Plan Review Details - Permit 06090292
Plan Review Stops For Permit 06090292
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-11-21 Cont ID  
Sent By lmartine Date 2006-11-21 Time 08:12 Rev Time 0.00
Received By lmartine Date 2006-11-21 Time 08:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-15 Cont ID  
Sent By alange Date 2006-11-15 Time 11:07 Rev Time 0.00
Received By alange Date 2006-11-13 Time 16:42 Sent To  
Notes
2006-11-15 11:09:06DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE AND A COPY
 SUBMITTED TO THIS OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT OR CONSTRUCTION IS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING.
  
 4.SIGN OWNER/AGENT ON ENERGY CALCS PER 2004 FBC.
  
 5.PRODUCT APPROVALS FOR GAF BITUMEN ROOF ARE MISSING
 PAGES.ALSO SELECT THE ASSEMBLY USED ON THE PRODUCT
 APPROVAL.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH QUALITY
 ASSURANCE SHALL HAVE THE FOLLOWING STATE APPROVAL
 ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL SHEETS THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM THE STATE. IF
 THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT AN
 APPLICATION FOR LOCAL PRODUCT APPROVAL OR SITE SPECIFIC
 FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.WPB AMENDMENT TO FBC
 106.3.3.
  
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS FOR REVIEW PER
 2004 FBC R-802.10.1TRUSS DRAWING REQUIRED TO BE
 APPROVED PRIOR TO INSTALLATION.
  
 9.A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR
 A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.SHOW HOW PLANS
 WILL COMPLY WITH THE SECTION(S) SELECTED.2004 FBC
 EXISTING BUILDING 301.5
  
 10.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHESWITHIN THE FIRST 10 FEET.
  
 11.DESIGN BUILDING FOR EITHER FLAT ROOFOR SLOPED
 ROOF.NOT BOTH ON THE SAME PLANS.
  
 13.SUBMIT TWO ORIGONAL SIGNED AND SEALED SURVEYS FS
 472.025
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. SUBMIT ONE
 COPY OF OLD PAGES FOR REFERENCE . A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DEPARTMENT
 561-805-6672
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-13 Cont ID  
Sent By alange Date 2006-10-13 Time 09:14 Rev Time 2.00
Received By alange Date 2006-10-13 Time 09:14 Sent To  
Notes
2006-10-13 09:21:05DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE AND A COPY
 SUBMITTED TO THIS OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT OR CONSTRUCTION IS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.BASED ON ICC BUILDING VALUATION DATA THE PERMIT
 VALUE HAS BEEN REVISED TO $30,483.00.ADDITIONAL
 PERMIT FEES ARE DUE.
  
 4.SIGN OWNER/AGENT ON ENERGY CALCS PER 2004 FBC.
  
 5.PRODUCT APPROVALS FOR GAF BITUMEN ROOF ARE MISSING
 PAGES.ALSO SELECT THE ASSEMBLY USED ON THE PRODUCT
 APPROVAL.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH QUALITY
 ASSURANCE SHALL HAVE THE FOLLOWING STATE APPROVAL
 ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL SHEETS THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM THE STATE. IF
 THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT AN
 APPLICATION FOR LOCAL PRODUCT APPROVAL OR SITE SPECIFIC
 FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.WPB AMENDMENT TO FBC
 106.3.3.
  
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS FOR REVIEW PER
 2004 FBC R-802.10.1TRUSS DRAWING REQUIRED TO BE
 APPROVED PRIOR TO INSTALLATION.
  
 9.A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR
 A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.SHOW HOW PLANS
 WILL COMPLY WITH THE SECTION(S) SELECTED.2004 FBC
 EXISTING BUILDING 301.5
  
 10.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHESWITHIN THE FIRST 10 FEET.
  
 11.DESIGN BUILDING FOR EITHER FLAT ROOFOR SLOPED
 ROOF.NOT BOTH ON THE SAME PLANS.
  
 12.SHOW SLAB TIE-IN DETAIL FROM EXISTING SLAB TO
 NEW.
  
