Plan Review Details - Permit 06082252
Plan Review Stops For Permit 06082252
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2007-06-25 Cont ID  
Sent By lursu Date 2007-06-25 Time 14:17 Rev Time 0.00
Received By lursu Date 2007-06-25 Time 14:17 Sent To  
Notes
2007-06-25 14:20:07THE RECORDED UOT FOR THESE TWO PARCELS : PCN -
 74434328100080290 AND PCN = 74434328090070250 ,WAS
 RECEIVED BY THIS OFFICE .PLEASE CONTACT THE PROPERTY
 APPRAISER'S OFFICE TO RECEIVE A NEW PARCEL CONTROL
 NUMBER .
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2007-03-19 Cont ID  
Sent By lursu Date 2007-03-19 Time 10:53 Rev Time 0.00
Received By lursu Date 2007-03-14 Time 15:57 Sent To  
Notes
2007-03-19 10:57:15BASED ON THE UNITY OF TITLE OF THE TWO PROPERTIES 1177
 CLARE AVE & 1156 CAROLINE ST ,PLEASE PROVIDE THE
 DIGITAL COPY OF THE PROJECT LAYOUT.THE NEW PARCEL
 CONTROL NUMBER WILL BE ASSIGNED BY THE PROPERTY
 APPRAISER'S OFFICE AND THE SITE ADDRESSES IN USE MUST
 BE REVIEWED BY THE CITY.
  
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-03-08 Cont ID  
Sent By jwitmer Date 2007-03-08 Time 10:12 Rev Time 1.77
Received By jwitmer Date 2007-03-08 Time 10:12 Sent To  
Notes
2007-03-08 10:14:55PERMIT: 06082252
 ADD: 1177 CLARE AVE.
 CONT: AK CONSTRUCTION
 TEL: (561)239-1852
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 ACTION:PROVISO
 FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3)COMPLIED, UNITY OF TITLE.
  
 4C) COMPLIED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-20 Cont ID  
Sent By jwitmer Date 2006-09-20 Time 14:02 Rev Time 2.22
Received By jwitmer Date 2006-09-20 Time 14:02 Sent To  
Notes
2006-09-20 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06082252
 ADD: 1177 CLARE AVE.
 CONT: AK CONSTRUCTION
 TEL: (561)239-1852
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) PLEASE PROVIDE A UNITY OF TITLE.
 THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 OF TITLE' DOCUMENT SO THAT 2004 FBC
 TABLE 601 BOUNDARY LINE REQUIREMENTS MAY
 BE DEEMED NOT APPLICABLE.
 IT APPEARS THE DOORWAY IN BAY# 4&5
 CROSSES INTO 1156 ELIZABETH AVE.
  
 4)110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.PROVIDE LEVEL
 OF ALTERATION IN ACCORDANCE WITH 2004
 FLORIDA EXISTING BUILDING CODE,
 BUILDING.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G) NUMBER OF UNITS
 H) FLOOD ZONE
 I) FLOOD ELEVATION
 J)L.O.M.R.
  
 5) SHEET F1 INDICATES A 1HR FIRE RATING
 USING METAL STUDS WITH 1 " METAL SCREWS
 WITH AN ALTERNATIVE OF WOOD STUDS.
 PLEASE PROVIDE TYPE OF DRYWALL SCREW YO
 BE USED AND LENGTH OF SCREW?
  
 6) PLANS INDICATE A DOOR AND WINDOW
 SCHEDULE BUT NO DESIGNATION TO OPENINGS,
 ARE THERE ANY NEW EXTERIOR WINDOWS OR
 DOORS, ADD INFO. 106.1.2*.
  
 7) E1 INDICATES BAY# 1 TO BE A
 AUTOMOTIVE REPAAIR SUITE, ARE THE
 VEHICLES TO BE ABLE TO ENTER THE SUITE
 OR IS THIS A PARTS ONLY WORK TO BE
 COMPLETED ON THE EXTERIOR OF THE
 BUILDING?ADD INFO. 106.1.2*.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-06-08 Cont ID  
Sent By dpalmer Date 2007-06-08 Time 17:22 Rev Time 0.00
Received By dpalmer Date 2007-06-08 Time 13:33 Sent To  
Notes
2007-06-08 17:22:28STAMPED

