Plan Review Details - Permit 06090266
Plan Review Stops For Permit 06090266
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-08-29 Cont ID  
Sent By jgomez Date 2007-08-29 Time 08:41 Rev Time 0.00
Received By jgomez Date 2007-08-29 Time 07:37 Sent To PC
Notes
2007-08-29 08:41:44PROVISO SUBMITTAL OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-04-30 Cont ID  
Sent By jgomez Date 2007-04-30 Time 10:20 Rev Time 0.00
Received By jgomez Date 2007-04-30 Time 10:20 Sent To PC
Notes
2007-04-30 10:21:02TRUSS PACKAGE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-04-23 Cont ID  
Sent By jgomez Date 2007-04-23 Time 08:09 Rev Time 0.00
Received By jgomez Date 2007-04-23 Time 07:42 Sent To PC
Notes
2007-04-23 09:01:47TRUSS PACKAGE CHECKLIST:
 1- ENGINEER OF RECORD NEED TO REVIEW AND APPROVE TRUSS
 PACKAGE PRIOR TO SUBMITTA L TO THIS OFFICE.
  
 2- PROVIDE ONLY THE INFORMATION THAT APPLIES TO THIS
 PROJECT. MOST OF THE INFORMATION SUBMITTED DON'T APPLY
 TO THIS JOB.
  
 3- SIGN, SEAL AND DATEALL SHEETS SUBMITTED AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
  
 4- DESIGN CRITERIA IN ALL SHEETS TO MATCH. EG: LIVE
 LOADS, DEAD LOADS, WIND EXPOSURE, ETC.
  
 5- ENGINEERED TRUSSES SPECIFY BUILDING TYPE AS OPEN,
 WHILE BUILDING IS DESIGNED AS ENCLOSED. SEE PLANS AND
 REVISE/CLARIFY AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-02-07 Cont ID  
Sent By jgomez Date 2007-02-07 Time 10:03 Rev Time 1.50
Received By jgomez Date 2007-02-06 Time 18:40 Sent To  
Notes
2007-02-07 10:16:18BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE TRUSSES FOR REVIEW PRIOR TO INSTALLATION AS
 REQUIRED BY SEC. R802.1.6 2004 FLORIDA RESIDENTIAL
 CODE. ENGINEER TO REVIEW AND APPROVE THEM PRIOR TO
 SUBMITTAL.
  
 2- ENGINEER OFRECORD TO PROVIDE SPECIFICATIONS
 SHOWING HOW TO PREVENT WATER ENTERING THRU VENTILATION
 OPENINGS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 3- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR WINDOW MULLIONS. REMAINDER: ENGINEEROF
 RECORD TO REVIEW AND APPROVE IT IN WRITING (NOT SIGNING
 AND SEALING) IR PRIOR TO SUBMITTAL TO THIS OFFICE AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-17 Cont ID  
Sent By jgomez Date 2006-11-17 Time 16:16 Rev Time 2.00
Received By jgomez Date 2006-11-17 Time 16:16 Sent To  
Notes
2006-11-17 17:08:48BUILDING REVIEW 2ND CHECKLIST:
 1- OWES $4.46 FOR RADON FEES.
  
 2- SOIL TEST REPORT SUBMITTED. COMMENTS ON FIRST
 CHECKLIST WERE NOT ADDRESSED AT ALL:
 A) NEED 2 COPIES WITH ORIGINAL SEAL, SIGNATURE AND
 DATE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES.
 B) NEED ENGINEERING FIRM CERTIFICATE OF
 AUTHORIZATION IN THE REPORT AS REQUIRED BY FLORIDA
 ADMINISTRATIVE CODE SEC. 61G15-23.002.
 C) REPORT SAYS THAT PROPOSED CONTRUCTION IS MASONRY.
 PLANS SHOW WOOD FRAME CONSTRUCTION. CLARIFY AND REVISE
 AS REQUIRED.
  
