT, PLEASE CORRELATE.
  
 6} THE BATTERY PACK EMERGENCU LIGHTS MUST BE ON A LOCAL
 CIRCUIT TO FUNCTION WHEN THAT CIRCUIT FAILS. SEE
 700.12(E) FOR VERBAGE.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-11-14 Cont ID  
Sent By btrobaug Date 2006-11-14 Time 17:42 Rev Time 0.75
Received By btrobaug Date 2006-11-14 Time 17:28 Sent To  
Notes
2006-11-14 17:42:30 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE LOAD CALCULATIONS ARE SHOWN AS
 USING THE DEMAND FACTOR IN 230.31 (40%),
 AND THEN TAKING AN ADDITIONAL DEMAND
 FACTOR FROM TABLE 230.32(45%). WHILE
 EITHER ONE IS PERMISSIBLE, NOT TOGETHER.
 ALSO SEE 230.32(B) REGARDING HOUSE
 LOADS. THIS COMMENT WAS ON THE PRIOR REVIEW.
  
 2} ALL BRANCH CIRCUIT PANEL DESIGNATIONSARE
 INCORRECT.(FA #S ETC).
  
 3} THE DISHWASHER CIRCUIT REFERENCED ON E-2 IS NOT ON
 THE PANEL SCHEDULE OR IN THE LOAD CALCULATION.
  
 4} THE WASHER/DRYER APPEARS TO BE STACKED ON THE PLAN,
 PLEASE CORRECT THE SCHEDULE.
  
 5} THE SMALL APPLIANCE CIRCUITS FOR THE KITCHEN MUST
 COMPLY WITH 210.52(B)(3), TWO IN THE KITCHEN, THERE IS
 ONLY ONE. CIRCUIT #12 MAY BE IN THE DINING ROOM, BUT
 MUST ALSO BE IN THE KITCHEN.
  
 6} THE GFI ON THE OUTSIDE IN FRONT IS IN VIOLATION OF
 210.52(B)(2), CANNOT BE ON THE SMALL APPLIANCE
 CIRCUIT.
  
 7} THE GFI IN THE BACK OUTSIDE IS IN VIOLATION OF
 210.11(C)(3), BATH CIRCUITS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-21 Cont ID  
Sent By btrobaug Date 2006-09-21 Time 13:16 Rev Time 1.00
Received By btrobaug Date 2006-09-21 Time 11:25 Sent To  
Notes
2006-09-21 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE LOAD CALCULATIIONS ARE SHOWN AS
 USING THE DEMAND FACTOR IN 230.31 (40%),
 AND THEN TAKING AN ADDITIONAL DEMAND
 FACTOR FROM TABLE 230.32(45%). WHILE
 EITHER ONE IS PERMISIBLE, NOT TOGETHER.
 ALSO SEE 230.32(B) REGARDING HOUSE
 LOADS.
  
 2} TH EGROUNDING ELECTRODE CONDUCTOR IS
 TOO SMALL FOR THE SERVICE SHOWN AND WILL
 CERTAINLY BE TOO SMALL FOR THE SERVICE
 WHEN THE CALCULATIONS ARE ADJUSTED. SEE
 250.66.
  
 3} PLEASE LIST THE CONDUCTOR SIZES WITH
 THE BREAKER SIZES ON THE PANEL SCHEDULE
 SO THAT COMPLIANCE WITH 310.16 AND
 240.CAN BE REVIEWED.
  
 4} THERE ARE AIR HANDLERS SHOWN ON THE
 PLAN BUT NOT LISTED ON THE SCHEDULE OR
 NOT INCLUDED IN THE CALCULATIONS. PLEASE
 INCLUDE.
  
 5} THE BATH CIRCUIT REQUIRED BY
 210.11(C)(3)IS NOT IN THE SCHEDULE.
  
 6} THERE APPEARS TO BE ONLY ONE SMALL
 APPLIANCE CIRCUIT IN THE KITCHEN, TWO
 ARE REQUIRED PER 210.52(B)(1).
  
 7} BEDROOM 1 AND BEDROOM 2 CIRCUIT
 NUMBERS DO NOT CORRESPOND TO THE
 SCHEDULE .
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-09-28 Cont ID  
Sent By mwennerg Date 2007-09-28 Time 14:15 Rev Time 0.00
Received By mwennerg Date 2007-09-28 Time 14:15 Sent To  
Notes
2007-09-28 14:15:43PLANS WERE APPROVED ON 2/23/07.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-02-23 Cont ID  
Sent By mawillia Date 2007-02-23 Time 16:37 Rev Time 0.00
Received By mawillia Date 2007-02-23 Time 16:36 Sent To  
Notes
2007-02-23 16:39:07*****APPROVED******
  
  
 ALL COMMENTS FROM PREVIOUS FIRE PLAN REVIEWS HAVE BEEN
 ADDRESSED.SHEETS A-3 AND E-3 WERE STAMPED, INITIALED,
 AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-11-16 Cont ID  
Sent By mawillia Date 2006-11-16 Time 09:41 Rev Time 0.00
Received By mawillia Date 2006-11-16 Time 09:41 Sent To  
Notes
2006-11-16 09:52:53*****PROVISO*****
  
  
  
  
 1.PLEASE SHOW THE ADDRESS OF THE PROPOSED STRUCTURE
 ON THE ELEVATION SHEET.BE ADVISED THAT THE
 APARTMENT/UNIT ALPHABET OR NUMBER FOR THE FRONT
 ENTRANCE SHOULD NOT BE ON THE DOORS, BUT INSTEAD ON THE
 BUILDING ABOVE OR NEAR THE DOOR OPPOSITE OF THE SWING
 OF THE DOOR.IF THE UNITS ARE EQUIPPED WITH REAR
 DOORS, THE ALPHABET OR NUMBER MAY BE ON THE DOOR.
  
  
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-804-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-09-21 Cont ID  
Sent By mwennerg Date 2006-09-21 Time 15:05 Rev Time 0.00
Received By mwennerg Date 2006-09-21 Time 15:05 Sent To  
Notes
2006-09-21 00:00:00***DENIED***
  
 1) PLEASE NOTE THAT BEDROOM WINDOWS
 SHALL COMPLY WITH NFPA 101, 2003
 EDITION, REGARDING SECONDARY MEANS OF
 EGRESS.
  
 2) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
 DEBRIS TO BE CLEANED FROM SITE DAILY.
  
 3) IF REPAIR TO BALCONIES IMPACT
 HANDRAILS AND GUARDS, PLEASE PROVIDE
 DETAILS AND PRESCRIPTIVE STRENGTH
 REQUIREMENTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-09-13 Cont ID  
Sent By adarroug Date 2007-09-13 Time 08:28 Rev Time 0.00
Received By adarroug Date 2007-09-13 Time 08:28 Sent To  
Notes
2007-09-25 15:50:01TO "COMM" BD#25--EXPEDITED--
2007-09-13 08:28:44WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-07-16 Cont ID  
Sent By adarroug Date 2007-07-16 Time 10:48 Rev Time 0.00
Received By adarroug Date 2007-07-16 Time 10:48 Sent To B
Notes
2007-07-16 10:49:29TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-06-19 Cont ID  
Sent By adarroug Date 2007-06-19 Time 16:27 Rev Time 0.00
Received By adarroug Date 2007-06-19 Time 16:27 Sent To B
Notes
2007-06-19 16:27:26TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-06-15 Cont ID  
Sent By adarroug Date 2007-06-15 Time 14:30 Rev Time 0.00
Received By adarroug Date 2007-06-15 Time 14:29 Sent To  
Notes
2007-06-26 09:25:00TO "COMM" BD#12
2007-06-15 14:30:19WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-04-25 Cont ID  
Sent By adarroug Date 2007-04-25 Time 11:20 Rev Time 0.00
Received By adarroug Date 2007-04-25 Time 11:20 Sent To B
Notes
2007-04-25 11:20:30TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-22 Cont ID  
Sent By adarroug Date 2007-02-22 Time 11:57 Rev Time 0.00
Received By adarroug Date 2007-02-22 Time 11:57 Sent To E
Notes
2007-02-22 11:58:19TO "BTROBAUG" DESK/RESUB--EXPEDITED PERMIT

