Plan Review Details - Permit 06082225
Plan Review Stops For Permit 06082225
Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-09-12 Cont ID  
Sent By lursu Date 2006-09-12 Time 15:01 Rev Time 0.00
Received By lursu Date 2006-09-11 Time 15:54 Sent To  
Notes
2006-09-12 00:00:00PROJECT UNDER REVIEW. WHICH UNIT IS
 USED?

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-13 Cont ID  
Sent By rmcdouga Date 2006-09-13 Time 10:38 Rev Time 0.00
Received By rmcdouga Date 2006-09-13 Time 07:20 Sent To  
Notes
2006-09-13 00:00:00DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) ONE OF THE THREE SETS OF PLANS IS
 MISSING PAGE 3 OF 4 (E5.1).
  
 3) GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE SPECIFY THE SIZE OF THE SPECIFIC
 GENERATOR(WXL) THAT WILL BE INSTALLED
 AND SPECIFY THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
  
 4) SPECIFY THE BASIC WIND SPEED ON THE
 PLAN. SEE FBC 1603.1.4 AND 1609.1.3.
  
 5) SPECIFY THE UNIT/SUITE THAT THE
 GENERATOR WILL SERVICE ON THE PERMIT
 APPLICATION.
  
 6) THE PROJECT IS LOCATED IN AN "AO"
 FLOOD ZONE. EQUIPMENT MUST BE LOCATED 6"
 ABOVE BASE FLOOD ELEVATION. AN ELEVATION
 CERTIFICATE WILL BE REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-10 Cont ID  
Sent By dpalmer Date 2006-09-10 Time 10:55 Rev Time 0.00
Received By dpalmer Date 2006-09-10 Time 09:50 Sent To  
Notes
2006-09-10 00:00:00*********** UNSAT ************
  
 1) NOTE: PLEASE SEE PLANS SHALL INDICATE
 ALL RELEVANT CODES TO PROPOSED PROJECT
 AND DESIGN.
 PLEASE SEE THE FOLLOWING ARE REQUIRED AT
 A MINIMUM.
 2002 NFPA-70, 2002 NFPA-110, 2004 FBC.
  
 2) NOTE: PLEASE SEE THE VALUE FOR
 COMPLETE SCOPE OF WORK SHALL INCLUDE ALL
 LABOUR AND MATERIALS EVEN IF ANY
 EQUIPMENT IS OWNER SPPLIED.
 FBC 108.3.
 ** VALUE AS SHOWN ON APPLICATION IS LOW,
 PLEASE SEE THAT IF NOT ADJUSTED, A VALUE
 WILL BE ASSESSED USING THE MARSHALL'S &
 SWIFT GUIIDE AS ADOPTED BY THE FBC.
 PLEASE ALSO KNOW, SIGNED, CONTRACTS FOR
 ALL EQUIPMENT, ALL LABOUR AND MATERIALS
 MAY ALSO BE REQUESTED.
 THE VALUE ON THE GEN ALONE IS ABOVE THE
 VALUE APPLIED FOR.
  
 3) NOTE: PLEASE SEE THE PROPOSED SCOPE
 AND GROUPING OF DISCONNECTS IS NOT CODE
 COMPLIANT. PLEASE ALSO SEE RISER IS NOT
 COMPLETE AT THIS TIME AS THE FEEDERS
 FROM THE LOAD SIDE OF THE ATS DO NOT
 APPEAR TO GO ANYWHERE?
 PLEASE SEE 225.34 AND 230.72 FOR
 GROUPING OF MAINS. THE NEW PROPOSED MAIN
 2 OF 2 IS OUTSIDE AND THE OTHER MAIN 1
 IS INSIDE. THE REQUIRED MAINS AND
 DISCONNECTS ARE NOT GROUPED AS REQUIRED.
 PLEASE SEE THE PERMIT APPLIED FOR #
 06081714 HAS BEEN PLACED INTO A "HOLD"
 STATUS UNTIL DESIGN IS ADJUSTED.
 PLEASE PROVIDE A COMPLETE LAYOUT OF ALL
 THE EXISTING SERVICE AND NEW WORK.
 PLEASE KNOW THE ATS AND DISCONNECT BEING
 SHOWN AS EXISTING ON THIS RISER SHALL BE
 SHOWN AS NEW AS THIS SEPARATE PERMIT AS
 SHOWN WILL NOT BE GRANTED.
 215.5,225.31-225.39, 230.72ETC
  