 13.SUBMIT TWO ORIGONAL SIGNED AND SEALED SURVEYS FS
 472.025
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. SUBMIT ONE
 COPY OF OLD PAGES FOR REFERENCE . A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DEPARTMENT
 561-805-6672
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-09-28 Cont ID  
Sent By btrobaug Date 2006-09-28 Time 06:57 Rev Time 0.50
Received By btrobaug Date 2006-09-27 Time 18:23 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-01 Cont ID  
Sent By adarroug Date 2006-11-01 Time 14:50 Rev Time 0.00
Received By adarroug Date 2006-11-01 Time 14:50 Sent To M
Notes
2006-11-01 14:50:53TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-20 Cont ID  
Sent By adarroug Date 2006-09-20 Time 14:15 Rev Time 0.00
Received By adarroug Date 2006-09-20 Time 14:15 Sent To E
Notes
2006-09-20 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-13 Cont ID  
Sent By alange Date 2006-10-13 Time 09:21 Rev Time 0.00
Received By alange Date 2006-09-12 Time 09:46 Sent To  
Notes
2006-09-12 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2006-11-20 Cont ID  
Sent By pkrauss Date 2006-11-20 Time 11:23 Rev Time 0.00
Received By pkrauss Date 2006-11-20 Time 11:23 Sent To  
Notes
2006-11-20 11:25:28 
 NO MECHANICAL WORK OR CONTRACTOR INDICATED FOR THE 300
 SQ FT ADDITION.PLEASE PROVIDE MECHANICAL PLANS WITH
 A/C EQUIPMENT INFORMATION WITH MECHANICAL PERMIT
 APPLICATION.FORM 600C SUBMITTED W/BUILDING PERMIT
 WITH NO A/C INDICATED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-11-03 Cont ID  
Sent By pkrauss Date 2006-11-03 Time 07:10 Rev Time 0.00
Received By pkrauss Date 2006-11-03 Time 07:10 Sent To  
Notes
2006-11-03 07:16:23DENIED:
 COMMMENT FROM REVIEW DATED 10-06-06 WERE NOT ADDRESSED
 (SEE ATTACHED)
  
 1.PLEASE NOTE, FORM 600C WAS SUBMITTED FOR THE ENERGY
 CALCULATIONS.ITEM #11 & 12 WERE NOT COMPLETED.TWO
 COPIES ARE REQUIRED TO BE SUBMITTED FOR APPROVAL PER
 CITY AMENDMENTS TO THE 2004 FBC 106.1.
  
 2.PLEASE ALSO NOTE, NO MECHANICAL PLANS OR CONTRACTOR
 INDICATED WITH PERMIT APPLICATION.PLEASE PROVIDE
 PLANS AND EQUIPMENT SCHEDULE INDICATING IF SYSTEMS IS
 NEW OR EXISTING, WITH MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-06 Cont ID  
Sent By tgordon Date 2006-10-06 Time 10:40 Rev Time 0.20
Received By tgordon Date 2006-10-06 Time 10:40 Sent To B
Notes
2006-10-06 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT ALSO, PER 2004 FBC
 13-600.3.ABC.2.
  
 2) PLEASE SUBMIT TWO COPYS OF ENERGY
 CALCULATIONS, ONLY ONE HAS BEEN
 SUBMITTED.
  
 3) NO MECHANICAL PLANS WERE SUBMITTED
 FOR REVIEW. PLEASE SUBMIT MECHANICAL
 PLANS FOR REVIEW, REQUIRED PER 2004 FBC
 WPB AMEND. 106.3.5.4, IF NO A/C WORK IS
 TO BE DONE PLEASE STATE SO ON PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-10-04 Cont ID  
Sent By jleech Date 2006-10-04 Time 13:03 Rev Time 0.00
Received By jleech Date 2006-10-04 Time 13:03 Sent To M
Notes
2006-10-04 00:00:00NO PLUMBING TO BE INSTALLED. RISER
 DIAGRAM SHOWN ON PLANS IS EXISTING.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-09-16 Cont ID  
Sent By mmclean Date 2006-09-16 Time 15:34 Rev Time 0.00
Received By mmclean Date 2006-09-16 Time 15:33 Sent To I
Notes
***NONE***