| Plan Review Stops For Permit 06090444 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
P |
Date |
2007-09-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-09-27 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-09-27 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2007-09-27 11:34:02 | REVISED SHEETS D1,A1,A2,A3 AND A5 HAVE BEEN REVIEWED | | | FOR BUILDING CODE COMPLIANCE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
F |
Date |
2007-07-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-07-20 |
Time |
07:46 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-07-20 |
Time |
07:46 |
Sent To |
|
|
| Notes |
| 2007-07-20 07:51:30 | REVISIONS TO SHEETS D1, A1, A2, A3 AND A5 ARE DENIED. | | | | | | 1) ON SHEET A1 THE WINDOW NOTES SPECIFY PGT WINDGUARD | | | WINDOWS. THE CONTRACTOR IS IN THE PROCESS OF CHANGING | | | THE WINDOW PRODUCT APPROVALS TO IMPACT RATED KD | | | WINDOWS. PLEASE REVISE. | | | | | | 2) THE WINDOWS SIZES SHOWN ON THE ELEVATIONS AND FLOOR | | | PLAN DO NOT CORRESPOND WITH THE DIMENSIONS IN THE | | | WINDOW SCHEDULE ON A1 FOR THE KITCHEN AND BATHROOM | | | WINDOWS. | | | | | | 3) PROVIDE A DETAIL OF THE IN FILL FRAMING AT THE | | | BATHROOMWINDOWS. | | | | | | 4) THE OPENING WIDTH DIMENSION IN DETAIL 1 ON A5 IS TOO | | | SMALL FOR THE WINDOWS SPECIFIED IN THE SCHEDULE ON A1. | | | PLEASE REVISE. | | | | | | - ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2007-06-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-06-26 |
Time |
13:58 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-06-26 |
Time |
13:58 |
Sent To |
|
|
| Notes |
| 2007-06-26 15:11:49 | REVISED PRODUCT APPROVALS FOR WINDOWS ARE DENIED | | | | | | 1) PLAN SHEET A-1 WILL BE REQUIRED TO BE REVISED TO | | | REFLECT THE CHANGES TO THE WINDOW TYPES THAT ARE NOT | | | INDICATED IN THE WINDOW SCHEDULE. | | | | | | 2)WPB ADMIN CODE 106.3* PRODUCT | | | APPROVALS. THOSE PRODUCT WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. | | | | | | 3) THE PRODUCT APPROVAL FOR THE SERIES 455 IS MISSING | | | PAGES E-1 AND E-2. | | | | | | 4) THE PRODUCT APPROVALS SUBMITTED FOR THE MULLIONS AND | | | CASEMENT WINDOWS DO NOT COMPLY WITH THE 2004 FBC FOR | | | NOT ALLOWING A 1/3 STRESS INCREASE OF STEEL FASTENERS, | | | BUT HAVE REVISED NOAS THAT DO COMPLY. SUBMIT THE LATEST | | | NOAS. | | | | | | 5) THE PRODUCT APPROVALS FOR THE FIXED WINDOW AND THE | | | SINGLE HUNG WINDOW DO NOT COMPLY WITH THE 2004 FBC FOR | | | THE REASON STATED ABOVE. | | | | | | 6) ADDITIONAL FEES ARE DUE. 5 PRODUCT APPROVALS WERE | | | SUBMITTED AND THE FEE WAS ASSESSED FOR ONE. AN | | | ADDITIONAL $40.00 IS DUE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2007-04-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-04-23 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-04-23 |
Time |
13:32 |
Sent To |
|
|
| Notes |
| 2007-04-23 13:34:54 | THE REVISION FOR BALCONY REPAIR PER SIGNED AND SEALED | | | DRAWING SUBMITTED IS OK. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2007-04-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-04-23 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-04-23 |
Time |
12:42 |
Sent To |
|
|
| Notes |
| 2007-04-23 13:16:33 | REVISION DENIED | | | | | | 1) THE PRODUCT APPROVALS FOR THE BRUNSWICK EXTERIOR | | | DOORS ARE REQUIRED TO BE REVIEWED AND APPROVED IN | | | WRITING BY THE DESIGNER OF RECORD FOR THE PROJECT. | | | WPB ADMIN CODE 106.3* PRODUCT | | | APPROVALS. THOSE PRODUCT WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2007-04-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-04-09 |