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-02-11 Cont ID  
Sent By dpalmer Date 2007-02-11 Time 16:34 Rev Time 0.00
Received By dpalmer Date 2007-02-11 Time 15:27 Sent To  
Notes
2007-02-11 16:35:16** UNSAT ** 2ND REVIEW
  
  
  
 1) NOTE: PLEASE SEE THAT PLANS SHALL STATE ALL RELEVANT
 CODES FOR DESIGN. PLEASE SEE PLANS NOTES MENTIONS THE
 2001 FBC.
 PLEASE STATE THE FOLLOWING AT A MINIMUM FOR THIS
 REVIEWER AND PLEASE SEE ANY OTHER RELEVANT CODES WHICH
 MAY BE REQUIRED BY OTHER REVIEWER(S).
 2002 NFPA-70, 2002 NFPA-72, 2003, NFPA-101, AND THE
 2004 FBC.
 PLEASE SEE SOME LOCATIONS ON PLANS WHICH MENTIONS *PALM
 BEACH COUNTY*.
  
 2) NOTE: PLEASE CLARIFY THE DESIGNERS OF RECORD FOR
 SCOPES AS SHOWN. PLEASE SEE SOME SHEETS WHICH CONTAIN
 ELECTRICAL AND ELECTRICAL INFORMATION IS DONE BY A
 DIFFERENT DESIGN PROFESSIONAL THAN THAT ON ELECTRICAL
 SHEETS. PLEASE SEE OTHER SHEETS WITH NOTES FOR
 ELECTRICAL ALSO CONTAIN YET ANOTHER DESIGNER OF
 RECORD??
 THIS IS UNCLEAR AT THIS TIME.
 FS 471.025
  
 3) NOTE: PLEASE KNOW, ALL SPACES SHALL STATE THE
 OCCUPANCY CLASSIFICATIONS AND/OR THE INTENDED OCCUPANCY
 CLASSIFICATIONS.
 PLEASE SEE THE STORAGE AREAS IF HAZARDOUS NEED TO BE
 STATED AS SUCH.
 PLEASE SEE THAT SPACES 6 AND 7 WHICH ARE BEING SHOWN AS
 SEPARATE TENANTS AND OCCUPANCIES ARE BEING SHOWN WITH
 SEVERAL OPENINGS AND DOORS BETWEEN THE TWO. ACCESS FROM
 ONE TENANT TO ANOTHER OR THROUGH ANOTHER IS UNCLEAR.
 HOW DOES THIS MEET TENANT SEPARATION OF OCCUPANCIES?
 *PLEASE SEE ANY BUILDING REVIEW AND/OR FIRE REVIEW
 COMMENTS FOR THIS.
  
 4) NOTE: PLEASE SEE PERMIT APPLICATION SCOPE OF WORK
 DOES NOT CORRELATE WITH THE PLANS SUBMITTED IN ANY
 FASHION. PLEASE SEE THE SQ FOOTAGE AND THE PLANS
 INDICATE ALMOST TWICE THE SQ FT?? PLEASE CORRELATE.
 PLEASE SEE PERMIT APPLICATION WHICH REQUIRES PROJECT
 AND SCOPE TO BE DESCRIBED IN DETAIL.
  
 5) NOTE: PLEASE SEE THE PREVIOUS REVIEW MENTIONED THE
 VALUE FOR THE COMPLETE SCOPE OF WORK WAS EXTREMELY LOW
 AND THE VALUE WAS ONLY INCREASED TO $38K WHICH WOULD
 NOT COVER THE ELECTRICAL ALONE FOR MATERIALS OR LABOR.
 PLEASE KNOW THAT WAS VALUE WILL BE ASSESSED FOR ACTUAL
 SCOPE AS APPLIED AND SHOWN ON PLANS.
 *PREVIOUS REVIEW NOTE**
 PLEASE SEE THE VALUE IS EXTREMELY LOW AS STATED FOR
 THE SCOPE OF WORK BEING PROPOSED. PLEASE SEE THAT ONE
 WILL BE ASSESSED PER MARSHALL'S & SWIFT GUIDE AS
 ADOPTED UNDER THE FBC IF AN ACCURATE FIGURE IS NOT
 ADJUSTED FOR SCOPE.
 FBC 108.3, MUST INCLUDE ALL LABOR AND MATERIALS,
 WHETHER OR NOT OWNER SUPPLIED.
  
