Plan Review Details - Permit 06090444
Plan Review Stops For Permit 06090444
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2007-09-27 Cont ID  
Sent By rmcdouga Date 2007-09-27 Time 11:34 Rev Time 0.00
Received By rmcdouga Date 2007-09-27 Time 11:30 Sent To  
Notes
2007-09-27 11:34:02REVISED SHEETS D1,A1,A2,A3 AND A5 HAVE BEEN REVIEWED
 FOR BUILDING CODE COMPLIANCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2007-07-20 Cont ID  
Sent By rmcdouga Date 2007-07-20 Time 07:46 Rev Time 0.00
Received By rmcdouga Date 2007-07-20 Time 07:46 Sent To  
Notes
2007-07-20 07:51:30REVISIONS TO SHEETS D1, A1, A2, A3 AND A5 ARE DENIED.
  
 1) ON SHEET A1 THE WINDOW NOTES SPECIFY PGT WINDGUARD
 WINDOWS. THE CONTRACTOR IS IN THE PROCESS OF CHANGING
 THE WINDOW PRODUCT APPROVALS TO IMPACT RATED KD
 WINDOWS. PLEASE REVISE.
  
 2) THE WINDOWS SIZES SHOWN ON THE ELEVATIONS AND FLOOR
 PLAN DO NOT CORRESPOND WITH THE DIMENSIONS IN THE
 WINDOW SCHEDULE ON A1 FOR THE KITCHEN AND BATHROOM
 WINDOWS.
  
 3) PROVIDE A DETAIL OF THE IN FILL FRAMING AT THE
 BATHROOMWINDOWS.
  
 4) THE OPENING WIDTH DIMENSION IN DETAIL 1 ON A5 IS TOO
 SMALL FOR THE WINDOWS SPECIFIED IN THE SCHEDULE ON A1.
 PLEASE REVISE.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2007-06-26 Cont ID  
Sent By rmcdouga Date 2007-06-26 Time 13:58 Rev Time 0.00
Received By rmcdouga Date 2007-06-26 Time 13:58 Sent To  
Notes
2007-06-26 15:11:49REVISED PRODUCT APPROVALS FOR WINDOWS ARE DENIED
  
 1) PLAN SHEET A-1 WILL BE REQUIRED TO BE REVISED TO
 REFLECT THE CHANGES TO THE WINDOW TYPES THAT ARE NOT
 INDICATED IN THE WINDOW SCHEDULE.
  
 2)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 3) THE PRODUCT APPROVAL FOR THE SERIES 455 IS MISSING
 PAGES E-1 AND E-2.
  
 4) THE PRODUCT APPROVALS SUBMITTED FOR THE MULLIONS AND
 CASEMENT WINDOWS DO NOT COMPLY WITH THE 2004 FBC FOR
 NOT ALLOWING A 1/3 STRESS INCREASE OF STEEL FASTENERS,
 BUT HAVE REVISED NOAS THAT DO COMPLY. SUBMIT THE LATEST
 NOAS.
  
 5) THE PRODUCT APPROVALS FOR THE FIXED WINDOW AND THE
 SINGLE HUNG WINDOW DO NOT COMPLY WITH THE 2004 FBC FOR
 THE REASON STATED ABOVE.
  
 6) ADDITIONAL FEES ARE DUE. 5 PRODUCT APPROVALS WERE
 SUBMITTED AND THE FEE WAS ASSESSED FOR ONE. AN
 ADDITIONAL $40.00 IS DUE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-04-23 Cont ID  
Sent By rmcdouga Date 2007-04-23 Time 13:33 Rev Time 0.00
Received By rmcdouga Date 2007-04-23 Time 13:32 Sent To  
Notes
2007-04-23 13:34:54THE REVISION FOR BALCONY REPAIR PER SIGNED AND SEALED
 DRAWING SUBMITTED IS OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-04-23 Cont ID  
Sent By rmcdouga Date 2007-04-23 Time 13:01 Rev Time 0.00
Received By rmcdouga Date 2007-04-23 Time 12:42 Sent To  
Notes
2007-04-23 13:16:33REVISION DENIED
  