Time |
18:22 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-04-09 |
Time |
17:58 |
Sent To |
|
|
| Notes |
| 2007-04-09 18:23:13 | DENIED BY BUILDING | | | | | | 1) THE ENGINEERING SUBMITTED FOR THE NEW SLAB EDGE | | | SUPPORT AT THE REAR BALCONY WAS NOT INCLUDED IN THE | | | SCOPE OF WORK THAT WAS PERMITTED. THE COST OF THE | | | ADDITIONAL WORK IS REQUIRED SO THAT IT CAN BE ADDED TO | | | THE VALUE OF THE PROJECT. THIS SHOULD BE SUBMITTED AS A | | | REVISION. | | | | | | 2) PLEASE CLARIFY IF THIS IS NEW WORK OR IS IT REPAIRS | | | TO THE EXISTING BALCONY OR IS A PORTION OF THE EXISTING | | | BALCONY BEING REPLACED. | | | | | | 3) PROVIDE SIGNED AND SEALED DRAWINGS INDICATING THE | | | LOCATION AND EXTENT OF THE REPAIRS OR NEW CONSTRUCTION. | | | | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-01-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-01-09 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-01-09 |
Time |
11:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-11-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-11-16 |
Time |
06:42 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-11-15 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2006-11-16 07:09:23 | DENIED BY BUILDING | | | | | | 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | | MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) SPECIFY THE STUD SPACING IN THE WALL SECTION ON | | | SHEET A-5. | | | | | | 3) ASTM C926REQUIRES STUCCO APPLIED VERTICALLY OVER | | | METAL LATH WITH A SOLID BASE TO HAVE A MINIMUM | | | THICKNESS OF 7/8". SEE FBC 2510.3. PLEASE CORRECT WALL | | | SECTION ON A-5. | | | | | | 4)FBC 2510.6 REQUIRES A WEATHER RESISTANT BARRIER | | | OVER THE PLYWOOD BACKING BEHIND THE LATH AND STUCCO. | | | PLEASE SPECIFY ON WALL SECTION ON A-5. | | | | | | 5) THE SECOND FLOOR DEMO PLANS ON SHEET D-2 DO NOT SHOW | | | THE BATHROOM WINDOWS. PLEASE CORRECT. | | | | | | 6) PLEASE SUBMIT PRODUCT APPROVALS ( APPROVED BY THE | | | D.O.R.) FOR THE STRUCTURAL WINDOW MULLIONS. | | | | | | 7) THE WINDOW SCHEDULE ON A-1 STILL HAS ERRORS. THERE | | | ARE MASONRY OPENINGS SPECIFIED THAT ARE SMALLER THAN | | | THE WINDOW SIZES.PLEASE CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-09-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-09-18 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-09-18 |
Time |
07:12 |
Sent To |
|
|
| Notes |
| 2006-09-18 00:00:00 | DENIED BY BUILDING | | | | | | 1)A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) SPECIFY THE LEVEL OF ALTERATION FOR | | | THE PROJECT. SEE 2004 FBC EXISTING | | | BUILDING CODE CHAPTER 3. | | | | | | 3) BEDROOM WINDOWS MUST COMPLY WITH | | | EMERGENCY EGRESS REQUIREMENTS OF FBC | | | 1025. | | | | | | 4) THE NOTE ON SHEET A5 STATES TO FASTEN | | | P.T. TO CONC. W/ 1/4" DIA.X 3/4"CONC. | | | SCEWS @ 16" O.C. THAT LENGTH FASTENER | | | WILL NOT BE SUFFICENT. PLEASE CORRECT. | | | | | | 5) A TAG FOR DETAIL 2/SK IS SPECIFIED ON | | | SHEET A3. I WAS UNABLE TO LOCATE THIS | | | DETAIL. PLEASE SPECIFY THE SHEET ON | | | WHICH THE DETAIL IS LOCATED AS THE | | | BOTTOM CHARACTERS OF THE ID TAG. | | | | | | 6) PLEASE SPECIFY THE REPAIRS THAT WILL | | | BE DONE TO THE BALCONIES. "REPAIR AS | | | NEEDED" IS TOO GENERAL. SEE CITY | | | AMENDMENTS TO FBC 106.1.1. | | | | | | 7) ON SHEET A3 THE KITCHEN DOORS ARE | | | SHOWN ON THE SOUTH ELEVATION WITH | | | WINDOWS. SUBMIT PRODUCT APPROVALS FOR | | | DOORS WITH WINDOWS AS INDICATED BY | | | PLANS. | | | | | | 8) SUBMIT PRODUCT APPROVALS FOR THE | | | VENTED STORAGE ROOM DOORS AS SHOWN ON A3 | | | OF PLANS. | | | | | | 9) THE WINDOW SCHEDULE ON A2 CONTAINS | | | SEVERAL ERRORS. | | | - WINDOW JJ IS LOCATED IN A BEDROOM, NOT | | | A BATHROOM. | | | - THE MASONRY OPENING HEIGHTS ARE | | | SMALLER THAN THE WINDOW HEIGHTS FOR | | | SEVERAL OF THE WINDOWS LISTED. | | | - THE WINDOW CODE SIZE FOR SEVERAL OF | | | THE ONES LISTED SHOULD BE SH25 NOT H25. | | | PLEASE REVIEW SCHEDULE AND CORRECT. | | | | | | 10) CLARIFY THE SCOPE OF WORK THAT IS | | | INDICATED BY DETAIL 1/SK. IS THIS THE | | | EXTERIOR WALL BEING DEMOLISHED AND | | | REPLACED WITH A NEW WALL? IF IT IS, | | | PROVIDE A CROSS-SECTION OF THE NEW WALL | | | SPECIFYING EXTERIOR AND INTERIOR WALL | | | COVERINGS, EXTERIOR SUBSTRATE, VAPOR | | | BARRIER, INSULATION (R-VALUE), ETC. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2007-09-26 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-09-26 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-09-26 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2007-09-26 11:59:56 | | | | | | | MARKED AS REV #5, 9/6/07./WRT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2007-06-29 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-06-29 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-06-29 |
Time |
12:06 |
Sent To |
|
|
| Notes |
| 2007-06-29 13:41:27 | | | | | | | | | | REVISION DENIED | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE CONDUIT FOR THE SERVICE RISER DOES NOT COMPLY | | | WITH TABLE C-8 FOR FILL REQUIREMENT, THIS WAS REDLINED | | | ON THE PREVIOUS REVIEW, PLEASE CORRECT ON THE PLAN. | | | SHEET E-2. | | | | | | 2} VERIVY CIRCUIT #3 & #4ON THE PANEL SCHEDULE, 20 AMP | | | WITH #12 CONDUCTORS, LISTED A SPARE. | | | | | | 3} CLOUD THE REVISIONS ON ALL SHEETS. | | | | | | 4} RELOCATE THE RANGE AND WATER HEATER RECEPTACLES TO | | | THEIR RELEVANT LOCATION, OR REMOVE IF NOT BEING | | | INSTALLED. | | | | | | 5} CIRCUITS #13, 15 AND 17 ARE #14 CONDUCTOR IN | | | CONFLICT WITH THE ELECTRICAL SPECIFICATIONS ON SHEET | | | E-4 CALLING FOR #12 CONDUCTORS MINIMUM. PLEASE | | | CLARIFY. | | | | | | 6} THE ENGINEER NEEDS TO SEAL THE PLANS SO THE | | | IMPRESSION IS LEGIBLE PER 471.025 FS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2007-02-23 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-02-23 |
Time |
14:57 |
Rev Time |
2.00 |
| Received By |
btrobaug |
Date |
2007-02-22 |
Time |
17:08 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-01-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-01-08 |
Time |
17:47 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2007-01-02 |
Time |
07:55 |
Sent To |
|
|
| Notes |
| 2007-01-08 17:46:07 | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE NOTES ARE INDICATING 240 VOLT CIRCUITS FOR THE | | | BATHROOM CIRCUIT, PLEASE CORRECT. | | | | | | 2} THE SYMBOL ON THE PLAN AT THE WASHER INDICATES A 240 | | | VOLT RECEPTACLE, ALL UNITS, CORRELATE WITH SCHEDULE. | | | | | | 3} THE SMALL APPLIANCE CIRCUIT IN EACH OF THE UNITS | | | EXTENDS INTO THE LIVING ROOM IN VIOLATION OF | | | 210.52(B)(1). | | | | | | 4} THE EMERGENCY LIGHTS MUST BE ON THE SAME CIRCUIT AS | | | THE STAIR LIGHTING PER 700.12(E). | | | | | | 5} THE PANELS INDICATE THEY ARE 24 POLE, BUT ONLY 18 | | | CIRCUITS ARE SHOWN ON EACH. PLEASE COMPLETE THE PANEL | | | SCHEDULES PER 408.4. | | | | | | 6} THE DESIGNATION FOR SMOKE DETECTORS ON THE PLAN | | | INDICATES A LOW VOLTAGE ALARM TYPE SYSTEMWITH | | | AUDIO/VISUAL DEVICES. PLEASE LOCATE ALL DEVICES ON THE | | | PLAN.IF THESE ARE 120 VOLT ALARMS WITH BATTERY BACK UP | | | PLEASE CORRECTLY DESIGNATE AS "SA" TO ELIMINATE | | | CONFUSIONFOR THE INSTALLER. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | | | | ONE SET OF PLANS IS BEING RETAINED BY THIS OFFICE. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-11-14 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-11-14 |
