| Plan Review Stops For Permit 06090447 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2006-09-14 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2006-09-14 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2006-09-14 |
Time |
11:24 |
Sent To |
|
|
| Notes |
| 2006-09-14 00:00:00 | ADDRESS ON APP READS 611 21ST ST/PAPA | | | READS 608 23RD ST | | | ADDRESS HAD BEEN CORRECTED |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2007-09-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-09-26 |
Time |
18:57 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-09-26 |
Time |
18:57 |
Sent To |
|
|
| Notes |
| 2007-09-26 18:58:12 | REVISIONS TO SHEETS D1, A1, A2,A3, A5 AND A6 HAVE BEEN | | | REVIEWED FOR CODE COMPLIANCE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2007-07-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-07-19 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-07-19 |
Time |
10:21 |
Sent To |
|
|
| Notes |
| 2007-07-19 10:30:48 | REVISIONS TO SHEETS A1, A2, A3, A5, A6 ARE DENIED. | | | | | | 1) ON SHEET A1 THE WINDOW NOTES SPECIFY PGT WINDGUARD | | | WINDOWS. THE CONTRACTOR HAS REVISED THE WINDOW PRODUCT | | | APPROVALS TO IMPACT RATED KDWINDOWS. PLEASE REVISE. | | | | | | 2) THE WINDOWS SIZES SHOWN ON THE ELEVATIONS AND FLOOR | | | PLAN DO NOT CORRESPOND WITH THE DIMENSIONS IN THE | | | WINDOW SCHEDULE ON A1 FOR THE KITCHEN AND BATHROOM | | | WINDOWS. | | | | | | 3) PROVIDE A DETAIL OF THE IN FILL FRAMING AT THE | | | BATHROOMWINDOWS. | | | | | | 4) THE REAR ELEVATION ON A3 HAS THE WRONG DETAIL TAG | | | FOR THE IN FILL FRAMING. IT SHOULD BE 1 ON A6. | | | | | | 5) THE OPENING WIDTH DIMENSION IN DETAIL 1 ON A5 IS TOO | | | SMALL FOR THE WINDOWS SPECIFIED IN THE SCHEDULE ON A1. | | | PLEASE REVISE. | | | | | | 6) THE OPENING WIDTH DIMENSION IN DETAIL 1 ON A6 IS TOO | | | SMALL FOR THE WINDOWS SPECIFIED IN THE SCHEDULE ON A1. | | | PLEASE REVISE. | | | | | | - ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2007-07-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-07-18 |
Time |
18:59 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-07-18 |
Time |
18:59 |
Sent To |
|
|
| Notes |
| 2007-07-18 18:44:58 | REVISED PRODUCT APPROVALS FOR SINGLE HUNG WINDOWS, | | | MULLIONS AND CASEMENT WINDOWS. LETTER FROM ENGINEER | | | CERTIFYING PRODUCTS TO THE 2004 FBC. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2007-06-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-06-26 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-06-26 |
Time |
15:32 |
Sent To |
|
|
| Notes |
| 2007-06-26 15:33:10 | REVISED PRODUCT APPROVALS FOR WINDOWS ARE DENIED | | | | | | 1) PLAN SHEET A-1 WILL BE REQUIRED TO BE REVISED TO | | | REFLECT THE CHANGES TO THE WINDOW TYPES THAT ARE NOT | | | INDICATED IN THE WINDOW SCHEDULE. | | | | | | 2)WPB ADMIN CODE 106.3* PRODUCT | | | APPROVALS. THOSE PRODUCT WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. | | | | | | 3) THE PRODUCT APPROVAL FOR THE SERIES 455 IS MISSING | | | PAGES E-1 AND E-2. | | | | | | 4) THE PRODUCT APPROVALS SUBMITTED FOR THE MULLIONS AND | | | CASEMENT WINDOWS DO NOT COMPLY WITH THE 2004 FBC FOR | | | NOT ALLOWING A 1/3 STRESS INCREASE OF STEEL FASTENERS, | | | BUT HAVE REVISED NOAS THAT DO COMPLY. SUBMIT THE LATEST | | | NOAS. | | | | | | 5) THE PRODUCT APPROVALS FOR THE FIXED WINDOW AND THE | | | SINGLE HUNG WINDOW DO NOT COMPLY WITH THE 2004 FBC FOR | | | THE REASON STATED ABOVE. | | | | | | 6) ADDITIONAL FEES ARE DUE. 5 PRODUCT APPROVALS WERE | | | SUBMITTED AND THE FEE WAS ASSESSED FOR ONE. AN | | | ADDITIONAL $40.00 IS DUE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2007-04-25 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-04-25 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-04-25 |