 3- ENGINEER IN SOIL TEST REPORT RECOMMENDS STEM WALL
 FOOTING FOUNDATION SYSTEM RATHER THAN A MONOLITHIC
 FOUNDATION SYSTEM. SEE PAGE 2 OF REPORT.DRAWINGS SHOW
 MONOLITHIC FOOTING. ENGINEER OF RECORD TO AKNOWLEDGE
 THAT HE REVIEWED THE SOIL TEST REPORT AND DECIDES TO
 USE MONOLITHIC FOOTING EVEN THOUGH SOILS ENGINEER
 RECOMMENDS STEM WALL SYSTEM.ENGINEER OF RECORD TO
 PROVIDE LETTER ADDRESSING THIS ISSUE. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 4- REMAINDER: COMPLETE TRUSS PACKAGE WILL NEED TO BE
 PROVIDED FOR REVIEW PRIOR TO INSTALLATION. SEE SEC.
 R802.10 2004 FLORIDA RESIDENTIAL CODE FOR REQUIRED
 INFORMATION TO BE INCLUDED.
  
 5- SHOW IN PLANS AND ELEVATIONS ALL SPECIFIC LOCATION
 OF VENTILATION OPENINGS. ALSO, SPECIFY SIZE TO VERIFY
 COMPLIANCE WITH SEC. R806.2 2004 FLORIDA RESIDENTIAL
 CODE. CALCULATIONS SHOWN ONLY SAYS THAT NEED 3S.F..
 THAT'S WHY NEED SPECIFIC SIZE AND NUMBER OF VENTS TO
 VERIFY COMPLIANCE.
 ***NOTE: VENTS SHALL PROVIDE TOTAL NET FREE VENTILATING
 AREA.
  
 6- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. .
 ENGINEER'S STAMP ALONE IS NOT ACCEPTABLE.ENGINEER
 NEEDS TO APPROVE IN WRITING THE PRODUCT APPROVAL AS
 REQUIRED BY SEC. ABOVE.
  
 7- PROVIDE FLORIDA PRODUCT APPROVAL AS REQUIRED BY RULE
 9B-72 FOR:
 A) WINDOW MULLIONS. NEED COPY OF APPROVED FLORIDA
 PRODUCT APPROVAL #261 WITH THE APPROVED APPLICATION
 STATUS. ONE SUBMITTED SAYS VALIDATED.PRODUCT MUST BE
 APPROVED TO BE USED.
  
 B) FLAT ROOF SYSTEM:
 * NEED TO IDENTIFY SPECIFIC APPROVED ASSEMBLY TO BE
 INSTALLED. SEE LIST OF APPROVED ASSEMBLIES ON DADE
 COUNTY NOA REPORT.
 ** IF SYSTEM IS LIMITED BY GENERAL LIMITATION #7,
 THEN NEED TO PROVIDE RAS 117 CALCULATIONS. CALCULATIONS
 SUBMITTED ARE DONE BY THE HOUSE OWNER (LARRY LUNDER)
 AND ARE NOT ACCEPTABLE UNLESS THE OWNER IS ONE OF THE
 PROFESSIONALS LISTED IN THE GENERAL LIMITATION #7.
 *** IF SYSTEM IS LIMITED BY GENERAL LIMITATION #9,
 THEN THE SYSTEM MAY NOT BE USED IN THIS REGION BECAUSE
 THE DESIGN PRESSURES ARE TOO LOW AND THEY CANN'T BE
 ENHANCED. SEE GENERAL LIMITATION #9 ON LAST PAGE OF
 DADE COUNTY NOA 02-0212.07 SUBMITTED.
 ****NOTE: KEEP IN MIND THAT SELECTED ASSEMBLY NEEDS
 TO BE AN INSULATED ONE AS SPECIFIED ON PLANS.
  
 C) SIMPSON CONNECTOR SPH6. PROVIDE FLORIDA PRODUCT
 APPROVAL COVER PAGE FOR 2004 VERSION. ONE SUBMITTED IS
 FOR 2001 VERSION. PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE FOR 2004 VERSION AND THE SPECIFIC
 PAGE WITH THE SELECTED CONNECTOR.
  
