Plan Review Details - Permit 06090295
Plan Review Stops For Permit 06090295
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2007-06-12 Cont ID  
Sent By jgomez Date 2007-06-12 Time 09:59 Rev Time 0.00
Received By jgomez Date 2007-06-12 Time 09:59 Sent To PC
Notes
2007-06-12 10:03:40BUILDING REVISION APPROVED WITH PROVISO:
 1- NEED TO PROVIDE VENTILATION IN CRAWLSPACE IN
 CORNER AREAS AS REQUIRED BY SEC. R408.1 AND R408.2 OF
 FLORIDA 2004 RESIDENTIAL CODE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2007-04-24 Cont ID  
Sent By jgomez Date 2007-04-24 Time 07:59 Rev Time 0.00
Received By jgomez Date 2007-04-24 Time 07:41 Sent To PC
Notes
2007-04-24 08:38:35BUILDING REVISION CHECKLIST:
 1- SOUTH ELEVATIONDOESN'T MATCH FLOOR PLAN.SEE
 WINDOWS BY BREAKFAST AREA. REVISE AS REQUIRED.
  
 2- NEED TO PROVIDE SPECIFICATIONS AND DETAILS SHOWING
 COMPLIANCE WITH CRAWL SPACE VENTILATION AND ACCESS AS
 REQUIRED BY SECTIONS R408.1, R408.2, R408.3 AND R408.4
 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 3- CONTRACTOR TO UPDATE INSURANCE. SEE PERMIT CLERK.
  
 4- ENERGY CALCULATIONS:
 A) NEED TO USE REVISED FORM 600A-R.
  
 B) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 5- WIND LOAD SCHEDULE ON SHEET A-5 NEED TO BE REVISED.
 SEE REVISED DESIGN PRESSURES SUBMITTED ON LETTER DATED
 FEBRUARY 6, 2007.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-03-07 Cont ID  
Sent By jgomez Date 2007-03-07 Time 17:10 Rev Time 1.00
Received By jgomez Date 2007-03-07 Time 17:05 Sent To E
Notes
2007-03-07 17:11:32THERE IS A NEW REVISED ELECTRICAL SHEET SUBMITTED IN
 THIS PACKAGE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-01-29 Cont ID  
Sent By jgomez Date 2007-01-29 Time 15:09 Rev Time 1.00
Received By jgomez Date 2007-01-29 Time 12:50 Sent To  
Notes
2007-01-29 14:35:54BUILDING REVISION CHECKLIST:
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR STRUCTURAL WINDOW MULLIONS.
 ALSO, SPECIFY MULLION FASTENING TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC. R301 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITTING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 3- PROVIDE COMPLETE INFORMATION FOR SPIRAL STAIR TO
 VERIFY COMPLIANCE WITH SEC. R311.5.8.1 2004 FLORIDA
 RESIDENTIAL CODE . ALSO, PROVIDE COMPLETE INSTALLATION
 DETAILS TO SHOW COMPLIANCE WITH WIND LOADS SEC. R301
 2004 RESIDENTIAL CODE.SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 4-PROVIDE COMPLETE SPECS FOR GUARDRAIL TO SHOW
 COMPLIANCE WITH SEC. R312 2004 FLORIDA RESIDENTIAL CODE
 AND SEC. 1607.7.1 FBC 2004.
  
 5- PROVIDE INFORMATION REQUESTED ON PROVISO DATED
 12/08/06. SEE ATTACHED COPY.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-12-11 Cont ID  
Sent By jgomez Date 2006-12-08 Time 16:30 Rev Time 1.50
Received By jgomez Date 2006-12-08 Time 16:30 Sent To M
Notes
2006-12-08 16:38:33BUILDING REVIEW PROVISO:
 1- PROVIDE UPDATED NOA FOR PRECAST LINTELS. NOA
 03-0605.05 EXPIRED IN 05/21/06..
 2- AS PER PHONE CONVERSATION WITH JOHN ANDERSEN,
 PROVIDE COMPLETE INFORMATION FOR FLAT ROOF SYSTEM UNDER
 A SEPARATE PERMIT AND FEES. SEE ATTACHED COPY OF CITY
 POLICY FOR ROOFING PERMITS FOR REQUIRED INFORMATION.
  
