| Plan Review Stops For Permit 06090295 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2007-06-12 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-06-12 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-06-12 |
Time |
09:59 |
Sent To |
PC |
|
| Notes |
| 2007-06-12 10:03:40 | BUILDING REVISION APPROVED WITH PROVISO: | | | 1- NEED TO PROVIDE VENTILATION IN CRAWLSPACE IN | | | CORNER AREAS AS REQUIRED BY SEC. R408.1 AND R408.2 OF | | | FLORIDA 2004 RESIDENTIAL CODE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2007-04-24 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-04-24 |
Time |
07:59 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-04-24 |
Time |
07:41 |
Sent To |
PC |
|
| Notes |
| 2007-04-24 08:38:35 | BUILDING REVISION CHECKLIST: | | | 1- SOUTH ELEVATIONDOESN'T MATCH FLOOR PLAN.SEE | | | WINDOWS BY BREAKFAST AREA. REVISE AS REQUIRED. | | | | | | 2- NEED TO PROVIDE SPECIFICATIONS AND DETAILS SHOWING | | | COMPLIANCE WITH CRAWL SPACE VENTILATION AND ACCESS AS | | | REQUIRED BY SECTIONS R408.1, R408.2, R408.3 AND R408.4 | | | OF 2004 FLORIDA RESIDENTIAL CODE. | | | | | | 3- CONTRACTOR TO UPDATE INSURANCE. SEE PERMIT CLERK. | | | | | | 4- ENERGY CALCULATIONS: | | | A) NEED TO USE REVISED FORM 600A-R. | | | | | | B) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. | | | | | | 5- WIND LOAD SCHEDULE ON SHEET A-5 NEED TO BE REVISED. | | | SEE REVISED DESIGN PRESSURES SUBMITTED ON LETTER DATED | | | FEBRUARY 6, 2007. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2007-03-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-03-07 |
Time |
17:10 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
2007-03-07 |
Time |
17:05 |
Sent To |
E |
|
| Notes |
| 2007-03-07 17:11:32 | THERE IS A NEW REVISED ELECTRICAL SHEET SUBMITTED IN | | | THIS PACKAGE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2007-01-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-01-29 |
Time |
15:09 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
2007-01-29 |
Time |
12:50 |
Sent To |
|
|
| Notes |
| 2007-01-29 14:35:54 | BUILDING REVISION CHECKLIST: | | | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE | | | 9B-72 FOR STRUCTURAL WINDOW MULLIONS. | | | ALSO, SPECIFY MULLION FASTENING TO VERIFY COMPLIANCE | | | WITH THE DESIGN PRESSURES OF SEC. R301 OF 2004 FLORIDA | | | RESIDENTIAL CODE. | | | | | | 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITTING | | | ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY | | | AMENDMENTS TO FBC 2004. | | | | | | 3- PROVIDE COMPLETE INFORMATION FOR SPIRAL STAIR TO | | | VERIFY COMPLIANCE WITH SEC. R311.5.8.1 2004 FLORIDA | | | RESIDENTIAL CODE . ALSO, PROVIDE COMPLETE INSTALLATION | | | DETAILS TO SHOW COMPLIANCE WITH WIND LOADS SEC. R301 | | | 2004 RESIDENTIAL CODE.SEC. 106.1.2 CITY AMENDMENTS TO | | | FBC 2004. | | | | | | 4-PROVIDE COMPLETE SPECS FOR GUARDRAIL TO SHOW | | | COMPLIANCE WITH SEC. R312 2004 FLORIDA RESIDENTIAL CODE | | | AND SEC. 1607.7.1 FBC 2004. | | | | | | 5- PROVIDE INFORMATION REQUESTED ON PROVISO DATED | | | 12/08/06. SEE ATTACHED COPY. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2006-12-11 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-12-08 |
Time |
16:30 |
Rev Time |
1.50 |
| Received By |
jgomez |
Date |
2006-12-08 |
Time |
16:30 |
Sent To |
M |
|
| Notes |