 8- ON FIRST SUBMITTAL ALL DOORS AND WINDOWS PRODUCT
 APPROVALS WERE FOR IMPACT GLAZING. NOW THE ONLY PRODUCT
 APPROVAL SUBMITTED FORIMPACT GLAZING IS FOR THE FIXED
 WINDOWS. CLARIFY IF ONLY THE FIXED WINDOWS WILL HAVE
 IMPACT GLASS, THEN HOW ARE THE OTHER WINDOWS GOING TO
 BE PROTECTED. PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS INCLUDING PRODUCT APPROVAL, KEY PLAN AND
 COMPLETE INSTALLATION SCHEDULE. SEE ATTACHED SAMPLE.
  
 9- SHEET 2/3:
 A) TYPICAL WALL SECTION: REVISE SPECIFIED FASTENERS
 FOR MTS20. SEE LATEST SIMPSON CATALOGUE. OTHERWISE,
 PROVIDE COMPLETE ENGINEERING ANALYSIS FOR FASTENERS AND
 UPLIFT LOADS THAT DIFFER FROM THOSE TESTED AND
 PUBLISHED BY THE MANUFACTURER. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 B) CLARIFY ROOF TRUSSES SPACING. ROOF FRAMING PLAN
 SAYS 24"O.C. WHILE TYPICAL WALL SECTION SAYS 16"O.C..
 REVISE AS REQUIRED. ALSO, TYP. WALL SECTION CALLS FOR
 FLOOR TRUSSES INSTEAD OF ROOF TRUSSES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-12 Cont ID  
Sent By jgomez Date 2006-10-12 Time 18:00 Rev Time 3.00
Received By jgomez Date 2006-10-12 Time 17:28 Sent To  
Notes
2006-10-12 18:10:23BUILDING REVIEW CHECKLIST:
 1- SPECIFY SAFETY GLASS BY MASTER BATH BATHTUB. SEC.
 R308.4 2004 FLORIDA RESIDENTIAL CODE.
  
 2- UPDATE STRUCTURAL NOTE #2(C). NEED TO REFERENCE ASCE
 7-02 NOT ASCE 7-98.
  
 3- REVISE STRUCTURAL NOTE #14. NAIL SIZE IS NOT LONG
 ENOUGH ACCORDING TO ASTM C-926 AND ASTM C-1063. NEED
 FASTENER THAT IS LONG ENOUGH TO PROVIDE MIN. EMBEDMENT
 OF 1 3/4" INTO TRUSS. REVISE AS REQUIRED. ALSO, CLARIFY
 NOTE REGARDING VENTING. STUCCO SOFFIT HAS NOTHING TO DO
 WITH PLYWOOD VENTING?
  
 4- OWES $4.46 FOR RADON FEES.
  
 5- SOIL TEST REPORT SUBMITTED:
 A) NEED 2 COPIES WITH ORIGINAL SEAL, SIGNATURE AND
 DATE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES.B)
 NEED ENGINEERING FIRM CERTIFICATE OF AUTHORIZATION IN
 THE REPORT LETTERHEAD AS REQUIRED BY FLORIDA
 ADMINISTRATIVE CODE SEC. 61G15-23.002. SEE ATTACHED
 COPY.
 C) REPORT SAYS THAT PROPOSED CONSTRUCTION IS MASONRY.
 PLANS SHOW WOOD FRAME CONSTRUCTION. CLARIFY AND REVISE
 AS REQUIRED.
  
 6- TRUSS DRAWINGSWILL NEED TO BE SUBMITTED PRIOR TO
 INSTALLATION AS REQUIRED BY SEC. R802.10 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 7- SURVEY WITH PROPOSED ADDITION DON'T MATCH PLANS.
 REVISE AS REQUIRED. ONLY 2 COPIES REQUIRED. SEE
 COMMENTS FROM ZONING REVIEW.
  