 6) NOTE: PLEASE SEE FBC CHAPTER 13, PLEASE SUBMIT
 COMPLETED PLANS FOR SYSTEM BEING INSTALLED. PLEASE
 INDICATE AND SHOW ALL OVER RIDES ON PLANS, AT LOCATIONS
 AS REQUIRED UNDER THE FBC.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3
 PLEASE SEE NOTE #1 WHICH MENTIONS TIME FOR DEVICE TO
 TURN OFF IN (30FEET) THIS SEEMS TO BE A MISPRINT.
 PLEASE SEE THERE ARE AREAS WHICH A SINGLE CEILING
 MOUNTED OC SENSOR WILL NOT PROVIDE THE NEEDED COVERAGE
 WHEN AN OCCUPANT ENTERS A SPACE.
 PLEASE CHECK THE LIMITATIONS ON THE DEVICES BEING
 SPECIFIED ON PLANS AND ADJUST ACCORDINGLY. PLEASE SEE
 ANY AREAS WHICH WALLS WOULD BLOCK THESE DEVICES WOULD
 BE REQUIRED TO CONTAIN ANOTHER DEVICE FOR COVERAGE FOR
 LIFE SAFETY. (LS101 7.8)
 PLEASE SEE SUBMITTED PACKAGE DID NOT SEEM TO CONTAIN
 ANY ENERGY CALCULATIONS?
 13-415.1.AB.1.(THE LPD?S SEEM TO BE OK.)
 PLEASE ALSO SUBMIT ENERGY CALCULATIONS SIGNED, DATED
 AND SEALED.
 13-415.1.AB.1.
 PLEASE SEE 13-415.ABC.1.4 FOR EXT LTS.
  
 7) NOTE: PLEASE CLARIFY HOW THE LOADS FOR SHOW WINDOW
 AREAS WERE DERIVED. PLEASE SEE 220.12.
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW, IF ANY SPACE WILL BE MERCANTILE, AND HAVE
 WINDOWS IN FRONT FACING STREET WHICH IS SUBJECT TO
 PEDESTRIAN TRAFFIC, RECEPTS ABOVE THOSE WINDOWS WILL BE
 REQUIRED.
 210.62
  
 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS, WHICH IS ONLY BEING NOTED AT THIS
 TIME.
  
 9) NOTE: PLEASE SEE BASED ON PREVIOUS BUILDING REVIEW
 COMMENTS, THERE MAY STILL BE ADUSTMENTS IN PLANS WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-17 Cont ID  
Sent By dpalmer Date 2006-09-17 Time 15:07 Rev Time 0.00
Received By dpalmer Date 2006-09-12 Time 17:56 Sent To  
Notes
2006-09-17 00:00:00*** UNSAT ***
  
 ** PLEASE KNOW, IT IS KNOWN TO THIS
 OFFICE SOME OF THIS WORK WAS ALREADY
 DONE FOR THESE SEPARATION WALLS ETC.
  
 1) NOTE: PLEASE SEE FAC 61G15-23.002
 WHICH REQUIRES TITLE BLOCKS ON ALL
 SHEETS.
 PLEASE SEE PLANS ARE BEING DONE BY A
 STRUCTURAL ENGINEER KNOWN TO THIS
 OFFICE. PLEASE SEE FS 471.025.
  
 2) NOTE: PLEASE SEE THAT PLANS STATE ALL
 RELELVANT CODES FOR DESIGN. PLEASE SEE
 PLANS NOTES MENTIONS THE 2001 FBC.
 PLEASE STAE THE FOLLOWING AT A MINIMUM
 FOR THIS REVIEWER AND PLEASE SEE ANY
 OTHER RELEVANT CODES WHICH MAY BE
 REQUIRED BY OTHER REVIEWER(S).
 2002 NFPA-70, 2002 NFPA-72, 2003
 NFPA-101, AND THE 2004 FBC.
  