Time |
16:08 |
Sent To |
|
|
| Notes |
| 2007-04-25 16:12:56 | REVISED DOOR PRODUCT APPROVAL IS OK. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-01-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-01-09 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-01-09 |
Time |
15:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-11-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-11-16 |
Time |
08:05 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-11-16 |
Time |
07:30 |
Sent To |
|
|
| Notes |
| 2006-11-16 08:04:52 | DENIED BY BUILDING | | | | | | 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | | MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) SPECIFY THE STUD SPACING IN THE WALL SECTION ON | | | SHEET A-5. | | | | | | 3) ASTM C926REQUIRES STUCCO APPLIED VERTICALLY OVER | | | METAL LATH WITH A SOLID BASE TO HAVE A MINIMUM | | | THICKNESS OF 7/8". SEE FBC 2510.3. PLEASE CORRECT WALL | | | SECTION ON A-5. | | | | | | 4)FBC 2510.6 REQUIRES A WEATHER RESISTANT BARRIER | | | OVER THE PLYWOOD BACKING BEHIND THE LATH AND STUCCO. | | | PLEASE SPECIFY ON WALL SECTION ON A-5. | | | | | | 5) THE WINDOW SCHEDULE ON A-1 STILL HAS ERRORS. THERE | | | ARE MASONRY OPENINGS SPECIFIED THAT ARE THE SAME SIZE | | | OR SMALLER THAN THE WINDOW SIZES. THE SIZE CODE FOR | | | CASEMENT WINDOWS D, O, V & GG ARE NOT CORRECT. PLEASE | | | CORRECT. | | | | | | 6) PLEASE SUBMIT PRODUCT APPROVALS ( APPROVED BY THE | | | D.O.R.) FOR THE STRUCTURAL WINDOW MULLIONS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-09-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-09-19 |
Time |
10:44 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-09-19 |
Time |
09:10 |
Sent To |
|
|
| Notes |
| 2006-09-19 00:00:00 | DENIED BY BUILDING | | | | | | 1)A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) SPECIFY THE LEVEL OF ALTERATION FOR | | | THE PROJECT. SEE 2004 FBC EXISTING | | | BUILDING CODE CHAPTER 3. | | | | | | 3) BEDROOM WINDOWS MUST COMPLY WITH | | | EMERGENCY EGRESS REQUIREMENTS OF FBC | | | 1025. | | | | | | 4) THE NOTE ON SHEET A5 STATES TO FASTEN | | | P.T. TO CONC. W/ 1/4" DIA.X 3/4"CONC. | | | SCEWS @ 16" O.C. THAT LENGTH FASTENER | | | WILL NOT BE SUFFICENT TO ATTACH THE | | | 2X8S. PLEASE CORRECT. | | | | | | 5) THE TAGS FOR DETAIL 1/SK IS SPECIFIED | | | ON SHEET A-3. IN ORDER TO BETTER LOCATE | | | THESE DETAILS, PLEASE SPECIFY THE SHEET | | | ON WHICH THE DETAIL IS LOCATED AS THE | | | BOTTOM CHARACTERS OF THE ID TAG. | | | | | | 6) PLEASE SPECIFY THE REPAIRS THAT WILL | | | BE DONE TO THE BALCONIES. "REPAIR AS | | | NEEDED" IS TOO GENERAL. SEE CITY | | | AMENDMENTS TO FBC 106.1.1. | | | | | | 7) ON SHEET A3 THE KITCHEN DOORS ARE | | | SHOWN ON THE SOUTH ELEVATION WITH | | | WINDOWS. SUBMIT PRODUCT APPROVALS FOR | | | DOORS WITH WINDOWS AS INDICATED BY | | | PLANS. | | | | | | 8) SUBMIT PRODUCT APPROVALS FOR THE | | | VENTED STORAGE