| 2006-09-21 00:00:00 | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE VALUE ON THE APPLICATION MUST |
| | INCLUDE THE TOTAL COST OF LABOR AND |
| | MATERIAL. VALUATION REFERENCES MAY |
| | INCLUDE THE LATEST PUBLISHED DATA OF |
| | NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES PER 108.3 FBC AS AMENDED. |
| | |
| | 2} SHOW THE PHYSICAL LOCATION OF ALL |
| | SERVICE EQUIPMENT ON THE PLAN. 215.5. |
| | |
| | 3} PLEASE PROVIDE A PANEL SCHEDULE SO |
| | THAT BRANCH/FEEDER CIRCUIT CONDUCTOR AND |
| | OVER CURRENT PROTECTION COMPLIANCE MAY |
| | BE REVIEWED PER 106.3.5.4 FBC AS |
| | AMENDED |
| | |
| | 4} PROVIDE LOAD CALCULATIONS PER ARTICLE |
| | 220. |
| | |
| | 5} PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. |
| | |
| | 6} SMOKE DETECTORS MUST BE INSTALLED TO |
| | COMPLY WITH R313.1 RESIDENTIAL FLORIDA |
| | BUILDING CODE. |
| | |
| | 7} KITCHEN RECEPTACLE SPACING MUST |
| | COMPLY WITH 210.52(A), 210.52(C), AND |
| | 210.8(A)(6) GFI. |
| | |
| | 8} BATH CIRCUIT REQUIRED TO HAVE A 20 |
| | AMP RECEPTACLE PER 210.11(C) (3), |
| | LOCATED PER 210.52(D), AND BE GFI |
| | PROTECTED PER 210.8(A) (1). |
| | |
| | 9} RECEPTACLE SPACING MUST COMPLY WITH |
| | 210.52(A) (1) AND 210.52(A)(2), ALL |
| | ROOMS. |
| | |
| | 10} EGRESS LIGHTING IS REQUIRED PER 210.70(A)(2)(B). |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | |
| | |
| | |