Plan Review Details - Permit 06090324
Plan Review Stops For Permit 06090324
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-07-05 Cont ID  
Sent By shill Date 2007-07-05 Time 13:55 Rev Time 0.00
Received By shill Date 2007-07-05 Time 13:55 Sent To  
Notes
2007-07-05 13:58:54****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)TWO IDENTICAL COLLATED SETS REQUIRED FOR PERMIT
 ISSUANCE.TWO DISTINCT COLLATED PACKAGES, BOUND
 (EITHER STAPLED OR WITH A CLIP) SHOULD BE SUBMITTED
 WITH OLD SHEETS MARKED "VOID" AND SUBMITTED SEPARATELY
 FROM THE COLLATED PACKAGE.I ATTEMPTED TO STAMP THE
 SHEETS SHOWING BUILDING APPROVAL BUT WAS UNABLE TO FIND
 TWO SETS OF SOME OF THE DOCUMENTS.ADDITIONALLY IT IS
 DIFFICULT TO DETERMINE WHICH SHEETS ARE INTENDED FOR
 PERMITTING AND WHICH ARE OLD SHEETS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-02-02 Cont ID  
Sent By shill Date 2007-02-02 Time 11:18 Rev Time 0.00
Received By shill Date 2007-02-02 Time 11:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-10-18 Cont ID  
Sent By alange Date 2006-10-18 Time 08:16 Rev Time 0.00
Received By alange Date 2006-10-18 Time 08:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-06-18 Cont ID  
Sent By btrobaug Date 2007-06-18 Time 10:19 Rev Time 0.00
Received By btrobaug Date 2007-06-18 Time 09:23 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-01-23 Cont ID  
Sent By btrobaug Date 2007-01-23 Time 15:52 Rev Time 0.25
Received By btrobaug Date 2007-01-23 Time 15:25 Sent To P
Notes
2007-01-23 15:52:04 
  
  
  
 DENIED
  
 THE LOAD CALCULATION FOR THE PANEL SERVED BY THE
 GENERATOR EXCEEDS THE GENERATOR OUTPUT. NONCOMPLIANT
 WITH 702.5 CAPACITY AND RATING. AN OPTIONAL STANDBY
 SYSTEM SHALL HAVE ADEQUATE CAPACITY AND RATING FOR THE
 SUPPLY OF ALL EQUIPMENT INTENDED TO BE OPERATED AT ONE
 TIME.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-21 Cont ID  
Sent By btrobaug Date 2006-09-21 Time 15:21 Rev Time 0.50
Received By btrobaug Date 2006-09-21 Time 14:52 Sent To P
Notes
2006-09-21 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE MANUFACTURERS
 SPECIFICATIONS/RECOMMENDATION, REGARDING
 CLEARANCES.
  
 2} PROVIDE SPECIFICATIONS FOR THE
 TRANSFER SWITCH.
  
 3} PROVIDE A CALCULATION FOR THE LOAD
 BEING SERVED BY THE GENERATOR. SEE
 700.15 LOADS ON EMERGENCY BRANCH
 CIRCUITS.
  
 4} INDICATE HOW THE TRANSFER SWITCH IS
 FED FROM THE PANEL.THERE MUST BE A
 MAIN IN THIS PANEL OR OCP IN THE MAIN
 PANEL.
  
 5} THE PLAN INDICATES A 25 KW GENERATOR
 AND THE SPECS INDICATE A 20 KW, PLEASE
 CORRELATE.
  