Time |
17:21 |
Rev Time |
0.75 |
| Received By |
btrobaug |
Date |
2006-11-14 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2006-11-14 17:20:33 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE LOAD CALCULATIONS ARE SHOWN AS | | | USING THE DEMAND FACTOR IN 230.31 (40%), | | | AND THEN TAKING AN ADDITIONAL DEMAND | | | FACTOR FROM TABLE 230.32(45%). WHILE | | | EITHER ONE IS PERMISSIBLE, NOT TOGETHER. | | | ALSO SEE 230.32(B) REGARDING HOUSE | | | LOADS. THIS COMMENT WAS ON THE PRIOR REVIEW. | | | | | | 2} ALL LIGHTING BRANCH CIRCUIT PANEL DESIGNATIONS ON | | | SHEETS E-1 AND E-2 ARE INCORRECT.(FA #S) | | | | | | 3} THE DISHWASHER CIRCUIT REFERENCED ON E-2 IS NOT ON | | | THE PANEL SCHEDULE OR IN THE LOAD CALCULATION. | | | | | | 4} THE WASHER/DRYER APPEARS TO BE STACKED ON THE PLAN, | | | PLEASE CORRECT THE SCHEDULE. | | | | | | 5} THE SMALL APPLIANCE CIRCUITS FOR THE KITCHEN MUST | | | COMPLY WITH 210.52(B)(3), TWO IN THE KITCHEN, THERE IS | | | ONLY ONE. CIRCUIT #12 MAY BE IN THE DINING ROOM, BUT | | | MUST ALSO BE IN THE KITCHEN. | | | | | | 6} THE GFI ON THE OUTSIDE IN FRONT IS IN VIOLATION OF | | | 210.52(B)(2), CANNO TBE ON THTE SMALL APPLIANCE | | | CIRCUIT. | | | | | | 7} THE GFI IN THE BACK OUTSIDE IS IN VIOLATION OF | | | 210.11(C)(3), BATH CIRCUITS. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | 2006-11-14 16:23:52 | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-09-25 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-09-25 |
Time |
18:09 |
Rev Time |
0.75 |
| Received By |
btrobaug |
Date |
2006-09-25 |
Time |
17:52 |
Sent To |
|
|
| Notes |
| 2006-09-25 00:00:00 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE LOAD CALCULATIIONS ARE SHOWN AS | | | USING THE DEMAND FACTOR IN 230.31 (40%), | | | AND THEN TAKING AN ADDITIONAL DEMAND | | | FACTOR FROM TABLE 230.32(45%). WHILE | | | EITHER ONE IS PERMISIBLE, NOT TOGETHER. | | | ALSO SEE 230.32(B) REGARDING HOUSE | | | LOADS. | | | | | | 2} THE GROUNDING ELECTRODE CONDUCTOR IS | | | TOO SMALL FOR THE SERVICE SHOWN AND WILL | | | CERTAINLY BE TOO SMALL FOR THE SERVICE | | | WHEN THE CALCULATIONS ARE ADJUSTED. SEE | | | 250.66. | | | | | | 3} PLEASE LIST THE CONDUCTOR SIZES WITH | | | THE BREAKER SIZES ON THE PANEL SCHEDULE | | | SO THAT COMPLIANCE WITH 310.16 AND | | | 240.CAN BE REVIEWED. | | | | | | 4} THERE ARE AIR HANDLERS SHOWN ON THE | | | PLAN BUT NOT LISTED ON THE SCHEDULE OR | | | NOT INCLUDED IN THE CALCULATIONS. PLEASE | | | INCLUDE. | | | | | | 5} THE BATH CIRCUIT REQUIRED BY | | | 210.11(C)(3)IS NOT IN THE SCHEDULE. | | | | | | 6} THERE APPEARS TO BE ONLY ONE SMALL | | | APPLIANCE CIRCUIT IN THE KITCHEN, TWO | | | ARE REQUIRED PER 210.52(B)(1). LIST SAME | | | ON SCHEDULE. | | | | | | 7} BEDROOM 1 AND BEDROOM 2 CIRCUIT | | | NUMBERS DO NOT CORRESPOND TO THE | | | SCHEDULE . | | | | | | 8} SEE THAT ALL ITEMS ON PLAN SHOWN ON | | | THE GROUNDING ELECTRODE SYSTEM MUST BE | | | INSTALLED IF SHOWN ON PLANS , PLEASE | | | VERIFY IF ALL ARE AVAILABLE PER | | | 250.50-250.52. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2006-12-29 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2006-12-29 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2006-12-29 |
Time |