| 2006-12-08 16:38:33 | BUILDING REVIEW PROVISO: | | | 1- PROVIDE UPDATED NOA FOR PRECAST LINTELS. NOA | | | 03-0605.05 EXPIRED IN 05/21/06.. | | | 2- AS PER PHONE CONVERSATION WITH JOHN ANDERSEN, | | | PROVIDE COMPLETE INFORMATION FOR FLAT ROOF SYSTEM UNDER | | | A SEPARATE PERMIT AND FEES. SEE ATTACHED COPY OF CITY | | | POLICY FOR ROOFING PERMITS FOR REQUIRED INFORMATION. | | | | | | 3- PROVIDE COMPLETE TRUSS PACKAGE FOR REVIEW PRIOR | | | TO INSTALLATION. DESIGNER OF RECORD TO REVIEW AND | | | APPROVE IT PRIOR TO SUBMITTAL. SEE SEC. R802.10 FOR ALL | | | INFORMATION REQUIRED TO BE IN THE TRUSS PACKAGE. TWO | | | COPIES REQUIRED. | | | 4- WIND LOAD CHART: DESIGN PRESSURES FOR FLAT ROOF | | | AREAS ARE LOW IN COMPARISON WITH ASCE 7-02 AND TABLE | | | 1609.6B FBC 2004. PROVIDE ACTUAL CALCULATIONS TO VERIFY | | | COMPLIANCE WITH SEC. 1609 FBC 2004. SEC. 106.1.2 CITY | | | AMENDMENTS TO FBC 2004. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-11-27 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-11-27 |
Time |
15:00 |
Rev Time |
2.00 |
| Received By |
jgomez |
Date |
2006-11-27 |
Time |
15:00 |
Sent To |
|
|
| Notes |
| 2006-11-27 15:16:02 | BUILDING REVIEW 2ND CHECKLIST: | | | | | | 1- PAY IMPACT FEES TO PALM BEACH COUNTY. BRING BACK | | | STAMPED PLANS AND PAID RECEIPT. | | | | | | 2- SOIL TEST REPORT: | | | A) BOTH COPIES TO HAVE ORIGINAL ENGINEER'S SIGNATURE | | | (NO COPIES) AS REQUIRED BY CHAPTER 471 FLORIDA | | | STATUTES. | | | | | | B) NEED THE ENGINEERING FIRM CERTIFICATE OF | | | AUTHORIZATION NUMBER AS REQUIRED BY FLORIDA | | | ADMINISTRATIVE CODE SEC. 61G15-23.002. | | | | | | 3- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72 | | | FOR: | | | A) FRENCH DOOR. DADE COUNTY NOA #01-0417.04 | | | SUBMITTEDEXPIRED ON 11-22-06. | | | | | | B) PRECAST LINTELS. NO INFORMATION SUBMITTED. | | | | | | C) ROOF TILE. NO INFORMATION SUBMITTED. | | | | | | D) FLAT ROOF SYSTEMS. SEE PLANS. NO INFORMATION | | | SUBMITTED. | | | ***NOTE: NEED TO IDENTIFY SPECIFIC APPROVED ASSEMBLIES. | | | CHECK SYSTEM LIMITATIONS BECAUSE GENERAL LIMITATION #9 | | | MAY NOT BE USED IN THIS AREA. IF SYSTEM IS LIMITED BY | | | GENERAL LIMITATION #7, THEN PROVIDE REQUIRED | | | INFORMATION. SEE LAST PAGE OF NOA TO CHECK GENERAL | | | LIMITATIONS. | | | | | | E) ALL USP OR SIMPSON CONNECTORS SPECIFIED ON | | | PLANS. | | | | | | F) WINDOWS WERE REVISED FROM CASEMENT WINDOWS TO | | | SINGLE HUNG WINDOWS.ONLY THE FLORIDA PRODUCT APPROVAL | | | COVER PAGES WERE SUBMITTED. NEED TO PROVIDE COMPLETE | | | WINDOW DRAWINGS PACKAGE ALSO. | | | | | | 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOSIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. | | | | | | 5-DETAIL A/A3 DOESN'T COMPLY WITH SEC. R311.5.3.2 | | | 2004 FLORIDA RESIDENTIAL CODE. 7" RISERS AND 12" DON'T | | | COMPLY WITH THE 24 TO 25 RISER TREAD RATIO. REVISE AS | | | REQUIRED. | | | | | | 6- SHEET A-4:CLARIFY WHY TREAD DIMENSIONS ON STAIRS | | | BY BREAKFAST AREAARE DIFFERENT FROM TREAD DIMENSIONS | | | ON OTHER STAIRS. ALSO, COORDINATE DIMENSIONS WITH | | | DETAIL A/A3 REVISION. | | | | | | 7- SHEET A-5: | | | A) WIND LOAD SCHEDULE CHART IS INCOMPLETE. IT | | | DOESN'T SPECIFY THE WIND LOAD FOR THIS AREA AND THE | | | EXPOSURE TYPE AS REQUIRED BY SEC. R301 2004 RESIDENTIAL | | | CODE.ALSO, MISSING THE DESIGN PRESSURES FOR FLAT | | | ROOF. SEE TABLE 1609.6B FBC 2004. | | | | | | B) ROOF SHEATHING NAILING SCHEDULE DOESN'T MATCH | | | INFORMATION GIVEN ON SHEET A-8 WALL SECTION "A". REVISE | | | AS REQUIRED. | | | | | | 8- PROVIDE COMPLETE DETAILS AND SPECS FOR RAILING, | | | INCLUDING FASTENING TO ROOF SYSTEM AS REQUIRED BY SEC. | | | 1607.7.1 FBC 2004 AND SEC. 106.1.2 CITY AMENDMENTS TO | | | FBC 2004. | | | | | | 9- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS | | | REQUIRED BY SEC. 106.1.1.2 CITY AMENDMENTS TO FBC 2004. | | | INFORMATION NO PROVIDED. | | | | | | 10- WALL SECTION "A" ON SHEET A-8 DOENS'T SHOW OR | | | SPECIFY ATTIC VENTILATION. PROVIDE INFORMATION AS | | | REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-10-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-10-13 |