 1) THE PRODUCT APPROVALS FOR THE BRUNSWICK EXTERIOR
 DOORS ARE REQUIRED TO BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD FOR THE PROJECT.
 WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-04-09 Cont ID  
Sent By rmcdouga Date 2007-04-09 Time 18:22 Rev Time 0.00
Received By rmcdouga Date 2007-04-09 Time 17:58 Sent To  
Notes
2007-04-09 18:23:13DENIED BY BUILDING
  
 1) THE ENGINEERING SUBMITTED FOR THE NEW SLAB EDGE
 SUPPORT AT THE REAR BALCONY WAS NOT INCLUDED IN THE
 SCOPE OF WORK THAT WAS PERMITTED. THE COST OF THE
 ADDITIONAL WORK IS REQUIRED SO THAT IT CAN BE ADDED TO
 THE VALUE OF THE PROJECT. THIS SHOULD BE SUBMITTED AS A
 REVISION.
  
 2) PLEASE CLARIFY IF THIS IS NEW WORK OR IS IT REPAIRS
 TO THE EXISTING BALCONY OR IS A PORTION OF THE EXISTING
 BALCONY BEING REPLACED.
  
 3) PROVIDE SIGNED AND SEALED DRAWINGS INDICATING THE
 LOCATION AND EXTENT OF THE REPAIRS OR NEW CONSTRUCTION.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-01-09 Cont ID  
Sent By rmcdouga Date 2007-01-09 Time 14:29 Rev Time 0.00
Received By rmcdouga Date 2007-01-09 Time 11:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-16 Cont ID  
Sent By rmcdouga Date 2006-11-16 Time 06:42 Rev Time 0.00
Received By rmcdouga Date 2006-11-15 Time 16:55 Sent To  
Notes
2006-11-16 07:09:23DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SPECIFY THE STUD SPACING IN THE WALL SECTION ON
 SHEET A-5.
  
 3) ASTM C926REQUIRES STUCCO APPLIED VERTICALLY OVER
 METAL LATH WITH A SOLID BASE TO HAVE A MINIMUM
 THICKNESS OF 7/8". SEE FBC 2510.3. PLEASE CORRECT WALL
 SECTION ON A-5.
  
 4)FBC 2510.6 REQUIRES A WEATHER RESISTANT BARRIER
 OVER THE PLYWOOD BACKING BEHIND THE LATH AND STUCCO.
 PLEASE SPECIFY ON WALL SECTION ON A-5.
  
 5) THE SECOND FLOOR DEMO PLANS ON SHEET D-2 DO NOT SHOW
 THE BATHROOM WINDOWS. PLEASE CORRECT.
  
 6) PLEASE SUBMIT PRODUCT APPROVALS ( APPROVED BY THE
 D.O.R.) FOR THE STRUCTURAL WINDOW MULLIONS.
  
 7) THE WINDOW SCHEDULE ON A-1 STILL HAS ERRORS. THERE
 ARE MASONRY OPENINGS SPECIFIED THAT ARE SMALLER THAN
 THE WINDOW SIZES.PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-18 Cont ID  
Sent By rmcdouga Date 2006-09-18 Time 11:41 Rev Time 0.00
Received By rmcdouga Date 2006-09-18 Time 07:12 Sent To  
Notes
2006-09-18 00:00:00DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SPECIFY THE LEVEL OF ALTERATION FOR
 THE PROJECT. SEE 2004 FBC EXISTING
 BUILDING CODE CHAPTER 3.
  
 3) BEDROOM WINDOWS MUST COMPLY WITH
 EMERGENCY EGRESS REQUIREMENTS OF FBC
 1025.
  
