Plan Review Details - Permit 06090015
| Plan Review Stops For Permit 06090015 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2006-11-25 |
|
|
Cont ID |
|
| Sent By |
rnuquist |
Date |
2006-11-25 |
Time |
12:42 |
Rev Time |
0.00 |
| Received By |
rnuquist |
Date |
2006-11-25 |
Time |
12:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-09-09 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2006-09-09 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2006-09-09 |
Time |
15:24 |
Sent To |
PC |
|
| Notes |
| 2006-09-09 00:00:00 | | | | | | | DENIED | | | | | | 1) PLEASE SEE THAT THEIR ARE ONLY 2 | | | SHUTTERS YET EVERY ATTACHMENT METHOD IS | | | CIRCLED, THE MARKED DESIGN PRESSURE DOES | | | NOT CORRESPOND WITH THE ENGINEERED | | | PRESSURES,THE MAX DESIGN PRESSURE DOES | | | NOT ALLOW FOR THE SHUTTER SPAN IF WALL | | | MOUNT IS USED SEEPAGE 9 OF DRAWING | | | | | | 2) WE HAVE CORRECTED MANY DRAWING | | | SUBMITTED BY THIS CONTRACTOR IF ALL | | | DRAWINGS ARE GOING TO BE MARKED EXACTLY | | | ALIKE THEY WILL BE DENIED, PLEASE MARK | | | CORRECT INFORMATION AS IT APPLIES TO | | | SPECIFIC JOB | | | | | | 3) SITE SPECIFIC ENGINEERING FOR | | | BUILDING IS INCORRECTLY STATING 2001 | | | CODE. 2004 CODE IS THE ADOPTED CODE AS | | | OF OCT.1, 2005 | | | | | | 4) ENG FIRM NEEDS CA# |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-11-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-11-16 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-16 |
Time |
10:58 |
Sent To |
B |
|
| Notes |
| 2006-11-16 10:58:19 | TO "LMARTINEZ" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2006-09-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-06 |
Time |
16:15 |
Sent To |
|
|
| Notes |
| 2006-09-06 00:00:00 | TO "MISC" BOX#1 |
|
|
|