Time |
16:56 |
Rev Time |
2.50 |
| Received By |
jgomez |
Date |
2006-10-13 |
Time |
16:56 |
Sent To |
|
|
| Notes |
| 2006-10-16 11:07:40 | BUILDING REVIEW CHECKLIST: | | | 1- PAY IMPACT FEES TO PALM BEACH COUNTY. BRING BACK | | | STAMPED PLANS AND PAID RECEIPT. | | | | | | 2- PROVIDE SOIL TEST REPORT. | | | | | | 3- PROVIDE FLORIDA OR LOCAL PRODUCT APPROVAL AS | | | REQUIRED BY RULE 9B-72 FOR (GO TO THE DCA WEBSITE | | | WWW.FLORIDABUILDING.ORG TO DOWNLOAD ALL FLORIDA PRODUCT | | | APPROVALS): | | | A) CASEMENT WINDOWS. PROVIDE FLORIDA PRODUCT APPROVAL | | | COVER PAGE FOR FL-245 WHICH IS THE ONE THAT MATCHES | | | SELECTED NOA. | | | B) FRENCH DOORS. PROVIDE FLORIDA PRODUCT APPROVAL | | | COVER PAGE FL-253 AND CORRESPONDING NOA NO 02-0701.12 | | | WHICH IS THE ONE SUBMITTED FOR FLORIDA PRODUCT | | | APPROVAL. | | | C) PRECAST LINTELS SPECIFIED ON PLANS. | | | D) ROOF TILE. | | | E) FLAT ROOF SYSTEM. NOTE: CLEARLY IDENTIFY SPECIFIC | | | APPROVED ASSEMBLY TO BE INSTALLED. CHECK IF SELECTED | | | ASSEBLY IS LIMITED BY GENERAL LIMITATION #7 OR #9. SEE | | | GENERAL LIMITATIONS ON LAST PAGE OF NOA AND PROVIDE | | | REQUIRED INFORMATION. | | | F) ALL USP OR SIMPSON CONNECTORS SPECIFIED ON PLANS. | | | SEE PLANS AND DETAILS. | | | | | | 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITTING | | | ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY | | | AMENDMENTS TO FBC 2004. | | | | | | 5- OWNER/AGENT TO SIGN AND DATE THE ENERGY | | | CALCULATIONS. | | | | | | 6- ENGINEER TO PROVIDE ALL DESIGN CRITERIA REQUIRED BY | | | SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE. INCLUDE | | | SPCIFIC CODE AND ALL DESIGN LOADS INCLUDING LIVE, DEAD | | | AND ATTIC LOADS. SEE TABLE R301.5 2004 FLORIDA | | | RESIDENTIAL CODE. | | | | | | 7- SHEET A-3: | | | A) PROVIDE COMPLETE SPECS FOR ALL THREE LANDING AND | | | STEPS. NEED DIMENSIONS INCLUDING RISER AND TREADS TO | | | VERIFY COMPLIANCE WITH SEC. R311.5.3.2 2004 FLORIDA | | | RESIDENTIAL CODE. | | | B) SPECIFY CONNECTOR AT THE ENDS OF (3)2X12 BEAM. | | | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. | | | | | | 8- SHEET A-4: | | | A) SPECIFY SIZE AND TYPE OF NEW WINDOWS. AND ALL NEW | | | DOORS SIZES. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. | | | B) SPECIFY SAFETY GLAZING FOR WINDOW IN BATH LOCATED ON | | | THE EAST CORNER. SEC. R308.4 2004 FLORIDA RESIDENTIAL | | | CODE. | | | | | | 9- SHEET A-5: | | | A) PROVIDE COMPLETE SPECS FOR ROOF CONSTRUCTION AT | | | FLAT AREA ABOVE NEW BATH LOCATED ON THE EAST CORNER. | | | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. | | | B) PROVIDE COMPLETE DRAWINGS AND SPECS SHOWING | | | LANDING FOR SPIRAL STAIRCASE. SEC. 106.1.2 CITY | | | AMENDMENTS TO FBC 2004. | | | C) PROVIDE COMPLETE DETAILS AND SPECS FOR RAILING TO | | | VERIFY COMPLIANCE WITH SEC R312 2004 FLORIDA | | | RESIDENTIAL CODE. | | | D) PROVIDE COMPLETE DRAWINGS AND SPECS FOR SPIRAL | | | STAIRCASE TO VERIFY COMPLIANCE WITH SEC. R311.5.8 2004 | | | FLORIDA RESIDENTIAL CODE. | | | | | | 10- SHEET A-6: | | | A) WEST ELEVATION IS INCOMPLETE BY SPIRAL STAIRCASE. | | | MISSING ROOF AREA. PROVIDE COMPLETE INFORMATION. | | | B) PROVIDE STRUCTURAL BUCK DETAILS FOR DOORS AND | | | WINDOWS. SPECIFY FASTENERS. SEC. R613.6.2 2004 | | | RESIDENTIAL CODE. | | | | | | 11- PROVIDE VENTILATION CALCULATIONS AND LOCATION AND | | | SIZE OF ROOF VENTS INCLUDING AT FLAT ROOF AS REQUIRED | | | BY SEC. R806 2004 FLORIDA RESIDENTIAL CODE. | | | | | | 12- OWES $13.30 FOR RADON FEES. | | | | | | 13- SPECIFY ROOF TILE FASTENING AS REQUIRED BY SEC. | | | 106.1.1.2 CITY AMENDMENTS TO FBC 2004. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