ROOM DOORS AS SHOWN ON A3 | | | OF PLANS. | | | | | | 9) THE WINDOW SCHEDULE ON A2 CONTAINS | | | SEVERAL ERRORS. | | | - THE MASONRY OPENING HEIGHTS ARE | | | SMALLER THAN THE WINDOW HEIGHTS FOR | | | SEVERAL OF THE WINDOWS LISTED. | | | - THE WINDOW CODE SIZE FOR SEVERAL OF | | | THE ONES LISTED SHOULD BE SH25 OR 25, | | | NOT H25 FOR THE SINGLE HUNG WINDOWS. | | | PLEASE REVIEW SCHEDULE AND CORRECT. | | | | | | 10) THE STREET HAS BEEN CHANGED IN THE | | | TITLE BLOCK OF THE PLANS. ALL CHANGES TO | | | SIGNED AND SEALED PLANS ARE REQUIRED TO | | | BE MADE BY THE DESIGN PROFESSIONAL THAT | | | IS SEALING THEM. | | | | | | 11) CLARIFY THE SCOPE WORK THAT IS | | | INDICATED BY DETAIL 1/SK. IS THIS | | | EXTERIOR WALL BEING DEMOLISHED AND | | | REPLACED WITH A NEW WALL? IF IT IS | | | PROVIDE A WALL CROSS-SECTION SPECIFYING | | | THE EXTERIOR SUBSTRATE BEHIND THE | | | STUCCO, VAPOR BARRIER, THE R-VALUE OF | | | THE WALL INSULATION, ETC. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2007-09-26 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-09-26 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-09-26 |
Time |
12:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2007-06-29 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-06-27 |
Time |
13:28 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-06-27 |
Time |
12:14 |
Sent To |
|
|
| Notes |
| 2007-06-27 13:30:58 | | | | | | | REVISION DENIED | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE CONDUIT FOR THE SERVICE RISER DOES NOT COMPLY | | | WITH TABLE C-8 FOR FILL REQUIREMENT, THIS WAS REDLINED | | | ON THE PREVIOUS REVIEW, PLEASE CORRECT ON THE PLAN. | | | SHEET E-2. | | | | | | 2} VERIVY CIRCUIT #3 ON THE PANEL SCHEDULE, 20 AMP WITH | | | #8 CONDUCTORS, LISTED A SPARE. | | | | | | 3} CLOUD THE REVISIONS ON SHEETS E-3 AND E-4. | | | | | | 4} RELOCATE THE RANGE AND WATER HEATER RECEPTACLES TO | | | THEIR RELEVANT LOCATION, OR REMOVE IF NOT BEING | | | INSTALLED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2007-03-02 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-03-02 |
Time |
16:40 |
Rev Time |
2.00 |
| Received By |
btrobaug |
Date |
2007-02-23 |
Time |
16:04 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-01-03 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-01-03 |
Time |
18:08 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2007-01-03 |
Time |
17:05 |
Sent To |
|
|
| Notes |
| 2007-01-03 18:08:26 | | | | NONCOMPLIANT. | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE PANELS ARE SHOWING THREE PHASE BUSSES (A,,B,C), | | | REMOVE "C". | | | | | | 2} THE #8 EQUIPMENT GROUND FROM THE METER TO THE HOUSE | | | PANEL IS IN VIOLATION OF 250.6 AND SHALL BE REMOVED. | | | THIS WILL BE INSTALLED AFTER THE DISCONNECT WHERE THE | | | NEUTRAL WILL BE ISOLATED FROM THE GROUND.. | | | | | | 3} THE DISHWASHER STILL APPEARS ON THE PLAN. ADD TO THE | | | CALCS OR REMOVE SAME, 220 | | | | | | 4} THE BATHROOM CIRCUIT IS LISTED AS 240 VOLTS IN THE | | | NOTES SHEET E-1 AND E-2. | | | | | | 5} THE WASHER/DRYER STACK UNITS ARE SHOWN ON THE PLAN | | | BUT NOT IN THE CALCS. SOME ARE 240 AND SOME ARE 120 | | | VOLT, PLEASE CORRELATE. | | | | | | 6} THE BATTERY PACK EMERGENCU LIGHTS MUST BE ON A LOCAL | | | CIRCUIT TO FUNCTION WHEN THAT CIRCUIT FAILS. SEE | | | 700.12(E) FOR VERBAGE. | | | | | | WILLIAM R. TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-11-14 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-11-14 |
