| Plan Review Stops For Permit 06090246 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2006-09-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-09-15 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-09-15 |
Time |
16:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-09-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-09-11 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-09-11 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2006-09-11 00:00:00 | DENIED | | | | | | 1) THE DESIGN PRESSURES FOR THE FLAT | | | ROOF SYSTEM ARE TOO LOW FOR ROOF ZONES 2 | | | AND 3. THE MAXIMUM DESIGN PRESSURE FOR | | | THE PRODUCT APPROVAL SUBMITTED FOR THE | | | MODIFIED BITUMEN SYSTEM OVER A WOOD DECK | | | IS -52.5 PSF. THE PRODUCT APPROVAL DOES | | | NOT ALLOW THE DESIGN PRESSURE TO BE | | | INCREASED FOR BONDED SYSTEMS. SEE PAGES | | | 1 AND 2 OF 17. | | | | | | 2)A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
|