Plan Review Details - Permit 06090272
Plan Review Stops For Permit 06090272
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-12-22 Cont ID  
Sent By shill Date 2008-12-22 Time 14:19 Rev Time 0.00
Received By shill Date 2008-12-22 Time 14:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-07-17 Cont ID  
Sent By shill Date 2008-07-17 Time 16:47 Rev Time 0.00
Received By shill Date 2008-07-17 Time 16:47 Sent To  
Notes
2008-07-17 16:50:54****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.AS THIS IS A PROJECT, THIS PLAN REVIEW MUST REMAIN
 IN FAIL STATUS UNTIL A CONTRACTOR LICENSED TO DO THIS
 WORK APPLIES FOR PERMIT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-05-05 Cont ID  
Sent By lmartine Date 2008-05-05 Time 17:27 Rev Time 0.00
Received By lmartine Date 2008-05-05 Time 17:27 Sent To  
Notes
2008-05-05 17:28:19COMPLY WITH SAMANTHA'S NOTES FROM PREVIOUS REVIEW
 LM

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-02-22 Cont ID  
Sent By shill Date 2008-02-22 Time 10:21 Rev Time 0.00
Received By shill Date 2008-02-22 Time 10:21 Sent To  
Notes
2008-02-22 10:22:23****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 PLAN CHECK ONLY -
  
 1.PERMIT APPLICATION REQUIRED
  
 2.PLANS APPEAR CODE COMPLIANT AND WILL GET A PASS
 WITH PROVISO (REVISE OCCUPANCY CLASSIFICATION ON PLAN
 (ARCHITECT DECLARED R3; INCORRECT - THIS IS NOT
 RESIDENTIAL).

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-12-28 Cont ID  
Sent By shill Date 2007-12-28 Time 18:31 Rev Time 0.00
Received By shill Date 2007-12-28 Time 18:31 Sent To  
Notes
2007-12-28 18:40:41****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST, NUMBERING REMAINING THE SAME FOR
 CONSISTENCY:
  
 **REVISION IS DATED 12/05/07.NOTHING ON THE PLAN WAS
 CLOUDED.PLEASE CLOUD ALL CHANGES**
  
 1.)ADDRESSED.
  
 2.)WHAT WILL BE STORED IN THE NEW
 STORAGE ROOM?INDICATE NON HAZARDOUS
 STORAGE ON THE PLAN OR DECLARE A STORAGE
 OCCUPANCY AND SHOW SEPARATION FBC TABLE
 302.3.2.
  
 3-4.)ADDRESSED.
  
 5.)PROVIDE A DETAIL FOR THE NEW 4IN
 WALL AND THE NEW 8IN WALL.
  
 CONFIRMED WITH KEN CONRAD, CHIEF BUILDING INSPECTOR; AN
 INFILL DETAIL IS ALWAYS REQUIRED.
  
 6.)DECLARE WIND DESIGN CRITERIA,
 FBC1603.1.4.
  
 7.)ADDRESSED.
  
 8.)THIS IS A MAJOR WORKING DRAWING
 REVIEW.APPLICATION BY A CONTRACTOR
 REQUIRED BEFORE A PERMIT CAN BE ISSUED.
  
 9.)DECLARE GOVERNING CODE, INCLUDING
 FBC EB, AND DECLARE LEVEL OF ALTERATION
 FBC EB 3.
  
 10.)PROVIDE A DETAIL FOR THE WOOD
 LOUVERS, INCLUDING METHOD OF ATTACHMENT TO RESIST WIND
 LOAD FORCES.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-05 Cont ID  
Sent By shill Date 2006-10-05 Time 15:06 Rev Time 0.00
Received By shill Date 2006-10-05 Time 15:06 Sent To  
Notes
2006-10-05 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
  
 1.)DOCUMENTS PREPARED BY AN ARCHITECT
 AND SUBMITTED FOR PUBLIC RECORD ARE TO
 BE SIGNED, SEALED, DATED ORIGINALS.
 SHEETS A4 THROUGH A9 PREPARED BY REG
 ARCHITECTS APPEAR TO BE EXISTING
 BUILDING DRAWINGS, SUBMITTED FOR
 REFERENCE.EITHER HAVE THEM SIGNED AND
 SEALED, OR INCORPORATE THE INFORMATION
 REQUIRED TO SHOW SCOPE OF WORK AND CODE
 COMPLIANCE INTO MR. YECKES? DRAWINGS.
  
 2.)WHAT WILL BE STORED IN THE NEW
 STORAGE ROOM?INDICATE NON HAZARDOUS
 STORAGE ON THE PLAN OR DECLARE A STORAGE
 OCCUPANCY AND SHOW SEPARATION FBC TABLE
 302.3.2.
  