 4) THE NOTE ON SHEET A5 STATES TO FASTEN
 P.T. TO CONC. W/ 1/4" DIA.X 3/4"CONC.
 SCEWS @ 16" O.C. THAT LENGTH FASTENER
 WILL NOT BE SUFFICENT. PLEASE CORRECT.
  
 5) A TAG FOR DETAIL 2/SK IS SPECIFIED ON
 SHEET A3. I WAS UNABLE TO LOCATE THIS
 DETAIL. PLEASE SPECIFY THE SHEET ON
 WHICH THE DETAIL IS LOCATED AS THE
 BOTTOM CHARACTERS OF THE ID TAG.
  
 6) PLEASE SPECIFY THE REPAIRS THAT WILL
 BE DONE TO THE BALCONIES. "REPAIR AS
 NEEDED" IS TOO GENERAL. SEE CITY
 AMENDMENTS TO FBC 106.1.1.
  
 7) ON SHEET A3 THE KITCHEN DOORS ARE
 SHOWN ON THE SOUTH ELEVATION WITH
 WINDOWS. SUBMIT PRODUCT APPROVALS FOR
 DOORS WITH WINDOWS AS INDICATED BY
 PLANS.
  
 8) SUBMIT PRODUCT APPROVALS FOR THE
 VENTED STORAGE ROOM DOORS AS SHOWN ON A3
 OF PLANS.
  
 9) THE WINDOW SCHEDULE ON A2 CONTAINS
 SEVERAL ERRORS.
 - WINDOW JJ IS LOCATED IN A BEDROOM, NOT
 A BATHROOM.
 - THE MASONRY OPENING HEIGHTS ARE
 SMALLER THAN THE WINDOW HEIGHTS FOR
 SEVERAL OF THE WINDOWS LISTED.
 - THE WINDOW CODE SIZE FOR SEVERAL OF
 THE ONES LISTED SHOULD BE SH25 NOT H25.
 PLEASE REVIEW SCHEDULE AND CORRECT.
  
 10) CLARIFY THE SCOPE OF WORK THAT IS
 INDICATED BY DETAIL 1/SK. IS THIS THE
 EXTERIOR WALL BEING DEMOLISHED AND
 REPLACED WITH A NEW WALL? IF IT IS,
 PROVIDE A CROSS-SECTION OF THE NEW WALL
 SPECIFYING EXTERIOR AND INTERIOR WALL
 COVERINGS, EXTERIOR SUBSTRATE, VAPOR
 BARRIER, INSULATION (R-VALUE), ETC.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-09-26 Cont ID  
Sent By btrobaug Date 2007-09-26 Time 11:58 Rev Time 0.00
Received By btrobaug Date 2007-09-26 Time 11:14 Sent To  
Notes
2007-09-26 11:59:56 
  
 MARKED AS REV #5, 9/6/07./WRT.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-06-29 Cont ID  
Sent By btrobaug Date 2007-06-29 Time 13:41 Rev Time 0.00
Received By btrobaug Date 2007-06-29 Time 12:06 Sent To  
Notes
2007-06-29 13:41:27 
  
  
 REVISION DENIED
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE CONDUIT FOR THE SERVICE RISER DOES NOT COMPLY
 WITH TABLE C-8 FOR FILL REQUIREMENT, THIS WAS REDLINED
 ON THE PREVIOUS REVIEW, PLEASE CORRECT ON THE PLAN.
 SHEET E-2.
  
 2} VERIVY CIRCUIT #3 & #4ON THE PANEL SCHEDULE, 20 AMP
 WITH #12 CONDUCTORS, LISTED A SPARE.
  
 3} CLOUD THE REVISIONS ON ALL SHEETS.
  
 4} RELOCATE THE RANGE AND WATER HEATER RECEPTACLES TO
 THEIR RELEVANT LOCATION, OR REMOVE IF NOT BEING
 INSTALLED.
  
 5} CIRCUITS #13, 15 AND 17 ARE #14 CONDUCTOR IN
 CONFLICT WITH THE ELECTRICAL SPECIFICATIONS ON SHEET
 E-4 CALLING FOR #12 CONDUCTORS MINIMUM. PLEASE
 CLARIFY.
  
 6} THE ENGINEER NEEDS TO SEAL THE PLANS SO THE
 IMPRESSION IS LEGIBLE PER 471.025 FS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-02-23 Cont ID  
Sent By btrobaug Date 2007-02-23 Time 14:57 Rev Time 2.00
Received By btrobaug Date 2007-02-22 Time 17:08 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-01-08 Cont ID  
Sent By btrobaug Date 2007-01-08 Time 17:47 Rev Time 1.00
Received By btrobaug Date 2007-01-02 Time 07:55 Sent To  
Notes
2007-01-08 17:46:07 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE NOTES ARE INDICATING 240 VOLT CIRCUITS FOR THE
 BATHROOM CIRCUIT, PLEASE CORRECT.
  
 2} THE SYMBOL ON THE PLAN AT THE WASHER INDICATES A 240
 VOLT RECEPTACLE, ALL UNITS, CORRELATE WITH SCHEDULE.
  
 3} THE SMALL APPLIANCE CIRCUIT IN EACH OF THE UNITS
 EXTENDS INTO THE LIVING ROOM IN VIOLATION OF
 210.52(B)(1).
  
 4} THE EMERGENCY LIGHTS MUST BE ON THE SAME CIRCUIT AS
 THE STAIR LIGHTING PER 700.12(E).
  
 5} THE PANELS INDICATE THEY ARE 24 POLE, BUT ONLY 18
 CIRCUITS ARE SHOWN ON EACH. PLEASE COMPLETE THE PANEL
 SCHEDULES PER 408.4.
  
 6} THE DESIGNATION FOR SMOKE DETECTORS ON THE PLAN
 INDICATES A LOW VOLTAGE ALARM TYPE SYSTEMWITH
 AUDIO/VISUAL DEVICES. PLEASE LOCATE ALL DEVICES ON THE
 PLAN.IF THESE ARE 120 VOLT ALARMS WITH BATTERY BACK UP
 PLEASE CORRECTLY DESIGNATE AS "SA" TO ELIMINATE
 CONFUSIONFOR THE INSTALLER.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
 ONE SET OF PLANS IS BEING RETAINED BY THIS OFFICE.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-11-14 Cont ID  
Sent By btrobaug Date 2006-11-14 Time 17:21 Rev Time 0.75
Received By btrobaug Date 2006-11-14 Time 15:34 Sent To  
Notes
2006-11-14 17:20:33 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE LOAD CALCULATIONS ARE SHOWN AS
 USING THE DEMAND FACTOR IN 230.31 (40%),
 AND THEN TAKING AN ADDITIONAL DEMAND
 FACTOR FROM TABLE 230.32(45%). WHILE
 EITHER ONE IS PERMISSIBLE, NOT TOGETHER.
 ALSO SEE 230.32(B) REGARDING HOUSE
 LOADS. THIS COMMENT WAS ON THE PRIOR REVIEW.
  
 2} ALL LIGHTING BRANCH CIRCUIT PANEL DESIGNATIONS ON
 SHEETS E-1 AND E-2 ARE INCORRECT.(FA #S)
  
 3} THE DISHWASHER CIRCUIT REFERENCED ON E-2 IS NOT ON
 THE PANEL SCHEDULE OR IN THE LOAD CALCULATION.
  
 4} THE WASHER/DRYER APPEARS TO BE STACKED ON THE PLAN,
 PLEASE CORRECT THE SCHEDULE.
  
 5} THE SMALL APPLIANCE CIRCUITS FOR THE KITCHEN MUST
 COMPLY WITH 210.52(B)(3), TWO IN THE KITCHEN, THERE IS
 ONLY ONE. CIRCUIT #12 MAY BE IN THE DINING ROOM, BUT
 MUST ALSO BE IN THE KITCHEN.
  
 6} THE GFI ON THE OUTSIDE IN FRONT IS IN VIOLATION OF
 210.52(B)(2), CANNO TBE ON THTE SMALL APPLIANCE
 CIRCUIT.
  
 7} THE GFI IN THE BACK OUTSIDE IS IN VIOLATION OF
 210.11(C)(3), BATH CIRCUITS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
2006-11-14 16:23:52 
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-25 Cont ID  
Sent By btrobaug Date 2006-09-25 Time 18:09 Rev Time 0.75
Received By btrobaug Date 2006-09-25 Time 17:52 Sent To  
Notes
2006-09-25 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE LOAD CALCULATIIONS ARE SHOWN AS
 USING THE DEMAND FACTOR IN 230.31 (40%),
 AND THEN TAKING AN ADDITIONAL DEMAND
 FACTOR FROM TABLE 230.32(45%). WHILE
 EITHER ONE IS PERMISIBLE, NOT TOGETHER.
 ALSO SEE 230.32(B) REGARDING HOUSE
 LOADS.
  
 2} THE GROUNDING ELECTRODE CONDUCTOR IS
 TOO SMALL FOR THE SERVICE SHOWN AND WILL
 CERTAINLY BE TOO SMALL FOR THE SERVICE
 WHEN THE CALCULATIONS ARE ADJUSTED. SEE
 250.66.
  
 3} PLEASE LIST THE CONDUCTOR SIZES WITH
 THE BREAKER SIZES ON THE PANEL SCHEDULE
 SO THAT COMPLIANCE WITH 310.16 AND
 240.CAN BE REVIEWED.
  
 4} THERE ARE AIR HANDLERS SHOWN ON THE
 PLAN BUT NOT LISTED ON THE SCHEDULE OR
 NOT INCLUDED IN THE CALCULATIONS. PLEASE
 INCLUDE.
  
 5} THE BATH CIRCUIT REQUIRED BY
 210.11(C)(3)IS NOT IN THE SCHEDULE.
  
 6} THERE APPEARS TO BE ONLY ONE SMALL
 APPLIANCE CIRCUIT IN THE KITCHEN, TWO
 ARE REQUIRED PER 210.52(B)(1). LIST SAME
 ON SCHEDULE.
  
 7} BEDROOM 1 AND BEDROOM 2 CIRCUIT
 NUMBERS DO NOT CORRESPOND TO THE
 SCHEDULE .
  
 8} SEE THAT ALL ITEMS ON PLAN SHOWN ON
 THE GROUNDING ELECTRODE SYSTEM MUST BE
 INSTALLED IF SHOWN ON PLANS , PLEASE
 VERIFY IF ALL ARE AVAILABLE PER
 250.50-250.52.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2006-12-29 Cont ID  
Sent By rchokshi Date 2006-12-29 Time 09:00 Rev Time 0.00
Received By rchokshi Date 2006-12-29 Time 08:56 Sent To  
Notes
2006-12-29 09:00:24ACCORDING TO THE DESCRIPTION STATEMEMENT, THERE IS NO
 ENG REQUIRED.IT ALL INTERIOR RENOVATION AND IMPACT
 GLASS WINDOWS REPLACEMENT. THEREFOE, LUIS M. & I
 CONCLUDED THAT ENG REVIEW IS NOT REQUIRED.
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-09-28 Cont ID  
Sent By mwennerg Date 2007-09-28 Time 13:36 Rev Time 0.00
Received By mwennerg Date 2007-09-28 Time 13:36 Sent To  
Notes
2007-09-28 13:37:04COMMENTS FROM LAST FIRE REVIEW HAVE BEEN ADDRESSED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2007-07-26 Cont ID  
Sent By mawillia Date 2007-07-26 Time 14:33 Rev Time 0.00
Received By mawillia Date 2007-07-26 Time 14:13 Sent To  
Notes
2007-07-26 14:28:43*****UNSAT*****
  
 SHEETS A-3, E-1, AND E-2 WERE STAMPED, INITIALED, AND
 DATED AS APPROVED ON 02/23/2007;HOWEVER THE REVISED
 DRAWINGS NEED TO BE RECTIFIED AS LISTED BELOW:
  
  
 1.ON DRAWING A-3,NO UNIT LETTER SHOWN/DISPLAYED ON
 THE UPPER APT./UNITS.
  
 2.NO DISTINGUISHABLE SEAL ON DRAWING E-1 AND E-2.
  
 3.COULD YOU PLEASE EXPLAIN THE REFERENCE TO UNIT 7G
 ATTACHED TO THE ADDRESS AND ITS RELEVANCE?
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-02-23 Cont ID  
Sent By mawillia Date 2007-02-23 Time 15:25 Rev Time 0.00
Received By mawillia Date 2007-02-23 Time 15:25 Sent To  
Notes
2007-02-23 15:28:24*****APPROVED*****
  
  
 ALL PREVIOUS FIRE PLAN REVIEW COMMENTS HAVE BEEN
 ADDRESSED.SHEETS A-3, E-1, AND E-2 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-11-16 Cont ID  
Sent By mawillia Date 2006-11-16 Time 10:10 Rev Time 0.00
Received By mawillia Date 2006-11-16 Time 10:10 Sent To  
Notes
2006-11-16 10:11:41*****PROVISO*****
  
  
  
  
 1.PLEASE SHOW THE ADDRESS OF THE PROPOSED STRUCTURE
 ON THE ELEVATION SHEET.BE ADVISED THAT THE
 APARTMENT/UNIT ALPHABET OR NUMBER FOR THE FRONT
 ENTRANCE SHOULD NOT BE ON THE DOORS, BUT INSTEAD ON THE
 BUILDING ABOVE OR NEAR THE DOOR OPPOSITE OF THE SWING
 OF THE DOOR.IF THE UNITS ARE EQUIPPED WITH REAR
 DOORS, THE ALPHABET OR NUMBER MAY BE ON THE DOOR.
  
  
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-804-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-09-21 Cont ID  
Sent By mawillia Date 2006-09-21 Time 12:22 Rev Time 0.00
Received By mawillia Date 2006-09-21 Time 12:22 Sent To  
Notes
2006-09-21 00:00:00*****DENIED*****
  
  
 1.) SHOW BUILDING/STRUCTURE AS IT
 RELATES TO THE STREET(S), CLOSEST FIRE
 HYDRANT(S), ETC.
  
 2.) CORRECT SHEETS A-3 & A-4 BASED UPON
 BEAUTIFUL AVENUE BEING THE WEST
 ELEVATION.
  
 3.) SHOW/DISPLAY THE NUMERICAL ADDRESS
 OF THE STRUCTURE AS WELL AS THE APT/UNIT
 LETTER OR ALPHABET.
  
 4.) CONSTRUCTION AND/OR DEMOLITION
 OPERATIONS SHALL NOT INTERFERE OR HINDER
 EMERGENCY ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF.
  
 5.) EXITS SHALL BE MAINTAINED, CLEAR AND
 UNOBSTRUCTED.
  
 6.) INTERIOR WALLS AND CEILINGS SHALL BE
 CLASS "A" OR CLASS "B".
  
 7.) LOCATION/PLACEMENT OF2A10BC FIRE
 EXTINGUISHERS (WHETHER INTERIOR OR
 EXTERIOR) ARE NOT SHOWN.