08:56 |
Sent To |
|
|
| Notes |
| 2006-12-29 09:00:24 | ACCORDING TO THE DESCRIPTION STATEMEMENT, THERE IS NO | | | ENG REQUIRED.IT ALL INTERIOR RENOVATION AND IMPACT | | | GLASS WINDOWS REPLACEMENT. THEREFOE, LUIS M. & I | | | CONCLUDED THAT ENG REVIEW IS NOT REQUIRED. | | | | | | RASIK CHOKSHI805-6723 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2007-09-28 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-09-28 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-09-28 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2007-09-28 13:37:04 | COMMENTS FROM LAST FIRE REVIEW HAVE BEEN ADDRESSED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
F |
Date |
2007-07-26 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-07-26 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-07-26 |
Time |
14:13 |
Sent To |
|
|
| Notes |
| 2007-07-26 14:28:43 | *****UNSAT***** | | | | | | SHEETS A-3, E-1, AND E-2 WERE STAMPED, INITIALED, AND | | | DATED AS APPROVED ON 02/23/2007;HOWEVER THE REVISED | | | DRAWINGS NEED TO BE RECTIFIED AS LISTED BELOW: | | | | | | | | | 1.ON DRAWING A-3,NO UNIT LETTER SHOWN/DISPLAYED ON | | | THE UPPER APT./UNITS. | | | | | | 2.NO DISTINGUISHABLE SEAL ON DRAWING E-1 AND E-2. | | | | | | 3.COULD YOU PLEASE EXPLAIN THE REFERENCE TO UNIT 7G | | | ATTACHED TO THE ADDRESS AND ITS RELEVANCE? | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-02-23 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-02-23 |
Time |
15:25 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-02-23 |
Time |
15:25 |
Sent To |
|
|
| Notes |
| 2007-02-23 15:28:24 | *****APPROVED***** | | | | | | | | | ALL PREVIOUS FIRE PLAN REVIEW COMMENTS HAVE BEEN | | | ADDRESSED.SHEETS A-3, E-1, AND E-2 WERE STAMPED, | | | INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2006-11-16 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-11-16 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-11-16 |
Time |
10:10 |
Sent To |
|
|
| Notes |
| 2006-11-16 10:11:41 | *****PROVISO***** | | | | | | | | | | | | | | | 1.PLEASE SHOW THE ADDRESS OF THE PROPOSED STRUCTURE | | | ON THE ELEVATION SHEET.BE ADVISED THAT THE | | | APARTMENT/UNIT ALPHABET OR NUMBER FOR THE FRONT | | | ENTRANCE SHOULD NOT BE ON THE DOORS, BUT INSTEAD ON THE | | | BUILDING ABOVE OR NEAR THE DOOR OPPOSITE OF THE SWING | | | OF THE DOOR.IF THE UNITS ARE EQUIPPED WITH REAR | | | DOORS, THE ALPHABET OR NUMBER MAY BE ON THE DOOR. | | | | | | | | | | | | | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-804-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-09-21 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-09-21 |
Time |
12:22 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-09-21 |
Time |
12:22 |
Sent To |
|
|
| Notes |
| 2006-09-21 00:00:00 | *****DENIED***** | | | | | | | | | 1.) SHOW BUILDING/STRUCTURE AS IT | | | RELATES TO THE STREET(S), CLOSEST FIRE | | | HYDRANT(S), ETC. | | | | | | 2.) CORRECT SHEETS A-3 & A-4 BASED UPON | | | BEAUTIFUL AVENUE BEING THE WEST | | | ELEVATION. | | | | | | 3.) SHOW/DISPLAY THE NUMERICAL ADDRESS | | | OF THE STRUCTURE AS WELL AS THE APT/UNIT | | | LETTER OR ALPHABET. | | | | | | 4.) CONSTRUCTION AND/OR DEMOLITION | | | OPERATIONS SHALL NOT INTERFERE OR HINDER | | | EMERGENCY ACCESS TO THE SAID PROPERTY OR | | | VICINITY THEREOF. | | | | | | 5.) EXITS SHALL BE MAINTAINED, CLEAR AND | | | UNOBSTRUCTED. | | | | | | 6.) INTERIOR WALLS AND CEILINGS SHALL BE | | | CLASS "A" OR CLASS "B". | | | | | | 7.) LOCATION/PLACEMENT OF2A10BC FIRE | | | EXTINGUISHERS (WHETHER INTERIOR OR | | | EXTERIOR) ARE NOT SHOWN. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2007-09-27 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-09-27 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-09-27 |