 3- PROVIDE COMPLETE TRUSS PACKAGE FOR REVIEW PRIOR
 TO INSTALLATION. DESIGNER OF RECORD TO REVIEW AND
 APPROVE IT PRIOR TO SUBMITTAL. SEE SEC. R802.10 FOR ALL
 INFORMATION REQUIRED TO BE IN THE TRUSS PACKAGE. TWO
 COPIES REQUIRED.
 4- WIND LOAD CHART: DESIGN PRESSURES FOR FLAT ROOF
 AREAS ARE LOW IN COMPARISON WITH ASCE 7-02 AND TABLE
 1609.6B FBC 2004. PROVIDE ACTUAL CALCULATIONS TO VERIFY
 COMPLIANCE WITH SEC. 1609 FBC 2004. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-27 Cont ID  
Sent By jgomez Date 2006-11-27 Time 15:00 Rev Time 2.00
Received By jgomez Date 2006-11-27 Time 15:00 Sent To  
Notes
2006-11-27 15:16:02BUILDING REVIEW 2ND CHECKLIST:
  
 1- PAY IMPACT FEES TO PALM BEACH COUNTY. BRING BACK
 STAMPED PLANS AND PAID RECEIPT.
  
 2- SOIL TEST REPORT:
 A) BOTH COPIES TO HAVE ORIGINAL ENGINEER'S SIGNATURE
 (NO COPIES) AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTES.
  
 B) NEED THE ENGINEERING FIRM CERTIFICATE OF
 AUTHORIZATION NUMBER AS REQUIRED BY FLORIDA
 ADMINISTRATIVE CODE SEC. 61G15-23.002.
  
 3- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72
 FOR:
 A) FRENCH DOOR. DADE COUNTY NOA #01-0417.04
 SUBMITTEDEXPIRED ON 11-22-06.
  
 B) PRECAST LINTELS. NO INFORMATION SUBMITTED.
  
 C) ROOF TILE. NO INFORMATION SUBMITTED.
  
 D) FLAT ROOF SYSTEMS. SEE PLANS. NO INFORMATION
 SUBMITTED.
 ***NOTE: NEED TO IDENTIFY SPECIFIC APPROVED ASSEMBLIES.
 CHECK SYSTEM LIMITATIONS BECAUSE GENERAL LIMITATION #9
 MAY NOT BE USED IN THIS AREA. IF SYSTEM IS LIMITED BY
 GENERAL LIMITATION #7, THEN PROVIDE REQUIRED
 INFORMATION. SEE LAST PAGE OF NOA TO CHECK GENERAL
 LIMITATIONS.
  
 E) ALL USP OR SIMPSON CONNECTORS SPECIFIED ON
 PLANS.
  
 F) WINDOWS WERE REVISED FROM CASEMENT WINDOWS TO
 SINGLE HUNG WINDOWS.ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGES WERE SUBMITTED. NEED TO PROVIDE COMPLETE
 WINDOW DRAWINGS PACKAGE ALSO.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOSIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 5-DETAIL A/A3 DOESN'T COMPLY WITH SEC. R311.5.3.2
 2004 FLORIDA RESIDENTIAL CODE. 7" RISERS AND 12" DON'T
 COMPLY WITH THE 24 TO 25 RISER TREAD RATIO. REVISE AS
 REQUIRED.
  
 6- SHEET A-4:CLARIFY WHY TREAD DIMENSIONS ON STAIRS
 BY BREAKFAST AREAARE DIFFERENT FROM TREAD DIMENSIONS
 ON OTHER STAIRS. ALSO, COORDINATE DIMENSIONS WITH
 DETAIL A/A3 REVISION.
  
 7- SHEET A-5:
 A) WIND LOAD SCHEDULE CHART IS INCOMPLETE. IT
 DOESN'T SPECIFY THE WIND LOAD FOR THIS AREA AND THE
 EXPOSURE TYPE AS REQUIRED BY SEC. R301 2004 RESIDENTIAL
 CODE.ALSO, MISSING THE DESIGN PRESSURES FOR FLAT
 ROOF. SEE TABLE 1609.6B FBC 2004.
  
 B) ROOF SHEATHING NAILING SCHEDULE DOESN'T MATCH
 INFORMATION GIVEN ON SHEET A-8 WALL SECTION "A". REVISE
 AS REQUIRED.
  
 8- PROVIDE COMPLETE DETAILS AND SPECS FOR RAILING,
 INCLUDING FASTENING TO ROOF SYSTEM AS REQUIRED BY SEC.
 1607.7.1 FBC 2004 AND SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 9- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 106.1.1.2 CITY AMENDMENTS TO FBC 2004.
 INFORMATION NO PROVIDED.
  
 10- WALL SECTION "A" ON SHEET A-8 DOENS'T SHOW OR
 SPECIFY ATTIC VENTILATION. PROVIDE INFORMATION AS
 REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-16 Cont ID  
Sent By jgomez Date 2006-10-13 Time 16:56 Rev Time 2.50
Received By jgomez Date 2006-10-13 Time 16:56 Sent To  
Notes
2006-10-16 11:07:40BUILDING REVIEW CHECKLIST:
 1- PAY IMPACT FEES TO PALM BEACH COUNTY. BRING BACK
 STAMPED PLANS AND PAID RECEIPT.
  
 2- PROVIDE SOIL TEST REPORT.
  
 3- PROVIDE FLORIDA OR LOCAL PRODUCT APPROVAL AS
 REQUIRED BY RULE 9B-72 FOR (GO TO THE DCA WEBSITE
 WWW.FLORIDABUILDING.ORG TO DOWNLOAD ALL FLORIDA PRODUCT
 APPROVALS):
 A) CASEMENT WINDOWS. PROVIDE FLORIDA PRODUCT APPROVAL
 COVER PAGE FOR FL-245 WHICH IS THE ONE THAT MATCHES
 SELECTED NOA.
 B) FRENCH DOORS. PROVIDE FLORIDA PRODUCT APPROVAL
 COVER PAGE FL-253 AND CORRESPONDING NOA NO 02-0701.12
 WHICH IS THE ONE SUBMITTED FOR FLORIDA PRODUCT
 APPROVAL.
 C) PRECAST LINTELS SPECIFIED ON PLANS.
 D) ROOF TILE.
 E) FLAT ROOF SYSTEM. NOTE: CLEARLY IDENTIFY SPECIFIC
 APPROVED ASSEMBLY TO BE INSTALLED. CHECK IF SELECTED
 ASSEBLY IS LIMITED BY GENERAL LIMITATION #7 OR #9. SEE
 GENERAL LIMITATIONS ON LAST PAGE OF NOA AND PROVIDE
 REQUIRED INFORMATION.
 F) ALL USP OR SIMPSON CONNECTORS SPECIFIED ON PLANS.
 SEE PLANS AND DETAILS.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITTING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 5- OWNER/AGENT TO SIGN AND DATE THE ENERGY
 CALCULATIONS.
  
 6- ENGINEER TO PROVIDE ALL DESIGN CRITERIA REQUIRED BY
 SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE. INCLUDE
 SPCIFIC CODE AND ALL DESIGN LOADS INCLUDING LIVE, DEAD
 AND ATTIC LOADS. SEE TABLE R301.5 2004 FLORIDA
 RESIDENTIAL CODE.
  
 7- SHEET A-3:
 A) PROVIDE COMPLETE SPECS FOR ALL THREE LANDING AND
 STEPS. NEED DIMENSIONS INCLUDING RISER AND TREADS TO
 VERIFY COMPLIANCE WITH SEC. R311.5.3.2 2004 FLORIDA
 RESIDENTIAL CODE.
 B) SPECIFY CONNECTOR AT THE ENDS OF (3)2X12 BEAM.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 8- SHEET A-4:
 A) SPECIFY SIZE AND TYPE OF NEW WINDOWS. AND ALL NEW
 DOORS SIZES. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
 B) SPECIFY SAFETY GLAZING FOR WINDOW IN BATH LOCATED ON
 THE EAST CORNER. SEC. R308.4 2004 FLORIDA RESIDENTIAL
 CODE.
  
