| 2006-11-15 15:22:37 | UNSAT 2ND TIME |
| | REFERENCE: FBC-2004 PLUMBING AND FBC-2004 CHAPTER 1 |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING |
| | PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. THE WASHING MACHINE ON THE SANITARY RISER DIAGRAM IS |
| | SIZED INCORRECT PER FBC-2004 PLUMBING SECTION 406.3 AND |
| | PLEASE INDICATE THE STANDPIPE (FBC-2004 PLUMBING |
| | SECTION 802.4) ON THE RESUBMITTAL. |
| | (A) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL |
| | CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| | STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER. |
| | (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY |
| | TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING. PLEASE INDICATE THE STANDPIPE ON THE |
| | RESUBMITTAL. |
| | |
| | 2. PLEASE INDICATE A CLEANOUT FOR THE WASHING MACHINE |
| | AT 4' AFF PER FBC-2004 PLUMBING SECTION 708.9 ON THE |
| | SANITARY RISER DIAGRAM ON THE RESUBMITTAL. |
| | |
| | 3. THE SPACING BETWEEN THE LAVATORY AND THE SHOWER IS |
| | WRONG ON THE FLOOR PLAN LAYOUT DRAWING PER FBC-2004 |
| | PLUMBING SECTION 405.3.1. A MINIMUM OF 15" IS REQUIRED |
| | FROM THE LAVATORY CENTER TO THE SIDE OF THE SHOWER. |
| | PLEASE CORRECT THE FIXTURE SPACING ON THE RESUBMITTAL. |
| | |
| | 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| | NAME, AND ALSO DATE DRAWING. PLEASE DO |
| | THIS PRIOR TO RESUBMITTING. |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |