Plan Review Details - Permit 06090224
Plan Review Stops For Permit 06090224
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-10-06 Cont ID  
Sent By mperson Date 2006-10-06 Time 09:29 Rev Time 0.33
Received By mperson Date 2006-10-06 Time 09:29 Sent To PC
Notes
2006-10-06 00:00:00REVISION: NEW PLANS INDICATING LONGER
 LENGTH IN PIPING.
  
  
 **********PROVISO**********
 A) FUTURE GENERATOR GAS PIPING AT OWN
 RISK. A SEPERATE GEN/RES PERMIT REQUIRED
 WITH ZONING, ELECTRICAL, AND GAS
 APPROVAL OF GENERATOR PLACEMENT.
 B) PER FBC-2004 FUEL GAS A SEDIMENT TRAP
 SHALL BE INSTALLED DOWNSTREAM OF THE
 EQUIPMENT SHUTOFF VALVE AS CLOSE TO THE
 INLET OF THE EQUIPMENT AS PRACTICAL.
 C) FBC-2004 FUEL GAS SEC. 404.12 OUTLET
 CLOSURES: GAS OUTLETS THAT DO NOT CON-
 NECT TO APPLIANCES SHALL BE CAPPED GAS
 TIGHT.

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2006-09-13 Cont ID  
Sent By mperson Date 2006-09-13 Time 15:18 Rev Time 0.33
Received By mperson Date 2006-09-13 Time 15:18 Sent To PC
Notes
2006-09-13 00:00:00 
  
 ******PROVISO******
 A) FBC-2004 FUEL GAS SEC. 404.12 OUTLET
 CLOSURES: GAS OUTLETS THAT DO NOT CON-
 NECT TO APPLIANCES SHALL BE CAPPED GAS
 TIGHT.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-05 Cont ID  
Sent By adarroug Date 2006-10-05 Time 16:43 Rev Time 0.00
Received By adarroug Date 2006-10-05 Time 16:43 Sent To G
Notes
2006-10-05 00:00:00TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-13 Cont ID  
Sent By mperson Date 2006-09-13 Time 15:29 Rev Time 0.00
Received By mperson Date 2006-09-09 Time 18:42 Sent To  
Notes
2006-09-09 00:00:00TO "G" BOX