 8- ENERGY CALCULATIONS PAGE 2.MINIMUM INSULATION
 REQUIRED FOR 2"X6" WALL IS R-19, NOT R-11. REVISE AS
 REQUIRED.
  
 9- REVISE TYPICAL WALL SECTION ON DRAWING 2/3 TO
 REFLECT THE R-19 INSULATION AS REQUIRED BY ENERGY
 CALCULATIONS.
  
 10- SHOW IN PLANS SPECIFIC LOCATION AND SIZE OF
 VENTILATION OPENINGS THAT COMPLY WITH SEC. R806.2.
 SPECIFICATIONS SHOWN ON PLAN "VENTILATIONTO MATCH
 EXISTING" IS NOT ENOUGH INFORMATION TO VERIFY
 COMPLIANCE. PROVIDE VENTILATION CALCULATIONS.
  
 11- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
 NOAS 03-0514.01 AND 02-0701.12 WERE SIGNED AND SEALED
 BY AN ARCHITECT WHO HAS NOTHING TO DO WITH THIS JOB. ON
 THE OTHER HAND,NOA'S NO NEED TO BE SIGNED AND SEALED
 AND ONLY THE PROFESSIONAL RESPONSIBLE OF THE DESIGN OF
 THE PRODUCT IS ALLOWED TO SIGN AND SEAL IT.
  
 12- ALL PRODUCT APPROVALS NEED TO BE APPROVED IN
 WRITTING BY DESIGNER OF RECORD FOR THIS PROJECT. BUCK
 ENGINEERING STAMP ALONE IS NOT ENOUGH INFORMATION TO
 SHOW ENGINEER'S APPROVAL.STAMP DOESN'T IDENTIFY WHAT
 IS THE STAMP FOR AND IS NOT SIGNED/INITIALIZED BY THE
 ENGINEER.CLEARLY SPECIFY THAT PRODUCT WAS REVIEWED
 AND APPROVEDAS REQUIRED BY SEC. 106.3.3 OF CITY
 AMENDMENTS TO FBC 2004.
  
 13- BUCK ENGINEERING INC NEED TO PROVIDE THE FIRM
 CERTIFICATE OF AUTHORIZATION AS REQUIRED BY FLORIDA
 ADMINISTRATIVE CODE SEC. 61G15-23.002. SEE ATTACHED
 COPY.
  
 14- PROVIDE FLORIDA OR LOCAL PRODUCT APPROVAL FOR:A)
 SINGLE HUNG WINDOWS. NEED TO PROVIDE NOA THAT MATCHES
 ONE SUBMITTED FOR FLORIDA PRODUCT APPROVAL FL 239.
  
 B) WINDOW MULLIONS. NEED TO PROVIDE NOA THAT MATCHES
 ONE SUBMITTED FOR FLORIDA PRODUCT APPROVAL FL 261.
 ALSO, NOA 02-0701.05 SUBMITTED EXPIRED ON 06/28/06.
  
 C) FLAT ROOF SYSTEM.
 * NEED TO IDENTIFY SPECIFIC APPROVED ASSEMBLY FROM THE
 NOA TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES. ***
 NOTE: KEEP IN MIND THAT PLANS CALL FOR INSULATED
 ASSEMBLY. SEE TYPICAL WALL SECTION IN PLANS. **NEED TO
 PROVIDE RAS 117 CALCULATIONS DONE ONLY BY ANY OF THE
 PROFESSIONALS LISTED ON GENERAL LIMITATION #7 OF
 PRODUCT APPROVAL. SEE LAST PAGE OF THE NOA.
  
 D) FIXED WINDOWS. NEED TO PROVIDE NOA THAT MATCHES
 ONE SUBMITTED FOR FLORIDA PRODUCT APPROVAL FL 243.NOA
 01-0102.01 EXPIRED ON 09/13/06.
  
 E) ALL SIMPSON CONNECTORS SPECIFIED ON PLANS AND
 DETAILS. SEE PLANS. PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND DRAWING SHOWING SPECIFIC
 CONNECTORS. NO NEED TO INCLUDE COMPLETEREPORT.
  