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-09-27 Cont ID  
Sent By jleech Date 2007-09-27 Time 09:31 Rev Time 0.00
Received By jleech Date 2007-09-27 Time 09:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-09-13 Cont ID  
Sent By adarroug Date 2007-09-13 Time 08:39 Rev Time 0.00
Received By adarroug Date 2007-09-13 Time 08:39 Sent To  
Notes
2007-09-25 15:50:47TO "COMM" BD#24--EXPEDITED--
2007-09-13 08:39:56WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-06-19 Cont ID  
Sent By adarroug Date 2007-06-19 Time 16:26 Rev Time 0.00
Received By adarroug Date 2007-06-19 Time 16:26 Sent To B
Notes
2007-06-19 16:26:30TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-06-15 Cont ID  
Sent By adarroug Date 2007-06-15 Time 15:51 Rev Time 0.00
Received By adarroug Date 2007-06-15 Time 15:51 Sent To  
Notes
2007-06-27 13:12:06TO "COMM" BD#34
2007-06-15 15:51:27WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-04-23 Cont ID  
Sent By adarroug Date 2007-04-23 Time 11:50 Rev Time 0.00
Received By adarroug Date 2007-04-23 Time 11:50 Sent To B
Notes
2007-04-23 11:52:05TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-04-20 Cont ID  
Sent By adarroug Date 2007-04-20 Time 16:47 Rev Time 0.00
Received By adarroug Date 2007-04-20 Time 16:47 Sent To B
Notes
2007-04-20 16:48:34TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-04-06 Cont ID  
Sent By spalmer Date 2007-04-06 Time 17:20 Rev Time 0.00
Received By spalmer Date 2007-04-06 Time 17:20 Sent To B
Notes
2007-04-06 17:20:39TO ROBERT MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-22 Cont ID  
Sent By adarroug Date 2007-02-22 Time 11:53 Rev Time 0.00
Received By adarroug Date 2007-02-22 Time 11:53 Sent To E
Notes
2007-02-22 11:53:21TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-22 Cont ID  
Sent By adarroug Date 2006-12-22 Time 10:21 Rev Time 0.00
Received By adarroug Date 2006-12-22 Time 10:21 Sent To  
Notes
2006-12-22 15:32:20TO "COMM" BD#53
2006-12-22 10:22:25NEXT TO GO ON "COMM" BD--EXPEDITED PERMIT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-09 Cont ID  
Sent By adarroug Date 2006-11-09 Time 14:59 Rev Time 0.00
Received By adarroug Date 2006-11-09 Time 14:59 Sent To B
Notes
2006-11-09 14:59:47TO "LMARTINEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-25 Cont ID  
Sent By btrobaug Date 2006-09-25 Time 18:11 Rev Time 0.00
Received By btrobaug Date 2006-09-15 Time 15:38 Sent To PC
Notes
2006-09-15 00:00:00TO "BOB"#17
2006-09-14 00:00:00EXPEDITED PERMIT

Review Stop P PLUMBING
Rev No 5 Status P Date 2007-09-27 Cont ID  
Sent By jleech Date 2007-09-27 Time 09:32 Rev Time 0.00
Received By jleech Date 2007-09-27 Time 09:32 Sent To  
Notes
2007-09-27 09:33:52GAS PERMIT REQUIRED. PLANS REQUIRED WITH APPLICATION.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-07-27 Cont ID  
Sent By jleech Date 2007-07-27 Time 09:15 Rev Time 0.00
Received By jleech Date 2007-07-27 Time 07:21 Sent To  
Notes
2007-07-27 09:17:20REVISED WATER HEATERS TO ON DEMAND GAS HEATERS. CHANGED
 WATER RISER.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-01-12 Cont ID  
Sent By jleech Date 2007-01-12 Time 07:39 Rev Time 0.00
Received By jleech Date 2007-01-12 Time 07:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-11-17 Cont ID  
Sent By jleech Date 2006-11-17 Time 08:51 Rev Time 0.00
Received By jleech Date 2006-11-17 Time 08:40 Sent To  
Notes
2006-11-17 08:51:03DENIED;
 1.AUTOMATIC CLOTHES WASHERS ARE NOT SHOWN ON FLOOR
 PLAN, PAGE A-1 AND A-2. PLEASE ADD.
 2. AUTOMATIC CLOTHES WASHER BRANCH DRAIN IS REQUIRED TO
 BE 3". FBC-2004 PLUMBING SECTION 406.3.
 3. PLEASE SIZE ALL PIPES ON RISER DIAGRAM.
 4. ENGINEERS REQUIRED TO SIGN NOT INITIAL PLANS.
 5. WATER RISER DIAGRAM PAGE P-2. WATER HAMMER
 ARRESTORES ARE REQUIRED AT AUTOMATIC CLOTHES WASHERS.
 PLEASE SHOW ON PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-11-17 Cont ID  
Sent By kstevens Date 2006-09-20 Time 17:54 Rev Time 0.00
Received By kstevens Date 2006-09-20 Time 17:54 Sent To  
Notes
2006-09-20 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS. THE ADDRESS
 FOR THE ARCHITECT SHOWN ON THE TITLE
 BLOCK DOES NOT REFLECT THE INFORMATION
 ON FILE ON DBPR WEBSITE. PLEASE
 CORRELATE INFORMATION AS REQUIRED IN FAC
 61G1-16.004(1) BUSINESS ADDRESS. FS
 481.219. (SEE ATTACHED SHEET)
  
 2. ALL SHEETS BE AGILE ENGINEERING, INC.
 THE CERTIFICATE OF AUTHORIZATION IS
 REQUIRED IN THE TITLE BLOCK. FAC
 61G15-23.002(2). FS 471.025. (SEE
 ATTACHED SHEET)
  
 3. ITS NOT INDICATED IF PIPING WILL BE
 CHANGED OUT, BUT THE SANITARY RISER
 DIAGRAM DOES NOT MEET CODE REQUIREMENTS.
 A. THE FLOOR DRAINS ARE NOT VENTED.
 SECTION 1002.1
 B. THE VENTS FROM THE FIRST FLOOR SHALL
 CONNECT, (REVENT), ABOVE THE FLOOD RIM
 LEVEL OF THE FIXTURES OF THE SECOND
 FLOOR. SECTION 905.4.
 C. DISH WASHERS ARE NOT TRAPPED. D/W'S
 SHALL CONNECT ABOVE THE TRAP OF THE
 KITCHEN SINK ON THE TAILPIECE. SECTION
 1002.1.
 D. THE FIXTURES FROM THE SECOND FLOOR
 SHALL NOT DRAIN THRU THE FIXTURES ON THE
 FIRST FLOOR. SECTION 908.3.
 E. SECOND FLOOR FIXTURE BRANCH DRAIN
 CONNECTS BOTH TO THE MAIN STACK AND THE
 VENT STACK OF THE FIRST FLOOR FIXTURES
 ON ONE RISER. SECTION 106.1.1.
  
 4. THE WATER RISER DIAGRAMS DO NOT MEET
 CODE REQUIREMENTS.
 A. WATER HAMMER ARRESTORS ARE REQUIRED
 ON ALL QUICK CLOSING VALVES. (AT THE
 DISH WASHER AND AT THE ICE MAKER IN REF)
 SECTION 604.9
 B. WATER HEATER PIPING SHALL BE FULL
 SIZE TO THE SUPPLY INLET AND FROM THE
 OUTLET OF THE WATER HEATER. CHECK MANUF.
 SPECIFICATIONS. (SEE WATER HEATER
 DETAIL).
  
 5. WATER HEATER DETAIL:
 A. PAN DRAIN TO BE 3/4" PER SECTION
 504.7.1.
 B. P/T DISCHARGE PIPE SHALL BE FULL
 SIZE PER SECTION 504.6.1.
 C. CODE SECTION REFERENCE SHALL BE
 FBC-2004 PLUMBING, NOT 1997 SPC.
  
 6. MINIMUM FACILITIES INDICATE A WASH
 MACHINE CONNECTION PER DWELLING UNIT, OR
 ONE CLOTHES WASHER CONNECTION PER 20
 DWELLING UNITS IN A WASHER ROOM. PLEASE
 INDICATE COMPLIANCE WITH REQUIREMENT.
 TABLE 403.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]