Plan Review Details - Permit 06090435
Plan Review Stops For Permit 06090435
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-01-12 Cont ID  
Sent By lmartine Date 2007-01-12 Time 14:46 Rev Time 0.00
Received By lmartine Date 2007-01-12 Time 14:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-27 Cont ID  
Sent By alange Date 2006-11-27 Time 09:41 Rev Time 0.00
Received By alange Date 2006-11-27 Time 09:40 Sent To  
Notes
2006-11-27 09:56:55DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE AND A COPY
 SUBMITTED TO THIS OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT OR CONSTRUCTION IS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING.
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS PER 2004 FBC.
  
 5.PRODUCT APPROVALS REQUIRED FOR ROOFING.
 NOTE:PRODUCT APPROVALS SUBMITTED ARE INCOMPLETE.
 ONLY STATE PRODUCT APPROVALS SUBMITTED FOR CHEM-PRUF
 DOOR,CAST-CRETE LINTELS AND JELD-WEN WINDOW.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH QUALITY
 ASSURANCE SHALL HAVE THE FOLLOWING STATE APPROVAL
 ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL SHEETS THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM THE STATE. IF
 THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT AN
 APPLICATION FOR LOCAL PRODUCT APPROVAL OR SITE SPECIFIC
 FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.WPB AMENDMENT TO FBC
 106.3.3.
  
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS FOR REVIEW PER
 2004 FBC R-802.10.1TRUSS DRAWING REQUIRED TO BE
 APPROVED PRIOR TO INSTALLATION.
  
 NEW COMMENT:
 A.ORIGINAL PERMIT APPLICATION IS MISSING, PLEASE
 INCLUDE WHEN PLANS ARE RESUBMITTED.
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. SUBMIT ONE
 COPY OF OLD PAGES FOR REFERENCE . A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DEPARTMENT
 561-805-6672
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-10 Cont ID  
Sent By alange Date 2006-10-10 Time 08:27 Rev Time 0.00
Received By alange Date 2006-10-10 Time 08:27 Sent To  
Notes
2006-10-10 08:31:42DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE AND A COPY
 SUBMITTED TO THIS OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT OR CONSTRUCTION IS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.BASED ON ICC BUILDING VALUATION DATA THE PERMIT
 VALUE HAS BEEN REVISED TO $29,263.00.ADDITIONAL
 PERMIT FEES ARE DUE.
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS PER 2004 FBC.
  
 5.PRODUCT APPROVALS REQUIRED FOR ROOFING, STRAPS AND
 TIE-DOWNS AND LINTELS.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH QUALITY
 ASSURANCE SHALL HAVE THE FOLLOWING STATE APPROVAL
 ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL SHEETS THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM THE STATE. IF
 THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT AN
 APPLICATION FOR LOCAL PRODUCT APPROVAL OR SITE SPECIFIC
 FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.WPB AMENDMENT TO FBC
 106.3.3.
  
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS FOR REVIEW PER
 2004 FBC R-802.10.1TRUSS DRAWING REQUIRED TO BE
 APPROVED PRIOR TO INSTALLATION.
  
 9.A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR
 A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.SHOW HOW PLANS
 WILL COMPLY WITH THE SECTION(S) SELECTED.2004 FBC
 EXISTING BUILDING 301.5
  
 10.SHOW METHOD OF SLAB TIE-IN FROM NEW TO EXISTING.
  
 11.PAGE 3 NOT READABLE.SUBMIT NEW PAGE.
  
