Plan Review Details - Permit 06090366
Plan Review Stops For Permit 06090366
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2006-09-22 Cont ID  
Sent By lursu Date 2006-09-22 Time 10:40 Rev Time 0.00
Received By lursu Date 2006-09-22 Time 10:40 Sent To  
Notes
2006-09-22 00:00:00EXTENSION #0010 WAS CREATED FOR THE UNIT
 201-202 FOR THE 2ND FLOOR.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-09-14 Cont ID  
Sent By lursu Date 2006-09-14 Time 14:16 Rev Time 0.00
Received By lursu Date 2006-09-14 Time 14:16 Sent To  
Notes
2006-09-14 00:00:00PROJECT UNDER REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2009-07-28 Cont ID  
Sent By jwitmer Date 2009-07-28 Time 10:50 Rev Time 0.80
Received By jwitmer Date 2009-07-28 Time 10:00 Sent To  
Notes
2009-07-28 10:33:59REVISIONS:
 A-1 REV D 1-02-09
 A-3 REV E 4-08-09
 A-4 REV D 1-20-09
 A5 REV D 1-20-09

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2009-02-03 Cont ID  
Sent By jwitmer Date 2009-02-03 Time 11:40 Rev Time 1.55
Received By jwitmer Date 2009-02-03 Time 11:40 Sent To  
Notes
2009-02-03 11:46:17BUILDING PLAN REVIEW
 PERMIT: 06090366
 ADD: 221 CLEMATIS ST
 CONT: CASTLE FLORIDA
 TEL: (561)441-0492 MARK
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ * WEST PALM BEACH AMENDMENTS
  
 REVISION- DATED 1-21-09
 ACTION: DENIED
  
 1) SHEETS A1, A4 & A5 THE FRONT WINDOW/ FOLDING DOOR
 ASSEMBLY FOUND ON THE FRONT OF THE BUILDING 2ND FLOOR
 THE DESIGN PRESSURES AND PRODUCT APPROVALS DO NOT
 INDICATE THEY HAVE BEEN REVIEWED BY THE DESIGN TEAM.
 106.3* PRODUCT APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 2) THE DETAILED WIND LOAD DESIGN WAS COMPLETED USING A
 MEAN ROOF HEIGTH OF 30 FEET WHERE AS THE BUILDING
 HEIGTH IS TAKEN FROM THE HEIGHTEST FLOOR FOR THE
 NEGATIVE VALUES. SHEET A-5INDICATES TTHE HIGHEST ROOF
 DECK TO BE 48'-7" WHICH WILL ENACT TABLE 1609.6.2.1(4)
 ADJUSTMENT FACTORS FOR BUILDING HEIGHTS B-ZONE 50'-0"
 1.16 FACTOR PLEASE RE-RUN THE WIND CALCULATIONS AS PER
 TABLE 1609.6.2.1(4).
  
 3) WIND DESIGN BY GLENN GOLDBERG PE COMPANY NAME
 VINTAGE DESGN & CONSTRUCTION, INC, 61G15-23.002(2) FL.
 ADMIN. CODE. PLANS SIGNED & SEALED BY A PROFESSIONAL
 ENGINEER SHALL INCLUDE EITHER THE: NAME, ADDRESS AND
 LICENSE NUMBER OF THE ENGINEER OR, THE NAME AND LICENSE
 NUMBER OF THE ENGINEER AND THE NAME, ADDRESS AND
 CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS THROUGH WHICH THE ENGINEER IS PRACTICING
 (471.025 F.S. AND 471.023 F.S.).
  
 471.023 F.S. CERTIFICATE OF AUTHORIZATION. THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD
 THE NUMBER TO EACH SHEET. THIS MAY BE ADDED BY HAND.
  
 4) RCL STRUCTURAL ENGINEERING, LLC 61G15-23.002(2) FL.
 ADMIN. CODE. PLANS SIGNED & SEALED BY A PROFESSIONAL
 ENGINEER SHALL INCLUDE EITHER THE: NAME, ADDRESS AND
 LICENSE NUMBER OF THE ENGINEER OR, THE NAME AND LICENSE
 NUMBER OF THE ENGINEER AND THE NAME, ADDRESS AND
 CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS THROUGH WHICH THE ENGINEER IS PRACTICING
 (471.025 F.S. AND 471.023 F.S.).
  
 471.023 F.S. CERTIFICATE OF AUTHORIZATION. THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD
 THE NUMBER TO EACH SHEET. THIS MAY BE ADDED BY HAND.
  
 5) RCL ENGINEERING IS USING THE MORE RESTRICTIVE "C"
 EXPOSURE BUT DOES NOT INDICATE THE MEAN ROOF HEIGTH OF
 THE BUILDING, TABLE 1609.6.2.1(4) PLEASE CORRECT THE
 ASSUMPTIONS AND DESIGN PRESSURES.
  
 6) SHEET A-3 DETAIL4 &6 PLEASE PROVIDE THE CALCULATIONS
 FOR GUARDRAIL SYSTEM 1607.7.1.1.CONCENTRATED LOAD.
 HANDRAIL ASSEMBLIES AND GUARDS SHALL BE ABLE TO RESIST
 A SINGLE CONCENTRATED LOAD OF 200 POUNDS (0.89 KN),
 APPLIED IN ANY DIRECTION AT ANY POINT ALONG THE TOP,
 AND HAVE ATTACHMENT DEVICES AND SUPPORTING STRUCTURE TO
 TRANSFER THIS LOADING TO APPROPRIATE STRUCTURAL
 ELEMENTS OF THE BUILDING.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 MEMBER OF BOAF, THE BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA: PROTECTING LIVES AND PROPERTY SINCE 1953.
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. UNDER FLORIDA STATE STATUTE SB 80, E-MAIL
 ADDRESSES ARE PUBLIC RECORDS.WRITTEN COMMUNICATIONS TO
 OR FROM LOCAL OFFICIALS REGARDING CITY BUSINESS ARE
 PUBLIC RECORD, AVAILABLE TO THE PUBLIC UPON REQUEST.
 YOUR E-MAIL COMMUNICATIONS ARE THEREFORE SUBJECT TO
 PUBLIC DISCLOSURE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2008-07-01 Cont ID  
Sent By jwitmer Date 2008-07-01 Time 16:27 Rev Time 1.11
Received By jwitmer Date 2008-07-01 Time 16:27 Sent To  
Notes
2008-07-01 16:28:37REV "C" A-1, A-2, A-3 & A-4.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2008-05-30 Cont ID  
Sent By jwitmer Date 2008-05-30 Time 15:58 Rev Time 0.77
Received By jwitmer Date 2008-05-30 Time 15:58 Sent To  
Notes
2008-05-30 15:59:17REVISION- B OK SHEETS:
 COVERSHEET
 A-1
 A-4

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2008-05-30 Cont ID  
Sent By jwitmer Date 2008-05-30 Time 15:51 Rev Time 1.11
Received By jwitmer Date 2008-05-30 Time 15:51 Sent To  
Notes
2008-05-30 15:57:54BUILDING PLAN REVIEW
 PERMIT: 06090366
 ADD: 221 CLEMATIS ST
 CONT: CASTLE FLORIDA
 TEL: (561)441-0492 MARK
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION- B SHEET A2 REVIEW
 ACTION: DENIED
  
 SHEET A-2 DETAIL # 2 CLEARLY INDICATES THE 6'-9" CLEAR
 HEIGTH FROM THE EDGE OF THE STEEL BEAM TO BENEATH THE
 BOTTOM OF THE STAIRWELL STRINGER. THE CLEAR HEIGTH
 MAYBE 6'-0" AS DEPICTED ON THE PLANS.
 PLEASE SEE 1009.2 MINIMUM CLEAR HEIGTH OF 80".
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2008-04-03 Cont ID  
Sent By jwitmer Date 2008-04-03 Time 16:27 Rev Time 3.33
Received By jwitmer Date 2008-04-03 Time 16:27 Sent To  
Notes
2008-04-03 16:45:27BUILDING PLAN REVIEW
 PERMIT: 06090366
 ADD: 221 CLEMATIS STPHASE II SUITE 104 CONT:
 CASTLE FLORIDA
 TEL: (561)856-6655
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONREVIEW:
 ACTION: DENIED
  
 --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PLANS ARE MISSING THE BUILDING TYPE? TABLE 503/
 601.
  
 2) PLEASE SEE A1VERSES A4 FOR LAYOUT OF FURNATURE AND
 FOR LIFE SAFETY, THEY DO NOT MATCH AT THE FRONT OF THE
 UNIT BY THE GLASS WINDOW UNITS. PLANS INDICATE A COMMON
 PATH OF TRAVEL OF 76'-0".
 PLEASE SEE 1024.8 COMMON PATH OF TRAVEL FOR ASSEMBLY
 OCCUPANCY.
  
 3) ADDITIONAL INFORMATION IS REQUIRED, COVER SHEET
 INDICATE THESE PLANS ARE FOR PHASE II AREA IS HATCHED
 TO LOCATE AREA OF WORK TO BE COVERED UNDER PHASE II,
 BUT THE SHEET A-2 INDICATES WORK UNDER PHASE I INCLUDED
 IN THIS PLAN, POOL HALL STOREFRONT ELEVATIONS. NOTE
 SHEET A-4 INDICATES A "NEW TENANT" ON THE MEZZANINE
 LEVEL. NOTE WHEN YOU ENCLOSE THE MEZZANINE LEVEL IT
 WILL BECOME A TRUE SECOND FLOOR SEE 505.2 AREA OF
 MEZZANINE, PLEASE REMOVE THE WORDING OF MEZZANINE.
  
 4) THE WORDING OF "NEW TENANT" ON THE MEZZANINE LEVEL
 ALSO CREATES ANOTHER ISSUE, IN OUR MEETINGS IT WAS
 DISCUSSED IT IS THE SAME TENANT A NEW AREA IS BEING
 OPENED. NEW TENANT WILL REQUIRE, TENANT SEPERATION
 WALLS OR FIE WALLS REQUIRING A ONE HOUR RATING OF THIS
 WALL, SEE 708.3. IF THE INTENT IS DIFFERENT THEME
 AREAS, INDICATE SUCHBUT SINGLE TENANT.
  
 5)SHEET A-2 DETAIL# 2, STAIR ELEVATION INDICATES A
 6'-9" CLEAR HEIGTH BUT IN ACTUALLITY THE PLAN INDICATES
 6'-0" FROM THE EDGE OF THE NOSING, PLEASE SEE 1009.2
 HEADROOM.
  
 6)SHEET A-2 DETAIL# 2 INDICATES THE MECHANICAL
 EQUIPMENT AS BEING HOUSED WITHIN A MEZZANINE, THIS
 SPACE IS NOT TO BE CONSIDERED A MEZZANINEBUT A
 PENTHOUSE SEE 1509.2.
 THE STAIR THAT LEADS TO THE MECHANICAL PENTHOUSE
 INDICATES STORAGE IN WHAT WOULD BE CONSIDEREDTHE EXIT
 THAT LEADS TO THE MECHANICAL PENTHOUSE. THE COMMON WALL
 FROM THE MECHANICAL PENTHOUSE AND ELECTRIC ROOM IS TO
 BE 1 HOUR RATED. THIS WOULD CREATE PART OF THE RATED
 VERTICAL EXIT THE OTHER WALL THAT WOULD BE COMMON TO
 THE WOMENS RESTROOM TO THE DOORWAY WOULD ALSO CREATE
 THE 1 HR RATED EXIT TO THE MECHANICAL PENTHOUSE.
  
 7) SHEET A-4 PLEASE INDICATE COMPLIANCE WITH 11-5.1 AND
 11-5.2.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status   Date 2008-02-22 Cont ID  
Sent By jwitmer Date 2008-02-22 Time 09:59 Rev Time 0.00
Received By jwitmer Date 2008-02-22 Time 09:59 Sent To  
Notes
2008-02-22 09:59:38NOTES: REVISION "E"

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-12-20 Cont ID  
Sent By jwitmer Date 2007-12-20 Time 14:52 Rev Time 3.33
Received By jwitmer Date 2007-12-20 Time 14:51 Sent To  
Notes
2007-12-20 15:00:03BUILDING PLAN REVIEW
 PERMIT: 06090366
 ADD: 221 CLEMATIS ST.
 CONT: CASTLE FLORIDA BUILDING CORP.
 TEL: (561)756-2491
 DEC.21,2007
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISON REVIEW: (E)
 ACTION: REVIEWED
  
 BUILDING PROVISOS;
  
 1) NO CERTIFICATE OF OCCUPANCY FOR THIS INTERIOR
 REMODEL PERMIT UNTIL PERMIT # 06091101 EXTERIOR
 ALTERATIONS & NEW OVERHEAD GARAGE DOORS, SLOPED GLAZING
 HAZARDOUS LOCATION 2405.2HAS RECEIVED A CERTIFICATE OF
 COMPLETION.
  
 2) NEW ENERGY CALCULATIONS SINCE THE SOUTHERN EXPOSURE
 HAS CHANGED AND MORE GLAZING HAS BEEN ADDED TO THIS
 WALL FACE (NEW OVERHEAD GLAZED DOORS,), PLUS WORK TO BE
 COMPLETED UNDER THE OLD ENERGY CALCULATIONS HAS BEEN
 REMOVED FROM THIS PROJECT.
  
 3) PERMIT # 07120350 WILL NEED TO REFLECT THE SCOPE OF
 WORK THAT HAS BEEN DELETED FROM THIS PERMIT. THIS
 PLERMIT 07120350FOR A NEW STAIRWAY INDICATES THAT AN
 EXISTING NIGHTCLUB IS LOCATED ON THE 2ND FLOOR ADJACENT
 TO THIS NEW STAIR LOCATION WHICH WAS THE WORK DELETED
 FROM THIS PERMIT.
  
