| Plan Review Stops For Permit 06090272 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2008-12-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-12-22 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-12-22 |
Time |
14:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2008-07-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-07-17 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-07-17 |
Time |
16:47 |
Sent To |
|
|
| Notes |
| 2008-07-17 16:50:54 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.AS THIS IS A PROJECT, THIS PLAN REVIEW MUST REMAIN | | | IN FAIL STATUS UNTIL A CONTRACTOR LICENSED TO DO THIS | | | WORK APPLIES FOR PERMIT. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2008-05-05 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2008-05-05 |
Time |
17:27 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2008-05-05 |
Time |
17:27 |
Sent To |
|
|
| Notes |
| 2008-05-05 17:28:19 | COMPLY WITH SAMANTHA'S NOTES FROM PREVIOUS REVIEW | | | LM |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2008-02-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-02-22 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-02-22 |
Time |
10:21 |
Sent To |
|
|
| Notes |
| 2008-02-22 10:22:23 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | PLAN CHECK ONLY - | | | | | | 1.PERMIT APPLICATION REQUIRED | | | | | | 2.PLANS APPEAR CODE COMPLIANT AND WILL GET A PASS | | | WITH PROVISO (REVISE OCCUPANCY CLASSIFICATION ON PLAN | | | (ARCHITECT DECLARED R3; INCORRECT - THIS IS NOT | | | RESIDENTIAL). |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-12-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-12-28 |
Time |
18:31 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-12-28 |
Time |
18:31 |
Sent To |
|
|
| Notes |
| 2007-12-28 18:40:41 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC RFLORIDA BUILDING CODE 2004 | | | RESIDENTIAL | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | FROM PREVIOUS LIST, NUMBERING REMAINING THE SAME FOR | | | CONSISTENCY: | | | | | | **REVISION IS DATED 12/05/07.NOTHING ON THE PLAN WAS | | | CLOUDED.PLEASE CLOUD ALL CHANGES** | | | | | | 1.)ADDRESSED. | | | | | | 2.)WHAT WILL BE STORED IN THE NEW | | | STORAGE ROOM?INDICATE NON HAZARDOUS | | | STORAGE ON THE PLAN OR DECLARE A STORAGE | | | OCCUPANCY AND SHOW SEPARATION FBC TABLE | | | 302.3.2. | | | | | | 3-4.)ADDRESSED. | | | | | | 5.)PROVIDE A DETAIL FOR THE NEW 4IN | | | WALL AND THE NEW 8IN WALL. | | | | | | CONFIRMED WITH KEN CONRAD, CHIEF BUILDING INSPECTOR; AN | | | INFILL DETAIL IS ALWAYS REQUIRED. | | | | | | 6.)DECLARE WIND DESIGN CRITERIA, | | | FBC1603.1.4. | | | | | | 7.)ADDRESSED. | | | | | | 8.)THIS IS A MAJOR WORKING DRAWING | | | REVIEW.APPLICATION BY A CONTRACTOR | | | REQUIRED BEFORE A PERMIT CAN BE ISSUED. | | | | | | 9.)DECLARE GOVERNING CODE, INCLUDING | | | FBC EB, AND DECLARE LEVEL OF ALTERATION | | | FBC EB 3. | | | | | | 10.)PROVIDE A DETAIL FOR THE WOOD | | | LOUVERS, INCLUDING METHOD OF ATTACHMENT TO RESIST WIND | | | LOAD FORCES. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-10-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-10-05 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-10-05 |
Time |
15:06 |
Sent To |
|
|
| Notes |
| 2006-10-05 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC RFLORIDA BUILDING CODE 2004 | | | RESIDENTIAL | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | | | | 1.)DOCUMENTS PREPARED BY AN ARCHITECT | | | AND SUBMITTED FOR PUBLIC RECORD ARE TO | | | BE SIGNED, SEALED, DATED ORIGINALS. | | | SHEETS A4 THROUGH A9 PREPARED BY REG | | | ARCHITECTS APPEAR TO BE EXISTING | | | BUILDING DRAWINGS, SUBMITTED FOR | | | REFERENCE.EITHER HAVE THEM SIGNED AND | | | SEALED, OR INCORPORATE THE INFORMATION | | | REQUIRED TO SHOW SCOPE OF WORK AND CODE | | | COMPLIANCE INTO MR. YECKES? DRAWINGS. | | | | | | 2.)WHAT WILL BE STORED IN THE NEW | | | STORAGE ROOM?INDICATE NON HAZARDOUS | | | STORAGE ON THE PLAN OR DECLARE A STORAGE | | | OCCUPANCY AND SHOW SEPARATION FBC TABLE | | | 302.3.2. | | | | | | 3.)IS THE STORAGE AREA ACCESSORY?SEE | | | FBC 302.2; IF