 6} THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN/DRAWINGS, SHALL PRINT AND SIGN
 THEIR NAME ON THE SHEETS THEY DRAW.
 PLEASE DO THIS PRIOR TO RESUBMITTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-07-02 Cont ID  
Sent By mperson Date 2007-07-02 Time 09:00 Rev Time 0.33
Received By mperson Date 2007-07-02 Time 09:00 Sent To M
Notes
2007-07-02 09:04:55DENIED 3RD TIME
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A **NO** IS IF THE COMMENT WAS NOT FULLY ADDRESSED
 AND/OR FURTHER EXPLANATION OR CHANGES IN PLANS OR
 DOCUMENTS ARE STILL NEEDED. THIS REVIEWER WILL TRY TO
 BETTER EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN **OK** WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A **NO/OK** MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
 **NOTE: PLEASE ADD THE FOLLOWING INFORMATION ON AN
 ISOMETRTIC DRAWING**
  
 1. **NO** SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE RESUBMITTED DRAWING IS NOT AN ISOMETRIC AND
 DOES NOT CLEARLY SHOW ALL CUT SECTIONS OF PIPE WITH
 CORRESPONDING LENGTHS.
  
 2. **NO** SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 3. (OK)
  
 4. **NO** BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. **NO** SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. **NO** INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 7. (OK)
  
 8. **NO** SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 NOTE: IF NAT. GAS DELIVERY PRESSURE IS 2 PSI PLEASE
 SUBMIT MANUFACTURER SPECIFICATION SHEETS ON MP
 REGULATOR.
  
 9. (OK)
  
 10. (OK)
  
 11. (OK)
  
 **********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-01-24 Cont ID  
Sent By mperson Date 2007-01-24 Time 09:39 Rev Time 0.00
Received By mperson Date 2007-01-24 Time 09:54 Sent To M
Notes
2007-01-24 10:11:19DENIED 2ND TIME
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING CORRECTIONS ARE STILL REQUIRED FROM THE
 PREVIOUS GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 3. (OK)
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 7. (OK)
  
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 NOTE: IF NAT. GAS DELIVERY PRESSURE IS 2 PSI PLEASE
 SUBMIT MANUFACTURER SPECIFICATION SHEETS ON MP
 REGULATOR.
  
 9. (OK)
  
 10. (OK)
  
 11. (OK)
  
 **********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-09-27 Cont ID  
Sent By mperson Date 2006-09-27 Time 08:54 Rev Time 0.45
Received By mperson Date 2006-09-27 Time 08:54 Sent To B
Notes
2006-09-27 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PLAN REVIEW ON THE ISOMETRIC
 DRAWING:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: GALVANIZED SCHEDULE 40 METALLIC
 PIPE SHALL NOT BE INSTALLED UNDER GROUND
  
 3. TYPE OF GAS, (LP OR NATURAL)
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 7. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 8. SUBMIT MANUFACTURE SHEETS AND
 INSTALLATION INSTRUCTIONS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 9. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 10. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 11. FBC-2004 CHAPTER 1,SECTION
 106.3.4.2: THE PERSON RESPONSIBLE FOR
 THE DESIGN OF THE DRAWING SHALL CLEARLY
 PRINT AND SIGN NAME, AND ALSO DATE
 DRAWING. PLEASE DO THIS PRIOR TO
 RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-06-14 Cont ID  
Sent By adarroug Date 2007-06-14 Time 08:33 Rev Time 0.00
Received By adarroug Date 2007-06-14 Time 08:33 Sent To E
Notes
2007-06-14 08:34:11TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-06-11 Cont ID  
Sent By adarroug Date 2007-06-11 Time 16:00 Rev Time 0.00
Received By adarroug Date 2007-06-11 Time 15:59 Sent To Z
Notes
2007-06-11 16:00:22TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-01-16 Cont ID  
Sent By adarroug Date 2007-01-16 Time 17:30 Rev Time 0.00
Received By adarroug Date 2007-01-16 Time 17:30 Sent To E
Notes
2007-01-16 17:30:38TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-09 Cont ID  
Sent By adarroug Date 2007-01-09 Time 17:36 Rev Time 0.00
Received By adarroug Date 2007-01-09 Time 17:36 Sent To Z
Notes
2007-01-09 17:37:02TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-18 Cont ID  
Sent By adarroug Date 2006-09-18 Time 15:06 Rev Time 0.00
Received By adarroug Date 2006-09-18 Time 15:06 Sent To E
Notes
2006-09-18 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-18 Cont ID  
Sent By adarroug Date 2006-10-18 Time 17:29 Rev Time 0.00
Received By adarroug Date 2006-09-12 Time 09:02 Sent To  
Notes
2006-09-12 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-07-03 Cont ID  
Sent By tgordon Date 2007-07-03 Time 08:08 Rev Time 0.20
Received By tgordon Date 2007-07-03 Time 08:08 Sent To B
Notes
2007-07-03 08:11:54*** DENIED ***
 1) PLEASE SUBMIT TWO IDENTICAL COPIES OF THE SITE
 PLAN.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-01-24 Cont ID  
Sent By tgordon Date 2007-01-24 Time 15:03 Rev Time 0.20
Received By tgordon Date 2007-01-24 Time 15:03 Sent To B
Notes
2007-01-24 15:04:59*** DENIED ***
 1) SEE ZONING REVIEW, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-09-20 Cont ID  
Sent By tgordon Date 2006-09-20 Time 16:21 Rev Time 0.15
Received By tgordon Date 2006-09-20 Time 16:21 Sent To E
Notes
2006-09-20 00:00:00*** DENIED ***
 1) SEE ZONING REVIEW NOTES AND PLEASE
 CORRECT.
 *** NOTICE ***
 PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 FOLLOW MANUFACTURE'S RECOMMENDED
 CLEARANCES AROUND EQUIPMENT FOR
 SERVICING,AND PROVIDE MANUFACTURE'S
 INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 3 Status F Date 2007-06-12 Cont ID  
Sent By choops Date 2007-06-12 Time 08:20 Rev Time 0.00
Received By choops Date 2007-06-12 Time 08:20 Sent To I
Notes
2007-06-12 08:27:22***FAILED***
  