 4) NOTE, THIS TOTAL BUILDING TOOK THE SPRIKLER
 INCREASES FOR SIZE OF BUILDING UNDER TABLE 503, THIS
 TOTAL BUILDING INCLUDING FROM THE FORMER MONKEY CLUB TO
 FORTE IS ALL ONE BUILDING REQUIRING FIRE SPRINKLERS FOR
 TENANT SPACES, A OCCUPANCY CLASSIFICATION A2, 4 STORY
 BUILDING, BUILDING TYPE IIA,.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-09-20 Cont ID  
Sent By jwitmer Date 2007-09-20 Time 16:55 Rev Time 1.11
Received By jwitmer Date 2007-09-20 Time 16:55 Sent To  
Notes
2007-09-20 16:56:31BUILDING PROVISO: 1009.2 MINIMUM HEADROOM 6'-8"

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-07-17 Cont ID  
Sent By jwitmer Date 2007-07-17 Time 19:54 Rev Time 1.55
Received By jwitmer Date 2007-07-16 Time 22:18 Sent To  
Notes
2007-07-17 20:44:28BUILDING PLAN REVIEW
 PERMIT: 06090366
 ADD: 221 CLEMATIS ST SUITE 201 & 202
 CONT: CASTLE FLORIDA
 TEL: (561)856-6655
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) COMPLIED.
  
 3A)3RD REQUEST, PLANS INDICAE A CODE SUMMARY A TYPE
 II-BBUILDING SPRINKLERED AND A ASSEMBLY GROUP A-2.
 TABLE 503 A-2 TYPE II-B ALLOWABLE AREA IS 9,500 SQ FT 2
 STORIES. PLANS INDICATE THE FOOTPRINT OF THE BUILDING
 AS 21,213 SQ FT.
 PLEASE PROVIDE WHAT AREA AND OR HEIGHT INCREASES THAT
 YOU MAY TAKE, ALSO NOTE THIS ISCONSIDERED A (4) STORY
 BUILDING, THE
 3RD AND 4TH FLOORS BEING PROPOSED A BUSINESS
 OCCUPANCY.TABLE 503, 504.2 AUTOMATIC SPRINKLER
 INCREASES.
 NEW COMMENT: YES THE SPRINKLER AND FRONTAGE INCREASES
 WILL PROVIDE THE AREA FOR A TYPE II-B BUILDING, THE
 **HEIGHT** INCREASE IS ONLY ONE ADDITIONAL STORY. THE
 DESIGN TEAM WILL NEED TO EVALUATE IF THE TYPE IIA WILL
 MAKE THE REQUIREMENTS OF TABLE 503FOR A FULLY
 SPRINKLERED BUILDING. NOTE THIS WILL MEAN THE TOTAL
 BUILDINGS COLUMNS TO BE 1 HR FIRE RATED, FLOOR
 ASSEMBLIES SEE TABLE 601.
  
 3B)(1)COMPLIED.
  
 3B)(2)COMPLIED, NOT GOING TO CHANGE THE EXTERIOR OF
 THE BUILDING.
  
 3C)(1) COMPLIED, REMOVED FROM THIS PERMIT, UNDER
 SEPERATE PERMIT.
 PLEASE NOTE THERE IS NO MENTION OF THE EXITS AT
 THE REAR OF THE BUILDING ADJACENT TO THE ALLEY WAY. OUR
 JOBSITE MEETING (LAST
 WEEK OF DEC) REVEALED THE WEST EXIST STAIRS
 TO HAVE SEVERAL CODE VIOLATIONS:
 (1) THE EXIT DOOR TO THE STAIRWAY SWUNG INTO THE
 STAIRWELL, OCCUPANT LOAD > 50.
 (2) THERE APPEARED TO BE A KITHEN EXHAUST DUCK
 CUT INTO THE EXIT.
 (3) THERE ALSO WAS A VESTIBULE AREA DIRECTLY
 BEHIND THE STAIRWELL THE
 EXHAUST DUCK DUMPED INTO, THERE IS ANOTHER
 EXIT DOOR NOT DETERMINED
 WHERE IS AN EXIT FROM
 (4 THE STAIRWELL WAS NOT TRUELY FIRE RATED. (5)
 THERE WAS WINDOWS ON THE PROPERTY LINE. (6) AT
 THE TOP OF THE STAIRWAY NO DOOR OR ENCLOSURE.
 (7) IT APPEARS THAT THERE IS PLUMBING 6"OR 8" AT
 THE TOP OF THE LANDING
 (8) ALSO STAIRS TO THE MEZZANINE LEVEL ALSO HAD
 ISSUES WITH
 ELECTRICAL CONDUCTORS RUNNING THROUGH THE
 STAIRWELL.
 (9) THERE ALSO APPEARS TO BE HEIGTH PROBLEMS,
 MINIMUM HEADROOM
 (10) NO EXIT LIGTS OR DIRECTIONAL SIGNS
  
 3C()2)COMPLIED, UNDER A SEPERATE PERMIT.
 THE STAIRWELL TO THE EAST END OF THE ASSEMBLY
 OCCUPANCY SUITE# 202ALSO HAD SEVERAL CODE VIOLATIONS
 :
 (1) STORAGE IN THE STAIRWELL
 (2) ELECTRIC PANELS AT EACH FLOOR LEVEL
 (3) NO APPROVED EXIT LIGHTING, OR DIRECTIONAL
 SIGNS
 (4) THE EXIT DOOR ALSO SWINGS OUT OVER THE
 PROPERTY LINE.
 (5) IT APPEARS THERE IS ALSO PLUMBING IN THE
 STAIRWELL.
  
 4) WILL REFER BACK TO 3A) FOR ANSWER.
  
 5) COMPLIED, REMOVED FROM SCOPE OF WORK.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8A)COMPLIED, REMOVED FROM SCOPE OF WORK.
  
 8B)COMPLIED. REMOVED FROM THE SCOPE OF WORK.
  
 8C)COMPLIED. REMOVED FROM THE SCOPE OF WORK.
  
 8D) COMPLIED, REMOVEDFROM THE SCOPE OF WORK.
  
 8E)COMPLIED, REMOVED FROM SCOPE OF WORK.
  
 9) COMPLIED.
  
 10) COMPLIED, REMOVED FROM THE SCOPE OF WORK.
  
 11) COMPLIED.
  
 12)COMPLIED.
  
 13) COMPLIED.
  
 14) COMPLIED.
  
 15) COMPLIED.
  
 16) COMPLIED.
  
 17) COMPLIED.
  
 18)COMPLIED.
  
 19) COMPLIED, THE EAST EXIT IS IN A 2HR RATED SHAFT,
 4STORY BUILDING .
  
 20) COMPLIED.
  
 21) COMPLIED.
  
 22) COMPLIED.
  
 23) COMPLIED.
  
 24) COMPLIED.
  
 25) COMPLIED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-03 Cont ID  
Sent By jwitmer Date 2007-01-03 Time 09:46 Rev Time 5.33
Received By jwitmer Date 2007-01-03 Time 09:46 Sent To  
Notes
2007-01-03 13:42:21BUILDING PLAN REVIEW
 PERMIT: 06090366
 ADD: 221 CLEMATIS ST SUITE 201 & 202
 CONT: CASTLE FLORIDA
 TEL: (561)856-6655
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) COMPLIED.
  
 3A)2ND REQUEST, PLANS INDICAE A CODE SUMMARY A TYPE
 II-BBUILDING SPRINKLERED AND A ASSEMBLY GROUP A-2.
 TABLE 503 A-2 TYPE II-B ALLOWABLE AREA IS 9,500 SQ FT 2
 STORIES. PLANS INDICATE THE FOOTPRINT OF THE BUILDING
 AS 21,213 SQ FT.
 PLEASE PROVIDE WHAT AREA AND OR HEIGHT INCREASES THAT
 YOU MAY TAKE, ALSO NOTE THIS ISCONSIDERED A (4) STORY
 BUILDING, THE
 3RD AND 4TH FLOORS BEING PROPOSED A BUSINESS
 OCCUPANCY.TABLE 503, 504.2 AUTOMATIC SPRINKLER
 INCREASES.
  
 3B)(1)PLEASE PROVIDE A LIFE SAFETY PLAN OF THE TOTAL
 FIRST FLOOR AND SECOND FLOOR OF THIS ASSEMBLY
 OCCUPANCY. PLEASE INDICATE OCCUPANT LOADS FOR ALL AREAS
 OF THE FLOOR, EXAMPLE BARS ARE TO BE CONSIDERED AS A
 STANDING SPACE 5 NET, DANCE FLOORS 7 NET, TABLE AND
 CHAIRS 15 NET, POOL TABLES 15 NET, FIXED SEATING 1004.7
 AND PROVIDE A TOTAL OCCUPANT LOAD.PLEASE NOTE THE
 EXISTING SUITE 202 IS CONSIDERED A MEZANINE SEE 1004.6
 AS HOW TO HANDLE THE OCCUPANT LOADS, WHERE THIS
 ADDITIONALOCCUPANT LOAD WILL DISCHARGE THROUGH. ALSO
 INDICATE THE DISPERSAL OF THE OCCUPANT LOAD, PROVIDE
 ALLOWABLE OCCUPANT LOADS FOR DOORWAYS AND STAIRS. TABLE
 1005.1.NOTE THE BOTTLE NECKING EFFECT AT ELEVATOR LOBBY
 TO SUITE # 202.
  
 3B)(2)THERE IS ANOTHER ISSUE TO BE CONCERNED WITH,
 THE OCCUPANCY LOAD OF THE NIGHTCLUB, IF OVER 300 1609.5
 THE IMPORTANCE FACTOR
 OF THE BUILDING . THE BUILDING BECOMES A
 BUILDING CATEGORY III, THE IMPORTANCE FACTOR OF
 1.15.PLEASE PROVIDE THE FOLLOWING WIND INFORMATION.
 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN WIND
 PRESSURES IN TERMS OF PSF.
  
 3C)(1) PLEASE NOTE THERE IS NO MENTION OF THE EXITS AT
 THE REAR OF THE BUILDING ADJACENT TO THE ALLEY WAY. OUR
 JOBSITE MEETING (LAST
 WEEK OF DEC) REVEALED THE WEST EXIST STAIRS
 TO HAVE SEVERAL CODE VIOLATIONS:
 (1) THE EXIT DOOR TO THE STAIRWAY SWUNG INTO THE
 STAIRWELL, OCCUPANT LOAD > 50.
 (2) THERE APPEARED TO BE A KITHEN EXHAUST DUCK
 CUT INTO THE EXIT.
 (3) THERE ALSO WAS A VESTIBULE AREA DIRECTLY
 BEHIND THE STAIRWELL THE
 EXHAUST DUCK DUMPED INTO, THERE IS ANOTHER
 EXIT DOOR NOT DETERMINED
 WHERE IS AN EXIT FROM
 (4 THE STAIRWELL WAS NOT TRUELY FIRE RATED. (5)
 THERE WAS WINDOWS ON THE PROPERTY LINE. (6) AT
 THE TOP OF THE STAIRWAY NO DOOR OR ENCLOSURE.
 (7) IT APPEARS THAT THERE IS PLUMBING 6"OR 8" AT
 THE TOP OF THE LANDING
 (8) ALSO STAIRS TO THE MEZZANINE LEVEL ALSO HAD
 ISSUES WITH
 ELECTRICAL CONDUCTORS RUNNING THROUGH THE
 STAIRWELL.
 (9) THERE ALSO APPEARS TO BE HEIGTH PROBLEMS,
 MINIMUM HEADROOM
 (10) NO EXIT LIGTS OR DIRECTIONAL SIGNS
  
 3C()2) THE STAIRWELL TO THE EAST END OF THE ASSEMBLY
 OCCUPANCY SUITE# 202ALSO HAD SEVERAL CODE VIOLATIONS
 :
 (1) STORAGE IN THE STAIRWELL
 (2) ELECTRIC PANELS AT EACH FLOOR LEVEL
 (3) NO APPROVED EXIT LIGHTING, OR DIRECTIONAL
 SIGNS
 (4) THE EXIT DOOR ALSO SWINGS OUT OVER THE
 PROPERTY LINE.
 (5) IT APPEARS THERE IS ALSO PLUMBING IN THE
 STAIRWELL.
  
 4) WILL REFER BACK TO 3A) FOR ANSWER.
  
 5)2ND REQUEST, W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. THE DESIGNER OF RECORD
 INDICATES PRESSURES OF +52/-58 ON
 SHEET A-4 WHERE AS THE PRODUCT APPROVAL IS APPROVED FOR
 A DESIGN LOAD OF +30/-30?
  
 6) 2ND REQUEST, FIRE SPRINKLER PLANS ARE REQUIRED AT
 TIME OF PERMIT APPLICATION,IF THE BUILDING IS
 DESIGNED
 AS A FIRE SPRINKLERED BUILDING AND THE AREA INCREASES
 THAT ARE TAKEN IN TABLE 503 AND 504.2.. THE DESIGNER OF
 RECORD
 WILL DESIGN A SYSTEM AFTER THE PERMIT IS ISSUED, SHOP
 DRAWINGS
 WILL BE SUBMITTED AT THAT TIME. FL S S 553.79(2)
 WHENEVER FIRE
 SPRINKLER PLANS ARE REQUIRED, THEN THE DESIGN OF THOSE
 SYSTEMS
 MUST BE INCLUDED IN THE ORIGINAL PLANS AND
 SPECIFICATIONS FOR
 APPROVAL OF THE PERMIT.
  
 7)2ND REQUEST, THE OCCUPANT LOAD TO BE DETERMINED
 USING THE INFORMATION LISTED IN COMMENT 3B)(1) ABOVE.
  