 3) NOTE: PLEASE PROVIDE AND SUBMIT
 COMPLETE LOAD CALCULATIONS FOR THE
 ENTIRE SERVICE. PLEASE SEE THE FOLLOWING
 NOTE ALSO FOR SERVICES AS SHOWN ON
 RISER.
 220,215.5 ETC.
 FBC 106.1.2
  
 4) NOTE: PLEASE SEE SERVICES AS SHOWN
 ARE NOTE PERMITTED AT THIS TIME. PLEASE
 SEE 230.2. PLEASE ALSO SEE MORE THAN
 6-MEANS OF DISCONNET FOR BUILDING.
 PLEASE SEE FBC DEFINITIONS, THIS IS ONE
 BUILDING AND AT THIS TIME ONLY ONE
 SERVICE WILL BE GRANTED.
  
 5) NOTE: PLEASE PROVIDE COMPLETE FAULT
 CURRENT CALCULATIONS FOR SERVICE AND THE
 AVAILABLE FUALT CURRENT AT MAIN(S).
 IT IS NOTED BY THIS OFFICE THAT THE 10K
 RATING IS SHOWN, HOWEVER COMPLETE CALCS
 ARE BEING REQUESTED BY THIS AHJ.
  
 6) NOTE: PLEASE KNOW, ALL SPACES SHALL
 STATE THE OCCUPANCY CLASSIFICATIONS
 AND/OR THE INTENED OCCUPANCY
 CLASSIFICATIONS.
 PLEASE KNOW, IT HAS COME TO OUR
 ATTENTION THAT SOME SPACE WERE BEING
 USED AS AN ASSEMBLY OCCUPANCY ETC.
 PLEASE SEE INDICATE ALL ELECTRICAL
 REQUIREMENTS FOR THE "AUTOMOTIVE REPAIR
 SHOP" AS KNOWN TO THIS OFFICE AND
 INDIACTE D ON PLANS.
 PLEASE SEE NEC 511 AS THIS IS ONEOF THE
 HAZARDOUS LOCATIONS.
 PLEASE SHOW INDICATE THE DOOR OPENINGS
 FOR THIS AUTOMOTICE REPAIR LOCATION ON
 PLANS.
 ** PLEASE SEE FIRE AND BUIDLING REVIEW
 COMMENTS FOR THIS.
  
 7) NOTE: PLEASE SEE PERMIT APPLICATION
 STATES ONE SQ FOOTAGE AND THE PLANS
 INDICATE ALMOST TWICE THE SQ FT?? PLEASE CORRELATE.
  
 8) NOTE: PLEASE SEE THE VALUE IS
 EXTREMEMLY LOW AS STATED FOR THE SCOPE
 OF WORK BEING PROPOSED. PLEASE SEE THAT
 ONE WILL BE ASSESSED PER MARSHALL'S &
 SWIFT GUIDE AS ADOPTED UNDER THE FBC IF
 AN ACCURATE FIGNURE IS NOT ADJUSTED FOR
 SCOPE.
 FBC 108.3, MUST INCLUDE ALL LABOUR AND
 MATERIALS, WHETHER OR NOT OWNER
 SUPPLIED.
  
 9) NOTE: PLEASE SEE FBC CHAPTER 13,
 PLEASE SUBMIT COMPLETED PLANS FOR SYSTEM
 BEING INSTALLED. PLEASE INDICATE AND
 SHOW ALL OVER RIDES ON PLANS, AT
 LOCATIONS AS REQUIRED UNDER THE FBC.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3
 PLEASE PROVIDE COMPLETE LIGHTING DENSITY
 LOADS AS REQUIRED PER 13-415.2.ABC.1,
 TABLES 415.2.C.1, 415.2.B.1.
 PLEASE ALSO SUBMIT ENERGY CALCULATIONS
 SIGNED, DATED AND SEALED.
 13-415..1.AB.1.
 PLEASE SEE 13-415.ABC.1.4 FOR EXT LTS.
  
 10) NOTE: PLEASE KNOW, IF ANY SPACE WILL
 BE MERCHANTILE, AND HAVE WINDOWS IN
 FRONT FACING STREET WHICH IS SUBJECT TO
 PEDESTRIAN TRAFFIC, RECETPS ABOVE THSOE
 WINDOWS WILL BE REQUIRED.
 210.62
  
 11) NOTE: PLEASE SEE FORE REVIEW
 COMMENTS AS THE LARGER BATHRM WILL ALSO
 REQUIRE AN EM BATTERY BACK UP FIXTURE OF
 SOME SORT.
 LS 101 7.8,7.9.
  