 15- WEST ELEVATION ON SHEET 1/3 SHOWS MASTER BEDROOM
 DOOR AS 8'-0" HIGH DOOR. FLOOR PLAN CALLS FOR 6'-8"
 HIGH DOOR. REVISE AS REQUIRED TO MATCH.
  
 16- SHEET 2/3:
 A) TYPICAL WALL SECTION : REVISE FASTENER FOR MTS20
 CONNECTOR SPECIFIED. THIS IS WOOD FRAME CONSTRUCTION,
 NOT MASONRY. THEREFORE TITEN FASTENERS ARE NOT USED.
 SEE CATALOGUE FOR PROPER NUMBER AND TYPE OF FATENERS.
  
 B) TRUSS TIE DOWN SCHEDULE: SEE CURRENT CATALOGUE AND
 REVISE NUMBER,TYPEAND DESIGN PRESSURESFOR ALL
 CONNECTORS. OTHERWISE, PROVIDE COMPLETE ENGINEERING
 ANALYSIS FOR NUMBERS THAT DIFFER FROM THOSE TESTED AND
 PUBLISHED BY THE MANUFACTURER. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-06-19 Cont ID  
Sent By btrobaug Date 2007-06-19 Time 07:36 Rev Time 0.00
Received By btrobaug Date 2007-06-19 Time 07:15 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-11-14 Cont ID  
Sent By btrobaug Date 2006-11-14 Time 08:07 Rev Time 0.75
Received By btrobaug Date 2006-11-14 Time 06:38 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-09-27 Cont ID  
Sent By btrobaug Date 2006-09-27 Time 18:05 Rev Time 0.50
Received By btrobaug Date 2006-09-27 Time 17:50 Sent To P
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2006-09-11 Cont ID  
Sent By ssherman Date 2006-09-11 Time 11:01 Rev Time 0.00
Received By ssherman Date 2006-09-11 Time 11:00 Sent To  
Notes
2006-09-11 00:00:00HISTORICAL APPROVAL NO FEE PER GALINA
 JUDGE