 8A) 2ND REQUEST, FOR PRODUCT APPROVALS FOR THE
 OVERHEAD
  
 DOORS. PLANS MAY INDICATE LARGE MISSLE RATED GLASS, BUT
 THE
 PRODUCT SUBMITTED
 STATES THE SYSTEM BUILT AND TESTED DOES NOT HAVE LARGE
 MISSLE
 TESTING.1609.1.4(1) PROTECTION OF OPENINGS , GLAZED
 OPENINGS
 LOCATED WITHIN 30FEET OF GRADE SHALL MEET THE
 REQUIREMENTS OF
 THE LARGE MISSLE TEST.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED
 TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8B) THERE ARE OTHER CRITERIA TO BE REVIEWED BY THE
 DESIGNER OF RECORD
 BEFORE THIS PRODUCT CAN BE APPROVED FOR USE IN THIS
 BUILDING.
 CLOPAY SHEET W5 HAS TWO DESIGN CRITEREA TO CONSIDER,
 THIS REPORT
 INDICATES FOR A 140 MPH WIND ZONE THE MEAN ROOF HEIGHT
 OF 30' AND AN
 IPORTANCE FACTOR OF 1.0. COMMENTS 3B((1) AND 3B)(2)
 BOTH REFER BACK TO THIS ISSUE.
 THE SECOND ISSUE THIS BEING A 4 STORY BUILDING IS
 HEIGHT, ONCE ABOVE 30' THERE
 ARE MULTIPLIERS THAT EFFECT THE PRESSURES, THE BASIC
 WIND PRESSURES WILL SHOW AN
 INCREASEABOVE THE BASE TABLE IN 1609..6.B. THERE IS A
 HEIGHT MULTIPLIER PLUS THE IMPORTANCE MULTIPLIER!!!!!
  
 8C)THE OVERHEADDOOR IN THE OPEN POSITION NEEDS TO
 COMPLY WITH 2405 SLOPED GLAZING.
 2405.2 ALLOWABLE GLAZING MATERIALS AND LIMITATIONS.
 SLOPED GLAZING SHALL BE ANY OF THE FOLLOWING MATERIALS,
 SUBJECT TO THE LISTED LIMITATIONS.
 1.FOR MONOLITHIC GLAZING SYSTEMS, THE GLAZING
 MATERIAL OF THE SINGLE LIGHT OR LAYER SHALL BE
 LAMINATED GLASS WITH A MINIMUM 30-MIL (0.76 MM)
 POLYVINYL BUTYRAL (OR EQUIVALENT) INTERLAYER, WIRED
 GLASS, LIGHT-TRANSMITTING PLASTIC MATERIALS MEETING THE
 REQUIREMENTS OF SECTION 2607 , HEAT-STRENGTHENED GLASS
 OR FULLY TEMPERED GLASS.
 2.FOR MULTIPLE-LAYER GLAZING SYSTEMS, EACH LIGHT
 OR LAYER SHALL CONSIST OF ANY OF THE GLAZING MATERIALS
 SPECIFIED IN ITEM 1 ABOVE.
 ANNEALED GLASS IS PERMITTED TO BE USED AS SPECIFIED
 WITHIN EXCEPTIONS 2 AND 3 OF SECTION 2405.3 .
 FOR ADDITIONAL REQUIREMENTS FOR PLASTIC SKYLIGHTS, SEE
 SECTION 2610 . GLASS-BLOCK CONSTRUCTION SHALL CONFORM
 TO THE REQUIREMENTS OF SECTION 2101.2.5 .
  
 8D) THE ENERGY FORMS NEED TO REFLECT THIS OPENING ON
 THE SOUTH WALL, WITH THE DOORS OPEN, AND WHEN THE DOORS
 ARE CLOSED
 THE TYPE OF DOOR ,IT IS NOT A PAPER HONEYCOMB FILLED
 CORE TYPE OF DOOR!!!!!!
 NOTE THE FIRST FLOOR DOOR IS ALSO A PAIR OF DOORS NOT A
 3'-0" X 7'-0"DOOR.
  
 8E)DETAIL4 SHEET A-3 INDICATES THE NEW OVERHEAD
 DOORS, PLEASE PROVIDE THE THICKNESS OF THE BEAM BELOW
 AND THE CLOSENESS OF THE WINDOWS BELOW, FIRST FLOOR
 WINDOWS. SHEET A-4 INDICATES THE FIRST FLOOR WINDOWS
 BUT THE TRANSOMS ABOVE THE WINDOWS DO NOT APPEAR.
 PLEASE PROVIDE ADDITIONAL DETAIL. PROVIDE COMPLIANCE
 WITH 704.9 VERTICAL SEPERATION.OF OPENINGS.IF USING
 EXCEPTION# 2 AGAIN A COMPLETE SET OF FIRE SPRINKLER
 PLANS FOR THE"BUILDING" WILL NEED TO BE PROVIDED FOR
 THIS EXCEPTION!!!!!
  
 9) GUARDRAILS, THE RESPONCE SHOWS A DETAIL 4/ A-3, THIS
 NEW DETAIL INDICATES A NEW SLAB DETAIL 1'-0" THICK, NO
 STEEL INFORMATION,
 HOW FAR OUT THE SLAB OR HANDRAILPROTRUDE FROM THE
 BUILDING OR IF THEY ARE OVER THE PROPERTY LINE?
 3202.3.2 WINDOWS, BALCONIES, ARCHITECTURAL FEATURES AND
 MECHANICAL EQUIPMENT.
 WHERE THE VERTICAL CLEARANCE ABOVE GRADE TO PROJECTING
 WINDOWS, BALCONIES, ARCHITECTURAL FEATURES OR
 MECHANICAL EQUIPMENT IS MORE THAN 8 FEET (2438 MM), 1
 INCH (25 MM) OF ENCROACHMENT IS PERMITTED FOR EACH
 ADDITIONAL 1 INCH (25 MM) OF CLEARANCE ABOVE 8 FEET
 (2438 MM), BUT THE MAXIMUM ENCROACHMENT SHALL BE 4 FEET
 (1219 MM).
  
 10) 2ND REQUEST, GUARDRAIL DETAIL 4/ A-3 INDICATES A
 HANDRAIL DETAILIS TO SHOW THE MINIMUM DISTANCE FROM
 THE EDGE OF SLAB.
 RESPONCE INDICATES 4" IN LETTER BUT NO COMMENT ON THE
 PLANS!!!
  
 11) 2ND REQUEST, VERTICAL ACCESSIBLITY BETWEEN SUITE
 201 & 202. PLANS INDICATE A LIFT, MUST NOT EMPEDE
 EGRESS ON STAIRS. PLEASE PROVIDE INFORMATION ON THE
 LIFT.11-4.1.6.(1)(K)(III).
 11-4.11 PLATFORM LIFTS (WHEELCHAIR LIFTS). 11-4.11.1
 LOCATION.
 PLATFORM LIFTS (WHEELCHAIR LIFTS) PERMITTED BY SECTION
 11-4.1 SHALL COMPLY WITH THE REQUIREMENTS OF SECTION
 11-4.11 .
 11-4.11.2 OTHER REQUIREMENTS.
 IF PLATFORM LIFTS (WHEELCHAIR LIFTS) ARE USED, THEY
 SHALL COMPLY WITH SECTIONS 11-4.2.4 , 11-4.5 , 11-4.27
 , AND ASME A17.1, SAFETY CODE FOR ELEVATORS AND
 ESCALATORS , SECTION XX, 1990.
 11-4.11.3 ENTRANCE.
 IF PLATFORM LIFTS ARE USED THEN THEY SHALL FACILITATE
 UNASSISTED ENTRY, OPERATION, AND EXIT FROM THE LIFT IN
 COMPLIANCE WITH SECTION 11-4.11.2 .
  
 12)COMPLIED.
  
 13) COMPLIED.
  
 14) THE PLANS ARE NOT CLEAR ON THE HANDRAIL AND LIFT
 ARE TO COMBINE TO CREATE A OPENING FOR THE LIFT?
  
 15) RESPONCE STATES THE METAL CLAD DOOR (90 MIN RATING)
 IS TO ONLY BE AESTHETIC VALUE TO THE PROJECT, BUT THE
 FIELD MEETING
 INDICATED ON SLOW NIGHTS THIS AREA WILL BE CLOSED OFF,
 HOW WILL THIS OCCUR? WILL EACH AREA EVER BE OPENED
 SEPERATELY,
 SUITE 202 IS CLOSED THERE WILL BE NO VERTICAL MEANS OF
 EGRESS?
  
 16) POSSIBLY COMPLIED DEPENDING ON COMMENT RESPONCE
 15.
  
 17) COMPLIED.
  
 18) 2ND REQUEST,CORRIDOR 110 WILL HAVE ISSUES. THIS
 MAY TRUELY BE A CORRIDOR OR IT MAY END UP BEING
 DESIGNED AS A PART OF AN EXIT
 PASSAGEWAY. IF THE DESIGN IS A CORRIDORTHE ELECTRICAL
 ROOM DOOR WOULD BE ALLOWED. IF DESIGNED AS PART OF THE
 EXIT PASSAGE WAY
 NO ELECTRICAL ROOM DOOR CAN BE IN THIS EXIT. NOTE ALSO
 FROM THE JOBSITE MEETING THE ELECTRIC ROOM DOOR NEEDS
 TO SWING OUT OF THE
 ELECTRICAL ROOM.
  
 19) 2ND REQUEST, HOW MANY STORIES ARE IN THE BUILDING?
 A 1 HR CORRIDOR IS SHOWN. THE RESPONCE STATES THE AREA
 WHERE WORK IS TO OCCUR IS TWO STORIES. PLANS INDICATE
 IN SUITE 202 THE WALL OFTHE MENS RESTROOM THAT BACKS UP
 TO THE 4 STORY STAIR TOWER DOES SHOW A 1 HR RATING
 WHERE THERE SHOULD BE A 2 HR RATING . SHAFTS SEE
 SECTION 707.
  
 20) ELECTRICAL ROOM 108 AS DISCUSSED IN THE JOBSITE
 MEETING THIS DORR DOES NEED TO BE MOVED BEWARE OF THE
 DOOR SWINNG AND THE CLEAR SPACE REQUIRED FOR THE
 CORRIDOR. NOTE ALSO : 008.1.8.8
 DURING ITS SWING, ANY DOOR IN A MEANS OF EGRESS SHALL
 LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF THE REQUIRED
 WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY, OR LANDING,
 NOR PROJECT MORE THAN 7 INCHES (178 MM) INTO THE
 REQUIRED WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY OR
 LANDING, WHEN FULLY OPEN.
  
 21) 2ND REQUEST, PROVIDE INFORMATION IN REGARDS TO EXIT
 DISCHARGE? RESPONCE EXIT DIRECTION IS NOW SHOWN ON
 1/A-1. PLANS DO NOT SHOW THE EXIT AT THE FIRST FLOOR.
 THE JOB MEETING CLEARLY INDICATES PROBLEM AREAS AT BOTH
 THE EAST AND WEST EXITS. SEE COMMENT # 3.
  
 22) COMPLIED.
  
 23) COMPLIED.
  
 24) COMPLIED.
  
 25) COMPLIED.
  
 ADDITIONAL COMMENTS MAY APPEAR ON THE NEXT REVIEW AS A
 RESULT TO COMMENT RESPONCE TO THIS REVIEW AND NEW
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-06 Cont ID  
Sent By shill Date 2006-10-06 Time 16:10 Rev Time 0.00
Received By shill Date 2006-10-06 Time 09:25 Sent To  
Notes
2006-10-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
  
 1.)A NOTICE OF COMMENCEMENT WILL BE
 REQUIRED PRIOR TO PERMIT PICKUP,
 FS713.13.
  
 2.)INCLUDE FBC EB IN GOVERNING CODE.
 DECLARE LEVEL OF ALTERATION, FBC EB 3.
 DOES THIS INVOLVE A CHANGE OF OCCUPANCY?
 IF IT DOES, INCLUDE COMPLIANCE WITH FBC
 8.
  
 3.)INCLUDE A CODE SUMMARY ABOUT THE
 EXISTING BUILDING; (REVISE) BUILDING
 TYPE FBC6, BUILDING HEIGHT AND AREA
 FBC5, OCCUPANCY CLASSIFICATION FBC 3 AND
 AREA PER OCCUPANCY.OCCUPANCY
 CLASSIFICATION HAS BEEN DECLARED, A2,
 FOR THE RENOVATED SPACE, BUT PLEASE
 PROVIDE INFORMATION IN REGARDS TO THE
 REST OF THE BUILDING.
  
 4.)SHEET A1 STATES THAT THE BUILDING
 IS TYPE IV UNPROTECTED.SEE FBC 6, TYPE
 IV IS HEAVY TIMBER.TO MY KNOWLEDGE
 THIS IS NOT A HEAVY TIMBER BUILDING.
 PLEASE REVISE, AND INCLUDE A OR B.
  
 5.)PRODUCT APPROVALS TO BE REVIEWED BY
 DESIGNER OF RECORD, FBC*106.3.3.
  
 6.)FIRE SPRINKLER PLANS REQUIRED,
 FBC*106.3.5.1.1(5), FS553.79(2).ALSO
 SEE ATTACHED LETTER FROM DCA.
  
 7.)A1, OCCUPANT LOAD IS TO BE NOT LESS
 THAN SPECIFIED IN FBC TABLE 1004.1.2,
 FBC 1004.1.2 (ROUND UP RATHER THAN ROUND
 DOWN).
  
 8.)THE PRODUCT APPROVAL FOR THE
 OVERHEAD DOOR REQUIRES IMPACT PROTECTION
 FOR THE OPTIONAL GLASS. REMOVABLE
 SHUTTERS NOT ALLOWED ABOVE THE FIRST
 FLOOR.SEE ATTACHED POLICY IN REGARDS
 TO IMPACT PROTECTION.PLEASE CONTACT ME
 TO DISCUSS AND PLEASE RESOLVE THIS ISSUE
 PRIOR TO RESUBMITTAL.
  
 9.)GUARDRAIL REQUIRED AT THE OVERHEAD
 DOOR, FBC1012.1.
  
 10.)GUARDRAIL DETAIL, 4-A3, AND
 HANDRAIL DETAIL, SHOW MINIMUM DISTANCE
 FROM THE EDGE OF SLAB.
  