 ** PLEASE KNOW AT THIS TIME DUE TO SOME
 CHANGES WHICH WILL BE REQUIRED IN
 SERVICE ETC, PLANS AS SUBMITTED MAY HAVE
 FUTURE COMMENTS UPON NEXT REVIEW.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2006-09-12 00:00:00REVIEW ON HOLD.
 PLANS WILL BE GOING INTO "F" STATUS ONCE
 REVIEW IS COMPLETE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-06-21 Cont ID  
Sent By mawillia Date 2007-06-21 Time 09:41 Rev Time 0.00
Received By mawillia Date 2007-06-21 Time 09:31 Sent To  
Notes
2007-06-21 09:40:44 
 *****APPROVED*****
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEETS A-2 AND E1 WERE STAMPED,
 INITIALED, AND DATED.
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-03-07 Cont ID  
Sent By mawillia Date 2007-03-07 Time 16:07 Rev Time 0.00
Received By mawillia Date 2007-03-07 Time 15:22 Sent To  
Notes
2007-03-07 16:07:14 
 *****UNSAT*****
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED.
  
  
  
 1.) STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.ADD TO A PERTINENT
 DEMOLITION SHEET
  
 2.) CONSTRUCTION AND/OR DEMOLITION
 OPERATIONS SHALL NOT INTERFERE OR HINDER
 EMERGENCY ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF.ADD TO A PERTINENT DEMOLITION SHEET
  
 3.) ACCUMULATIONS OF COMBUSTIBLE WASTE
 MATERIAL, DUST AND DEBRIS SHALL BE
 REMOVED FROM THE STRUCTURE AND ITS
 IMMEDIATE VICINITY AT THE END OF EACH
 SHIFT OR MORE FREQUENTLY AS NECESSARY
 FOR SAFE OPERATIONS.ADD TO A PERTINENT DEMOLITION
 SHEET
  
 4.) ALL EXIT COMPONENTS SHALL BE
 MAINTAINED, CLEAR AND UNOBSTRUCTED.ADD TO A PERTINENT
 DEMOLITION SHEET
  
 5.) INTERIOR WALL AND CEILING FINISH
 SHALL BE CLASS "A" OR CLASS "B" IN
 ACCORDANCE WITH NFPA 101, 2003 EDITION,
 SECTION 10.2.THE UPDATED PLANS SHALL BE PRESENTED
 WITH NO INK, PENCIL, OR ANY OTHER HAND DRAWN MARKINGS
  
 7.)THE BUILDING IS NOT SPRINKLERED AS INDICATED ON
 PAGE A3.THIS INFORMATION ON THE UPDATED PLANS SHALL
 BE PRESENTED WITH NO INK, PENCIL, OR OTHER HAND DRAWN
 MARKINGS
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLAN) EACH ITEM WAS
 ADDRESSED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-05 Cont ID  
Sent By mawillia Date 2006-10-05 Time 11:49 Rev Time 0.00
Received By mawillia Date 2006-10-05 Time 11:35 Sent To  
Notes
2006-10-05 00:00:00*****DENIED*****
  
  
  
  
  
 1.) STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OF
 DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.
  
 2.) CONSTRUCTION AND/OR DEMOLITION
 OPERATIONS SHALL NOT INTERFERE OR HINDER
 EMERGENCY ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF.
  
 3.) ACCUMULATIONS OF COMBUSTIBLE WASTE
 MATERIAL, DUST AND DEBRIS SHALL BE
 REMOVED FROM THE STRUCTURE AND ITS
 IMMEDIATE VICINITY AT THE END OF EACH
 SHIFT OR MORE FREQUENTLY AS NECESSARY
 FOR SAFE OPERATIONS.
  
 4.) ALL EXIT COMPONENTS SHALL BE
 MAINTAINED, CLEAR AND UNOBSTRUCTED.
  
 5.) INTERIOR WALL AND CEILING FINISH
 SHALL BE CLASS "A" OR CLASS "B" IN
 ACCORDANCE WITH NFPA 101, 2003 EDITION,
 SECTION 10.2.
  
 6.) HOW WILL THE SCOPE OF WORK AFFECT
 THE ARRANGEMENT/LOCATION OF EXIT SIGNS,
 EMERGENCY LIGHTS, FIRE EXTINGUISHERS,;
 AND IF EQUIPPED, SPRINKLER OR FIRE ALARM
 SYSTEMS?
  