Time |
17:42 |
Rev Time |
0.75 |
| Received By |
btrobaug |
Date |
2006-11-14 |
Time |
17:28 |
Sent To |
|
|
| Notes |
| 2006-11-14 17:42:30 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE LOAD CALCULATIONS ARE SHOWN AS | | | USING THE DEMAND FACTOR IN 230.31 (40%), | | | AND THEN TAKING AN ADDITIONAL DEMAND | | | FACTOR FROM TABLE 230.32(45%). WHILE | | | EITHER ONE IS PERMISSIBLE, NOT TOGETHER. | | | ALSO SEE 230.32(B) REGARDING HOUSE | | | LOADS. THIS COMMENT WAS ON THE PRIOR REVIEW. | | | | | | 2} ALL BRANCH CIRCUIT PANEL DESIGNATIONSARE | | | INCORRECT.(FA #S ETC). | | | | | | 3} THE DISHWASHER CIRCUIT REFERENCED ON E-2 IS NOT ON | | | THE PANEL SCHEDULE OR IN THE LOAD CALCULATION. | | | | | | 4} THE WASHER/DRYER APPEARS TO BE STACKED ON THE PLAN, | | | PLEASE CORRECT THE SCHEDULE. | | | | | | 5} THE SMALL APPLIANCE CIRCUITS FOR THE KITCHEN MUST | | | COMPLY WITH 210.52(B)(3), TWO IN THE KITCHEN, THERE IS | | | ONLY ONE. CIRCUIT #12 MAY BE IN THE DINING ROOM, BUT | | | MUST ALSO BE IN THE KITCHEN. | | | | | | 6} THE GFI ON THE OUTSIDE IN FRONT IS IN VIOLATION OF | | | 210.52(B)(2), CANNOT BE ON THE SMALL APPLIANCE | | | CIRCUIT. | | | | | | 7} THE GFI IN THE BACK OUTSIDE IS IN VIOLATION OF | | | 210.11(C)(3), BATH CIRCUITS. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-09-21 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-09-21 |
Time |
13:16 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2006-09-21 |
Time |
11:25 |
Sent To |
|
|
| Notes |
| 2006-09-21 00:00:00 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE LOAD CALCULATIIONS ARE SHOWN AS | | | USING THE DEMAND FACTOR IN 230.31 (40%), | | | AND THEN TAKING AN ADDITIONAL DEMAND | | | FACTOR FROM TABLE 230.32(45%). WHILE | | | EITHER ONE IS PERMISIBLE, NOT TOGETHER. | | | ALSO SEE 230.32(B) REGARDING HOUSE | | | LOADS. | | | | | | 2} TH EGROUNDING ELECTRODE CONDUCTOR IS | | | TOO SMALL FOR THE SERVICE SHOWN AND WILL | | | CERTAINLY BE TOO SMALL FOR THE SERVICE | | | WHEN THE CALCULATIONS ARE ADJUSTED. SEE | | | 250.66. | | | | | | 3} PLEASE LIST THE CONDUCTOR SIZES WITH | | | THE BREAKER SIZES ON THE PANEL SCHEDULE | | | SO THAT COMPLIANCE WITH 310.16 AND | | | 240.CAN BE REVIEWED. | | | | | | 4} THERE ARE AIR HANDLERS SHOWN ON THE | | | PLAN BUT NOT LISTED ON THE SCHEDULE OR | | | NOT INCLUDED IN THE CALCULATIONS. PLEASE | | | INCLUDE. | | | | | | 5} THE BATH CIRCUIT REQUIRED BY | | | 210.11(C)(3)IS NOT IN THE SCHEDULE. | | | | | | 6} THERE APPEARS TO BE ONLY ONE SMALL | | | APPLIANCE CIRCUIT IN THE KITCHEN, TWO | | | ARE REQUIRED PER 210.52(B)(1). | | | | | | 7} BEDROOM 1 AND BEDROOM 2 CIRCUIT | | | NUMBERS DO NOT CORRESPOND TO THE | | | SCHEDULE . | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2007-09-28 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-09-28 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-09-28 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2007-09-28 14:15:43 | PLANS WERE APPROVED ON 2/23/07. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-02-23 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-02-23 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-02-23 |
Time |
16:36 |
Sent To |
|
|
| Notes |