Time |
09:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2007-09-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-13 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-13 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2007-09-25 15:50:47 | TO "COMM" BD#24--EXPEDITED-- | | 2007-09-13 08:39:56 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2007-06-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-19 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-19 |
Time |
16:26 |
Sent To |
B |
|
| Notes |
| 2007-06-19 16:26:30 | TO "RMCDOUGAL" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2007-06-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-15 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-15 |
Time |
15:51 |
Sent To |
|
|
| Notes |
| 2007-06-27 13:12:06 | TO "COMM" BD#34 | | 2007-06-15 15:51:27 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2007-04-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-23 |
Time |
11:50 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-23 |
Time |
11:50 |
Sent To |
B |
|
| Notes |
| 2007-04-23 11:52:05 | TO "RMCDOUGAL" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-04-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-20 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-20 |
Time |
16:47 |
Sent To |
B |
|
| Notes |
| 2007-04-20 16:48:34 | TO "RMCDOUGAL" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-04-06 |
|
|
Cont ID |
|
| Sent By |
spalmer |
Date |
2007-04-06 |
Time |
17:20 |
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2007-04-06 |
Time |
17:20 |
Sent To |
B |
|
| Notes |
| 2007-04-06 17:20:39 | TO ROBERT MCDOUGAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-02-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-22 |
Time |
11:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-22 |
Time |
11:53 |
Sent To |
E |
|
| Notes |
| 2007-02-22 11:53:21 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-12-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-22 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-22 |
Time |
10:21 |
Sent To |
|
|
| Notes |
| 2006-12-22 15:32:20 | TO "COMM" BD#53 | | 2006-12-22 10:22:25 | NEXT TO GO ON "COMM" BD--EXPEDITED PERMIT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-11-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-11-09 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-09 |
Time |
14:59 |
Sent To |
B |
|
| Notes |
| 2006-11-09 14:59:47 | TO "LMARTINEZ" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-09-25 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-09-25 |
Time |
18:11 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2006-09-15 |
Time |
15:38 |
Sent To |
PC |
|
| Notes |
| 2006-09-15 00:00:00 | TO "BOB"#17 | | 2006-09-14 00:00:00 | EXPEDITED PERMIT |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2007-09-27 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-09-27 |
Time |
09:32 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-09-27 |
Time |
09:32 |
Sent To |
|
|
| Notes |
| 2007-09-27 09:33:52 | GAS PERMIT REQUIRED. PLANS REQUIRED WITH APPLICATION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2007-07-27 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-07-27 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-07-27 |
Time |
07:21 |
Sent To |
|
|
| Notes |