9 |
Status |
P |
Date |
2007-11-28 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-11-28 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-11-28 |
Time |
12:58 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
P |
Date |
2007-06-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-06-20 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-06-20 |
Time |
15:37 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
F |
Date |
2007-05-30 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-05-30 |
Time |
16:18 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2007-05-30 |
Time |
15:43 |
Sent To |
M |
|
| Notes |
| 2007-05-30 16:18:08 | | | | | | | | | | REVISION DENIED/INCOMPLETE INFORMATION | | | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417 | | | FS, RESPECTIVELY. | | | | | | 2} LABEL THE PANELS. | | | | | | 3} LOCATE PANELS ON THE PLAN. PROVIDE A SITE PLAN IF | | | NECESSARY. MORE PANELS ARE ADDED AND NO RECORD OF THEIR | | | LOCATIONS. 106.1.3 FBC. | | | | | | 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH | | | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2007-04-19 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-04-19 |
Time |
09:17 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2007-04-19 |
Time |
08:45 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2007-03-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-03-08 |
Time |
07:22 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2007-03-08 |
Time |
06:59 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2007-01-29 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-01-29 |
Time |
09:57 |
Rev Time |
0.75 |
| Received By |
btrobaug |
Date |
2007-01-29 |
Time |
06:51 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-12-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-12-08 |
Time |
07:10 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-12-07 |
Time |
16:21 |
Sent To |
P |
|
| Notes |
| 2006-12-08 07:10:20 | | | | PROVISO | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW PRIOR TO ANY | | | ELECTRICAL INSPECTIONS. | | | | | | 1} THE SERVICE IS LOCATED REMOTE FROM THE RESIDENCE ON | | | SHEET A-1, THEREFORE A DISCONNECTING MEANS PER 225.31, | | | LOCATED PER 250.32 AND GROUNDED PER 250.32 IS REQUIRED | | | AT THE RESIDENSE. THE PANEL(S) INDICATED AS MLO ON THE | | | RISER DO NOT MEET THESE REQUIREMENTS. PLEASE CORRECT, | | | AND RESUBMIT FOR REVIEW. | | | | | | THE REVIEWED PLAN MUST BE ON THE JOB | | | SITE AT TIME OF INSPECTION. ALLOW AT | | | LEAST ONE WEEK (PER TRADE) FOR PLAN | | | REVIEW. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-11-14 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-11-14 |
Time |
11:36 |
Rev Time |
0.75 |
| Received By |
btrobaug |
Date |
2006-11-14 |
Time |
10:21 |
Sent To |
M |
|
| Notes |
| 2006-11-14 11:36:04 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE SERVICE IS LOPCATED REMOTE FROM THE RESIDENCE ON | | | SHEET A-1, THEREFORE A DISCONNECTING MEANS PER 225.31, | | | LOCATED PER 250.32 AND GROUNDED PER 250.32 IS REQUIRED | | | AT THE RESIDENSE. THE PANEL(S) INDICATED AS MLO ON THE | | | RISER DO NOT MEET THESE REQUIREMENTS. PLEASE CORRECT. | | | | | | 2} THE GROUNDING ELECTRODE CONDUCTOR SIZE PER 250.66 IS | | | NOT INDICATED ON THE RISER. ALSO THE REFERENCE TO A #5 | | | DRIVEN GROUND ROD IS INCORRECT. | | | | | | 3} THE KITCHEN COUNTERRECEPTACLES, INCLUDING THE | | | ISLAND, MUST BE GFI PROTECTEDPER 210.8(A)(7), INDICATE | | | THE SAME ON THE DRAWINGS. | | | | | | 4} A RECEPTACLE IS REQUIRED FOR SERVICING THE | | | CONDENSING UNITS PER 210.63. PLACE ON PLAN. | | | | | | 5} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH | | | R313.1 RESIDENTIAL FLORIDA BUILDING CODE. THIS IS THE | | | SECOND TIME THIS COMMENT HAS BEEN MADE. PLEASE ADDRESS, | | | LOCATE ON THE PLAN. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-10-04 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-10-04 |