 7.) IF THE SCOPE OF THE INTERIOR
 BUILDOUT REQUIRES MODIFICATION OF A FIRE PROTECTION
 SYSTEM, PROVIDESEPARATE
 PERMIT AND SHOP DRAWINGS/PLANS.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-05-21 Cont ID  
Sent By adarroug Date 2007-05-21 Time 13:37 Rev Time 0.00
Received By adarroug Date 2007-05-21 Time 13:36 Sent To  
Notes
2007-06-08 10:52:07TO "COMM" BD#40
2007-05-21 13:37:26WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-23 Cont ID  
Sent By adarroug Date 2007-04-23 Time 15:05 Rev Time 0.00
Received By adarroug Date 2007-04-23 Time 15:05 Sent To  
Notes
2007-04-23 15:05:49WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-29 Cont ID  
Sent By adarroug Date 2007-01-29 Time 15:26 Rev Time 0.00
Received By adarroug Date 2007-01-29 Time 15:25 Sent To  
Notes
2007-02-07 08:52:37TO" COMM" BD#47
2007-01-29 15:26:53WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-05 Cont ID  
Sent By mawillia Date 2006-10-05 Time 11:35 Rev Time 0.00
Received By mawillia Date 2006-09-05 Time 15:14 Sent To  
Notes
2006-09-11 00:00:00TO "COMM" BD#15
2006-09-05 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2007-06-16 Cont ID  
Sent By rregueir Date 2007-06-16 Time 09:50 Rev Time 0.00
Received By rregueir Date 2007-06-16 Time 09:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-03-13 Cont ID  
Sent By rregueir Date 2007-03-13 Time 09:16 Rev Time 0.00
Received By rregueir Date 2007-03-09 Time 08:30 Sent To  
Notes
2007-03-13 09:20:35-----------------DENIED------------------
  
 PLANS CONTAIN NO INFORMATION REGARDING SIZE, LOCATION
 AND NUMBER OF FIRE DAMPERS REQUIRED AS A RESULT OF THE
 ADDITION OF THE RATED TENANT SEPARATIONS. PLEASE
 PROVIDE ADDITIONAL INFORMATION, PERHAPS INCLUDING FIRE
 DAMPER SUBMITTALS/INSTALLATION INSTRUCTIONS.
  
 AN ATTEMPT WAS MADE TO CONTACT THE ENGINEER VIA
 VOICEMAIL. A RETURN CALL WAS NOT RECEIVED.
  
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-04 Cont ID  
Sent By hmoser Date 2006-10-04 Time 16:11 Rev Time 0.00
Received By hmoser Date 2006-10-04 Time 16:18 Sent To  
Notes
2006-10-04 00:00:00PLAN DENIED
 MISSING EQUIPMENT SCHEDULE.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-06-18 Cont ID  
Sent By kstevens Date 2007-06-18 Time 18:15 Rev Time 0.00
Received By kstevens Date 2007-06-18 Time 18:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-02-24 Cont ID  
Sent By kstevens Date 2007-02-24 Time 17:21 Rev Time 0.00
Received By kstevens Date 2007-02-24 Time 17:21 Sent To  
Notes
2007-02-24 17:46:37DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 EXISTING BUILDING
 MUNICIPAL CODE
  
 FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. OK
  
 3. SUBMIT CALCULATIONS FOR MINIMUM
 FACILITIES FOR EACH SPACE PER TABLES
 1004.2.1. AND 403.1.
 ****RESPONSE NOTED, BUT ALL UNITS WITH A STORAGE
 OCCUPANCY REQUIRES A SERVICE SINK. PLEASE INDICATE
 LOCATION OF REQUIRED SINK. (SUITES 1,2,3,4 & 5,6 & 9).
  
 4. OK
 5. OK
 6. OK - PER C. WILLIAMS
  
 7. CHANGE OF OCCUPANCY FOR ANY OR ALL
 UNITS IS REQUIRED. THIS CAN BE VERIFIED
 WITH PREVIOUS OCCUPATIONAL LICENSES.
 SECTION 306.1. INDICATE ALL UNITS THAT
 HAVE A CHANGE OF OCCUPANCY. INDICATE
 PREVIOUS OCCUPANCY, AND WHAT OCCUPANCY
 IT WILL BE CHANGED TO.
 ****RESPONSE NOTED, BUT UNIT 6 IS INDICATED AS A
 STORAGE OCCUPANCY. WAS THIS A CHANGE OF OCCUPANCY?
  
 8. A BUILDING, FACILITY, OR ELEMENT THAT
 IS ALTERED SHALL COMPLY WITH CHAPTER 11.
 SUBMIT DETAILS FOR ALL TOILET ROOMS &
 REQUIRED DRINKING FOUNTAINS PER SECTIONS
 11-4.15, 11-4.16, 11-4.19, 11-4.22 AND
 ALL SUBSECTIONS.
 ****RESPONSE NOTED, BUT PLEASE SHOW COMPLIANCE WITH THE
 FOLLOWING:
 DRINKING FOUNTAINS...
 A. INDICATE IF THE DRINKING FOUNTAINS ARE FLOOR MOUNT
 OR CANTILEVERED TYPE. IF CANTILEVERED TYPE, THE
 CLEARANCE SHALL BE INDICATED PER SECTION 11-4.15.4.
 B. 11-4.15.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
 WATER CLOSETS...
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
 LAVS...
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
  
 **********NEW COMMENTS**********
  
 1B. SUBMIT A SANITARY RISER DIAGRAM ISOMETRIC SHOWING
 THE CONNECTION TO THE BUILDING DRAIN AND THE VENT
 PIPING FOR THE SERVICE SINKS REQUIRED IN TABLE 403.1.
 THE SERVICE SINK SHALL DISCHARGE DOWNSTREAM OF THE
 BATHROOM FIXTURES PER SECTION 909.1. SECTION
 106.3.5.1.3(4)(6)(13).
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-09-27 Cont ID  
Sent By kstevens Date 2006-09-27 Time 18:40 Rev Time 0.00
Received By kstevens Date 2006-09-27 Time 18:40 Sent To  
Notes
2006-09-27 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 EXISTING BUILDING
 MUNICIPAL CODE
  
 1. OCCUPANCY IS REQUIRED FOR EACH SPACE.
 SECTION 301.4.
  
 2. INDICATE THE LEVEL OF ALTERATION PER
 SECTION 301.5.
  
 3. SUBMIT CALCULATIONS FOR MINIMUM
 FACILITIES FOR EACH SPACE PER TABLES
 1004.2.1. AND 403.1.
  
 4. SHT F1 NOTE #5 IS NOT INDICATED ON
 FLOOR PLAN. PLEASE CLARIFY. SECTION
 106.1.1.
  
 5. SHT E1 ONLY SUITE #8 INDICATES "NOT
 IN SCOPE OF WORK". DISCRIPTION OF WORK
 DOES NOT INDICATE THIS. INDICATE ALL
 WORK AS REQUIRED IN THE SCOPE OF WORK.
 SECTION 301.2.
  
 6. SHT E1 INDICATES AN AUTOMOTIVE REPAIR
 SUITE #1. CONTACT LYNN MASSON
 ENVIRONMENTAL COMPLIANCE MANAGER TO SEE
 IF AN OIL SEPARATOR IS REQUIRED IN THE
 SPACE. CONTACT NUMBER IS (561) 822-2271.
 FAX (561) 822-2279 OR E-MAIL
 LMASSON2WPB.ORG. WASTE ORD. #3434 &
 MUNICIPAL CODE SECTION 90-124.
  
 7. CHANGE OF OCCUPANCY FOR ANY OR ALL
 UNITS IS REQUIRED. THIS CAN BE VERIFIED
 WITH PREVIOUS OCCUPATIONAL LICENSES.
 SECTION 306.1. INDICATE ALL UNITS THAT
 HAVE A CHANGE OF OCCUPANCY. INDICATE
 PREVIOUS OCCUPANCY, AND WHAT OCCUPANCY
 IT WILL BE CHANGED TO.
  
 8. A BUILDING, FACILITY, OR ELEMENT THAT
 IS ALTERED SHALL COMPLY WITH CHAPTER 11.
 SUBMIT DETAILS FOR ALL TOILET ROOMS &
 REQUIRED DRINKING FOUNTAINS PER SECTIONS
 11-4.15, 11-4.16, 11-4.19, 11-4.22 AND
 ALL SUBSECTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]