THIS AREA IS ACCESSORY, | | | SHOW COMPLIANCE.OTHERWISE SHOW | | | REQUIRED OCCUPANCY SEPARATION FBC TABLE | | | 302.3.2. | | | | | | 4.)PROVIDE A CODE SUMMARY; BUILDING | | | HEIGHT, AREA, OCCUPANCY, BUILDING TYPE, | | | FIRE SPRINKLER INFORMATION.DECLARE A | | | SQUARE FOOT AREA FOR THE NEW STORAGE. | | | | | | 5.)PROVIDE A DETAIL FOR THE NEW 4IN | | | WALL AND THE NEW 8IN WALL. | | | | | | 6.)DECLARE WIND DESIGN CRITERIA, | | | FBC1603.1.4. | | | | | | 7.)THE PLANS STATE THAT THE EXISTING | | | WATER FOUNTAIN WILL BE RELOCATED. | | | PROVIDE A DETAIL FOR THE WATER FOUNTAIN | | | SHOWING COMPLIANCE WITH ALL REQUIREMENTS | | | OF FBC11-4.15. | | | | | | 8.)THIS IS A MAJOR WORKING DRAWING | | | REVIEW.APPLICATION BY A CONTRACTOR | | | REQUIRED BEFORE A PERMIT CAN BE ISSUED. | | | | | | 9.)DECLARE GOVERNING CODE, INCLUDING | | | FBC EB, AND DECLARE LEVEL OF ALTERATION | | | FBC EB 3. | | | | | | 10.)PROVIDE A DETAIL FOR THE WOOD | | | LOUVERS. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
P |
Date |
2008-12-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-12-08 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-12-08 |
Time |
09:53 |
Sent To |
|
|
| Notes |
| 2008-12-08 09:53:29 | 2ND SHEET BROUGHT IN BYJEFF HALVERSON. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
F |
Date |
2008-12-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-12-02 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-12-02 |
Time |
16:16 |
Sent To |
|
|
| Notes |
| 2008-12-02 16:16:42 | ** TEMPORARY FAILED*** | | | | | | 1) NOTE: SECOND SHEET IS A PHOTO-COPY OF SIGNED, DATED | | | AND SEALED PLANS. CONTACT WAS MADE TO JEFF HALVERSON | | | AND HE WILL LOCATE SECOND SHEETS TO BE BROUGHT IN. NO | | | FEE REQUIRED. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2008-07-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-07-03 |
Time |
14:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-07-03 |
Time |
14:38 |
Sent To |
|
|
| Notes |
| 2008-07-03 14:38:40 | ** DENIED *** | | | | | | 1) NOTE: PERMIT HAS STILL NOT YET BEEN APPLIED FOR BY A | | | LICENSED CONTRACTOR. REVIEW SHALL NOT BE PASSED UNTIL | | | PERMIT IS APPLIED AS STATED ON SEVERAL PREVIOUS | | | REVIEWS. | | | | | | | | | | | | IF THERE ARE QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2008-04-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-04-25 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-04-25 |
Time |
15:24 |
Sent To |
|
|
| Notes |
| 2008-04-25 15:35:13 | ** DENIED *** | | | | | | 1) NOTE: PERMIT HAS STILL NOT YET BEEN APPLIED FOR BY A | | | LICENSED CONTRACTOR. REVIEW SHALL NOT BE PASSED UNTIL | | | PERMIT IS APPLIED AS STATED ON SEVERAL PREVIOUS | | | REVIEWS. | | | | | | 2) NOTE: PLAN REVIEW FEES NOTE PAID AS OF THIS REVIEW | | | DATE. | | | | | | IF THERE ARE QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2008-02-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-02-15 |
Time |
16:54 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-02-15 |
Time |
16:54 |
Sent To |
|
|
| Notes |
| 2008-02-15 16:56:36 | ** DENIED** | | | | | | | | | PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN REVIEW AND NOT | | | FOR PERMIT. ONCE PERMIT APPLICATION HAS BEEN MADE, | | | LICENSING AND OTHER INFORMATION WILL BE REVIEWED AT | | | THAT TIME. | | | | | | IF THERE ARE QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH. | | | 561-805-6717 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-12-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-12-25 |
Time |
08:30 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-12-25 |
Time |
08:30 |
Sent To |
|
|
| Notes |
| 2007-12-25 08:31:03 | ** DENIED2ND REVIEW ** | | | | | | PROJECT/PLAN REVIEW ONLY | | | | | | | | | 1) NOTE: PLEASE KNOW AS PERMIT HAS NEVER BEEN APPLIED | | | FOR, THE CODES ADOPTED BY THE STATE HAVE CHANGED SINCE | | | ORIGINAL SUBMITTED DATE. | | | PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN THE | | | FOLLOWING ADOPTED CODE(S) BY THE STATE. | | | THE 2004 FBC W/ 2007 REVISION. | | | 2005 NFPA-70 | | | | | | 2) NOTE: PLEASE SEE COMMENTS FROM OTHER TRADES WHICH | | | WILL AFFECT THE SINGLE SHEET SUBMITTED. | | | PLEASE KNOW THE REVIEW STATUS WILL REMAIN IN *F* STATUS | | | UNTIL PERMIT HAS BEEN APPLIED FOR. | | | | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-09-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-09-24 |
Time |
17:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-09-24 |
Time |
17:14 |
Sent To |
|
|
| Notes |
| 2006-09-24 00:00:00 | **** NOTE ** | | | | | | | | | PLEASE SEE THAT PLANS ONLY SUIBMITTED | | | FOR "PLAN REVIEW". | | | ELECTRICAL OK, HOWEVER PLANS NOT STAMPED | | | AS ALL INFORMATION SUBMITTED IS ON ONE | | | SHEETT AND NO OTHER REVIEWS ARE DONE AS | | | OF YET. | | | WILL STAMP IF ALL OTHER REVIEWS ARE | | | PASSED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
P |
Date |
2008-12-11 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-12-11 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-12-11 |
Time |
15:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
F |
Date |
2008-07-08 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-07-08 |
Time |
15:18 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-07-08 |
Time |
15:18 |
Sent To |
|
|
| Notes |
| 2008-07-08 15:20:28 | ***APPROVED PROVISO*** | | | | | | | | | 1) FIRE REVIEW OK BUT STATUS WILL REMAIN FAILED UNTIL | | | ELECTRICAL COMMENT HAS BEEN ADDRESSED REGARDING PERMIT. | | | AT THAT TIME, PLANS WILL BE STAMPED. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
F |
Date |
2008-05-05 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-05-05 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-05-05 |
Time |
15:22 |
Sent To |
|
|
| Notes |
| 2008-05-05 15:33:07 | ***DENIED*** | | | | | | NO CHANGE FROM LAST REVIEW EXCEPT DIRECTION INDICATOR | | | ON SHEET A-1. OTHER NOTES HAVE NOT BEEN FOUND ON | | | DRAWINGS. PLEASE SPECIFY LOCATION OF NOTES TO HELP | | | EXPEDITE THIS PROCESS.IT APPEARS THAT ONLY ONE FULL | | | SET OF DRAWINGS WERE SUBMITTED FOR REVIEW. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2008-02-27 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-02-27 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-02-27 |
Time |
09:11 |
Sent To |
|
|
| Notes |
| 2008-02-27 09:13:55 | ***DENIED*** | | | | | | RESPONSE LETTER INDICATES THAT NOTES HAVE BEEN ADDED TO | | | PLANS ADDRESSING PREVIOUS FIRE REVIEW. NO SUCH NOTES | | | WERE FOUND DURING THIS REVIEW. PLEASE REFER TO PREVIOUS | | | COMMENTS AND ADDRESS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-12-28 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-12-28 |
Time |
12:18 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-12-28 |
Time |
11:52 |
Sent To |
|
|
| Notes |
| 2007-12-28 12:08:55 | *****UNSAT***** | | | | | | *THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN | | | REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 1.)STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.)DEMOLITION OPERATIONS INVOLVING THE USE OF CUTTING | | | AND WELDING SHALL BE DONE IN ACCORDANCE WITH NFPA 51B. | | | | | | 3.)CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL | | | NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID | | | PROPERTY (INCLUDING FIRE LANES). | | | | | | *NEW COMMENT: | | | | | | A.)ON SHEET A-1, INDICATE NORTH, SOUTH, EAST, OR WEST | | | ELEVATION FOR THE NEW FRONT ELEVATION. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-10-20 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-10-20 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-10-20 |
Time |
14:03 |
Sent To |
|
|
| Notes |
| 2006-10-20 14:28:20 | *****UNSAT***** | | | | | | | | | | | | | | | 1.)STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.)DEMOLITION OPERATIONS INVOLVING THE USE OF CUTTING | | | AND WELDING SHALL BE DONE IN ACCORDANCE WITH NFPA 51B. | | | | | | 3.)CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL | | | NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID | | | PROPERTY (INCLUDING FIRE LANES). | | | | | | 4.)PLEASE INDICATE/DISPLAY/SHOW THE LOCATION OF EXIT | | | LIGHTS AND EMERGENCY LIGHTS FOR THE EXIST/NEW TOWER. | | | | | | 5.)INTERIOR FINISH SHALL BE CLASS "A" OR CLASS "B". | | | | | | | | | 6.)PLEASE PROVIDE THE FLAME RETARDANT DETAILS FOR THE | | | CANOPY (SHEET A-5). | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2009-02-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-02-03 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-02-03 |