 9- SHEET A-5:
 A) PROVIDE COMPLETE SPECS FOR ROOF CONSTRUCTION AT
 FLAT AREA ABOVE NEW BATH LOCATED ON THE EAST CORNER.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
 B) PROVIDE COMPLETE DRAWINGS AND SPECS SHOWING
 LANDING FOR SPIRAL STAIRCASE. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
 C) PROVIDE COMPLETE DETAILS AND SPECS FOR RAILING TO
 VERIFY COMPLIANCE WITH SEC R312 2004 FLORIDA
 RESIDENTIAL CODE.
 D) PROVIDE COMPLETE DRAWINGS AND SPECS FOR SPIRAL
 STAIRCASE TO VERIFY COMPLIANCE WITH SEC. R311.5.8 2004
 FLORIDA RESIDENTIAL CODE.
  
 10- SHEET A-6:
 A) WEST ELEVATION IS INCOMPLETE BY SPIRAL STAIRCASE.
 MISSING ROOF AREA. PROVIDE COMPLETE INFORMATION.
 B) PROVIDE STRUCTURAL BUCK DETAILS FOR DOORS AND
 WINDOWS. SPECIFY FASTENERS. SEC. R613.6.2 2004
 RESIDENTIAL CODE.
  
 11- PROVIDE VENTILATION CALCULATIONS AND LOCATION AND
 SIZE OF ROOF VENTS INCLUDING AT FLAT ROOF AS REQUIRED
 BY SEC. R806 2004 FLORIDA RESIDENTIAL CODE.
  
 12- OWES $13.30 FOR RADON FEES.
  
 13- SPECIFY ROOF TILE FASTENING AS REQUIRED BY SEC.
 106.1.1.2 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  
  

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2007-11-28 Cont ID  
Sent By btrobaug Date 2007-11-28 Time 13:37 Rev Time 0.00
Received By btrobaug Date 2007-11-28 Time 12:58 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2007-06-20 Cont ID  
Sent By btrobaug Date 2007-06-20 Time 15:37 Rev Time 0.00
Received By btrobaug Date 2007-06-20 Time 15:37 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2007-05-30 Cont ID  
Sent By btrobaug Date 2007-05-30 Time 16:18 Rev Time 0.50
Received By btrobaug Date 2007-05-30 Time 15:43 Sent To M
Notes
2007-05-30 16:18:08 
  
  
 REVISION DENIED/INCOMPLETE INFORMATION
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY.
  
 2} LABEL THE PANELS.
  
 3} LOCATE PANELS ON THE PLAN. PROVIDE A SITE PLAN IF
 NECESSARY. MORE PANELS ARE ADDED AND NO RECORD OF THEIR
 LOCATIONS. 106.1.3 FBC.
  
 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-04-19 Cont ID  
Sent By btrobaug Date 2007-04-19 Time 09:17 Rev Time 0.50
Received By btrobaug Date 2007-04-19 Time 08:45 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-03-08 Cont ID  
Sent By btrobaug Date 2007-03-08 Time 07:22 Rev Time 0.50
Received By btrobaug Date 2007-03-08 Time 06:59 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-01-29 Cont ID  
Sent By btrobaug Date 2007-01-29 Time 09:57 Rev Time 0.75
Received By btrobaug Date 2007-01-29 Time 06:51 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-12-08 Cont ID  
Sent By btrobaug Date 2006-12-08 Time 07:10 Rev Time 0.50
Received By btrobaug Date 2006-12-07 Time 16:21 Sent To P
Notes
2006-12-08 07:10:20 
 PROVISO
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW PRIOR TO ANY
 ELECTRICAL INSPECTIONS.
  
 1} THE SERVICE IS LOCATED REMOTE FROM THE RESIDENCE ON
 SHEET A-1, THEREFORE A DISCONNECTING MEANS PER 225.31,
 LOCATED PER 250.32 AND GROUNDED PER 250.32 IS REQUIRED
 AT THE RESIDENSE. THE PANEL(S) INDICATED AS MLO ON THE
 RISER DO NOT MEET THESE REQUIREMENTS. PLEASE CORRECT,
 AND RESUBMIT FOR REVIEW.
  
 THE REVIEWED PLAN MUST BE ON THE JOB
 SITE AT TIME OF INSPECTION. ALLOW AT
 LEAST ONE WEEK (PER TRADE) FOR PLAN
 REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-11-14 Cont ID  
Sent By btrobaug Date 2006-11-14 Time 11:36 Rev Time 0.75
Received By btrobaug Date 2006-11-14 Time 10:21 Sent To M
Notes
2006-11-14 11:36:04 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE SERVICE IS LOPCATED REMOTE FROM THE RESIDENCE ON
 SHEET A-1, THEREFORE A DISCONNECTING MEANS PER 225.31,
 LOCATED PER 250.32 AND GROUNDED PER 250.32 IS REQUIRED
 AT THE RESIDENSE. THE PANEL(S) INDICATED AS MLO ON THE
 RISER DO NOT MEET THESE REQUIREMENTS. PLEASE CORRECT.
  
 2} THE GROUNDING ELECTRODE CONDUCTOR SIZE PER 250.66 IS
 NOT INDICATED ON THE RISER. ALSO THE REFERENCE TO A #5
 DRIVEN GROUND ROD IS INCORRECT.
  
 3} THE KITCHEN COUNTERRECEPTACLES, INCLUDING THE
 ISLAND, MUST BE GFI PROTECTEDPER 210.8(A)(7), INDICATE
 THE SAME ON THE DRAWINGS.
  
 4} A RECEPTACLE IS REQUIRED FOR SERVICING THE
 CONDENSING UNITS PER 210.63. PLACE ON PLAN.
  
 5} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH
 R313.1 RESIDENTIAL FLORIDA BUILDING CODE. THIS IS THE
 SECOND TIME THIS COMMENT HAS BEEN MADE. PLEASE ADDRESS,
 LOCATE ON THE PLAN.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-04 Cont ID  
Sent By btrobaug Date 2006-10-04 Time 09:53 Rev Time 1.00
Received By btrobaug Date 2006-09-28 Time 12:38 Sent To P
Notes
2006-09-28 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2.
  
 2} PROVIDE A LOAD CALCULATION PER
 220.31, INCLUDE ADDED LOADS.
  
 3} SUBMIT A PANEL SCHEDULE PER 408.4 NEC
 AND 106.3.5.4(8) FBC.
  
 4} INDICATE THE RATING OF THE EXISTING
 SERVICE.
  
 5} KITCHEN RECEPTACLE SPACING MUST
 COMPLY WITH 210.52(C), SEE REVIEWED
 PLAN, NORTH, EAST AND WEST COUNTER
 LOCATIONS.
  
 6} BATH CIRCUIT REQUIRED TO HAVE A 20
 AMP RECEPTACLE PER 210.11(C) (3),
 LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A)(1).
  
 7} SUNROOM REQUIRED TO HAVE RECEPTACLES
 PER 210.52(A)(1) AND (2). SEE REVIEWED
 SET FOR APPROXIMATE LOCATIONS.
  
 8} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH
 R313.1 RESIDENTIAL FLORIDA BUILDING CODE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2007-11-21 Cont ID  
Sent By adarroug Date 2007-11-21 Time 12:38 Rev Time 0.00
Received By adarroug Date 2007-11-21 Time 12:38 Sent To E
Notes
2007-11-21 12:38:55TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2007-09-05 Cont ID  
Sent By adarroug Date 2007-09-05 Time 12:00 Rev Time 0.00
Received By adarroug Date 2007-09-05 Time 12:00 Sent To P
Notes
2007-09-05 12:00:35TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2007-08-27 Cont ID  
Sent By adarroug Date 2007-08-27 Time 13:23 Rev Time 0.00
Received By adarroug Date 2007-08-27 Time 13:23 Sent To M
Notes
2007-08-27 13:23:28TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2007-08-08 Cont ID  
Sent By dpalmer Date 2007-08-08 Time 18:02 Rev Time 0.00
Received By dpalmer Date 2007-08-08 Time 18:02 Sent To M
Notes
2007-08-08 18:02:55TO TG'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-06-15 Cont ID  
Sent By adarroug Date 2007-06-15 Time 10:58 Rev Time 0.00
Received By adarroug Date 2007-06-15 Time 10:58 Sent To E
Notes
2007-06-15 10:58:44TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-05-23 Cont ID  
Sent By adarroug Date 2007-05-23 Time 11:47 Rev Time 0.00
Received By adarroug Date 2007-05-23 Time 11:47 Sent To E
Notes
2007-05-23 11:47:35TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-05-21 Cont ID  
Sent By shill Date 2007-05-21 Time 14:56 Rev Time 0.00
Received By shill Date 2007-05-21 Time 14:56 Sent To Z
Notes
2007-05-21 14:56:35TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-04-16 Cont ID  
Sent By adarroug Date 2007-04-16 Time 14:13 Rev Time 0.00
Received By adarroug Date 2007-04-16 Time 14:13 Sent To E
Notes
2007-04-16 14:14:17TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-04-04 Cont ID  
Sent By spalmer Date 2007-04-04 Time 17:37 Rev Time 0.00
Received By spalmer Date 2007-04-04 Time 17:37 Sent To Z
Notes
2007-04-04 17:38:07TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-03-02 Cont ID  
Sent By adarroug Date 2007-03-02 Time 13:16 Rev Time 0.00
Received By adarroug Date 2007-03-02 Time 13:13 Sent To E
Notes
2007-03-02 13:17:40TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-01-20 Cont ID  
Sent By adarroug Date 2007-01-20 Time 11:36 Rev Time 0.00
Received By adarroug Date 2007-01-20 Time 11:36 Sent To Z
Notes
2007-01-20 11:36:25TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-12-01 Cont ID  
Sent By adarroug Date 2006-12-01 Time 14:49 Rev Time 0.00
Received By adarroug Date 2006-12-01 Time 14:49 Sent To Z
Notes
2006-12-01 14:49:22TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-11-08 Cont ID  
Sent By adarroug Date 2006-11-08 Time 13:38 Rev Time 0.00
Received By adarroug Date 2006-11-08 Time 13:38 Sent To E
Notes
2006-11-08 13:38:56TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-01 Cont ID  
Sent By adarroug Date 2006-11-01 Time 17:17 Rev Time 0.00
Received By adarroug Date 2006-11-01 Time 17:17 Sent To Z
Notes
2006-11-01 17:17:42TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-18 Cont ID  
Sent By adarroug Date 2006-09-18 Time 14:54 Rev Time 0.00
Received By adarroug Date 2006-09-18 Time 14:54 Sent To E
Notes
2006-09-18 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-13 Cont ID  
Sent By jgomez Date 2006-10-13 Time 16:57 Rev Time 0.00
Received By jgomez Date 2006-09-12 Time 08:48 Sent To  
Notes
2006-09-12 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 7 Status F Date 2007-09-04 Cont ID  
Sent By tgordon Date 2007-09-04 Time 15:36 Rev Time 0.25
Received By tgordon Date 2007-09-04 Time 15:36 Sent To  
Notes
2007-09-04 15:51:40PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 MECHANICAL REVISION
 *** DENIED ***
 1) REVISED ENERGY CALCULATIONS LINE 15 IS TAKING A
 CREDIT FOR CEILING FANS, REVISED ELECTRICAL PLANS ON
 FILE SHOW NO CEILING FANS TO BE INSTALLED. PER 2004 FBC
 13-607.2.A.3.1.CEILING FAN CREDIT MAY BE TAKEN IF ONE
 OR MORE CEILING FANS ARE INSTALLED IN EACH OF THE
 BEDROOMS AND A MINIMUM OF ONE CEILING FAN IS INSTALLED
 IN ALL PRIMARY LIVING AREAS (LIVING ROOMS, FAMILY
 ROOMS, OR GREAT ROOMS). PRESCRIPTIVE REQUIREMENTS IN
 SECTION 13-607.1.A.1 SHALL BE MET. PLEASE REVISE
 ELECTRICAL PLANS TO SHOW CEILING FANS (NOT JUST
 JUNCTION BOX) AND SUBMIT WITH THIS REVISION OR CORRECT
 ENERGY CALCULATIONS.
  
 2)ENERGY CALCULATIONS NEED TO BE SIGNED BY
 OWNER/AGENT ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2007-08-10 Cont ID  
Sent By tgordon Date 2007-08-10 Time 10:35 Rev Time 0.40
Received By tgordon Date 2007-08-10 Time 10:35 Sent To  
Notes
2007-08-10 11:25:28PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** REVISION DENIED ***
 1) PLEASE SHOW CLOTHES DRYER VENTS ON PLAN AND STATE
 WERE THEY WILL DISCHARGE, SEE 2004 FBC/R M1501.1.
  