 11.)VERTICAL ACCESSIBILITY REQUIRED,
 FBC11-4.1.6. IT IS NOT CLEAR IF THE
 ELEVATOR IS DESIGNED TO COMMUNICATE
 BETWEEN SUITE 201 AND SUITE 202, NOTE ON
 THE PLAN.
  
 12.)PROVIDE A DETAIL FOR THE EXISTING
 STAIR BETWEEN SUITE 201 AND SUITE 202.
 THE NOTE STATES TO REPAIR AS NECESSARY,
 PROVIDE A DETAIL.
  
 13.)THE STAIR IS TO COMPLY WITH
 FBC1009.PROVIDE A DETAIL FOR BOTH
 STAIRS BETWEEN SUITE 201 AND SUITE 202.
  
 14.)PROVIDE A DETAIL FOR THE STAIR
 RAILS.HANDRAILS REQUIRED ON BOTH SIDES
 OF THE STAIR, FBC1009.11.PROVIDE A
 DETAIL AND SHOW ALL HANDRAILS ON THE
 PLAN.SHOW COMPLIANCE WITH FBC1607.7.
 SEE ALSO FBC11-4.26.
  
 15.)THE NOTE STATES TO REPAIR/REPLACE
 METAL CLAD DOOR 90 MINUTE (STAIR BETWEEN
 SUITE 201 AND SUITE 202).A DOOR IS NOT
 SHOWN GRAPHICALLY, WHAT IS SHOWN THERE
 ON EACH SIDE OF THE WALL?
  
 16.)LANDINGS REQUIRED AT THE STAIRS,
 FBC1009.4 AND AT DOORS FBC1008.1.5.
 NONE IS SHOWN AT THE EXISTING STAIRS TO
 BE REPAIRED.DOOR LOCATION AND SWING IS
 NOT CLEAR FROM THE PLAN.
  
 17.)IT APPEARS THAT THERE WAS A WALL
 BETWEEN SUITE 201 AND SUITE 202, TENANT
 SEPARATION.A 2 HOUR EXIT ENCLOSURE IS
 SHOWN.THE PURPOSE OF THE 90 MINUTE
 DOOR IS NOT CLEAR; IS THIS ONE TENANT
 SPACE OR TWO?
  
 18.)CORRIDOR 110, SHOW ANY REQUIRED
 FIRE RATING FOR THIS WALL.20MIN DOORS
 ARE NOTED ON THE PLAN, DOORS C.NO FIRE
 RATING SHOWN FOR THE ELECTRICAL 108
 DOOR.THIS APPEARS TO BE AN EXIT
 CORRIDOR; IS THE STAIR SHOWN AN EXIT FOR
 ANOTHER TENANT SPACE?YOU ARE REMOVING
 A DOOR AND INCORPORATING A STORAGE AREA
 INTO THE STAIRWAY, CANNOT USE ANEXIT
 ENCLOSURE FOR ANY OTHER PURPOSE,
 FBC1019.
  
 19.)HOW MANY STORIES IS THIS BUILDING?
 A 1 HOUR CORRIDOR WALL IS SHOWN, NO
 OTHER RATING SHOWN FOR THE STAIRS
 ADJACENT TO ELECTRICAL 108.2 HOUR
 REQUIRED FOR FOUR STORIES OR MORE,
 FBC1019.
  
 20.)PROVIDE DIMENSIONS THE ELECTRICAL
 108 DOOR.IT APPEARS CODE COMPLIANT
 WHEN SCALED; SEE FBC1005.2 AND SHOW
 COMPLIANCE ON THE PLAN.
  
 21.)PROVIDE INFORMATION IN REGARDS TO
 EXIT DISCHARGE; NONE SHOWN ON THE PLAN.
  
  
 22.)THERE ARE FOUR ITEMS SHOWN
 GRAPHICALLY ON THE PLAN AS RECTANGLES
 WITH AN X.TWO APPEAR TO BE ELEVATORS
 (AS THEY ARE LOCATED IN THE ELEVATOR
 LOBBY); WHAT ARE OTHER TWO?
  
 23.)PROVIDE A DETAIL FOR SIGNAGE FOR
 THE ELEVATORS, FBC11-4.10.
  
 24.)A WALL IS BEING REMOVED; DOES THIS
 WALL SERVE AS A TENANT AND/OR OCCUPANCY
 SEPARATION?THERE IS ALSO A STAIR FROM
 SUITE 202 GOING DOWNSTAIRS.WHAT IS IN
 THE AREA BELOW?IS IT A PART OF THIS
 SPACE OR IS IT ANOTHER TENANT SPACE?
  
 25.)SEE FBC11-5.2 REGARDING COUNTERS
 EXCEEDING 34INCHES, SHOW ACCESSIBLE
 SEATING ON THE PLAN (BARS 1, 2, AND 3).
  
 26.)A RESPONSE LETTER WHEN
 RESUBMITTING WILL HELP EXPEDITE PLAN
 REVIEW.ALL CHANGES TO THE PLAN ARE TO
 BE CLOUDED.
  
 27.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  
 28.)PROVIDE WIND DESIGN CRITERIA,
 FBC1603.1.4.

Review Stop E ELECTRICAL
Rev No 13 Status P Date 2008-12-26 Cont ID  
Sent By dpalmer Date 2008-12-26 Time 09:33 Rev Time 0.00
Received By dpalmer Date 2008-12-26 Time 09:33 Sent To PC
Notes
2008-12-26 09:34:11** NOTED**
  
 1) NOTE: REVISED FLA COM B NOW HAS REMOVED ALL
 COMPONENTS OTHER THAN ELECTRICAL LIGHTING COMPLIANCE.
 NO OTHER SYSTEMS ON CALCULATIONS AS THE BUILDING DOES
 NOT FALL UNDER THE DEFINITION OF A RENOVATION.
 PRESCRIPTIVE PER TABLE B, AND OCCUPANCY WAS REVISED.
  
  
 IF THERE ARE ANY QUESTIONS ON THIS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 12 Status P Date 2008-12-18 Cont ID  
Sent By dpalmer Date 2008-12-18 Time 13:45 Rev Time 0.00
Received By dpalmer Date 2008-12-18 Time 13:45 Sent To PC
Notes
2008-12-18 13:46:12** DENIED/PASSED REVIEW OF REVISIONS**
  
 1) NOTE: PLEASE SUBMIT REVISED LIGHTING PERFORMANCE
 CALCULATIONS FOR COMPLIANCE WITH FBC
 13-415.2,13-415.2.ABC.1.1,.1.2. SAME NOTE AS PREVIOUS
 REVIEW. PLEASE SEE TABLES 13-415.2.B (PRESCRIPTIVE)
 13-415.2.C (PRESCRIPTIVE)
 PLEASE SEE13-400.0.C.4 FOR RENOVATED BUILDINGS.
 RENOVATED BUILDINGS SHALL, WHEN APPLICABLE (SEE SECTION
 202), MEET THE EFFICIENCIES LISTED ON FORM 400C FOR
 COMPONENTS BEING CHANGED OR SHALL COMPLY WITH THE
 ENVELOPE OR SYSTEMS CRITERIA IN METHOD B OF FLA/COM FOR
 THE COMPONENTS BEING CHANGED. EXISTING BUILDINGS NOT
 MEETING THE DEFINITION OF A RENOVATION IN WHICH NEW
 HEATING, COOLING, WATER HEATING, ELECTRICAL OR LIGHTING
 SYSTEMS ARE INSTALLED SHALL MEET THE BASIC PRESCRIPTIVE
 MINIMUM EFFICIENCIES LISTED IN THIS CODE FOR THE
 SYSTEM(S) BEING CHANGED.
 THE SECTION 202 REFERENCE IS FOR 30% OR MORE OF THE
 BUILDING. AS THE SCOPE OF WORK DOES NOT MEET THIS
 PLEASE MEET PRESCRIPTIVE AS STATED.
 THE PREVIOUS METHOD B FLA-COM WAS GIVEN BACK AS N/A.
 THE TYPE IS ALSO SHOWN AS RETAIL WHICH THIS SPACE IS
 NOT. PLEASE SEE TABLE B, TABLE C FOR USE.
  
 ** A CALL WAS PLACED AND A MESSAGE WAS LEFT ON THE
 ANSWERING MACHINE OF THE ENGINEER.
  
 ** SEE PREVIOUS NOTES WHICH WERE THE SAME. ONCE
 CALCULATIONS HAVE BEEN ADDRESSED THE REVIEW OF PLANS
 AND CALCULATIONS WILL BE COORDINATED. REVIEW WILL THEN
 GO INTO A FINAL PASSED STATUS WITHOUT ANY OUTSTANDING
 COMMENTS.
  
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 11 Status F Date 2008-11-24 Cont ID  
Sent By dpalmer Date 2008-11-24 Time 15:28 Rev Time 0.00
Received By dpalmer Date 2008-11-24 Time 15:28 Sent To PC
Notes
2008-11-24 15:28:49** REVISION FAILED **
  
  
  
 1) NOTE: PLEASE SUBMIT UPDATED FIXTURE LEGEND FOR FINAL
 FIXTURES. PLEASE SUBMIT UPDATED REVISED LIGHTING
 PERFORMANCE CALCULATIONS BASED ON TABLES *B* OR *C*
 WITH EXCEPTIONS.
 13-415.2,13-415.2.B, 13-415.2.C
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2008-08-01 Cont ID  
Sent By dpalmer Date 2008-08-01 Time 10:50 Rev Time 0.00
Received By dpalmer Date 2008-08-01 Time 10:50 Sent To B
Notes
2008-08-01 10:52:00LIGHTING SHOWN ON FLA COM B ONLY FOR PERFORMANCE FOR
 13-415.2 AS THE DEFININTION DOES NOT MEET RENOVATION OF
 BUILDING PER 13-101.1.

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2008-07-30 Cont ID  
Sent By dpalmer Date 2008-07-30 Time 09:41 Rev Time 0.00
Received By dpalmer Date   Time   Sent To PC
Notes
2008-07-30 09:43:03PLANS TEMP FAILED AS THE PREVIOUS ELECTRICLA REVISIONS
 NEED TO COME BACK INTO OFFICE SO THE CALCULATIONS MAY
 BE COMPARED TO THE PLANS.
 CALLED JOHN SATEU AND LEFT MESSAGE. CALCS ARE UNDER "C"
 (LARGE BINS ON HOLD.

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2008-07-03 Cont ID  
Sent By dpalmer Date 2008-07-03 Time 13:25 Rev Time 0.00
Received By dpalmer Date 2008-07-03 Time 13:25 Sent To  
Notes
2008-07-03 13:26:05** DENIED **
  
 1) NOTE: ELECTRICAL PLANS ARE OK, HOWEVER THE PREVIOUS
 REVISED ENERGY CALCULATIONS WERE NOT IN SETS OR
 ATTACHED TO PLANS. CALLED AND SPOKE TO CONTRACTOR.
 WILL NEED REVISED CALCULATIONS TO BE SUBMITTED AT A
 LATER DATE.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2008-06-03 Cont ID  
Sent By dpalmer Date 2008-06-03 Time 14:29 Rev Time 0.00
Received By dpalmer Date 2008-06-03 Time 14:29 Sent To PC
Notes
2008-06-03 14:32:58**DENIED **
  
 1) NOTE:PREVIOUS ELECTRICAL PLANS WERE BROUGHT BACK AND
 RETIANED ELECTRICLA COPY FOR FILE SET.
  
 2) NOTE: PLEASE SEE ENERGY CALCULATIONS SUBMITTED STILL
 DO NOT CONTAIN ANY SIGNATURE BY OWNER AGENT AS
 PREVIOUSLY NOTED.
 PLEASE BE SURE ALL BUILDING COMPONENTS COORDINATE WITH
 AND SUBMITTED REVISED CALCULATIONS BEFORE FINALS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2008-03-24 Cont ID  
Sent By dpalmer Date 2008-03-24 Time 16:50 Rev Time 0.00
Received By dpalmer Date 2008-03-24 Time 16:50 Sent To  
Notes
2008-03-24 16:50:44** DENIEDREVIEW **
  
  
 1) NOTE:REVISED ENERGY CALCULATIONS ARE UNDER
 INCORRECT VERSION AS ADOPTED UNDER CODE IN AFFECT AT
 TIME OF PERMIT APPLICATION.
 PLEASE SEE 13-400.3.B BEFORE THE 2006 REVISIONS TO THE
 2004 FBC. (VERSION 2.11).
 ** PLEASE ALSO BE SURE THE ENGINEER SIGNS AND SEALS THE
 CERTIFICATION SHEET AND THE OWNER AGENT SIGNATURE IS ON
 THESE SAME SHEETS.
  