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-22 Cont ID  
Sent By adarroug Date 2006-12-22 Time 09:49 Rev Time 0.00
Received By adarroug Date 2006-12-22 Time 09:49 Sent To  
Notes
2006-12-22 09:53:22TO "COMM" BD#31--EXPEDITED PERMIT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-09 Cont ID  
Sent By adarroug Date 2006-11-09 Time 15:00 Rev Time 0.00
Received By adarroug Date 2006-11-09 Time 15:00 Sent To B
Notes
2006-11-09 15:00:37TO "LMARTINEZ" DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-22 Cont ID  
Sent By jleech Date 2006-09-22 Time 08:53 Rev Time 0.00
Received By jleech Date 2006-09-15 Time 15:11 Sent To  
Notes
2006-09-15 00:00:00TO "BOB"#7
2006-09-14 00:00:00EXPEDITED PERMIT

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-09-22 Cont ID  
Sent By jleech Date 2006-09-22 Time 08:53 Rev Time  
Received By jleech Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2007-09-27 Cont ID  
Sent By jleech Date 2007-09-27 Time 10:36 Rev Time 0.00
Received By jleech Date 2007-09-27 Time 10:36 Sent To  
Notes
2007-09-27 10:37:20GAS PERMIT REQUIRED

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-07-16 Cont ID  
Sent By jleech Date 2007-07-16 Time 09:43 Rev Time 0.00
Received By jleech Date 2007-07-16 Time 09:37 Sent To  
Notes
2007-07-16 09:55:39PROVISO
  
  
 GAS CONTRACTOR TO SUBMIT A GAS RISER DIAGRAM WITH ALL
 REQUIRED INFORMATION AND INSTALLATION SPECIFICATIONS
 WITH PERMIT APPLICATION. CLEARANCES BETWEEN WINDOWS
 MUST BE SHOWN IN DRAWING FORM.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-01-06 Cont ID  
Sent By jleech Date 2007-01-06 Time 08:32 Rev Time 0.00
Received By jleech Date 2007-01-06 Time 08:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-11-17 Cont ID  
Sent By jleech Date 2006-11-17 Time 08:03 Rev Time 0.00
Received By jleech Date 2006-11-17 Time 08:03 Sent To  
Notes
2006-11-17 08:28:01DENIED;
 1. AUTOMATIC CLOTHES WASHERS ARE NOT SHOWN ON FLOOR
 PLAN. PAGES A-1 AND A-2 PLEASE ADD.
 2. AUTOMATIC CLOTHES WASHER BRANCH DRAIN IS REQUIRED TO
 BE 3". SEE FBC-2004 PLUMBING SECTION 406.3.
 3. PLEASE SIZE ALL PIPES ON RISER DIAGRAM.
 4.ENGINEER TO SIGN NOT INITIAL PLANS.
 5. WATER RISER DIAGRAM PAGE P-2 WATER HAMMER ARRESTORS
 ARE REQUIRED AT THE AUTOMATIC CLOTHES WASHERS. PLEASE
 SHOW ON DRAWINGS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-09-22 Cont ID  
Sent By jleech Date 2006-09-22 Time 07:57 Rev Time 0.00
Received By jleech Date 2006-09-22 Time 07:57 Sent To  
Notes
2006-09-22 00:00:00DENIED;
 1.NO FLOOR DRAINS SHOULD BE IN UNITS.
 WATER HEATER ON 2ND FLOOR ARE REQUIRED
 TO HAVE WATER HEATER PANS. FLOOR DRAINS
 ARE NOT NEEDED. REMOVE FLOOR DRAINS.
 2.WATER HEATER DETAIL;
 A) PAN DRAIN LINE TO BE A MIN. OF
 3/4" FBC-2004 EXISTING BUILDING
 SEC.610.3 REFS. TO FBC PLUMBING
 SEC.504.7.1 .
 B)PRESSURE RELIEF VALVE CAN
 TERMINATE IN THE WATER HEATER
 PAN. PLEASE SHOW RELIEF DISCHARGE
 AT 3/4"
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695


Account Summary | Usage Policy | Privacy Policy