 3.)IS THE STORAGE AREA ACCESSORY?SEE
 FBC 302.2; IF THIS AREA IS ACCESSORY,
 SHOW COMPLIANCE.OTHERWISE SHOW
 REQUIRED OCCUPANCY SEPARATION FBC TABLE
 302.3.2.
  
 4.)PROVIDE A CODE SUMMARY; BUILDING
 HEIGHT, AREA, OCCUPANCY, BUILDING TYPE,
 FIRE SPRINKLER INFORMATION.DECLARE A
 SQUARE FOOT AREA FOR THE NEW STORAGE.
  
 5.)PROVIDE A DETAIL FOR THE NEW 4IN
 WALL AND THE NEW 8IN WALL.
  
 6.)DECLARE WIND DESIGN CRITERIA,
 FBC1603.1.4.
  
 7.)THE PLANS STATE THAT THE EXISTING
 WATER FOUNTAIN WILL BE RELOCATED.
 PROVIDE A DETAIL FOR THE WATER FOUNTAIN
 SHOWING COMPLIANCE WITH ALL REQUIREMENTS
 OF FBC11-4.15.
  
 8.)THIS IS A MAJOR WORKING DRAWING
 REVIEW.APPLICATION BY A CONTRACTOR
 REQUIRED BEFORE A PERMIT CAN BE ISSUED.
  
 9.)DECLARE GOVERNING CODE, INCLUDING
 FBC EB, AND DECLARE LEVEL OF ALTERATION
 FBC EB 3.
  
 10.)PROVIDE A DETAIL FOR THE WOOD
 LOUVERS.
  
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2008-12-08 Cont ID  
Sent By dpalmer Date 2008-12-08 Time 09:53 Rev Time 0.00
Received By dpalmer Date 2008-12-08 Time 09:53 Sent To  
Notes
2008-12-08 09:53:292ND SHEET BROUGHT IN BYJEFF HALVERSON.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2008-12-02 Cont ID  
Sent By dpalmer Date 2008-12-02 Time 16:16 Rev Time 0.00
Received By dpalmer Date 2008-12-02 Time 16:16 Sent To  
Notes
2008-12-02 16:16:42** TEMPORARY FAILED***
  
 1) NOTE: SECOND SHEET IS A PHOTO-COPY OF SIGNED, DATED
 AND SEALED PLANS. CONTACT WAS MADE TO JEFF HALVERSON
 AND HE WILL LOCATE SECOND SHEETS TO BE BROUGHT IN. NO
 FEE REQUIRED.
  
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-07-03 Cont ID  
Sent By dpalmer Date 2008-07-03 Time 14:38 Rev Time 0.00
Received By dpalmer Date 2008-07-03 Time 14:38 Sent To  
Notes
2008-07-03 14:38:40** DENIED ***
  
 1) NOTE: PERMIT HAS STILL NOT YET BEEN APPLIED FOR BY A
 LICENSED CONTRACTOR. REVIEW SHALL NOT BE PASSED UNTIL
 PERMIT IS APPLIED AS STATED ON SEVERAL PREVIOUS
 REVIEWS.
  
  
  
 IF THERE ARE QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-04-25 Cont ID  
Sent By dpalmer Date 2008-04-25 Time 15:24 Rev Time 0.00
Received By dpalmer Date 2008-04-25 Time 15:24 Sent To  
Notes
2008-04-25 15:35:13** DENIED ***
  
 1) NOTE: PERMIT HAS STILL NOT YET BEEN APPLIED FOR BY A
 LICENSED CONTRACTOR. REVIEW SHALL NOT BE PASSED UNTIL
 PERMIT IS APPLIED AS STATED ON SEVERAL PREVIOUS
 REVIEWS.
  
 2) NOTE: PLAN REVIEW FEES NOTE PAID AS OF THIS REVIEW
 DATE.
  
 IF THERE ARE QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-02-15 Cont ID  
Sent By dpalmer Date 2008-02-15 Time 16:54 Rev Time 0.00
Received By dpalmer Date 2008-02-15 Time 16:54 Sent To  
Notes
2008-02-15 16:56:36** DENIED**
  
  
 PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN REVIEW AND NOT
 FOR PERMIT. ONCE PERMIT APPLICATION HAS BEEN MADE,
 LICENSING AND OTHER INFORMATION WILL BE REVIEWED AT
 THAT TIME.
  