Time |
09:53 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2006-09-28 |
Time |
12:38 |
Sent To |
P |
|
| Notes |
| 2006-09-28 00:00:00 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR | | | THE DESIGN MUST PRINT AND SIGN THEIR | | | NAME TO SAME PER 106.3.4.2. | | | | | | 2} PROVIDE A LOAD CALCULATION PER | | | 220.31, INCLUDE ADDED LOADS. | | | | | | 3} SUBMIT A PANEL SCHEDULE PER 408.4 NEC | | | AND 106.3.5.4(8) FBC. | | | | | | 4} INDICATE THE RATING OF THE EXISTING | | | SERVICE. | | | | | | 5} KITCHEN RECEPTACLE SPACING MUST | | | COMPLY WITH 210.52(C), SEE REVIEWED | | | PLAN, NORTH, EAST AND WEST COUNTER | | | LOCATIONS. | | | | | | 6} BATH CIRCUIT REQUIRED TO HAVE A 20 | | | AMP RECEPTACLE PER 210.11(C) (3), | | | LOCATED PER 210.52(D), AND BE GFI | | | PROTECTED PER 210.8(A)(1). | | | | | | 7} SUNROOM REQUIRED TO HAVE RECEPTACLES | | | PER 210.52(A)(1) AND (2). SEE REVIEWED | | | SET FOR APPROXIMATE LOCATIONS. | | | | | | 8} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH | | | R313.1 RESIDENTIAL FLORIDA BUILDING CODE. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
16 |
Status |
N |
Date |
2007-11-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-21 |
Time |
12:38 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-21 |
Time |
12:38 |
Sent To |
E |
|
| Notes |
| 2007-11-21 12:38:55 | TO "BTROBAUG" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
15 |
Status |
N |
Date |
2007-09-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-05 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-05 |
Time |
12:00 |
Sent To |
P |
|
| Notes |
| 2007-09-05 12:00:35 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
14 |
Status |
N |
Date |
2007-08-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-27 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-27 |
Time |
13:23 |
Sent To |
M |
|
| Notes |
| 2007-08-27 13:23:28 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
13 |
Status |
N |
Date |
2007-08-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-08 |
Time |
18:02 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-08 |
Time |
18:02 |
Sent To |
M |
|
| Notes |
| 2007-08-08 18:02:55 | TO TG'S DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2007-06-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-15 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-15 |
Time |
10:58 |
Sent To |
E |
|
| Notes |
| 2007-06-15 10:58:44 | TO "BTROBAUG" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2007-05-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-23 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-23 |
Time |
11:47 |
Sent To |
E |
|
| Notes |
| 2007-05-23 11:47:35 | TO "BTROBAUG" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2007-05-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-05-21 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-05-21 |
Time |
14:56 |
Sent To |
Z |
|
| Notes |
| 2007-05-21 14:56:35 | TO "Z" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2007-04-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-16 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-16 |
Time |
14:13 |
Sent To |
E |
|
| Notes |
| 2007-04-16 14:14:17 | TO "BTROBAUG" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2007-04-04 |
|
|
Cont ID |
|
| Sent By |
spalmer |
Date |
2007-04-04 |
Time |
17:37 |
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2007-04-04 |