| 2007-07-27 09:17:20 | REVISED WATER HEATERS TO ON DEMAND GAS HEATERS. CHANGED | | | WATER RISER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2007-01-12 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-01-12 |
Time |
07:39 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-01-12 |
Time |
07:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2006-11-17 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-11-17 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-11-17 |
Time |
08:40 |
Sent To |
|
|
| Notes |
| 2006-11-17 08:51:03 | DENIED; | | | 1.AUTOMATIC CLOTHES WASHERS ARE NOT SHOWN ON FLOOR | | | PLAN, PAGE A-1 AND A-2. PLEASE ADD. | | | 2. AUTOMATIC CLOTHES WASHER BRANCH DRAIN IS REQUIRED TO | | | BE 3". FBC-2004 PLUMBING SECTION 406.3. | | | 3. PLEASE SIZE ALL PIPES ON RISER DIAGRAM. | | | 4. ENGINEERS REQUIRED TO SIGN NOT INITIAL PLANS. | | | 5. WATER RISER DIAGRAM PAGE P-2. WATER HAMMER | | | ARRESTORES ARE REQUIRED AT AUTOMATIC CLOTHES WASHERS. | | | PLEASE SHOW ON PLANS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-11-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-09-20 |
Time |
17:54 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-09-20 |
Time |
17:54 |
Sent To |
|
|
| Notes |
| 2006-09-20 00:00:00 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. ALL ARCHITECTURAL SHEETS. THE ADDRESS | | | FOR THE ARCHITECT SHOWN ON THE TITLE | | | BLOCK DOES NOT REFLECT THE INFORMATION | | | ON FILE ON DBPR WEBSITE. PLEASE | | | CORRELATE INFORMATION AS REQUIRED IN FAC | | | 61G1-16.004(1) BUSINESS ADDRESS. FS | | | 481.219. (SEE ATTACHED SHEET) | | | | | | 2. ALL SHEETS BE AGILE ENGINEERING, INC. | | | THE CERTIFICATE OF AUTHORIZATION IS | | | REQUIRED IN THE TITLE BLOCK. FAC | | | 61G15-23.002(2). FS 471.025. (SEE | | | ATTACHED SHEET) | | | | | | 3. ITS NOT INDICATED IF PIPING WILL BE | | | CHANGED OUT, BUT THE SANITARY RISER | | | DIAGRAM DOES NOT MEET CODE REQUIREMENTS. | | | A. THE FLOOR DRAINS ARE NOT VENTED. | | | SECTION 1002.1 | | | B. THE VENTS FROM THE FIRST FLOOR SHALL | | | CONNECT, (REVENT), ABOVE THE FLOOD RIM | | | LEVEL OF THE FIXTURES OF THE SECOND | | | FLOOR. SECTION 905.4. | | | C. DISH WASHERS ARE NOT TRAPPED. D/W'S | | | SHALL CONNECT ABOVE THE TRAP OF THE | | | KITCHEN SINK ON THE TAILPIECE. SECTION | | | 1002.1. | | | D. THE FIXTURES FROM THE SECOND FLOOR | | | SHALL NOT DRAIN THRU THE FIXTURES ON THE | | | FIRST FLOOR. SECTION 908.3. | | | E. SECOND FLOOR FIXTURE BRANCH DRAIN | | | CONNECTS BOTH TO THE MAIN STACK AND THE | | | VENT STACK OF THE FIRST FLOOR FIXTURES | | | ON ONE RISER. SECTION 106.1.1. | | | | | | 4. THE WATER RISER DIAGRAMS DO NOT MEET | | | CODE REQUIREMENTS. | | | A. WATER HAMMER ARRESTORS ARE REQUIRED | | | ON ALL QUICK CLOSING VALVES. (AT THE | | | DISH WASHER AND AT THE ICE MAKER IN REF) | | | SECTION 604.9 | | | B. WATER HEATER PIPING SHALL BE FULL | | | SIZE TO THE SUPPLY INLET AND FROM THE | | | OUTLET OF THE WATER HEATER. CHECK MANUF. | | | SPECIFICATIONS. (SEE WATER HEATER | | | DETAIL). | | | | | | 5. WATER HEATER DETAIL: | | | A. PAN DRAIN TO BE 3/4" PER SECTION | | | 504.7.1. | | | B. P/T DISCHARGE PIPE SHALL BE FULL | | | SIZE PER SECTION 504.6.1. | | | C. CODE SECTION REFERENCE SHALL BE | | | FBC-2004 PLUMBING, NOT 1997 SPC. | | | | | | 6. MINIMUM FACILITIES INDICATE A WASH | | | MACHINE CONNECTION PER DWELLING UNIT, OR | | | ONE CLOTHES WASHER CONNECTION PER 20 | | | DWELLING UNITS IN A WASHER ROOM. PLEASE | | | INDICATE COMPLIANCE WITH REQUIREMENT. | | | TABLE 403.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|