 IF THERE ARE QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH.
 561-805-6717

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-12-25 Cont ID  
Sent By dpalmer Date 2007-12-25 Time 08:30 Rev Time 0.00
Received By dpalmer Date 2007-12-25 Time 08:30 Sent To  
Notes
2007-12-25 08:31:03** DENIED2ND REVIEW **
  
 PROJECT/PLAN REVIEW ONLY
  
  
 1) NOTE: PLEASE KNOW AS PERMIT HAS NEVER BEEN APPLIED
 FOR, THE CODES ADOPTED BY THE STATE HAVE CHANGED SINCE
 ORIGINAL SUBMITTED DATE.
 PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN THE
 FOLLOWING ADOPTED CODE(S) BY THE STATE.
 THE 2004 FBC W/ 2007 REVISION.
 2005 NFPA-70
  
 2) NOTE: PLEASE SEE COMMENTS FROM OTHER TRADES WHICH
 WILL AFFECT THE SINGLE SHEET SUBMITTED.
 PLEASE KNOW THE REVIEW STATUS WILL REMAIN IN *F* STATUS
 UNTIL PERMIT HAS BEEN APPLIED FOR.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-24 Cont ID  
Sent By dpalmer Date 2006-09-24 Time 17:19 Rev Time 0.00
Received By dpalmer Date 2006-09-24 Time 17:14 Sent To  
Notes
2006-09-24 00:00:00**** NOTE **
  
  
 PLEASE SEE THAT PLANS ONLY SUIBMITTED
 FOR "PLAN REVIEW".
 ELECTRICAL OK, HOWEVER PLANS NOT STAMPED
 AS ALL INFORMATION SUBMITTED IS ON ONE
 SHEETT AND NO OTHER REVIEWS ARE DONE AS
 OF YET.
 WILL STAMP IF ALL OTHER REVIEWS ARE
 PASSED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2008-12-11 Cont ID  
Sent By mwennerg Date 2008-12-11 Time 15:22 Rev Time 0.00
Received By mwennerg Date 2008-12-11 Time 15:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2008-07-08 Cont ID  
Sent By mwennerg Date 2008-07-08 Time 15:18 Rev Time 0.00
Received By mwennerg Date 2008-07-08 Time 15:18 Sent To  
Notes
2008-07-08 15:20:28***APPROVED PROVISO***
  
  
 1) FIRE REVIEW OK BUT STATUS WILL REMAIN FAILED UNTIL
 ELECTRICAL COMMENT HAS BEEN ADDRESSED REGARDING PERMIT.
 AT THAT TIME, PLANS WILL BE STAMPED.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2008-05-05 Cont ID  
Sent By mwennerg Date 2008-05-05 Time 15:22 Rev Time 0.00
Received By mwennerg Date 2008-05-05 Time 15:22 Sent To  
Notes
2008-05-05 15:33:07***DENIED***
  
 NO CHANGE FROM LAST REVIEW EXCEPT DIRECTION INDICATOR
 ON SHEET A-1. OTHER NOTES HAVE NOT BEEN FOUND ON
 DRAWINGS. PLEASE SPECIFY LOCATION OF NOTES TO HELP
 EXPEDITE THIS PROCESS.IT APPEARS THAT ONLY ONE FULL
 SET OF DRAWINGS WERE SUBMITTED FOR REVIEW.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-02-27 Cont ID  
Sent By mwennerg Date 2008-02-27 Time 09:11 Rev Time 0.00
Received By mwennerg Date 2008-02-27 Time 09:11 Sent To  
Notes
2008-02-27 09:13:55***DENIED***
  
 RESPONSE LETTER INDICATES THAT NOTES HAVE BEEN ADDED TO
 PLANS ADDRESSING PREVIOUS FIRE REVIEW. NO SUCH NOTES
 WERE FOUND DURING THIS REVIEW. PLEASE REFER TO PREVIOUS
 COMMENTS AND ADDRESS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-12-28 Cont ID  
Sent By mawillia Date 2007-12-28 Time 12:18 Rev Time 0.00
Received By mawillia Date 2007-12-28 Time 11:52 Sent To  
Notes
2007-12-28 12:08:55*****UNSAT*****
  
 *THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
 1.)STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.)DEMOLITION OPERATIONS INVOLVING THE USE OF CUTTING
 AND WELDING SHALL BE DONE IN ACCORDANCE WITH NFPA 51B.
  
 3.)CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY (INCLUDING FIRE LANES).
  