 ** PLEASE NOTE: THE ELECTRICAL PLANS ARE OK AND HAVE
 BEEN STAMPED. PLEASE BE SURE TO BRING BACK STAMPED
 ELECTRICAL SHEETS WHEN RESUBMITTING.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-12-03 Cont ID  
Sent By dpalmer Date 2007-12-03 Time 18:50 Rev Time 0.00
Received By dpalmer Date 2007-12-03 Time 18:50 Sent To  
Notes
2007-12-03 18:51:33SCOPE OF WORK CHANGED, DELETED NIGHT CLUB AREA ON THE
 2ND FLR WEST SIDE.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-09-15 Cont ID  
Sent By dpalmer Date 2007-09-15 Time 08:05 Rev Time 0.00
Received By dpalmer Date 2007-09-15 Time 08:05 Sent To  
Notes
2007-09-15 08:07:242007-09-15 08:07:24
  
 PLANS STAMPED,BOTH NORTH STAIR TOWERS AREUNDER
 SEPARATE PERMIT FOR EGRESS ON THE NORTH SIDE OF
 BUILDING.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-06-20 Cont ID  
Sent By dpalmer Date 2007-06-20 Time 20:23 Rev Time 0.00
Received By dpalmer Date 2007-06-19 Time 19:49 Sent To  
Notes
2007-06-20 20:23:512007-06-20 20:23:51
  
 ** HOLD REMOVED**
  
 *** UNSAT 3RD REVIEW ***
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC
 CHAPTER 13 HAS NOT BEEN ACHIEVED ON PLANS FOR CODE
 COMPLIANCE. PLEASE SEE PLANS NOW INDICATE LIGHTING
 CONTROLS THROUGH-OUT BUILD OUT HOWEVER NO TIMES ON
 DEVICES IS NOTED OR SHOWN. PLEASE SEE THE TYPE OF
 DEVICES AS LISTED DOES NOT SHOW UP ON THE MANUFACTURES
 WEBSITE FOR THE DEVICE AS LISTED ON LEGEND. NO
 INFORMATION COULD BE LOCATED ON THESE. PLEASE SEE THE
 COMPLETE LIST OF DEVICES PRINTED OUT ON ATTACHED SHEETS
 FROM MANUFACTURE WHICH DOES NOT COORDINATE WITH THE
 DEVICES AS NOTED. PLEASE PROVIDE INFORMATION ON DEVICES
 AS NOTED.
 PLEASE SEE NO COVERAGE FOR CONTROL OF EGRESS LIGHTING
 FROM SECOND FLOOR. SEE ELECTRICAL COMMENT WITH RESPECT
 TO THE LIFE SAFETY METHODS OF CONTROL REQUIRED. PLEASE
 SEE THE AREAS WHICH THESE DEVICES ARE BEING PLACED IN
 MANY LOCATIONS ARE IN QUESTION. PLEASE SEE BATHROOMS AS
 SEPARATE SPACES MAY NOT HAVE THE COVERAGE NEEDED. MORE
 INFORMATION ON TYPES OF DEVICES AND MAXIMUM TIMES ON
 ARE NEEDED.
 PLEASE PROVIDE DETAIL FOR EMERGENCY/EXIT LIGHTING AS
 THESE ARE SHOWN ON THE SAME CONTROL OF DIMMERS OR
 SWITCHES. NOTE OR DETAIL THESE ON THE HOT/LINE SIDE OF
 THESE CONTROLS.
 PLEASE SEE THE ENERGY CALCULATIONS AS THE FIXTURES,
 TYPES, AND WATTAGE DO NOT CORRELATE WITH PLANS AND
 FIXTURE LEGEND.
 PLEASE SEE 13-415.1.ABC.1.1,.1.2, 13-415.1.AB.1.1.
 **PLEASE SEE THE OWNER AGENT IS NOT SIGNED ON ENERGY
 CALCULATION SHEETS AS REQUIRED.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS WHICH
 REQUESTED PHOTO-METRICS FOR ALL EGRESS PATHS BASED ON
 NEW CHANGE IN OCCUPANCY. PLEASE SEE THERE ARE STILL
 STAIR AREAS WHICH DO NOT CONTAIN ANY LIGHTING
 PHOTO-METRICS. THESE HAVE BEEN REDLINED ON PLANS.
 PLEASE SEE E-5 WHERE THE DETAILS ON THE LOWER RIGHT
 HAND SIDE SHOW BOTH DETAILS AS ENTRY STAIRS NORMAL?
 PLEASE SEE AREA WHICH EXITS INTO THE EXISTING AREA
 WHICH IS SHOWING OCCUPANCY TYPE DEVICES LOCATED AT THE
 UPPER LEVEL HOWEVER NOT METHOD OF CONTROL FOR THE
 LIGHTING ON STAIRS FROM LOWER LEVEL OR IN STAIR AREA.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2, 7.8.1.2.2, FBC
 CHAPTER 10, 1006.1.2.
  
 3) NOTE: PLEASE SEE THE REVISED RISER WHICH INDICATES
 THE SAME CONDUCTORS BEING TAPPED FROM GUTTER TO THE NEW
 MAIN WHICH ARE BEING SHOWN AS RATED 800AMPS INTO A NEW
 600AMP MAIN? PLEASE CLARIFY THE SIZES INTO THIS MAIN
 AND REVISE CONDUCTORS AT THIS TIME IF NEED. THE LARGER
 CONDUCTORS ARE NOT A CODE VIOLATION BUT MAY NOT FIT.
 PLEASE ALSO CLARIFY THE EXISTING SERVICE ENTRANCE
 CONDUCTOR SIZES FROM OUTSIDE INTO GUTTER.
 310.16, 240.4
  
 4) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS WITH
 RESPECT TO MINIMUM HEAD ROOM CLEARANCE FOR DETAIL SHOWN
 ON E-5 FOR STAIRWAY. DETAIL SHOWS 76 INCHES WHICH DOES
 NOT SEEM TO MEET BUILDING CODE.
  
 5) NOTE: PLEASE SEE THE PLANS INDICATE NEW SUITE
 NUMBERS FOR NEW TENANT SPACES HOWEVER THIS IS ACTUALLY
 BEING MADE AND ADDED INTO THE SAME EXISTING TENANT
 SPACE AS THE FIRST FLOOR SUITE 104. NEW EXTENSIONS FOR
 ADDRESS WAS GIVEN AND TITLE BLOCKS INDICATE THIS AS
 SEPARATE TENANT SPACES, HOWEVER THIS IS NOT POSSIBLE
 WHEN THERE IS NO TENANT SEPARATION FROM THE FIRST FLOOR
 EXISTING TENANT AREA.
  
 6) NOTE: PLEASE SEE THE VALUATION WAS INCREASED AND
 ADDITIONAL FEES ARE OWED.
  
 7) NOTE: PLEASE SEE PREVIOUS REVIEW A NOTICE WAS GIVEN
 WITH RESPECT TO CODE COMPLIANT COMMENTS BEING REPEATED
 PER FS 553.80(2)(B). PLANS ARE BEING RETAINED AND THE
 PLANS, ENERGY CALCULATIONS, AND REVIEW NOTES WILL BE
 GONE OVER AS CODE COMPLIANCE HAS NOT BEEN MET FOR THE
 THIRD REVIEW. PENDING PIER REVIEW A 4X FEE FOR THE PLAN
 REVIEW PORTION OF THE PERMIT FEE MAY BE ASSESSED TO THE
 DESIGNER OF RECORD AS REQUIRED BY THE FLORIDA
 STATUTES.
  
 THIS FEE HAS NOT YET BEEN ASSESSED AND IT NOT THE
 RESPONSIBILITY OF THE OWNER OR CONTRACTOR OF RECORD.
  
 ** AS STATED ON ALL PREVIOUS REVIEWS, PLEASE CALL TO GO
 OVER ANY COMMENTS, IF THERE ARE ANY QUESTIONS OR IF THE
 COMMENTS AS TYPED ARE NOT UNDERSTOOD.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
2007-06-20 09:29:362007-06-20 09:29:36
 ** ON HOLD **
  
 A MESSAGE WAS LEFT ON VOICE MAIL OF MR. JOHN SATEU OF
 CASTLE CONSTRUCTION FOR UPDATED VALUATION TO BE GIVEN
 BEFORE REVIEW CAN BE DONE.
 THIS WAS REQUESTED ON TWO PREVIOUS REVIEWS AND NO
 INFORMATION AND/OR CHANGES WERE MADE TO PERMIT
 APPLICATION.PLEASE SEE FBC 108.3 VALUE SHALL INCLUDE
 ALL LABOR, MATERIALS, EQUIPMENT, DESIGN ARCHITECT AND
 ENGINEERING COSTS EVEN IF ANY OF THIS IS OWNER
 SUPPLIED.
 PLANS ARE ON HOLD IN ELECTRICAL FOR REVIEW.
 IF A VALUE IS NOT PROVIDED, ONE WILL BE ASSESSED BASED
 ON PLANS AND VALUATION TABLES IN THE FBC AND ADOPTED
 REFERENCES FOR VALUATION GUIDES.
  
 IF THERE ARE ANY QUESTIONS PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH.
 561-805-6717

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-12-23 Cont ID  
Sent By dpalmer Date 2006-12-23 Time 13:15 Rev Time 0.00
Received By dpalmer Date 2006-12-21 Time 20:47 Sent To  
Notes
2006-12-23 13:17:47** UNSAT 2ND REVIEW **
  
 ** A FIELD MEETING WITH THE CONTRACTOR/ARCHITECT SHALL
 BE SCHEDULE AT THE EARLIEST POSSIBLE TIME TO VISIT
 SITE. THERE ARE SOME AREAS OF CONCERN WITH THE CREATION
 ONE NEW SPACE AND ADJOINING THE EXISTING SPACE TO
 BUILDING ADJACENT.
  
 THERE MAY ALSO BE ELECTRICAL COMMENTS TO FOLLOW AFTER
 FIELD MEETING IS HELD.
 PLEASE CONTACT THIS OFFICE AS SOON AS POSSIBLE TO SET
 UP A TIME. IF POSSIBLE BEFORE THE NEW YEAR. 26TH -28TH
 OF DECEMBER. THIS WILL HELP IN THE REVIEW OF SAID PLANS
 AND TO CLERIFY ITEMS AS SHOWN ON PLANS.
  
 ** PLEASE SEE NOTES BELOW ARE TAKEN DIRECTLY FROM THE
 PREVIOUS REVIEW WITH A NO OR OK FOR THE SAME NUMERICAL
 DESIGNATION AS PREVIOUS REVIEW. PLEASE SEE SOME MAY
 CONTAIN A NO/OK, AS PART OF A COMMENT MAY HAVE BEEN
 ADDRESSED HOWEVER NOT FULLY.
  
 ** PLEASE SEE ANY NEW COMMENTS BASED ON PLANS SUBMITTED
 MAY BE AT THE END OF THE PREVIOUS REVIEW NOTES.
  
  
  
  
 1) NOTE: OK.
  
 2) NOTE: NO. PLEASE KNOW BASED ON WORK AS SHOWN AND
 WILL BE REQUIRED THE VALUE IS SUBSTANTIALLY LOW AND ONE
 WILL BE ASSESSED IF NOT ADJUSTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK SHALL BE
 BASED ON ALL LABOR AND MATERIALS EVEN IF ANY MATERIALS
 ARE OWNER SUPPLIED. PLEASE KNOW, WHEN A VALUE IS LOW,
 ONE WILL BE ASSESSED PER FBC 108.3 USING THE
 MARSHALL'S& SWIFT
 GUIDE AS ADOPTED BY THE FLORIDA BUILDING CODE.
  
 3) NOTE:NO, PLEASE SEE THE OVERVIEW FOR THE CONDUITS
 BEING ENCASED DOES NOT PROVIDE THE DETAIL AS NEED FOR
 ALL CLEARANCES ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE BUILDING REVIEW NOTES AS 2ND FLOOR GARAGE
 DOOR.
 PLEASE SEE EXIT STAIRS MENTIONS TO ENCASED CONDUIT
 COMING IN THROUGH STAIRS, MUST PROVIDE COMPLETE
 ARCHITECTURAL DETAIL FOR DEPTH, DISTANCES, HEADROOM
 ETC.
 PLEASE ALSO SEE NO MORE THAN 8' OF UNDER PROTECTED
 CONDUCTORS ARE PERMITTED INSIDE THE BUILDING. THIS MAY
 ALSO INCLUDE ENCASEMENT OF CONDUITS IN MAIN ELECTRICAL
 ROOM.
 PLEASE SEE 230.70, 240.6
  
 4) NOTE: NO, PLEASE KNOW AT THIS TIME THE NEW PROPOSED
 SERVICE IS NOT GRANTED BY SPECIAL PERMISSION AS
 REQUIRED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE SIZES AND VOLTAGES FOR ALL EXISTING
 SERVICES.
 PLEASE SEE 230.2 AS AT THIS TIME THIS NEW SERVICE IS
 NOT GRANTED. AS PLANS SHOW, THIS SEEMS BE ADDING
 ADDITIONAL SERVICES WHERE NOT ALL INFORMATION IS
 PROVIDED TO POSSIBLY GRANT ANY SPECIAL PERMISSION.
  
 5) NOTE: NO, PLEASE SEE ENERGY CALCULATIONS STILL
 INDICATE MANUAL CONTROLS.
 PLEASE SEE NO SYSTEM IS BEING SHOWN IN DETAIL.
 PLEASE SEE NO TIMES FOR SCHEDULING.
 PLEASE SEE NO TIMES ON OVER RIDE DEVICES REQUIRED.
 PLEASE SEE NO DEVICES LOCATED IN SEPARATE SPACES.
 PLEASE SEE SECTIONS AS GIVEN IN PREVIOUS REVIEW.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1, .1.2,
 .1.3,.
 PLEASE SEE 13-415.1.B, 13-415.2,
 13-415.2.ABC.1, TABLES 415.2.C.1,
 415.2. B.1
 PLEASE COMPLY WITH THIS.
  
 6) NOTE: OK/NO, PLEASE SEE ADDRESSING ON SOME SHEETS DO
 NOT CORRELATE.
 PLEASE SEE E-4.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE ALL SUITE NUMBERS ON TITLE BLOCKS ON
 PLANS AS REQUIRED ON ALL SHEETS.
 FAC 61G1-16.004, 61G15-23.002
  
 7) NOTE: NO, NO INFORMATION SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2, AS A MIN OF 10FT
 CANDLES IS REQUIRED UNDER NORMAL AND 1FT CANDLE MIN
 UNDER EM PWR.
 PLEASE PROVIDE LIGHTING LEVELS.
  
 8) NOTE:NO/OK, SOME SHOWN, HOWEVER AS LIGHTING LEVELS
 HAVE NOT BEEN PROVIDED ADDITIONAL FIXTURES MAY BE
 REQUIRED.
  