Time |
17:37 |
Sent To |
Z |
|
| Notes |
| 2007-04-04 17:38:07 | TO ZONING |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2007-03-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-02 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-02 |
Time |
13:13 |
Sent To |
E |
|
| Notes |
| 2007-03-02 13:17:40 | TO "BTROBAUG" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-01-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-20 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-20 |
Time |
11:36 |
Sent To |
Z |
|
| Notes |
| 2007-01-20 11:36:25 | TO "Z" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-12-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-01 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-01 |
Time |
14:49 |
Sent To |
Z |
|
| Notes |
| 2006-12-01 14:49:22 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-11-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-11-08 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-08 |
Time |
13:38 |
Sent To |
E |
|
| Notes |
| 2006-11-08 13:38:56 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-11-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-11-01 |
Time |
17:17 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-01 |
Time |
17:17 |
Sent To |
Z |
|
| Notes |
| 2006-11-01 17:17:42 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-09-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-18 |
Time |
14:54 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-18 |
Time |
14:54 |
Sent To |
E |
|
| Notes |
| 2006-09-18 00:00:00 | TO "E" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-10-13 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-10-13 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2006-09-12 |
Time |
08:48 |
Sent To |
|
|
| Notes |
| 2006-09-12 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
7 |
Status |
F |
Date |
2007-09-04 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-09-04 |
Time |
15:36 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-09-04 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2007-09-04 15:51:40 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA | | | ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS). | | | | | | MECHANICAL REVISION | | | *** DENIED *** | | | 1) REVISED ENERGY CALCULATIONS LINE 15 IS TAKING A | | | CREDIT FOR CEILING FANS, REVISED ELECTRICAL PLANS ON | | | FILE SHOW NO CEILING FANS TO BE INSTALLED. PER 2004 FBC | | | 13-607.2.A.3.1.CEILING FAN CREDIT MAY BE TAKEN IF ONE | | | OR MORE CEILING FANS ARE INSTALLED IN EACH OF THE | | | BEDROOMS AND A MINIMUM OF ONE CEILING FAN IS INSTALLED | | | IN ALL PRIMARY LIVING AREAS (LIVING ROOMS, FAMILY | | | ROOMS, OR GREAT ROOMS). PRESCRIPTIVE REQUIREMENTS IN | | | SECTION 13-607.1.A.1 SHALL BE MET. PLEASE REVISE | | | ELECTRICAL PLANS TO SHOW CEILING FANS (NOT JUST | | | JUNCTION BOX) AND SUBMIT WITH THIS REVISION OR CORRECT | | | ENERGY CALCULATIONS. | | | | | | 2)ENERGY CALCULATIONS NEED TO BE SIGNED BY | | | OWNER/AGENT ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
F |
Date |
2007-08-10 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-08-10 |
Time |
10:35 |
Rev Time |
0.40 |
| Received By |
tgordon |
Date |
2007-08-10 |
Time |
10:35 |
Sent To |
|
|
| Notes |
