| 2006-09-10 00:00:00 | *********** UNSAT ************ |
| | |
| | 1) NOTE: PLEASE SEE PLANS SHALL INDICATE |
| | ALL RELEVANT CODES TO PROPOSED PROJECT |
| | AND DESIGN. |
| | PLEASE SEE THE FOLLOWING ARE REQUIRED AT |
| | A MINIMUM. |
| | 2002 NFPA-70, 2002 NFPA-110, 2004 FBC. |
| | |
| | 2) NOTE: PLEASE SEE THE VALUE FOR |
| | COMPLETE SCOPE OF WORK SHALL INCLUDE ALL |
| | LABOUR AND MATERIALS EVEN IF ANY |
| | EQUIPMENT IS OWNER SPPLIED. |
| | FBC 108.3. |
| | ** VALUE AS SHOWN ON APPLICATION IS LOW, |
| | PLEASE SEE THAT IF NOT ADJUSTED, A VALUE |
| | WILL BE ASSESSED USING THE MARSHALL'S & |
| | SWIFT GUIIDE AS ADOPTED BY THE FBC. |
| | PLEASE ALSO KNOW, SIGNED, CONTRACTS FOR |
| | ALL EQUIPMENT, ALL LABOUR AND MATERIALS |
| | MAY ALSO BE REQUESTED. |
| | THE VALUE ON THE GEN ALONE IS ABOVE THE |
| | VALUE APPLIED FOR. |
| | |
| | 3) NOTE: PLEASE SEE THE PROPOSED SCOPE |
| | AND GROUPING OF DISCONNECTS IS NOT CODE |
| | COMPLIANT. PLEASE ALSO SEE RISER IS NOT |
| | COMPLETE AT THIS TIME AS THE FEEDERS |
| | FROM THE LOAD SIDE OF THE ATS DO NOT |
| | APPEAR TO GO ANYWHERE? |
| | PLEASE SEE 225.34 AND 230.72 FOR |
| | GROUPING OF MAINS. THE NEW PROPOSED MAIN |
| | 2 OF 2 IS OUTSIDE AND THE OTHER MAIN 1 |
| | IS INSIDE. THE REQUIRED MAINS AND |
| | DISCONNECTS ARE NOT GROUPED AS REQUIRED. |
| | PLEASE SEE THE PERMIT APPLIED FOR # |
| | 06081714 HAS BEEN PLACED INTO A "HOLD" |
| | STATUS UNTIL DESIGN IS ADJUSTED. |
| | PLEASE PROVIDE A COMPLETE LAYOUT OF ALL |
| | THE EXISTING SERVICE AND NEW WORK. |
| | PLEASE KNOW THE ATS AND DISCONNECT BEING |
| | SHOWN AS EXISTING ON THIS RISER SHALL BE |
| | SHOWN AS NEW AS THIS SEPARATE PERMIT AS |
| | SHOWN WILL NOT BE GRANTED. |
| | 215.5,225.31-225.39, 230.72ETC |
| | |
| | 4) NOTE: PLEASE PROVIDE COMPLETE LOAD |
| | CALCULATIONS FOR PROPOSED GENERATOR AND |
| | ALL LOADS INTENDED FOR USE. PLEASE KNOW |
| | IF LOAD SHEDDING IS BEING PROPOSED, MUST |
| | SHOW LOAD SHEDDING DETAILS. |
| | ** PLEASE SEE 702.5, THE NOTE WHICH IS |
| | PLACE ON PLANS MENTIONS THE CONSUMER CAN |
| | MANUALLY TURN OFF BREAKERS TO CHOSE |
| | LOAD. PLEASE SEE 700.5 AND 701.5 THE AHJ |
| | AND OTHER CODES DETERMINE WHAT IS |
| | REQUIRED ON EMERGENCY AND LEGALLY |
| | REQUIRED STAND-BY SYSTEMS WHERE 702.5 |
| | MENTIONS THE CONSUMER CAN CHOSE WHICH |
| | LOADS THEY WANT TO HAVE ON AN OPTIONAL |
| | STAND-BY SYSTEM. THE PROPOSED BACK UP |
| | SYSTEM ON AN "AUTOMATIC STAND-BY" STILL |
| | MUST BE SIZED PER THE LOADS INTENDED. |
| | THE CODE DOES NOT STATE THE "OWNER CAN |
| | TURN OFF BREAKERS TO CHOOSE LOADS" |
| | THE SYSTEN AS SHOWN IS NOT BEING SHOWN A |
| | "MANUAL TRANSFER". |
| | 220.3,220.10,220.11,220.13, ETC. |
| | PLEASE SEE 215.3,230.42 FORANY |
| | CONTINUOUS LOADS. |
| | |
| | 5) NOTE: PLEASE SEE PERMIT APPLICATION |
| | SHALL STATE THE TENANT SPACE/UNIT |
| | NUMBER. PLEASE SEE THAT THE PERMIT |
| | APPLICATION SHALL ALSO STATE THE PROJECT |
| | IN DETAIL. PLEASE SEE APPL ONLY MENTIONS |
| | "INSTALL GENERATOR PAD", A HAND WRITTEN |
| | NOTE INCLUDING THE GENERATOR WAS DONE |
| | THE FRONT COUNTER STAFF. |
| | PLEASE LIST THE SIZE OF UNIT, ATS , |
| | SUB-BASE FUEL ETC. |
| | |
| | 6) NOTE: PLEASE PROVIDE A LEGAL SURVEY |
| | SHOWING THE EXACT LOCATION OF THE |
| | GENERATOR LOCATED ON PROPERTY INCLUDING |
| | ALL SETBACKS ETC. THIS WILL ALSO BE IN |
| | THE ZONING REVIEW NOTES. |
| | PLEASE KNOW, CODE COMPLIANCE CAN NOT BE |
| | DETERMINED AT THIS TIME. |
| | |
| | 7) NOTE: PLEASE SEE THAT ONCE THE |
| | UNIT/SUITE # IS OBTAINED, PLEASE INCLUDE |
| | ON TITLE BLOCKS WITH THE ADDRESS AS |
| | SHOWN. |
| | FAC 61G15-23.002 |
| | |
| | 8) NOTE: PLEASE SEE RISER CONTAINS THE |
| | SYMBOL FOR THE KEYNOTE #1 JUST BELOW |
| | TENANTS MCB #1 AND #2, HOWEVER KEY NOT |
| | #1 DOES NOT SEEM TO CORRELATE. |
| | |
| | ** ONE COPY OF THE ELECTRICAL RISER IN |
| | ONE SET HAS BEEN RETAINED BY THIS |
| | OFFICE. |
| | |
| | ** PLEASE KNOW AS THERE AREITEMS FOR |
| | CODE COMPLIANCE NOT YET SUBMITTED AND |
| | DESIGN AS SHOWN WILL BE CHANGING, THERE |
| | MAY BE COMMENTS ON NEW PLANS SUBMITTED. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |