Plan Review Details - Permit 06090421
Plan Review Stops For Permit 06090421
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-01-26 Cont ID  
Sent By lmartine Date 2007-01-26 Time 18:06 Rev Time 0.00
Received By lmartine Date 2007-01-26 Time 18:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-10-13 Cont ID  
Sent By alange Date 2006-10-13 Time 13:02 Rev Time 0.33
Received By alange Date 2006-10-13 Time 13:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-09-27 Cont ID  
Sent By btrobaug Date 2006-09-27 Time 14:22 Rev Time 0.33
Received By btrobaug Date 2006-09-27 Time 14:13 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-03 Cont ID  
Sent By adarroug Date 2007-01-03 Time 11:15 Rev Time 0.00
Received By adarroug Date 2007-01-03 Time 11:15 Sent To P
Notes
2007-01-03 11:16:13TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-04 Cont ID  
Sent By adarroug Date 2006-11-04 Time 18:04 Rev Time 0.00
Received By adarroug Date 2006-11-04 Time 18:04 Sent To M
Notes
2006-11-04 18:04:24TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-13 Cont ID  
Sent By alange Date 2006-10-13 Time 13:02 Rev Time 0.00
Received By alange Date 2006-09-21 Time 16:48 Sent To  
Notes
2006-09-21 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-11-15 Cont ID  
Sent By tgordon Date 2006-11-15 Time 10:54 Rev Time 0.20
Received By tgordon Date 2006-11-15 Time 10:54 Sent To P
Notes
2006-11-15 10:55:52FOR BATHROOM EXHAUST FAN ONLY.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-10 Cont ID  
Sent By tgordon Date 2006-10-10 Time 13:37 Rev Time 0.30
Received By tgordon Date 2006-10-10 Time 13:37 Sent To B
Notes
2006-10-10 13:41:23*** DENIED ***
 1) BATHROOM WILL NEED AN EXHAUST FAN
 IF THE ROOM HAS NO WINDOWS TO THE OUTSIDE
 PER 2004 FBC/R 303.3 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-01-03 Cont ID  
Sent By mperson Date 2007-01-03 Time 15:06 Rev Time 0.30
Received By mperson Date 2007-01-03 Time 15:05 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-11-15 Cont ID  
Sent By mperson Date 2006-11-15 Time 14:57 Rev Time 0.33
Received By mperson Date 2006-11-15 Time 14:57 Sent To PC
Notes
2006-11-15 15:22:37UNSAT 2ND TIME
 REFERENCE: FBC-2004 PLUMBING AND FBC-2004 CHAPTER 1
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. THE WASHING MACHINE ON THE SANITARY RISER DIAGRAM IS
 SIZED INCORRECT PER FBC-2004 PLUMBING SECTION 406.3 AND
 PLEASE INDICATE THE STANDPIPE (FBC-2004 PLUMBING
 SECTION 802.4) ON THE RESUBMITTAL.
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE THE STANDPIPE ON THE
 RESUBMITTAL.
  
 2. PLEASE INDICATE A CLEANOUT FOR THE WASHING MACHINE
 AT 4' AFF PER FBC-2004 PLUMBING SECTION 708.9 ON THE
 SANITARY RISER DIAGRAM ON THE RESUBMITTAL.
  
 3. THE SPACING BETWEEN THE LAVATORY AND THE SHOWER IS
 WRONG ON THE FLOOR PLAN LAYOUT DRAWING PER FBC-2004
 PLUMBING SECTION 405.3.1. A MINIMUM OF 15" IS REQUIRED
 FROM THE LAVATORY CENTER TO THE SIDE OF THE SHOWER.
 PLEASE CORRECT THE FIXTURE SPACING ON THE RESUBMITTAL.
  
 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-10-06 Cont ID  
Sent By mperson Date 2006-10-06 Time 11:49 Rev Time 0.33
Received By mperson Date 2006-10-06 Time 11:49 Sent To M
Notes
2006-10-06 00:00:00******UNSAT******
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW.
  
 1. PER FBC-2004 PLUMBING, SECTION
 106.3.5.4 RESIDENTIAL (ONE AND TWO
 FAMILY): PLEASE SUBMIT A PLUMBING
 SANITARY ISOMETRIC RISER DIAGRAM
 INDICATING ALL WASTE, VENTS, TRAPS WITH
 SIZES, AND CLEANOUT LOCATIONS OF
 PROPOSED BATHROOM IN THE UTILITY ROOM
 AND OF THE FIXTURE CHANGE IN THE
 EXISTING BATHROOM CHANGING THE BATHTUB
 TO A SHOWER.
  
 2. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
  
 END OF COMMENTS:
  