| 2007-08-10 11:25:28 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER | | | 1 CITY OF WEST PALM BEACH AMENDMENTS. | | | | | | *** REVISION DENIED *** | | | 1) PLEASE SHOW CLOTHES DRYER VENTS ON PLAN AND STATE | | | WERE THEY WILL DISCHARGE, SEE 2004 FBC/R M1501.1. | | | | | | 2) SHOW BATHROOM EXHAUST FANS ON PLAN, SEE 2004 FBC/R | | | R303.3. | | | | | | 3) SHOW LOCATION OF A/C CONDENSER UNITS ON PLAN. | | | | | | 4) SHOW ATTIC ACCESS ON PLANS FOR NEW AND RELOCATED AIR | | | HANDLERS, SEE 2004 FBC/R M1305.1.3 REFERENCING 6 FT.. | | | | | | 5) ENERGY CALCULATIONS ON FILE STATE AIR HANDLER IN | | | GARAGE, AS THE AIR HANDLER IS NOW BEING INSTALLED IN | | | THE ATTIC THE ENERGY CALCULATIONS NEED TO BE REVISED. | | | PLEASE SUBMIT REVISED ENERGY CALCULATIONS, SEE 2004 FBC | | | 13-103.1.2. | | | | | | 6) BUILDING PLANS ON FILE SHOW A DOOR BETWEEN THE FRONT | | | ENTRANCE AND THE KITCHEN, IF SO WHEN THE DOOR IS CLOSED | | | THE 30X14 RETURN AIR GRILL COULD NOT RETURN AIR BACK TO | | | THE AIR HANDLER, SEE 2004 FBC/R M1602.4. SEE YELLOW | | | HIGH LIGHT AND NOTE ON PLAN FOR LOCATION. IF THEIR IS A | | | DOOR RELOCATE GRILL, IF NO DOOR STATE SO ON PLAN. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL: [email protected]. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2007-05-31 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-05-31 |
Time |
07:58 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-05-31 |
Time |
07:57 |
Sent To |
P |
|
| Notes |
| 2007-05-31 08:04:48 | *** PROVISO *** | | | 1) DUCTS IN THE GARAGE AND DUCTS | | | PENETRATING THE WALLS OR CEILINGS | | | SEPARATING THE DWELLING FROM THE GARAGE | | | SHALL BE CONSTRUCTED OF A MINIMUM NO. 26 | | | GAGE SHEET STEEL OR OTHER APPROVED | | | MATERIAL AND SHALL HAVE NO OPENINGS INTO | | | THE GARAGE. PER 2004 FBC/R 309.1.1 . | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2007-04-19 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-04-19 |
Time |
10:58 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-04-19 |
Time |
10:58 |
Sent To |
P |
|
| Notes |
| 2007-04-19 10:59:23 | REVISION TO MECHANICAL PLANS AND E-CAL'S. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2006-12-11 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-12-11 |
Time |
11:31 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-12-11 |
Time |
08:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2006-11-14 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-11-14 |
Time |
13:33 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-11-14 |
Time |
13:33 |
Sent To |
P |
|
| Notes |
| 2006-11-14 13:42:07 | *** DENIED *** | | | 1) ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA | | | SHALL BEAR THE PRINTED NAME AND | | | SIGNATURE OF THE PERSON RESPONSIBLE | | | FOR THE DESIGN. PER FBC 104.2.1 . | | | | | | 2) PLEASE SHOW LOCATION OF CONDENSER UNIT ON MECHANICAL | | | PLANS. | | | | | | 3) BUILDING PLANS SHOW TWO CLOTHES DRYERS IN THE | | | LAUNDRY ROOM, PLEASE CORRECT MECHANICAL PLANS AND SHOW | | | DRYER VENTS AND LOCATION OF VENT TERMINATION. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-10-06 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-10-06 |
Time |
09:50 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-10-06 |
Time |
09:50 |
Sent To |
B |
|
| Notes |
| 2006-10-06 00:00:00 | *** DENIED *** | | | 1) NO MECHANICAL PLANS WERE SUBMITTED | | | FOR REVIEW. PLEASE SUBMIT MECHANICAL | | | PLANS FOR REVIEW, REQUIRED PER 2004 FBC | | | WPB AMEND. 106.3.5.4 (10). | | | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED | | | BY OWNER/AGENT ALSO, PER 2004 FBC | | | 13-600.3.ABC.2 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2007-09-18 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-09-18 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-09-18 |
Time |
08:44 |
Sent To |
|
|
| Notes |
| 2007-09-18 08:45:06 | REVISED RISER DIAGRAM AND CHANGED FLOOR PLAN. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2007-06-12 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-06-12 |
Time |
08:03 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-06-12 |
Time |