 *NEW COMMENT:
  
 A.)ON SHEET A-1, INDICATE NORTH, SOUTH, EAST, OR WEST
 ELEVATION FOR THE NEW FRONT ELEVATION.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-20 Cont ID  
Sent By mawillia Date 2006-10-20 Time 14:03 Rev Time 0.00
Received By mawillia Date 2006-10-20 Time 14:03 Sent To  
Notes
2006-10-20 14:28:20*****UNSAT*****
  
  
  
  
 1.)STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.)DEMOLITION OPERATIONS INVOLVING THE USE OF CUTTING
 AND WELDING SHALL BE DONE IN ACCORDANCE WITH NFPA 51B.
  
 3.)CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY (INCLUDING FIRE LANES).
  
 4.)PLEASE INDICATE/DISPLAY/SHOW THE LOCATION OF EXIT
 LIGHTS AND EMERGENCY LIGHTS FOR THE EXIST/NEW TOWER.
  
 5.)INTERIOR FINISH SHALL BE CLASS "A" OR CLASS "B".
  
  
 6.)PLEASE PROVIDE THE FLAME RETARDANT DETAILS FOR THE
 CANOPY (SHEET A-5).
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-02-03 Cont ID  
Sent By adarroug Date 2009-02-03 Time 09:12 Rev Time 0.00
Received By adarroug Date 2009-02-03 Time 09:12 Sent To P
Notes
2009-02-03 09:13:17TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-11-25 Cont ID  
Sent By adarroug Date 2008-11-25 Time 10:48 Rev Time 0.00
Received By adarroug Date 2008-11-25 Time 10:48 Sent To  
Notes
2008-11-25 10:59:37TO "COMM" BD#29

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-06-18 Cont ID  
Sent By adarroug Date 2008-06-18 Time 09:58 Rev Time 0.00
Received By adarroug Date 2008-06-18 Time 09:58 Sent To  
Notes
2008-06-18 16:01:53TO "COMM" BD#61
2008-06-18 09:59:26WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-04-22 Cont ID  
Sent By adarroug Date 2008-04-22 Time 14:23 Rev Time 0.00
Received By adarroug Date 2008-04-22 Time 14:23 Sent To  
Notes
2008-04-22 14:28:27TO "COMM" BD#19

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-15 Cont ID  
Sent By adarroug Date 2008-02-15 Time 11:07 Rev Time 0.00
Received By adarroug Date 2008-02-15 Time 11:07 Sent To  
Notes
2008-02-15 11:09:23TO "COMM" BD#49

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-21 Cont ID  
Sent By mmiller Date 2007-12-21 Time 16:56 Rev Time 0.00
Received By mmiller Date 2007-12-21 Time 16:56 Sent To  
Notes
2007-12-21 16:56:19SENT TO COMMERCIAL BOARD # 64 MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-20 Cont ID  
Sent By shill Date 2006-10-20 Time   Rev Time 0.00
Received By shill Date 2006-09-11 Time 11:55 Sent To  
Notes
2006-09-20 00:00:00TO "COMM" BD#17
2006-09-11 00:00:00WAITING FOR "COMM" BD

Review Stop P PLUMBING
Rev No 6 Status F Date 2009-02-26 Cont ID  
Sent By kstevens Date 2009-02-26 Time 11:37 Rev Time 0.00
Received By kstevens Date 2009-02-26 Time 11:37 Sent To  
Notes
2009-02-26 11:41:37DENIED
 REFERENCE:
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. REVISIONS TO A SIGNED, SEALED SANITARY RISER DIAGRAM
 DESIGN PROFESSIONAL SHALL BE SIGNED, SEALED & DATED BY
 THE DESIGN PROFESSIONAL. ALL REQUIRED INFORMATION
 REQUIRED FOR THE TITLE BLOCK SHALL BE INDICATED ON THE
 REVISION. SECTION 106.1, FAC 61G1-16.003, 61G1-16.004 &
 FS 481.2055.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-07-18 Cont ID  
Sent By kstevens Date 2008-07-18 Time 10:21 Rev Time 0.00
Received By kstevens Date 2008-07-18 Time 10:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2008-05-02 Cont ID  
Sent By kstevens Date 2008-05-02 Time 17:05 Rev Time 0.00
Received By kstevens Date 2008-05-02 Time 17:05 Sent To  
Notes
2008-05-02 17:10:21DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 ********FROM PREVIOUS REVIEWS:
  
 1. SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.15 AND ALL SUBSECTIONS, AS WELL AS 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. NO
 DETAIL SUBMITTED.
 ********RESPONSE NOTED, BUT SECTION 11-4.1.3(10)(A),
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING HAS NOT BEEN ADDRESSED.
  
