Plan Review Details - Permit 06090331
Plan Review Stops For Permit 06090331
Review Stop G GAS REVIEW
Rev No 1 Status P Date 2006-09-21 Cont ID  
Sent By mperson Date 2006-09-21 Time 15:27 Rev Time 0.45
Received By mperson Date 2006-09-21 Time 15:27 Sent To  
Notes
2006-09-21 00:00:00 
  
 ******PROVISO******
 404.7 ABOVE-GROUND OUTDOOR PIPING: ALL
 PIPING INSTALLED OUTDOORS SHALL BE
 ELEVATED NOT LESS THAN 3-1/2" ABOVE
 GROUND.
  
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 3,750 CUBIC FEET REQUIRED.