 4) NOTE: PLEASE PROVIDE COMPLETE LOAD
 CALCULATIONS FOR PROPOSED GENERATOR AND
 ALL LOADS INTENDED FOR USE. PLEASE KNOW
 IF LOAD SHEDDING IS BEING PROPOSED, MUST
 SHOW LOAD SHEDDING DETAILS.
 ** PLEASE SEE 702.5, THE NOTE WHICH IS
 PLACE ON PLANS MENTIONS THE CONSUMER CAN
 MANUALLY TURN OFF BREAKERS TO CHOSE
 LOAD. PLEASE SEE 700.5 AND 701.5 THE AHJ
 AND OTHER CODES DETERMINE WHAT IS
 REQUIRED ON EMERGENCY AND LEGALLY
 REQUIRED STAND-BY SYSTEMS WHERE 702.5
 MENTIONS THE CONSUMER CAN CHOSE WHICH
 LOADS THEY WANT TO HAVE ON AN OPTIONAL
 STAND-BY SYSTEM. THE PROPOSED BACK UP
 SYSTEM ON AN "AUTOMATIC STAND-BY" STILL
 MUST BE SIZED PER THE LOADS INTENDED.
 THE CODE DOES NOT STATE THE "OWNER CAN
 TURN OFF BREAKERS TO CHOOSE LOADS"
 THE SYSTEN AS SHOWN IS NOT BEING SHOWN A
 "MANUAL TRANSFER".
 220.3,220.10,220.11,220.13, ETC.
 PLEASE SEE 215.3,230.42 FORANY
 CONTINUOUS LOADS.
  
 5) NOTE: PLEASE SEE PERMIT APPLICATION
 SHALL STATE THE TENANT SPACE/UNIT
 NUMBER. PLEASE SEE THAT THE PERMIT
 APPLICATION SHALL ALSO STATE THE PROJECT
 IN DETAIL. PLEASE SEE APPL ONLY MENTIONS
 "INSTALL GENERATOR PAD", A HAND WRITTEN
 NOTE INCLUDING THE GENERATOR WAS DONE
 THE FRONT COUNTER STAFF.
 PLEASE LIST THE SIZE OF UNIT, ATS ,
 SUB-BASE FUEL ETC.
  
 6) NOTE: PLEASE PROVIDE A LEGAL SURVEY
 SHOWING THE EXACT LOCATION OF THE
 GENERATOR LOCATED ON PROPERTY INCLUDING
 ALL SETBACKS ETC. THIS WILL ALSO BE IN
 THE ZONING REVIEW NOTES.
 PLEASE KNOW, CODE COMPLIANCE CAN NOT BE
 DETERMINED AT THIS TIME.
  
 7) NOTE: PLEASE SEE THAT ONCE THE
 UNIT/SUITE # IS OBTAINED, PLEASE INCLUDE
 ON TITLE BLOCKS WITH THE ADDRESS AS
 SHOWN.
 FAC 61G15-23.002
  
 8) NOTE: PLEASE SEE RISER CONTAINS THE
 SYMBOL FOR THE KEYNOTE #1 JUST BELOW
 TENANTS MCB #1 AND #2, HOWEVER KEY NOT
 #1 DOES NOT SEEM TO CORRELATE.
  