08:03 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2007-04-23 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-04-23 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-04-23 |
Time |
13:33 |
Sent To |
B |
|
| Notes |
| 2007-04-23 13:34:25 | REVISED RISER DIAGRAM. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2006-11-22 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-11-22 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-11-22 |
Time |
14:56 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-10-04 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-10-04 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-10-04 |
Time |
13:44 |
Sent To |
M |
|
| Notes |
| 2006-10-04 00:00:00 | DENIED; | | | 1.AUTOMATIC CLOTHES WASHER BRANCH DRAIN | | | TO BE 3". FBC-2004 PLUMBING SECTION | | | 406.3. A CLEANOUT IS REQUIRED AT 48" | | | ABOVE FINISH FLOOR. | | | 2.KITCHEN SINK TO DISCHARGE DOWN STREAM | | | OF THE BATHROOM GROUP. SEC 909.1 | | | 3.ONLY 3 FIXTURE UNITS PERMITED ON 1 | | | 1/2" PIPE. TABLE 710.1(1). | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
2007-05-24 |
|
|
Cont ID |
|
| Sent By |
adavila |
Date |
2007-05-24 |
Time |
17:52 |
Rev Time |
0.00 |
| Received By |
adavila |
Date |
2007-05-24 |
Time |
17:52 |
Sent To |
E |
|
| Notes |
| 2007-05-24 17:52:33 | PER ERIC SCHNEIDER, PRINCIPAL PLANNER. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
2007-05-22 |
|
|
Cont ID |
|
| Sent By |
adavila |
Date |
2007-05-22 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
adavila |
Date |
2007-05-21 |
Time |
20:36 |
Sent To |
I |
|
| Notes |
| 2007-05-22 16:46:54 | PLANNING AND ZONING DEPARTMENT | | | | | | ***FAILED*** | | | | | | 1. NEED TO PROVIDE A COPY OF THE RECORDED UNITY OF | | | TITLE OF THE SUBJECT PROPERTY AND THE PROPERTY TO THE | | | SOUTH WHERE THE CABANA/POOL IS LOCATED (REPEAT | | | COMMENT). | | | | | | COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC | | | SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2007-04-13 |
|
|
Cont ID |
|
| Sent By |
adavila |
Date |
2007-04-13 |
Time |
11:53 |
Rev Time |
0.00 |
| Received By |
adavila |
Date |
2007-04-11 |
Time |
11:52 |
Sent To |
I |
|
| Notes |
| 2007-04-13 11:53:31 | PLANNING AND ZONING DEPARTMENT | | | | | | ***FAILED*** | | | | | | 1. NEED TO PROVIDE TWO (2) SIGNED AND SEALED SURVEYS. | | | SURVEY SHALL BE LESS THAN A YEAR OLD. | | | | | | 2. NEED TO PROVIDE A COPY OF THE RECORDED UNITY OF | | | TITLE OF THE SUBJECT PROPERTY AND THE PROPERTY TO THE | | | SOUTH WHERE THE CABANA/POOL IS LOCATED. | | | | | | 3. PROVIDE BUILDING HEIGHT DIMENSIONS FROM GRADE OF | | | PROPOSED ADDITION. | | | | | | 4. PROVIDE ROOF OVERHANG DIMENSION ON SHEET A8. | | | | | | COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC | | | SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2006-11-06 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-11-06 |
Time |
11:53 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-11-06 |
Time |
11:53 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2006-09-16 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-09-16 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-09-16 |
Time |
13:16 |
Sent To |
I |
|
| Notes |
| 2006-09-16 00:00:00 | DENIED, | | | 1. PLEASE PROVIDE THE REAR SETBACK OF | | | THE PROPOSED ADDITION. | | | 2. PLEASE IDENTIFY THE ROOM THAT THE | | | PROPOSED BATHROOMS IS CONNECTED. THE | | | ROOM NOT IDENTIFIED, MUST HAVE INTERIOR | | | ACCESS TO THE FAMILY ROOM. | | | 3. THE BATHROOM MUST HAVE INTERIOR | | | ACCESS TO THE HOUSE. THE ONLY ACCESS IS | | | EXTERIOR ONLY, NEED TO HAVE INTERIOR | | | ACCESS. | | | | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|