 2) SHOW BATHROOM EXHAUST FANS ON PLAN, SEE 2004 FBC/R
 R303.3.
  
 3) SHOW LOCATION OF A/C CONDENSER UNITS ON PLAN.
  
 4) SHOW ATTIC ACCESS ON PLANS FOR NEW AND RELOCATED AIR
 HANDLERS, SEE 2004 FBC/R M1305.1.3 REFERENCING 6 FT..
  
 5) ENERGY CALCULATIONS ON FILE STATE AIR HANDLER IN
 GARAGE, AS THE AIR HANDLER IS NOW BEING INSTALLED IN
 THE ATTIC THE ENERGY CALCULATIONS NEED TO BE REVISED.
 PLEASE SUBMIT REVISED ENERGY CALCULATIONS, SEE 2004 FBC
 13-103.1.2.
  
 6) BUILDING PLANS ON FILE SHOW A DOOR BETWEEN THE FRONT
 ENTRANCE AND THE KITCHEN, IF SO WHEN THE DOOR IS CLOSED
 THE 30X14 RETURN AIR GRILL COULD NOT RETURN AIR BACK TO
 THE AIR HANDLER, SEE 2004 FBC/R M1602.4. SEE YELLOW
 HIGH LIGHT AND NOTE ON PLAN FOR LOCATION. IF THEIR IS A
 DOOR RELOCATE GRILL, IF NO DOOR STATE SO ON PLAN.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-05-31 Cont ID  
Sent By tgordon Date 2007-05-31 Time 07:58 Rev Time 0.25
Received By tgordon Date 2007-05-31 Time 07:57 Sent To P
Notes
2007-05-31 08:04:48*** PROVISO ***
 1) DUCTS IN THE GARAGE AND DUCTS
 PENETRATING THE WALLS OR CEILINGS
 SEPARATING THE DWELLING FROM THE GARAGE
 SHALL BE CONSTRUCTED OF A MINIMUM NO. 26
 GAGE SHEET STEEL OR OTHER APPROVED
 MATERIAL AND SHALL HAVE NO OPENINGS INTO
 THE GARAGE. PER 2004 FBC/R 309.1.1 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-04-19 Cont ID  
Sent By tgordon Date 2007-04-19 Time 10:58 Rev Time 0.30
Received By tgordon Date 2007-04-19 Time 10:58 Sent To P
Notes
2007-04-19 10:59:23REVISION TO MECHANICAL PLANS AND E-CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-12-11 Cont ID  
Sent By jgomez Date 2006-12-11 Time 11:31 Rev Time 0.30
Received By tgordon Date 2006-12-11 Time 08:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-11-14 Cont ID  
Sent By tgordon Date 2006-11-14 Time 13:33 Rev Time 0.30
Received By tgordon Date 2006-11-14 Time 13:33 Sent To P
Notes
2006-11-14 13:42:07*** DENIED ***
 1) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN. PER FBC 104.2.1 .
  
 2) PLEASE SHOW LOCATION OF CONDENSER UNIT ON MECHANICAL
 PLANS.
  