| 2007-02-23 16:39:07 | *****APPROVED****** | | | | | | | | | ALL COMMENTS FROM PREVIOUS FIRE PLAN REVIEWS HAVE BEEN | | | ADDRESSED.SHEETS A-3 AND E-3 WERE STAMPED, INITIALED, | | | AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2006-11-16 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-11-16 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-11-16 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2006-11-16 09:52:53 | *****PROVISO***** | | | | | | | | | | | | | | | 1.PLEASE SHOW THE ADDRESS OF THE PROPOSED STRUCTURE | | | ON THE ELEVATION SHEET.BE ADVISED THAT THE | | | APARTMENT/UNIT ALPHABET OR NUMBER FOR THE FRONT | | | ENTRANCE SHOULD NOT BE ON THE DOORS, BUT INSTEAD ON THE | | | BUILDING ABOVE OR NEAR THE DOOR OPPOSITE OF THE SWING | | | OF THE DOOR.IF THE UNITS ARE EQUIPPED WITH REAR | | | DOORS, THE ALPHABET OR NUMBER MAY BE ON THE DOOR. | | | | | | | | | | | | | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-804-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-09-21 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-09-21 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-09-21 |
Time |
15:05 |
Sent To |
|
|
| Notes |
| 2006-09-21 00:00:00 | ***DENIED*** | | | | | | 1) PLEASE NOTE THAT BEDROOM WINDOWS | | | SHALL COMPLY WITH NFPA 101, 2003 | | | EDITION, REGARDING SECONDARY MEANS OF | | | EGRESS. | | | | | | 2) CONSTRUCTION, ALTERATION AND | | | DEMOLITION TO COMPLY WITH NFPA 241. | | | DEBRIS TO BE CLEANED FROM SITE DAILY. | | | | | | 3) IF REPAIR TO BALCONIES IMPACT | | | HANDRAILS AND GUARDS, PLEASE PROVIDE | | | DETAILS AND PRESCRIPTIVE STRENGTH | | | REQUIREMENTS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2007-09-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-13 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-13 |
Time |
08:28 |
Sent To |
|
|
| Notes |
| 2007-09-25 15:50:01 | TO "COMM" BD#25--EXPEDITED-- | | 2007-09-13 08:28:44 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2007-07-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-16 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-16 |
Time |
10:48 |
Sent To |
B |
|
| Notes |
| 2007-07-16 10:49:29 | TO "RMCDOUGAL" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2007-06-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-19 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-19 |
Time |
16:27 |
Sent To |
B |
|
| Notes |
| 2007-06-19 16:27:26 | TO "RMCDOUGAL" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-06-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-15 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-15 |
Time |
14:29 |
Sent To |
|
|
| Notes |
| 2007-06-26 09:25:00 | TO "COMM" BD#12 | | 2007-06-15 14:30:19 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-04-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-25 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-25 |
Time |
11:20 |
Sent To |
B |
|
| Notes |
| 2007-04-25 11:20:30 | TO "RMCDOUGAL" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-02-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-22 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-22 |
Time |
11:57 |
Sent To |
E |
|
| Notes |
| 2007-02-22 11:58:19 | TO "BTROBAUG" DESK/RESUB--EXPEDITED PERMIT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-12-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-22 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-22 |