 ** PREVIOUS REVIEW NOTE **
 ALONG WITH NOTE #7 ABOVE PLEASE INDICATE ALL EXISTING
 OTHER EMERGENCY LIGHTING AND EXIT LIGHTING AS THIS
 SPACE IS BEING INTRODUCED INTO THE 2ND FLR AND IF
 EXISTING DOES NOT MEET CODE, THEN THEY WILL BE
 REQUIRED.
 LS 101 7.8, 7.9, 700.12E.
  
 9) NOTE: NO, PLEASE SEE ONLY TWO ITEMS ON ONE PANEL ARE
 BEING NOTED FOR THIS. PLEASE SEE ALL CONTINUOUS SHALL
 BE INDICATED AS SUCH.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE ALL CONTINUOUS LOADS AT 125% 215.3,
 230.42 ETC.
  
 10) NOTE: NO, PLEASE KNOW BASED ON THE LAYOUT FOR
 SPACES AND WHICH TENANT IS WHICH AND REQUIRED
 SEPARATION REQUIREMENTS, THERE MAY BE OTHER ELECTRICAL
 WHICH WILL NEED TO BE SHOWN. PLEASE KNOW BASED ON SITE
 MEETING AND NOTES ABOVE, THE SERVICE AND EQUIPMENT AS
 SHOWN IS NOT YET GRANTED OR APPROVED FOR REVIEW.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE ALL ELECTRICAL PANELS ON POWER PLANS.
  
 11) NOTE: OK.
  
 12) NOTE: NO/OK. SOME ITEMS CAN NOT BE VERIFIED FOR
 CODE COMPLIANCE AT THIS TIME. PLEASE KNOW SINCE NOTED
 ABOVE FOR A REQUIRED SITE MEETING THERE MAY BE CHANGES
 WHICH WILL AFFECT THE ELECTRICAL PLANS AS SHOWN.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE BLDG REVIEW COMMENTS AS DOOR FROM MAIN
 ELECTRICAL ROOM IS SHOWN IMPEDING THE EGRESS OF
 OCCUPANTS. PLEASE SEE THE DOOR REQUIREMENTS MAY
 CHANGE.
  
 13) NOTE: NO. SAME NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PANEL SCHEDULE SHALL BE SPECIFIC TO ROOMS
 AND AREAS IN WHICH LTS AND RECEPTS FEEDS. IE; BATH LTS,
 POOL AREA ETC.
 ** IT IS KNOWN, THAT THESE WILL MOST LIKELY CHANGE
 DURING THE CONSTRUCTION.
  
 ** NEW NOTE **
  
 1) NOTE: PLEASE INDICATE ALL LIGHTING AND SOUND LEVELS
 FOR FIRE HORN AND STROBE DEVICES. PLEASE SEE FBC
 11-4.28.1, .2, .3(4). THIS HAS NOW BECOME A REQUIREMENT
 FOR ELECTRICAL PLAN REVIEW.
 PLEASE INDICATE BASE REQUIRED SYSTEM AND SUBMIT PLANS.
 FBC 106.3.5.1.1 ADMIN SECTION
  
 2) NOTE: PLEASE KNOW DUE TO SOME AREAS OF CONCERN ON
 PLANS NOT YET CLEAR FOR REVIEW, THERE MAY BE FURTHER
 COMMENTS.
  
 3) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-12-21 20:48:00IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-29 Cont ID  
Sent By dpalmer Date 2006-09-29 Time 19:52 Rev Time 0.00
Received By dpalmer Date 2006-09-29 Time 11:45 Sent To  
Notes
2006-09-29 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE ALL OF THE FOLLOWING
 RELEVANT CODES IN EFFECT SHALL BE STATED
 ON PLANS.
 2002 NFPA-70(NEC), 2002 NFPA-72, 2003
 NFPA-101 AND 2004 FBC.
  
  
 2)PLEASE SEE VALUE FOR COMPLETE SCOPE OF
 WORK SHALL BE BASED ON ALL LABOUR AND
 MATERIALS EVEN IF ANY MATERIALS ARE
 OWNER SUPPLIED. PLEASE KNOW, WHEN A
 VALUE IS LOW, ONE WILL BE ASSESSED PER
 FBC 108.3 USING THE MARSHALL'S& SWIFT
 GUIDE AS ADOPTED BY THE FLORIDA BUILDING
 CODE.
  
 3) NOTE: PLEASE SEE BUILDING REVIEW
 NOTES AS 2ND FLR GARAGE DOOR.
 PLEASE SEE EXIT STAIRS MENTIONS TO
 ENCASED CONDUIT COMING IN THROUGH
 STAIRS, MUST PROVIDE COMPLETE
 ARCHITECTURAL DETAIL FOR DEPTH,
 DISTANCES, HEADROOM ETC ETC.
 PLEASE ALSO SEE NO MORE THAN 8' OF UNDER
 PROTECTED CONDUCTORS ARE PERMITTED
 INSIDE THE BUILDING. THIS MAY ALSO
 INCLUDE ENCASEMENT OF CONDUITS IN MAIN
 ELECTRICAL ROOM.
 PLEASE SEE 230.70, 240.6
  
 4) NOTE: PLEASE PROVIDE SIZES AND
 VOLTAGES FOR ALL EXISTING SERVICES.
 PLEASE SEE 230.2 AS AT THIS TIME THIS
 NEW SERVICE IS NOT GRANTED. AS PLANS
 SHOW, THIS SEEMS BE ADDING ADDITIONAL
 SERVICES WHERE NOT ALL INFORMATION IS
 PROVIDED TO POSSIBLY GRANT ANY SPECIAL PERMISSION.
  
 5) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1,
 .1.2, .1.3,.
 PLEASE SEE 13-415.1.B, 13-415.2,
 13-415.2.ABC.1, TABLES 415.2.C.1,
 415.2.B.1
 PLEASE COMPLY WITH THIS.
  
 6) NOTE: PLEASE INDICATE ALL SUITE
 NUMBERS ON TITLE BLOCKS ON PLANS AS
 REQUIRED ON ALL SHEETS.
 FAC 61G1-16.004, 61G15-23.002
  
 7) NOTE: PLEASE SEE NFPA-101 7.8.1.3,
 7.9.2.2, AS A MIN OF 10FT CANDLES IS
 REQUIRED UNDER NORMAL AND 1FT CANDLE MIN
 UNDER EM PWR.
 PLEASE PROVIDE LIGHTING LEVELS.
  
 8)NOTE: ALONG WITH NOTE #7 ABOVE PLEASE
 INDICATE ALL EXISTING OTHER EMERGENCY
 LIGHTING AND EXIT LIGHTING AS THIS SPACE
 IS BEING INTRODUCED INTO THE 2ND FLR AND
 IF EXISTING DOES NOT MEET CODE , THEN
 THEY WILL BE REQUIRED.
 LS 101 7.8, 7.9, 700.12E.
  
 9) NOTE: PLEASE INDICATE ALL CONTINUOUS
 LOADS AT 125% 215.3, 230.42 ETC.
  
 10) NOTE: PLEASE INDICATE ALL
 ELECTRICAL PANELS ON POWER PLANS.
  
 11) NOTE: PLEASE CLARIFY LIGHTING FOR
 MAIN ELECTRICAL ROOM. IS THIS ROOM ON
 THE FIRST FLR? PLEASE KNOW, IF AN EM
 BACK UP LT IS NOT EIXSITING, ONE WILL BE
 REQUIRED FOR LIFE SAFTEY AND FIRE DEPT
 PERSONEL.
 LS101 7.8, 7.9, 700.12E.
  
 12) NOTE: PLEASE SEE BLDG REVIEW
 COMMENTS AS DOOR FROM MAIN ELECTRICAL
 ROOM IS SHOWN IMPEDING THE EGRESS OF
 OCCUPANTS. PLEASE SEE THE DOOR
 REQUIREMENTS MAY CHANGE.
  
 13) NOTE: PLEASE SEE PANEL SCHEDULE
 SHALL BE SPECIFIC TO ROOMS AND AREAS IN
 WHICH LTS AND RECEPTS FEED.
 IE; BATH LTS, POOL AREA ETC.
 ** IT IS KNOWN, THAT THESE WILL MOST
 LIKELY CHANGE DURING THE CONSTRUCTION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 10 Status P Date 2009-07-28 Cont ID  
Sent By mwennerg Date 2009-07-28 Time 11:03 Rev Time 0.00
Received By mwennerg Date 2009-07-28 Time 11:03 Sent To  
Notes
2009-07-28 11:05:27REVISION D & E FOR SHEETS A-1, A-3, A-4 & A-5.

Review Stop FIRE FIRE DEPARTMENT
Rev No 9 Status F Date 2009-02-17 Cont ID  
Sent By mwennerg Date 2009-02-17 Time 15:28 Rev Time 0.00
Received By mwennerg Date 2009-02-17 Time 15:28 Sent To  
Notes
2009-02-17 15:30:45***DENIED***
  
 1) PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENT FOR
 HANDRAILS AND GUARDRAILS.
  
 2) SEE BUILDING REVIEW COMMENTS REGARDING FS
 REQUIREMENTS FOR PLANS.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status P Date 2008-07-11 Cont ID  
Sent By mwennerg Date 2008-07-11 Time 13:35 Rev Time 0.00
Received By mwennerg Date 2008-07-11 Time 13:35 Sent To  
Notes
2008-07-11 13:36:07REVISION C DATED 5/12/08

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2008-06-03 Cont ID  
Sent By mawillia Date 2008-06-02 Time 14:59 Rev Time 0.00
Received By mawillia Date 2008-06-02 Time 13:54 Sent To  
Notes
2008-06-02 14:08:15*****REVSION #B, DATED 4/15/08, APPROVED*****
  
 REVISED PLAN SHEET A-4 STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status F Date 2008-04-23 Cont ID  
Sent By mawillia Date 2008-04-23 Time 14:15 Rev Time 0.00
Received By mawillia Date 2008-04-16 Time 15:54 Sent To  
Notes
2008-04-23 13:33:53*****UNSAT*****
  
 1.WHERE IS THE REVISION (AS INDICATED BY CLOUDING)
 FOR THE LIFE SAFETY PLAN (SHEET A-4) ?
  
 2.THE APPROPIATE REVISED PLAN SHEETS TO BE
 FIRE-STAMPED WHEN THE OTHER PLAN REVIEWERS HAVE BEEN
 SATISFIED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-12-26 Cont ID  
Sent By mawillia Date 2007-12-26 Time 17:01 Rev Time 0.00
Received By mawillia Date 2007-12-26 Time 16:24 Sent To  
Notes
2007-12-26 17:01:14***** REVISION APPROVED*****
  
  
 REVISED PLAN SHEETS E-2 AND FP-2 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-10-23 Cont ID  
Sent By mawillia Date 2007-10-23 Time 09:44 Rev Time 0.00
Received By mawillia Date 2007-10-23 Time 09:19 Sent To  
Notes
2007-10-23 09:44:00*****APPROVED*****
  
  
 PLAN SHEETS A-5, E-2, E-4, FP-1, AND FP-2 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-07-24 Cont ID  
Sent By mwennerg Date 2007-07-24 Time 09:59 Rev Time 0.00
Received By mwennerg Date 2007-07-24 Time 09:59 Sent To  
Notes
2007-07-24 10:48:38***DENIED***
  
 1) OK
  
 2) OK
  
 3) OK
  
 4) OK
  
 5) OK
  
 6) OK
  
 7) OK
  
 8) OK
  
 9) OK
  
 10) PLEASE NOTE THAT ONLY ELECTRICAL CONDUIT THAT
 SERVES THAT PARTICULAR STAIRWAY WOULD BE ALLOWED WITHIN
 THE EXIT ENCLOSURE.
  
 11) OK
  
 12) OK
  
 13) OK
  
 14) OK
  
 15) OK
  
 16) OK
  
 17) OK
  
 18) OK
  
 19) OK
  
 NEW COMMENT:
  
 1) THE MINIMUM HEADROOM REQUIREMENT FOR NEW AND
 EXISTING STAIRS IS EIGHTY (80") IN ACCORDANCE WITH NFPA
 101.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-12-29 Cont ID  
Sent By mawillia Date 2006-12-29 Time 15:32 Rev Time 0.00
Received By mawillia Date 2006-12-29 Time 15:31 Sent To  
Notes
2006-12-29 15:36:59*****DENIED*****
  
  
 INCOMPLETE RESPONSE SHEET TO FIRE PLAN REVIEW COMMENTS
 OF 10-20-2006.TO EXPEDITE THE PLAN REVIEW PROCESS
 WHEN RESUBMITTING, INCLUDE A RESPONSE LETTER INDICATING
 HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-20 Cont ID  
Sent By mwennerg Date 2006-10-20 Time 12:39 Rev Time 0.00
Received By mwennerg Date 2006-10-20 Time 12:39 Sent To Z
Notes
2006-10-20 13:08:19***DENIED***
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003
 EDITION.
  
 2) KNOX BOX APPLICATIONS MAY BE OBTAINED AT THE BUREAU
 OF FIRE PREVENTION, (561) 804-4724.
  
 3) FIRE EXTINGUISHERS SHALL BE 2A-10B,C RATED AND
 MOUNTED MOUNTED NOT TO EXCEED 75' TRAVEL DISTANCE.
  
 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 5) ALL EXIT DOORS AND DOORS THAT ARE PART OF THE
 REQUIRED MEANS OF EGRESS SHALL SWING IN THE DIRECTION
 OF TRAVEL.
  
 6) PLEASE PROVIDE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS IN ACCORDANCE
 WITH NFPA 101, CHAPTER 10.
  
 7) OCCUPANT LOAD SIGNS WILL BE REQUIRED PRIOR TO FIRE
 FINAL.
  
 8) STAIS SHALL COMPLY WITH NFPA 101, SECTION 7.2.2.2.1
 (A).
  
 9) NO COMBUSTIBLE PERMITTED ABOVE CEILING IF BEING USED
 AS RETURN AIR PLENUM.
  