Time |
09:12 |
Sent To |
P |
|
| Notes |
| 2009-02-03 09:13:17 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2008-11-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-11-25 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-25 |
Time |
10:48 |
Sent To |
|
|
| Notes |
| 2008-11-25 10:59:37 | TO "COMM" BD#29 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-06-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-06-18 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-06-18 |
Time |
09:58 |
Sent To |
|
|
| Notes |
| 2008-06-18 16:01:53 | TO "COMM" BD#61 | | 2008-06-18 09:59:26 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-04-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-22 |
Time |
14:23 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-22 |
Time |
14:23 |
Sent To |
|
|
| Notes |
| 2008-04-22 14:28:27 | TO "COMM" BD#19 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-02-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-15 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-15 |
Time |
11:07 |
Sent To |
|
|
| Notes |
| 2008-02-15 11:09:23 | TO "COMM" BD#49 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-12-21 |
|
|
Cont ID |
|
| Sent By |
mmiller |
Date |
2007-12-21 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
mmiller |
Date |
2007-12-21 |
Time |
16:56 |
Sent To |
|
|
| Notes |
| 2007-12-21 16:56:19 | SENT TO COMMERCIAL BOARD # 64 MMILLER |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-10-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-10-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-09-11 |
Time |
11:55 |
Sent To |
|
|
| Notes |
| 2006-09-20 00:00:00 | TO "COMM" BD#17 | | 2006-09-11 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
F |
Date |
2009-02-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-02-26 |
Time |
11:37 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-02-26 |
Time |
11:37 |
Sent To |
|
|
| Notes |
| 2009-02-26 11:41:37 | DENIED | | | REFERENCE: | | | FBC-2004 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. REVISIONS TO A SIGNED, SEALED SANITARY RISER DIAGRAM | | | DESIGN PROFESSIONAL SHALL BE SIGNED, SEALED & DATED BY | | | THE DESIGN PROFESSIONAL. ALL REQUIRED INFORMATION | | | REQUIRED FOR THE TITLE BLOCK SHALL BE INDICATED ON THE | | | REVISION. SECTION 106.1, FAC 61G1-16.003, 61G1-16.004 & | | | FS 481.2055. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2008-07-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-07-18 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-07-18 |
Time |
10:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2008-05-02 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-05-02 |
Time |
17:05 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-05-02 |
Time |
17:05 |
Sent To |
|
|
| Notes |
| 2008-05-02 17:10:21 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | ******FROM PREVIOUS REVIEWS: | | | | | | ********FROM PREVIOUS REVIEWS: | | | | | | 1. SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION | | | 11-4.15 AND ALL SUBSECTIONS, AS WELL AS 11-4.1.3(10)(A) | | | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR | | | STOOPING. | | | ****NO RESPONSE, NOT ADDRESSED. | | | ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. NO | | | DETAIL SUBMITTED. | | | ********RESPONSE NOTED, BUT SECTION 11-4.1.3(10)(A), | | | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR | | | STOOPING HAS NOT BEEN ADDRESSED. | | | | | | 2. SUBMIT A SANITARY RISER DIAGRAM ISOMETRIC TO REFLECT | | | THE FLOOR PLAN SHOWING PIPE SIZE, VENTING, TRAPS, POINT | | | OF CONNECTION ETC. SECTION 106.3.5.1.3.