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-08-28 Cont ID  
Sent By adarroug Date 2007-08-28 Time 11:31 Rev Time 0.00
Received By adarroug Date 2007-08-28 Time 11:31 Sent To B
Notes
2007-08-28 11:32:11TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-06-18 Cont ID  
Sent By adarroug Date 2007-06-18 Time 09:52 Rev Time 0.00
Received By adarroug Date 2007-06-18 Time 09:52 Sent To E
Notes
2007-06-18 09:56:03TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-05-25 Cont ID  
Sent By adarroug Date 2007-05-25 Time 09:41 Rev Time 0.00
Received By adarroug Date 2007-05-25 Time 09:41 Sent To M
Notes
2007-05-25 09:41:39TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-04-27 Cont ID  
Sent By adarroug Date 2007-04-27 Time 11:45 Rev Time 0.00
Received By adarroug Date 2007-04-27 Time 11:45 Sent To B
Notes
2007-04-27 11:46:05TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-04-17 Cont ID  
Sent By adarroug Date 2007-04-17 Time 11:53 Rev Time 0.00
Received By adarroug Date 2007-04-17 Time 11:52 Sent To B
Notes
2007-04-17 11:53:17TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-02-05 Cont ID  
Sent By adarroug Date 2007-02-05 Time 13:34 Rev Time 0.00
Received By adarroug Date 2007-02-05 Time 13:34 Sent To B
Notes
2007-02-05 13:34:44TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-01-29 Cont ID  
Sent By adarroug Date 2007-01-29 Time 17:56 Rev Time 0.00
Received By adarroug Date 2007-01-29 Time 17:56 Sent To Z
Notes
2007-01-29 17:57:12TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-11-12 Cont ID  
Sent By adarroug Date 2006-11-12 Time 12:45 Rev Time 0.00
Received By adarroug Date 2006-11-12 Time 12:45 Sent To E
Notes
2006-11-12 12:45:30TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-08 Cont ID  
Sent By adarroug Date 2006-11-08 Time 15:31 Rev Time 0.00
Received By adarroug Date 2006-11-08 Time 15:31 Sent To Z
Notes
2006-11-08 15:32:06TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-19 Cont ID  
Sent By adarroug Date 2006-09-19 Time 09:19 Rev Time 0.00
Received By adarroug Date 2006-09-19 Time 09:19 Sent To E
Notes
2006-09-19 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-12 Cont ID  
Sent By jgomez Date 2006-10-12 Time 18:10 Rev Time 0.00
Received By jgomez Date 2006-09-11 Time 12:00 Sent To  
Notes
2006-09-11 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-06-19 Cont ID  
Sent By tgordon Date 2007-06-19 Time 09:51 Rev Time 0.25
Received By tgordon Date 2007-06-19 Time 09:51 Sent To  
Notes
2007-06-19 09:52:19REVISION TO MECH. PLANS PAGE 3/3.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-05-25 Cont ID  
Sent By tgordon Date 2007-05-25 Time 15:58 Rev Time 0.25
Received By tgordon Date 2007-05-25 Time 15:58 Sent To  
Notes
2007-05-25 15:59:42SUBMITTAL REVISION ATTACHED TO MECHANICAL PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-11-14 Cont ID  
Sent By tgordon Date 2006-11-14 Time 13:58 Rev Time 0.25
Received By tgordon Date 2006-11-14 Time 13:58 Sent To B
Notes
2006-11-14 13:59:49RESTAMP MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-10-06 Cont ID  
Sent By tgordon Date 2006-10-06 Time 11:04 Rev Time 0.25
Received By tgordon Date 2006-10-06 Time 11:04 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-11-14 Cont ID  
Sent By mperson Date 2006-11-14 Time 10:50 Rev Time 0.33
Received By mperson Date 2006-11-14 Time 10:50 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-10-05 Cont ID  
Sent By mperson Date 2006-10-05 Time 16:10 Rev Time 0.45
Received By mperson Date 2006-10-05 Time 16:10 Sent To M
Notes
2006-10-05 00:00:00******UNSAT******
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW:
  
 1. PER FBC-2004,PLUMBING, SECTION 905.3
 VENT CONNECTIONS TO DRAINAGE SYSTEM.
 EVERY DRY VENT CONNECTING TO A
 HORIZONTAL DRAIN SHALL CONNECT ABOVE THE
 CENTERLINE OF THE HORIZONTAL DRAIN PIPE.
 PLEASE REFERENCE THE CORRECTED SANITARY
 PLUMBING LAYOUT AND SANITARY ISOMETRIC
 RISER DIAGRAM IN RED INK ON SHEET 3/3
 FOR RESUBMITTAL.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2007-02-02 Cont ID  
Sent By mmclean Date 2007-02-02 Time 14:13 Rev Time 0.00
Received By mmclean Date 2007-02-02 Time 13:10 Sent To I
Notes
2007-02-02 14:13:11PROVISO: THE PROPOSED ADDITION MUST NOT BE USED FOR
 SEPARATE LIVING SPACE.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-11-11 Cont ID  
Sent By mmclean Date 2006-11-11 Time 14:12 Rev Time 0.00
Received By mmclean Date 2006-11-11 Time 14:12 Sent To I
Notes
2006-11-11 14:14:12PROVISO: THE PROPOSED ADDITION MUST NOT BE USED FOR
 SEPARATE LIVING SPACE.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-09-16 Cont ID  
Sent By mmclean Date 2006-09-16 Time 13:48 Rev Time 0.00
Received By mmclean Date 2006-09-16 Time 13:48 Sent To I
Notes
2006-09-16 00:00:00DENIED,
 1. PLEASE SHOW THE PROPOSED ADDITION ON
 THE CURRENT SURVEY (8/17/06) ONLY TWO
 COPIES IS NEEDED FOR REVIEW.
  
  
 NOTE: THE PROPOSED ADDITION CANNOT BE
 USED AS A SEPARATE LIVING SPACE.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720