 10) PENETRATIONS AND OPENINGS ARE PROHIBITED INTO EXIT
 ENCLOSURES UNLESS PERMITTED IN NFPA 101, SECTION
 7.1.3.2.1 (6). PLEASE SEE CONDUITS THROUGH EXIT STAIRS
 ON SHEET E-1.
  
 11) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. SHT E-3 FA
 NOTE (7)
  
 12) SEPARATE SHOP DRAWINGS AND PERMITS IN ADDITION TO
 FIRE SPRINKLER REMODEL WILL BE REQUIRED FOR FIRE ALARM
 SYSTEM.
  
 13) PLEASE PROVIDE MORE INFORMATION IN REFERENCE TO
 PROPOSED VOICE ALARM. (MESSAGE)
  
 14) HANDRAILS ARE REQUIRED FOR BOTH SIDES OF STAIRS.
  
 15) PLANS DON'T SHOW A SMOKE DETECTOR IN ELEVATOR
 LOBBY. E SHEETS
  
 16) AN EXIT SIGN IS SHOWN ON E-2 DIRECTING PERSONS FROM
 VESTIBULE 100. FROM THAT POINT IT IS UNCLEAR WHERE
 PERSONS CONTINUE TO EXIT.
  
 17) THERE APPEARS TO BE AN EXIT SIGN MISSING IN
 ELEVATOR 111. SHT E-2
  
 18) PLEASE CLEARLY ILLUSTRATE THE DOOR SWING OR
 OPERATION OF THE REPAIR OR REPLACE METAL CLAD 90 MIN
 DOOR BETWEEN SUITES 201 AND 202.
  
 19) WHERE DO PERSONS EXIT AFTER THEY ENTER THE EXIT
 ENCLOSURE ASSEMBLIES? PLEASE SHOW EXIT DISCHARGE AS IT
 RELATES TO THIS PROJECT.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2009-07-15 Cont ID  
Sent By shill Date 2009-07-15 Time 09:41 Rev Time 0.00
Received By shill Date 2009-07-15 Time 09:41 Sent To  
Notes
2009-07-15 09:43:50C28
  

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2009-01-26 Cont ID  
Sent By adarroug Date 2009-01-26 Time 10:17 Rev Time 0.00
Received By adarroug Date 2009-01-26 Time 10:17 Sent To  
Notes
2009-01-26 10:20:27TO "COMM" BD#21

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-12-12 Cont ID  
Sent By shill Date 2008-12-12 Time 08:34 Rev Time 0.00
Received By shill Date 2008-12-12 Time 08:34 Sent To E
Notes
2008-12-12 08:34:43TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-11-17 Cont ID  
Sent By adarroug Date 2008-11-17 Time 14:49 Rev Time 0.00
Received By adarroug Date 2008-11-17 Time 14:49 Sent To E
Notes
2008-11-17 14:50:16TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-07-11 Cont ID  
Sent By adarroug Date 2008-07-11 Time 14:50 Rev Time 0.00
Received By adarroug Date 2008-07-11 Time 14:50 Sent To E
Notes
2008-07-11 14:51:14TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-06-12 Cont ID  
Sent By adarroug Date 2008-06-12 Time 09:34 Rev Time 0.00
Received By adarroug Date 2008-06-12 Time 09:34 Sent To  
Notes
2008-06-12 09:34:27TO "COMM" BD#25

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-05-07 Cont ID  
Sent By adarroug Date 2008-05-07 Time 14:14 Rev Time 0.00
Received By adarroug Date 2008-05-07 Time 14:14 Sent To  
Notes
2008-05-07 14:20:38TO "COMM" BD#25

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-04-03 Cont ID  
Sent By adarroug Date 2008-04-03 Time 13:27 Rev Time 0.00
Received By adarroug Date 2008-04-03 Time 13:27 Sent To B
Notes
2008-04-03 13:28:49TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-03-21 Cont ID  
Sent By adarroug Date 2008-03-21 Time 13:01 Rev Time 0.00
Received By adarroug Date 2008-03-21 Time 13:01 Sent To  
Notes
2008-03-21 13:01:56TO "COMM" BD#1

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-01-31 Cont ID  
Sent By adarroug Date 2008-01-31 Time 12:21 Rev Time 0.00
Received By adarroug Date 2008-01-31 Time 12:21 Sent To P
Notes
2008-01-31 12:21:36TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-11-28 Cont ID  
Sent By adarroug Date 2007-11-28 Time 11:36 Rev Time 0.00
Received By adarroug Date 2007-11-28 Time 11:36 Sent To  
Notes
2007-12-03 08:35:43TO "COMM" BD#24
2007-11-28 11:37:04WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-24 Cont ID  
Sent By adarroug Date 2007-08-24 Time 15:22 Rev Time 0.00
Received By adarroug Date 2007-08-24 Time 15:22 Sent To  
Notes
2007-09-15 07:57:41TO COMM BOARDSPACE #46
2007-08-24 15:22:55WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-29 Cont ID  
Sent By adarroug Date 2007-05-29 Time 11:22 Rev Time 0.00
Received By adarroug Date 2007-05-29 Time 11:22 Sent To  
Notes
2007-06-19 18:46:26 
  
 CORRECTION: ON COMM BD #5
2007-06-15 16:06:34TO "COMM" BD#54
2007-05-29 11:22:24WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-05 Cont ID  
Sent By adarroug Date 2006-12-05 Time 08:39 Rev Time 0.00
Received By adarroug Date 2006-12-05 Time 08:39 Sent To Z
Notes
2006-12-18 14:36:13TO "COMM" BD#10
2006-12-05 08:40:31WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-20 Cont ID  
Sent By mwennerg Date 2006-10-20 Time 13:10 Rev Time 0.00
Received By mwennerg Date 2006-09-13 Time 15:29 Sent To  
Notes
2006-09-13 00:00:00WAITING FOR "COMM" BD
 TO "COMM" BD#13

Review Stop L LANDSCAPING
Rev No 1 Status N Date 2008-12-24 Cont ID  
Sent By adarroug Date 2008-12-24 Time 10:15 Rev Time 0.00
Received By adarroug Date 2008-12-24 Time 10:15 Sent To E
Notes
2008-12-24 10:16:37TO "DPALMER" DESK/SUBMITTAL

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2008-08-21 Cont ID  
Sent By tgordon Date 2008-08-21 Time 08:29 Rev Time 0.40
Received By tgordon Date 2008-08-21 Time 08:29 Sent To  
Notes
2008-08-21 08:30:01REVISION TO MECH. PLAN M-1.

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2008-06-13 Cont ID  
Sent By tgordon Date 2008-06-13 Time 10:52 Rev Time 1.15
Received By tgordon Date 2008-06-13 Time 10:52 Sent To  
Notes
2008-06-13 10:52:51REVISION TO MECH. PLAN MM-1, M-2, AND M-3.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status N Date 2008-05-08 Cont ID  
Sent By tgordon Date 2008-05-08 Time 08:45 Rev Time 1.00
Received By tgordon Date 2008-05-08 Time 08:45 Sent To  
Notes
2008-05-08 08:52:44NO CHANGES TO MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-03-26 Cont ID  
Sent By tgordon Date 2008-03-26 Time 11:28 Rev Time 0.45
Received By tgordon Date 2008-03-26 Time 11:28 Sent To  
Notes
2008-03-26 11:28:57REVISION TO MECH. PLANS PAGE M-1 AND M-2.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-12-06 Cont ID  
Sent By tgordon Date 2007-12-06 Time 12:13 Rev Time 0.35
Received By tgordon Date 2007-12-06 Time 12:13 Sent To  
Notes
2007-12-06 12:14:18REVISION TO MECH. PLANS PAGES M-1 AND M-2.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-09-18 Cont ID  
Sent By tgordon Date 2007-09-18 Time 16:14 Rev Time 0.45
Received By tgordon Date 2007-09-18 Time 16:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-07-26 Cont ID  
Sent By hmoser Date 2007-07-26 Time 19:00 Rev Time 0.00
Received By hmoser Date 2007-07-26 Time 19:00 Sent To  
Notes
2007-07-26 18:58:23PLAN DENIED
 PLEASE PROVIDE RETURN AIR SIZE FOR THE NEW WALL ON THE
 PLANS.
 PLEASE PROVIDE DUCT AND GRILL SIZE ON ALL NEW DUCT AND
 GRILLS ON THE PLANS
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-12-19 Cont ID  
Sent By hmoser Date 2006-12-19 Time 18:09 Rev Time 0.00
Received By hmoser Date 2006-12-19 Time 17:01 Sent To  
Notes
2006-12-19 18:21:01PLAN DENIED
 1) PLEASE PROVIDE MANUFACTURERS INSTALLATION
 INSTRUCTIONS FOR EVR 1& 2.
 2) PLEASE PROVIDE A CURB TO ROOF TIE DOWN DETAIL ON
 PLANS.
 3) YOU CAN NOT USE GALVANIZED STRAP OVER THE RTU FOR
 TIE DOWN. SEE SECTION 306.5 EQUIPMENT AND APPLIANCES ON
 ROOFS FBC (M ) 2004
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
2006-12-19 18:10:44PLAN DENIED

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-14 Cont ID  
Sent By hmoser Date 2006-10-14 Time 08:27 Rev Time 0.00
Received By hmoser Date 2006-10-14 Time 07:11 Sent To  
Notes
2006-10-14 08:54:051)PLEASE PROVIDE MANUFACTURERS INSTALLATION
 INSTRUCTIONS FOR ERV #1 & #2 WITH PLANS.
 2)PLEASE PROVIDE A DETAIL ON THE CURB TO ROOF TIEDOWN
 ON THE PLANS.
 3)PLEASE PROVIDE A DETAIL ON RTU TO CURB TIEDOWN ON
 THE OPANS.
 4)PLEASE SHOW A CONTINUATION OF BATHROOM EXHAUST DUCT
 ON PLANS.
 5) PLEASE PROVIDE RETURN AIR SIZE AND CFM ON EXISTING
 20 TON EQUIPMENT.
 6) PLEASE REFER TO SECTION 306.4.1 SUPERVISON FBC (M)
 2004.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 9 Status P Date 2008-07-14 Cont ID  
Sent By kstevens Date 2008-07-14 Time 10:10 Rev Time 0.00
Received By kstevens Date 2008-07-14 Time 08:04 Sent To  
Notes
2008-07-14 10:19:37REVISIONS OK--SHTS P-1, P-2 & P-3--VENT LINE
 DOWNSTREAM OF ACCESSIBLE W/C IN MEN'S TOILET ROOM 105
 NOT APPLICABLE. SEE SHT P-3 SANT RISER DIAGRAM.
 (DELETED PER ENGINEER R. GILMAN).

Review Stop P PLUMBING
Rev No 8 Status F Date 2008-05-21 Cont ID  
Sent By kstevens Date 2008-05-21 Time 08:49 Rev Time 0.00
Received By kstevens Date 2008-05-20 Time 12:59 Sent To  
Notes
2008-05-21 09:48:27REVISION DENIED
 REFERENCE: FBC-2004 CHAPTER 1
  
 ****FROM PREVIOUS REVISION REVIEW:
  
 1. SHT P-1 PREVIOUS REVISION SIGNED, SEALED & DATED JAN
 24, 2008 SUBMITTED REVISIONS 1 THRU 5. REVISION
 SUBMITTED AT THIS TIME IS SHOWING NEW REVISION #1. THE
 REVISION SEQUENCE SHALL REMAIN IN EFECT THRU THE LIFE
 OF THE JOB, NOT REPEATING OR RESTARTING THE SEQUENCE AT
 REVISION #1 AGAIN. THE REVISION NUMBERS TRACK THE
 REVISION HISTORY AND THE NEXT REVISION SHOULD BE NUMBER
 6 TO CONTINUE THE SEQUENCE. SECTION 106.1.3.
 ****RESPONSE NOTED, BUT THE REVISION NUMBERS SHALL BE
 KEPT IN SEQUENTIAL ORDER AND NOW THE INFORMATION FOR
 PHASE I HAS BEEN DELETED. PLEASE CONTINUE WITH THE
 REVISION NUMBERS ESTABLISHED AND SHOW ALL INFORMATION
 FOR PHASE I AND REVISIONS TO PHASE II ON THE REVISED
 SHEET.
  
 2. SHT P-2 PREVIOUS REVISION SIGNED, SEALED & DATED JAN
 24, 2008 SUBMITTED REVISIONS 1 THRU 3. NO NEW REVISION
 NUMBER OR CLOUD IS INDICATED THIS REVISION. PLEASE
 INDICATE ALL REVISIONS WITH A CLOUD AND REVISION
 NUMBER. THE REVISION NUMBER SHALL BE SEQUENTIAL TO
 PREVIOUS REVISION NUMBERS. SECTION 106.1.3.
 ****RESPONSE NOTED, BUT THE REVISION NUMBERS SHALL BE
 KEPT IN SEQUENTIAL ORDER AND NOW THE INFORMATION FOR
 PHASE I HAS BEEN DELETED. PLEASE CONTINUE WITH THE
 REVISION NUMBERS ESTABLISHED AND SHOW ALL INFORMATION
 FOR PHASE I AND REVISIONS TO PHASE II ON THE REVISED
 SHEET.
  