 3) BUILDING PLANS SHOW TWO CLOTHES DRYERS IN THE
 LAUNDRY ROOM, PLEASE CORRECT MECHANICAL PLANS AND SHOW
 DRYER VENTS AND LOCATION OF VENT TERMINATION.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-06 Cont ID  
Sent By tgordon Date 2006-10-06 Time 09:50 Rev Time 0.30
Received By tgordon Date 2006-10-06 Time 09:50 Sent To B
Notes
2006-10-06 00:00:00*** DENIED ***
 1) NO MECHANICAL PLANS WERE SUBMITTED
 FOR REVIEW. PLEASE SUBMIT MECHANICAL
 PLANS FOR REVIEW, REQUIRED PER 2004 FBC
 WPB AMEND. 106.3.5.4 (10).
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT ALSO, PER 2004 FBC
 13-600.3.ABC.2 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 5 Status P Date 2007-09-18 Cont ID  
Sent By jleech Date 2007-09-18 Time 08:44 Rev Time 0.00
Received By jleech Date 2007-09-18 Time 08:44 Sent To  
Notes
2007-09-18 08:45:06REVISED RISER DIAGRAM AND CHANGED FLOOR PLAN.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-06-12 Cont ID  
Sent By jleech Date 2007-06-12 Time 08:03 Rev Time 0.00
Received By jleech Date 2007-06-12 Time 08:03 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-04-23 Cont ID  
Sent By jleech Date 2007-04-23 Time 13:33 Rev Time 0.00
Received By jleech Date 2007-04-23 Time 13:33 Sent To B
Notes
2007-04-23 13:34:25REVISED RISER DIAGRAM.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-11-22 Cont ID  
Sent By jleech Date 2006-11-22 Time 14:56 Rev Time 0.00
Received By jleech Date 2006-11-22 Time 14:56 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-10-04 Cont ID  
Sent By jleech Date 2006-10-04 Time 13:44 Rev Time 0.00
Received By jleech Date 2006-10-04 Time 13:44 Sent To M
Notes
2006-10-04 00:00:00DENIED;
 1.AUTOMATIC CLOTHES WASHER BRANCH DRAIN
 TO BE 3". FBC-2004 PLUMBING SECTION
 406.3. A CLEANOUT IS REQUIRED AT 48"
 ABOVE FINISH FLOOR.
 2.KITCHEN SINK TO DISCHARGE DOWN STREAM
 OF THE BATHROOM GROUP. SEC 909.1
 3.ONLY 3 FIXTURE UNITS PERMITED ON 1
 1/2" PIPE. TABLE 710.1(1).
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 5 Status P Date 2007-05-24 Cont ID  
Sent By adavila Date 2007-05-24 Time 17:52 Rev Time 0.00
Received By adavila Date 2007-05-24 Time 17:52 Sent To E
Notes
2007-05-24 17:52:33PER ERIC SCHNEIDER, PRINCIPAL PLANNER.

Review Stop Z ZONING
Rev No 4 Status F Date 2007-05-22 Cont ID  
Sent By adavila Date 2007-05-22 Time 16:45 Rev Time 0.00
Received By adavila Date 2007-05-21 Time 20:36 Sent To I
Notes
2007-05-22 16:46:54PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. NEED TO PROVIDE A COPY OF THE RECORDED UNITY OF
 TITLE OF THE SUBJECT PROPERTY AND THE PROPERTY TO THE
 SOUTH WHERE THE CABANA/POOL IS LOCATED (REPEAT
 COMMENT).
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 3 Status F Date 2007-04-13 Cont ID  
Sent By adavila Date 2007-04-13 Time 11:53 Rev Time 0.00
Received By adavila Date 2007-04-11 Time 11:52 Sent To I
Notes
2007-04-13 11:53:31PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. NEED TO PROVIDE TWO (2) SIGNED AND SEALED SURVEYS.
 SURVEY SHALL BE LESS THAN A YEAR OLD.
  
 2. NEED TO PROVIDE A COPY OF THE RECORDED UNITY OF
 TITLE OF THE SUBJECT PROPERTY AND THE PROPERTY TO THE
 SOUTH WHERE THE CABANA/POOL IS LOCATED.
  
 3. PROVIDE BUILDING HEIGHT DIMENSIONS FROM GRADE OF
 PROPOSED ADDITION.
  
 4. PROVIDE ROOF OVERHANG DIMENSION ON SHEET A8.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-11-06 Cont ID  
Sent By mmclean Date 2006-11-06 Time 11:53 Rev Time 0.00
Received By mmclean Date 2006-11-06 Time 11:53 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-09-16 Cont ID  
Sent By mmclean Date 2006-09-16 Time 13:16 Rev Time 0.00
Received By mmclean Date 2006-09-16 Time 13:16 Sent To I
Notes
2006-09-16 00:00:00DENIED,
 1. PLEASE PROVIDE THE REAR SETBACK OF
 THE PROPOSED ADDITION.
 2. PLEASE IDENTIFY THE ROOM THAT THE
 PROPOSED BATHROOMS IS CONNECTED. THE
 ROOM NOT IDENTIFIED, MUST HAVE INTERIOR
 ACCESS TO THE FAMILY ROOM.
 3. THE BATHROOM MUST HAVE INTERIOR
 ACCESS TO THE HOUSE. THE ONLY ACCESS IS
 EXTERIOR ONLY, NEED TO HAVE INTERIOR
 ACCESS.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720