Time |
09:49 |
Sent To |
|
|
| Notes |
| 2006-12-22 09:53:22 | TO "COMM" BD#31--EXPEDITED PERMIT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-11-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-11-09 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-09 |
Time |
15:00 |
Sent To |
B |
|
| Notes |
| 2006-11-09 15:00:37 | TO "LMARTINEZ" DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-09-22 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-09-22 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-09-15 |
Time |
15:11 |
Sent To |
|
|
| Notes |
| 2006-09-15 00:00:00 | TO "BOB"#7 | | 2006-09-14 00:00:00 | EXPEDITED PERMIT |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2006-09-22 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-09-22 |
Time |
08:53 |
Rev Time |
|
| Received By |
jleech |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2007-09-27 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-09-27 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-09-27 |
Time |
10:36 |
Sent To |
|
|
| Notes |
| 2007-09-27 10:37:20 | GAS PERMIT REQUIRED |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2007-07-16 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-07-16 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-07-16 |
Time |
09:37 |
Sent To |
|
|
| Notes |
| 2007-07-16 09:55:39 | PROVISO | | | | | | | | | GAS CONTRACTOR TO SUBMIT A GAS RISER DIAGRAM WITH ALL | | | REQUIRED INFORMATION AND INSTALLATION SPECIFICATIONS | | | WITH PERMIT APPLICATION. CLEARANCES BETWEEN WINDOWS | | | MUST BE SHOWN IN DRAWING FORM. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2007-01-06 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-01-06 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-01-06 |
Time |
08:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2006-11-17 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-11-17 |
Time |
08:03 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-11-17 |
Time |
08:03 |
Sent To |
|
|
| Notes |
| 2006-11-17 08:28:01 | DENIED; | | | 1. AUTOMATIC CLOTHES WASHERS ARE NOT SHOWN ON FLOOR | | | PLAN. PAGES A-1 AND A-2 PLEASE ADD. | | | 2. AUTOMATIC CLOTHES WASHER BRANCH DRAIN IS REQUIRED TO | | | BE 3". SEE FBC-2004 PLUMBING SECTION 406.3. | | | 3. PLEASE SIZE ALL PIPES ON RISER DIAGRAM. | | | 4.ENGINEER TO SIGN NOT INITIAL PLANS. | | | 5. WATER RISER DIAGRAM PAGE P-2 WATER HAMMER ARRESTORS | | | ARE REQUIRED AT THE AUTOMATIC CLOTHES WASHERS. PLEASE | | | SHOW ON DRAWINGS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-09-22 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-09-22 |
Time |
07:57 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-09-22 |
Time |
07:57 |
Sent To |
|
|
| Notes |
| 2006-09-22 00:00:00 | DENIED; | | | 1.NO FLOOR DRAINS SHOULD BE IN UNITS. | | | WATER HEATER ON 2ND FLOOR ARE REQUIRED | | | TO HAVE WATER HEATER PANS. FLOOR DRAINS | | | ARE NOT NEEDED. REMOVE FLOOR DRAINS. | | | 2.WATER HEATER DETAIL; | | | A) PAN DRAIN LINE TO BE A MIN. OF | | | 3/4" FBC-2004 EXISTING BUILDING | | | SEC.610.3 REFS. TO FBC PLUMBING | | | SEC.504.7.1 . | | | B)PRESSURE RELIEF VALVE CAN | | | TERMINATE IN THE WATER HEATER | | | PAN. PLEASE SHOW RELIEF DISCHARGE | | | AT 3/4" | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|