 3. SHT P-3 PREVIOUS REVISION SIGNED, SEALED & DATED JAN
 24, 2008 SUBMITTED REVISIONS 1 THRU 4. NO NEW REVISION
 NUMBER OR CLOUD IS INDICATED THIS REVISION. PLEASE
 INDICATE ALL REVISIONS WITH A CLOUD AND REVISION
 NUMBER. THE REVISION NUMBER SHALL BE SEQUENTIAL TO
 PREVIOUS REVISION NUMBERS. SECTION 106.1.3.
 ****RESPONSE NOTED, BUT THE REVISION NUMBERS SHALL BE
 KEPT IN SEQUENTIAL ORDER AND NOW THE INFORMATION FOR
 PHASE I HAS BEEN DELETED. PLEASE CONTINUE WITH THE
 REVISION NUMBERS ESTABLISHED AND SHOW ALL INFORMATION
 FOR PHASE I AND REVISIONS TO PHASE II ON THE REVISED
 SHEET.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 7 Status F Date 2008-04-12 Cont ID  
Sent By kstevens Date 2008-04-12 Time 05:56 Rev Time 0.00
Received By kstevens Date 2008-04-11 Time 18:58 Sent To  
Notes
2008-04-12 06:10:11REVISION DENIED
 REFERENCE: FBC-2004 CHAPTER 1
  
 1. SHT P-1 PREVIOUS REVISION SIGNED, SEALED & DATED JAN
 24, 2008 SUBMITTED REVISIONS 1 THRU 5. REVISION
 SUBMITTED AT THIS TIME IS SHOWING NEW REVISION #1. THE
 REVISION SEQUENCE SHALL REMAIN IN EFECT THRU THE LIFE
 OF THE JOB, NOT REPEATING OR RESTARTING THE SEQUENCE AT
 REVISION #1 AGAIN. THE REVISION NUMBERS TRACK THE
 REVISION HISTORY AND THE NEXT REVISION SHOULD BE NUMBER
 6 TO CONTINUE THE SEQUENCE. SECTION 106.1.3.
  
 2. SHT P-2 PREVIOUS REVISION SIGNED, SEALED & DATED JAN
 24, 2008 SUBMITTED REVISIONS 1 THRU 3. NO NEW REVISION
 NUMBER OR CLOUD IS INDICATED THIS REVISION. PLEASE
 INDICATE ALL REVISIONS WITH A CLOUD AND REVISION
 NUMBER. THE REVISION NUMBER SHALL BE SEQUENTIAL TO
 PREVIOUS REVISION NUMBERS. SECTION 106.1.3.
  
 3. SHT P-3 PREVIOUS REVISION SIGNED, SEALED & DATED JAN
 24, 2008 SUBMITTED REVISIONS 1 THRU 4. NO NEW REVISION
 NUMBER OR CLOUD IS INDICATED THIS REVISION. PLEASE
 INDICATE ALL REVISIONS WITH A CLOUD AND REVISION
 NUMBER. THE REVISION NUMBER SHALL BE SEQUENTIAL TO
 PREVIOUS REVISION NUMBERS. SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 6 Status P Date 2008-02-22 Cont ID  
Sent By kstevens Date 2008-02-22 Time 07:52 Rev Time 0.00
Received By kstevens Date 2008-02-22 Time 07:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2007-12-15 Cont ID  
Sent By kstevens Date 2007-12-15 Time 08:52 Rev Time 0.00
Received By kstevens Date 2007-12-15 Time 08:52 Sent To  
Notes
2007-12-15 08:59:11REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 11
  
 1. SHT A-1 PER TABLE 403.1 A DRINKING FOUNTAIN IS
 REQUIRED. PLEASE INDICATE ON MINIMUM FIXTURES REQUIRED,
 SHOW THE LOCATION ON THE FLOOR PLAN AND SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTIONS 11-4.15 WITH ALL
 SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING IF THE DRINKING FOUNTAIN IS NOT A HI/LOW
 TYPE.
  
 2. SHTS P-1 KEY NOTE #8, P-2 WATER HEATER DETAIL & P-3
 SANITARY RISER DIAGRAM. HUB DRAIN ABOVE THE CEILING FOR
 THE T/P, PAN DRAIN, THERMAL EXPANSION VALVE IS NOT
 APPROVED. THE AIR GAP FOR THE P/T VALVE SHALL BE
 VISIBLE, A TRAP PRIMER IS REQUIRED PER SECTION 1002.4
 AND THERE IS NO PIPE, TRAP SUPPORT INDICATED AS
 REQUIRED PER SECTION 308.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-10-23 Cont ID  
Sent By kstevens Date 2007-10-23 Time 07:37 Rev Time 0.00
Received By kstevens Date 2007-10-23 Time 07:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-07-07 Cont ID  
Sent By kstevens Date 2007-07-07 Time 18:21 Rev Time 0.00
Received By kstevens Date 2007-07-07 Time 18:21 Sent To  
Notes
2007-07-07 18:29:46DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
 ********FROM PREVIOUS REVIEWS:
  
 1. PERMIT APPLICATION STATES GROSS
 SQUARE FOOTAGE AS 5423SF. COVER SHEET
 INDICATES 54243SF BAR, AND 3571SF POOL
 HALL. PLEASE CLARIFY. SECTION 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED.
 *******RESPONSE NOTED, AND WHEN THE APPLICATION IS
 CORRECTED THIS COMMENT WILL BE OK. WHEN THIS AND
 COMMENT #9 ARE ADDRESS, THE STATUS OF THIS REVIEW WILL
 BE APPROVED.
  
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
  
 9. ROUTE PLANS TO THE PALM BEACH COUNTY
 HEALTH UNIT DIVISION OF ENVIRONMENTAL
 HEALTH FOR REVIEW PRIOR SO RESUBMITTING
 TO THE CITY WPB FOR REVIEW. A MINIMUM OF
 2 SETS OF PLANS SHALL BE STAMPED AS
 REVIEWED BY THE HEALTH DEPT. SECTION
 102.2.1.
 ****NO RESPONSE, NOT ADDRESSED.
 ********RESPONSE NOTED, AND WHEN THE PLANS COME BACK
 WITH THE HEALTH DEPT. REVIEW STAMP THIS COMMENT WILL BE
 OK. WHEN THIS AND COMMENT #1 ARE ADDRESSED THE REVIEW
 STATUS WILL BE APPROVED.
  
 10. OK
 11. OK
 12. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-01-17 Cont ID  
Sent By kstevens Date 2007-01-17 Time 14:27 Rev Time 0.00
Received By kstevens Date 2007-01-17 Time 14:27 Sent To  
Notes
2007-01-17 14:43:59DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 1. PERMIT APPLICATION STATES GROSS
 SQUARE FOOTAGE AS 5423SF. COVER SHEET
 INDICATES 54243SF BAR, AND 3571SF POOL
 HALL. PLEASE CLARIFY. SECTION 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 2. ALL ARCHITECTURAL SHEETS. THE ADDRESS
 ON THE TITLE BLOCK DOES NOT RELFECT THE INFORMATION FOR
 THE ADDRESS ON THE DBPR
 WEBSITE. PLEASE CLARIFY. (SEE ATTACHED
 SHEET). FAC 61G1-16.004(1) FS 481.219.
 ****NO RESPONSE, NOT ADDRESSED.
  
 3. SHT A-1 SUITE 202 DEMO NOTES. IN THE
 REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS ARE PROHIBITED.
 SECTION 704.5. SUBMIT AN EXISTING FLOOR
 PLAN TO DETERMINE THE LOCATION OF ALL
 DEMO'D PLUMBING SYSTEMS, AND TO VERIFY
 THE EXTENT OF THE DEMOLITION. SECTION
 106.1.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
  
 9. ROUTE PLANS TO THE PALM BEACH COUNTY
 HEALTH UNIT DIVISION OF ENVIRONMENTAL
 HEALTH FOR REVIEW PRIOR SO RESUBMITTING
 TO THE CITY WPB FOR REVIEW. A MINIMUM OF
 2 SETS OF PLANS SHALL BE STAMPED AS
 REVIEWED BY THE HEALTH DEPT. SECTION
 102.2.1.
 ****NO RESPONSE, NOT ADDRESSED
  
 10. SHT P-1 KEY NOTE #4, AND SHT P-3
 SANT. RISER DIAGRAM. EVERY DRY VENT
 SHALL RISE VERTICALLY TO A MINIMUM OF 6"
 ABOVE THE FLOOD LEVEL RIM OF THE HIGHEST
 TRAP OR TRAPPED FIXTURE BEING VENTED.
 SECTION 905.4.
 ****RESPONSE NOTED, BUT THE VENTS ARE STILL SHOWN ON
 SHT P-3. THESE VENTS BETWEEN THE W/C'S ARE NOT
 REQUIRED, AND DO NOT MEET THE CODE REQUIREMENTS OF
 SECTION 905.4.
  
 11. OK
 12. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-10-05 Cont ID  
Sent By kstevens Date 2006-10-05 Time 14:07 Rev Time 0.00
Received By kstevens Date 2006-10-05 Time 09:28 Sent To  
Notes
2006-10-05 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. PERMIT APPLICATION STATES GROSS
 SQUARE FOOTAGE AS 5423SF. COVER SHEET
 INDICATES 54243SF BAR, AND 3571SF POOL
 HALL. PLEASE CLARIFY. SECTION 106.1.1.
  
 2. ALL ARCHITECTURAL SHEETS. THE ADDRESS
 ON THE TITLE BLOCK DOES NOT RELFECT THE INFORMATION FOR
 THE ADDRESS ON THE DBPR
 WEBSITE. PLEASE CLARIFY. (SEE ATTACHED
 SHEET). FAC 61G1-16.004(1) FS 481.219.
  
 3. SHT A-1 SUITE 202 DEMO NOTES. IN THE
 REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS ARE PROHIBITED.
 SECTION 704.5. SUBMIT AN EXISTING FLOOR
 PLAN TO DETERMINE THE LOCATION OF ALL
 DEMO'D PLUMBING SYSTEMS, AND TO VERIFY
 THE EXTENT OF THE DEMOLITION. SECTION
 106.1.2.
  
 4. SHT A-2 DETAILS 1 & 2. TURNING AREA
 TO BE SHOWN IN THE TOILET ROOM, NOT IN
 THE ACCESSIBLE STALL. SECTION 11-4.22.3.
  
 5. SHT A-2 DETAIL 6 INDICATES 2 HEIGHTS
 FOR THE WATER CLOSETS. BOTH INDICATE
 STANDARD HEIGHT. ONE, (19"), SHALL BE
 INDICATED AS ACCESSIBLE HEIGHT. SECTIONS
 106.1.1, AND 11-4.16.3.
  
 6. SHT A-2 DETAIL 6 GRAB BAR ON THE SIDE
 OF THE W/C SHALL BE 42" MINIMUM. SEE
 FIGURES 11-29 & 11-30.
  
 7. SHT A-2 DETAIL 6 FLUSH CONTROLS TO
 COMPLY WITH SECTION 11-4.16.5.
  
 8. SHT A-2 SUBMIT A DETAIL FOR THE
 URINALS SHOWING COMPLIANCE WITH:
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
  
 9. ROUTE PLANS TO THE PALM BEACH COUNTY
 HEALTH UNIT DIVISION OF ENVIRONMENTAL
 HEALTH FOR REVIEW PRIOR SO RESUBMITTING
 TO THE CITY WPB FOR REVIEW. A MINIMUM OF
 2 SETS OF PLANS SHALL BE STAMPED AS
 REVIEWED BY THE HEALTH DEPT. SECTION
 102.2.1.
  
 10. SHT P-1 KEY NOTE #4, AND SHT P-3
 SANT. RISER DIAGRAM. EVERY DRY VENT
 SHALL RISE VERTICALLY TO A MINIMUM OF 6"
 ABOVE THE FLOOD LEVEL RIM OF THE HIGHEST
 TRAP OR TRAPPED FIXTURE BEING VENTED.
 SECTION 905.4.
  
 11. SHT P-2 WATER HEATER PIPING DIAGRAM
 SHOWS A 2" HUB DRAIN FOR THE INDIRECT
 WASTE OF THE PAN DRAIN, P/T DISCHARGE,
 AND THE THERMAL EXPANSION VALVE. THIS IS
 NOT SHOWN ON THE FLOOR PLAN, NOR ON THE
 SANT. RISER DIAGRAM. IS THIS HUB DRAIN
 EXISTING? PLEASE CLARIFY. SECTION
 106.1.1.
  
 12. ALL INDIRECT WASTE SHALL DRAIN INTO
 A FLOOR SINK OR A HUB DRAIN. SECTIONS
 802.3 & 802.3.2. FLOOR DRAINS ARE NOT
 APPROVED INDIRECT WASTE RECEPTORS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2009-01-30 Cont ID  
Sent By mflis Date 2009-01-30 Time 14:46 Rev Time 0.00
Received By mflis Date 2009-01-30 Time 14:46 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status N Date 2007-06-26 Cont ID  
Sent By mflis Date 2007-06-26 Time 09:06 Rev Time 0.00
Received By mflis Date 2007-06-26 Time 09:05 Sent To  
Notes
2007-06-26 09:06:47ZONING REVIEW: NOT REQUIRED
  
 * PERMIT HAS BEEN MODIFIED TO BE INTERIOR WORK ONLY
  
 * EXTERIOR MODIFICATIONS REMOVED
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 2 Status P Date 2006-12-20 Cont ID  
Sent By mflis Date 2006-12-20 Time 11:39 Rev Time 0.00
Received By mflis Date 2006-12-20 Time 11:39 Sent To  
Notes
2006-12-20 11:40:40APPROVED -
  
 LIMITS OF WORK ONLY INCLUDE 2ND FLOOR INTERIOR AND
 EXTERIOR WORK.
  
 MATT FLIS 822-1445

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-26 Cont ID  
Sent By mflis Date 2006-10-31 Time 13:41 Rev Time 0.00
Received By hmoser Date 2007-07-26 Time 18:59 Sent To  
Notes
2006-10-31 13:46:35ZONING COMMENTS:
  
 - PLEASE PROVIDE ENTIRE BUILDING ELEVATION INCLUDING
 PROPOSED MODIFICATION TO OPENING.
 - CLARIFY HOW OVERHEAD DOOR WILL BE USED; IS THIS AN
 OPERABLE DOOR? THIS IS ON THE SECOND LEVEL. WILL THERE
 BE SOME RAILING OR BARRIER?
 - PLEASE CONFIRM OH DOOR DETAILS BASED UPON ABOVE
 COMMENTS; ELEVATIONS FOR "TYPICAL" OH DOOR DO NOT MATCH
 ON 2/A-3 AND 9/A-3.
  
 -MATT FLIS 822-1445