 12.SHOW SIZE AND LOCATION OF ATTIC ACCESS COMPLYING
 WITH FBC R-807.1
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. SUBMIT ONE
 COPY OF OLD PAGES FOR REFERENCE . A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DEPARTMENT
 561-805-6672
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-12-12 Cont ID  
Sent By btrobaug Date 2006-12-12 Time 13:06 Rev Time 0.50
Received By btrobaug Date 2006-12-12 Time 12:30 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-11-22 Cont ID  
Sent By btrobaug Date 2006-11-22 Time 13:50 Rev Time 0.33
Received By btrobaug Date 2006-11-22 Time 13:41 Sent To B
Notes
2006-11-22 13:50:13 
  
 THE ELECTRICAL PLAN IS IN COMPLIANCE WITH THE 2002 NEC,
 BUT THE PERMIT APPLICATION WAS NOT WITH THE RESUBMITTED
 PACKAGE AT THIS REVIEW. PLEASE SUBMIT THE APPLICATION
 WITH RESUB FOR ZONING COMMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-09-25 Cont ID  
Sent By btrobaug Date 2006-09-25 Time 11:22 Rev Time 0.33
Received By btrobaug Date 2006-09-25 Time 11:22 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-12-12 Cont ID  
Sent By adarroug Date 2006-12-12 Time 10:12 Rev Time 0.00
Received By adarroug Date 2006-12-12 Time 10:12 Sent To E
Notes
2006-12-12 10:13:19TO "BTROBAUGH" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-01-12 Cont ID  
Sent By mmiller Date 2006-11-29 Time 19:30 Rev Time 0.00
Received By lmartine Date 2006-11-29 Time 19:30 Sent To Z
Notes
2006-12-01 11:25:30SENT TO ZONING
2006-11-29 19:30:44SENT TO ART LANGE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-11-17 Cont ID  
Sent By adarroug Date 2006-11-17 Time 10:03 Rev Time 0.00
Received By adarroug Date 2006-11-17 Time 10:03 Sent To E
Notes
2006-11-17 10:04:02TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-13 Cont ID  
Sent By adarroug Date 2006-11-13 Time 16:54 Rev Time 0.00
Received By adarroug Date 2006-11-13 Time 16:54 Sent To Z
Notes
2006-11-13 16:55:07TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-23 Cont ID  
Sent By adarroug Date 2006-09-23 Time 15:06 Rev Time 0.00
Received By adarroug Date 2006-09-23 Time 15:06 Sent To E
Notes
2006-09-23 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-10 Cont ID  
Sent By alange Date 2006-10-10 Time 08:41 Rev Time 0.00
Received By alange Date 2006-09-14 Time 16:36 Sent To  
Notes
2006-09-14 00:00:00TO "Z" BOX

Review Stop Z ZONING
Rev No 3 Status P Date 2006-12-08 Cont ID  
Sent By lmartine Date 2007-01-12 Time 14:47 Rev Time 0.00
Received By mmclean Date 2006-12-08 Time 13:57 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2006-11-16 Cont ID  
Sent By mmclean Date 2006-11-16 Time 09:31 Rev Time 0.00
Received By mmclean Date 2006-11-16 Time 09:31 Sent To I
Notes
2006-11-16 09:41:10DENIED, 2ND REQUEST
 1. THE SUBMITTEDSURVEYS DOES NOT SHOW THE PROPOSED
 WORK AS REQUESTED.
 2. PLEASE SHOW ON THE TWO COPIES OF SURVEYS THE
 LOCATION OF THE PROPOSED WORK WITH SETBACKS FOR THE
 SIDE AND REAR (HOW FAR IT WILL BE FROM SIDE AND REAR
 PROPERTY LINE).
 3. THE INFORMATION MUST BE MARKED CLEAR (NO
 HIGHLIGHTER).
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-09-21 Cont ID  
Sent By mmclean Date 2006-09-21 Time 14:36 Rev Time 0.00
Received By mmclean Date 2006-09-21 Time 14:36 Sent To I
Notes
2006-09-21 00:00:00DENIED,
 1. PLEASE SHOW ON THE TWO COPY OF
 SURVEYS THE LOCATION OF THE PROPOSED
 WORK WITH SETBACKS (SIDE & REAR) FROM
 PROPERTY LINE.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720