(4)(13). ****NO | | | RESPONSE, NOT ADDRESSED. | | | ******RESPONSE NOTED, BUT THE DRINKING FOUNTAIN IS NOT | | | VENTED AS SHOWN. SEE RED LINE CORRECTION INDICATED ON | | | ONE SHEET FOR AN EXAMPLE OF A RISER DIAGRAM THAT MEETS | | | CODE AT THE DRINKING FOUNTAIN. SECTION 901.2.1. | | | ********RESPONSE NOTED, BUT THE VENT WILL BE COMMING | | | OUT THE TOP OF THE DRINKING FOUNTAIN AS SHOWN. PLEASE | | | SEE THE RED LINE RISER DIAGRAM DRAWING AS AN EXAMPLE OF | | | A RISER DIAGRAM THAT MEETS CODE AT THE DRINKING | | | FOUNTAIN. | | | | | | 3. OK | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2008-02-21 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-02-21 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-02-21 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2008-02-21 14:56:50 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | ******FROM PREVIOUS REVIEWS: | | | | | | 1. SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION | | | 11-4.15 AND ALL SUBSECTIONS, AS WELL AS 11-4.1.3(10)(A) | | | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR | | | STOOPING. | | | ****NO RESPONSE, NOT ADDRESSED. | | | ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. NO | | | DETAIL SUBMITTED. | | | | | | 2. SUBMIT A SANITARY RISER DIAGRAM ISOMETRIC TO REFLECT | | | THE FLOOR PLAN SHOWING PIPE SIZE, VENTING, TRAPS, POINT | | | OF CONNECTION ETC. SECTION 106.3.5.1.3.(4)(13). ****NO | | | RESPONSE, NOT ADDRESSED. | | | ******RESPONSE NOTED, BUT THE DRINKING FOUNTAIN IS NOT | | | VENTED AS SHOWN. SEE RED LINE CORRECTION INDICATED ON | | | ONE SHEET FOR AN EXAMPLE OF A RISER DIAGRAM THAT MEETS | | | CODE AT THE DRINKING FOUNTAIN. SECTION 901.2.1. | | | | | | 3. OK | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-12-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-12-27 |
Time |
16:52 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-12-27 |
Time |
16:52 |
Sent To |
|
|
| Notes |
| 2007-12-27 16:53:52 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION | | | 11-4.15 AND ALL SUBSECTIONS, AS WELL AS 11-4.1.3(10)(A) | | | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR | | | STOOPING. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | 2. SUBMIT A SANITARY RISER DIAGRAM ISOMETRIC TO REFLECT | | | THE FLOOR PLAN SHOWING PIPE SIZE, VENTING, TRAPS, POINT | | | OF CONNECTION ETC. SECTION 106.3.5.1.3.(4)(13). ****NO | | | RESPONSE, NOT ADDRESSED. | | | | | | 3. SUBMIT A WATER RISER DIAGRAM ISOMETRIC SHOWING PIPE | | | SIZE, VALVES, WATER HAMMER IF REQUIRED BY SECTION | | | 604.9, AND POINT OF CONNCECTION. SECTION | | | 106.3.4.1.3(3)(13). | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-10-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-10-14 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-10-13 |
Time |
18:29 |
Sent To |
|
|
| Notes |
| 2006-10-14 09:19:26 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | 1. SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION | | | 11-4.15 AND ALL SUBSECTIONS, AS WELL AS 11-4.1.3(10)(A) | | | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR | | | STOOPING. | | | | | | 2. SUBMIT A SANITARY RISER DIAGRAM ISOMETRIC TO REFLECT | | | THE FLOOR PLAN SHOWING PIPE SIZE, VENTING, TRAPS, POINT | | | OF CONNECTION ETC. SECTION 106.3.5.1.3.(4)(13). | | | | | | 3. SUBMIT A WATER RISER DIAGRAM ISOMETRIC SHOWING PIPE | | | SIZE, VALVES, WATER HAMMER IF REQUIRED BY SECTION | | | 604.9, AND POINT OF CONNCECTION. SECTION | | | 106.3.4.1.3(3)(13). | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2008-12-01 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2008-12-01 |
Time |
17:45 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2008-12-01 |
Time |
17:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2008-06-27 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2008-06-27 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2008-06-27 |
Time |
13:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2008-02-26 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2008-02-26 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2008-02-26 |
Time |
09:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2006-10-30 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2006-10-30 |
Time |
16:25 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2006-10-30 |
Time |
16:25 |
Sent To |
I |
|
| Notes |
|
|