 ** ONE COPY OF THE ELECTRICAL RISER IN
 ONE SET HAS BEEN RETAINED BY THIS
 OFFICE.
  
 ** PLEASE KNOW AS THERE AREITEMS FOR
 CODE COMPLIANCE NOT YET SUBMITTED AND
 DESIGN AS SHOWN WILL BE CHANGING, THERE
 MAY BE COMMENTS ON NEW PLANS SUBMITTED.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-10 Cont ID  
Sent By mawillia Date 2006-10-10 Time 13:43 Rev Time 0.00
Received By mawillia Date 2006-10-10 Time 13:43 Sent To  
Notes
2006-10-10 14:21:18*****DENIED*****
  
  
  
 1.)NFPA 101, 2003 EDITION, AND FLORIDA FIRE
 PREVENTION CODE, 2004 EDITION SHALL BE REFERENCED.
  
 2.)NFPA 110, STANDARD FOR EMERGENCY AND STAND-BY
 POWER SYSTEMS, SHALL BE REFERENCED.
  
 3.)THE INSTALLATION OF THE PROPOSED STRUCTURE SHALL
 IN NO WAY OBSTRUCT EMERGENCY RESPONSE TO THE SAID
 PROPERTY AND/OR VICINITY.
  
 4.)CONSTRUCTION, ALTERATION, AND DEMOLITION
 OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 5.)PROVIDE ALL MANUFACTURER SPECIFICATION SHEETS FOR
 THE GENERATOR AND ASSOCIATED EQUIPMENT.
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-09-09 Cont ID  
Sent By kstevens Date 2006-09-09 Time 13:08 Rev Time 0.00
Received By kstevens Date 2006-09-09 Time 13:08 Sent To  
Notes
2006-09-09 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 A. AS OF 8-25-06 ELECTRICAL INFORMATION
 AND GAS/DIESEL INFORMATION IS REQUIRED
 TO BE SUBMITTED AT THE SAME TIME.
  
 B. IF NATURAL OR LP GAS A SEPARATE
 PERMIT IS REQUIRED, AND THE FOLLOWING
 INFORMATION IS TO BE SUBMITTED WITH THE
 APPLICATION:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 7. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. MANUF.
 SHEETS SHALL CONTAIN THE INSTALLATION
 INSTRUCTIONS TO VERIFY CLEARANCES FORM
 ALL STRUCTURES.
  
 9. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 10. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-10 Cont ID  
Sent By mawillia Date 2006-10-10 Time 13:42 Rev Time 0.00
Received By mawillia Date 2006-09-01 Time 10:38 Sent To  
Notes
2006-09-05 00:00:00TO "COMM" BD#28
2006-09-01 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-09-13 Cont ID  
Sent By tgordon Date 2006-09-13 Time 11:52 Rev Time 0.30
Received By tgordon Date 2006-09-13 Time 11:52 Sent To  
Notes
2006-09-13 00:00:00*** DENIED ***
 1) PLEASE SUBMIT A SITE PLAN SHOWING THE
 PROPOSED LOCATION OF THE GENERATOR.
  
 2) PLEASE SUBMIT DETAILED MANUFACTURE'S
 SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS FOR GENERATOR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-09-12 Cont ID  
Sent By kdfreema Date 2006-09-12 Time 09:38 Rev Time 0.00
Received By kdfreema Date 2006-09-12 Time 14:24 Sent To  
Notes
2006-09-12 00:00:00A MINOR AMENDMENT TO THE LAKE POINT
 CENTRE COMMERCIAL PLANNED DEVELOPMENT IS
 REQUIRED.
  
 PLEASE PROVIDE A SCALE DRAWING OF THE
 GENERATOR SITE AND ITS SURROUNDINGS.
 SHOWN MUST BE ALL STRUCTURES, SURFACES,
 AND LOT LINES.
  
 GENERATOR ENCLOSURES ARE SUBJECT TO THE
 LANDSCAPING AND SCREENING REQUIREMENTS
 FOUND IN SEC. 94-444(B) OF THE CITY OF
 WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS.
  
 THE MAXIMUM FENCE HEIGHT IS 8 FEET.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER,
 AT 822-1435 WITH ANY QUESTIONS YOU MAY
 HAVE.