 2. SUBMIT A SANITARY RISER DIAGRAM ISOMETRIC TO REFLECT
 THE FLOOR PLAN SHOWING PIPE SIZE, VENTING, TRAPS, POINT
 OF CONNECTION ETC. SECTION 106.3.5.1.3.(4)(13). ****NO
 RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE DRINKING FOUNTAIN IS NOT
 VENTED AS SHOWN. SEE RED LINE CORRECTION INDICATED ON
 ONE SHEET FOR AN EXAMPLE OF A RISER DIAGRAM THAT MEETS
 CODE AT THE DRINKING FOUNTAIN. SECTION 901.2.1.
 ********RESPONSE NOTED, BUT THE VENT WILL BE COMMING
 OUT THE TOP OF THE DRINKING FOUNTAIN AS SHOWN. PLEASE
 SEE THE RED LINE RISER DIAGRAM DRAWING AS AN EXAMPLE OF
 A RISER DIAGRAM THAT MEETS CODE AT THE DRINKING
 FOUNTAIN.
  
 3. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-02-21 Cont ID  
Sent By kstevens Date 2008-02-21 Time 14:53 Rev Time 0.00
Received By kstevens Date 2008-02-21 Time 14:53 Sent To  
Notes
2008-02-21 14:56:50DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 1. SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.15 AND ALL SUBSECTIONS, AS WELL AS 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. NO
 DETAIL SUBMITTED.
  
 2. SUBMIT A SANITARY RISER DIAGRAM ISOMETRIC TO REFLECT
 THE FLOOR PLAN SHOWING PIPE SIZE, VENTING, TRAPS, POINT
 OF CONNECTION ETC. SECTION 106.3.5.1.3.(4)(13). ****NO
 RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE DRINKING FOUNTAIN IS NOT
 VENTED AS SHOWN. SEE RED LINE CORRECTION INDICATED ON
 ONE SHEET FOR AN EXAMPLE OF A RISER DIAGRAM THAT MEETS
 CODE AT THE DRINKING FOUNTAIN. SECTION 901.2.1.
  
 3. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-12-27 Cont ID  
Sent By kstevens Date 2007-12-27 Time 16:52 Rev Time 0.00
Received By kstevens Date 2007-12-27 Time 16:52 Sent To  
Notes
2007-12-27 16:53:52DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 1. SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.15 AND ALL SUBSECTIONS, AS WELL AS 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 ****NO RESPONSE, NOT ADDRESSED.
  
 2. SUBMIT A SANITARY RISER DIAGRAM ISOMETRIC TO REFLECT
 THE FLOOR PLAN SHOWING PIPE SIZE, VENTING, TRAPS, POINT
 OF CONNECTION ETC. SECTION 106.3.5.1.3.(4)(13). ****NO
 RESPONSE, NOT ADDRESSED.
  
 3. SUBMIT A WATER RISER DIAGRAM ISOMETRIC SHOWING PIPE
 SIZE, VALVES, WATER HAMMER IF REQUIRED BY SECTION
 604.9, AND POINT OF CONNCECTION. SECTION
 106.3.4.1.3(3)(13).
 ****NO RESPONSE, NOT ADDRESSED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-10-14 Cont ID  
Sent By kstevens Date 2006-10-14 Time 08:54 Rev Time 0.00
Received By kstevens Date 2006-10-13 Time 18:29 Sent To  
Notes
2006-10-14 09:19:26DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.15 AND ALL SUBSECTIONS, AS WELL AS 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
  
 2. SUBMIT A SANITARY RISER DIAGRAM ISOMETRIC TO REFLECT
 THE FLOOR PLAN SHOWING PIPE SIZE, VENTING, TRAPS, POINT
 OF CONNECTION ETC. SECTION 106.3.5.1.3.(4)(13).
  
 3. SUBMIT A WATER RISER DIAGRAM ISOMETRIC SHOWING PIPE
 SIZE, VALVES, WATER HAMMER IF REQUIRED BY SECTION
 604.9, AND POINT OF CONNCECTION. SECTION
 106.3.4.1.3(3)(13).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2008-12-01 Cont ID  
Sent By jroach Date 2008-12-01 Time 17:45 Rev Time 0.00
Received By jroach Date 2008-12-01 Time 17:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2008-06-27 Cont ID  
Sent By jroach Date 2008-06-27 Time 13:21 Rev Time 0.00
Received By jroach Date 2008-06-27 Time 13:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2008-02-26 Cont ID  
Sent By jroach Date 2008-02-26 Time 09:17 Rev Time 0.00
Received By jroach Date 2008-02-26 Time 09:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-10-30 Cont ID  
Sent By jroach Date 2006-10-30 Time 16:25 Rev Time 0.00
Received By jroach Date 2006-10-30 Time 16:25 Sent To I
Notes
***NONE***