  
 1)PLEASE PROVIDE SETBACK DIMENSIONS OF HIGHLIGHTED
 AREAS ON SURVEY TO THE PROPERTY LINES.(THE SIDE
 SETBACK OF PRINCIPAL BUILDING NEXT TO LOT 86, THE
 SETBACK FROM GENERATOR TO SIDE PROPERTY LINE, SETBACK
 FROM GENERATOR TO REAR PROPERTY LINE, SETBACK DIMENSION
 FROM GENERATOR TO FRONT PROPERTY LINE.)
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720

Review Stop Z ZONING
Rev No 2 Status F Date 2007-01-12 Cont ID  
Sent By mmclean Date 2007-01-12 Time 12:20 Rev Time 0.00
Received By mmclean Date 2007-01-12 Time 12:20 Sent To I
Notes
2007-01-12 12:25:33DENIED.
 1. PLEASE SUBMIT A COPY OF THE SURVEY, SITEPLAN
 SUBMITTED DOES NOT PROVIDE THE SIDE SETBACK (OPPOSITE
 OF THE PROPOSED GENERATOR). (NOT ALL SETBACKS SHOWN).
 2. THE PROPOSED GENERATOR CANNOT BE LOCATED INTO THE
 10FT U.E. AND CAN ONLY PROJECT 4FT INTO SETBACK.
 3. THE SITPLAN SUBMITTED DOES NOT PROVIDE ALL
 INFORMATION NEEDED TO COMPLETE REVIEW THE PROPOSED
 GENERATOR.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-09-16 Cont ID  
Sent By mmclean Date 2006-09-16 Time 16:34 Rev Time 0.00
Received By mmclean Date 2006-09-16 Time 16:34 Sent To I
Notes
2006-09-16 00:00:00DENIED,
 1. THE PROPOSED GENERATOR MUST BE SHOWN
 ON THE PROPERTY, CANNOT BE LOCATED ON
 THE NEIGHBORING PROPERTY.
 2. THE PROPOSED GENERATOR CANNOT BE
 LOCATED IN THE 10FT UTILITY EASEMENT IN
 THE REAR OF THE PROPERTY.
 3. NEED TO SHOW THE LOCATION OF THE
 PROPOSED GENERATOR ON THE PROPERTY WITH
 SETBACKS (FROM PROPERTY LINE).
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720