Plan Review Details - Permit 06082204
Plan Review Stops For Permit 06082204
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-09-29 Cont ID  
Sent By alange Date 2006-09-29 Time 16:37 Rev Time 0.50
Received By alange Date 2006-09-29 Time 16:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-12-12 Cont ID  
Sent By btrobaug Date 2006-12-12 Time 07:15 Rev Time 0.50
Received By btrobaug Date 2006-12-12 Time 06:48 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-09-14 Cont ID  
Sent By btrobaug Date 2006-09-14 Time 14:08 Rev Time 0.50
Received By btrobaug Date 2006-09-14 Time 13:51 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2006-09-27 Cont ID  
Sent By mperson Date 2006-09-27 Time 16:37 Rev Time 0.00
Received By mperson Date 2006-09-27 Time 16:36 Sent To B
Notes
2006-09-27 00:00:00NOTE: RECIEVED REVISION FROM FLORIDA
 PUBLIC UTILITIES CO. FOR PLAN REVIEW
 9/27/06 ON GAS PERMIT #06061080.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-09-20 Cont ID  
Sent By mperson Date 2006-09-20 Time 11:25 Rev Time 0.33
Received By mperson Date 2006-09-20 Time 11:25 Sent To B
Notes
2006-09-20 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PLAN REVIEW:
  
 ******IMPORTANT INFORMATION******
 AS OF 8/25/06 GENERATOR (GEN/RES AND
 GEN/COM) PERMIT APPLICATIONS SHALL NOT
 BE ACCEPTED UNLESS THE ELECTRICAL INFOR-
 MATION AND GAS (OR DIESEL) INFORMATION
 IS ALL SUBMITTED AT THE SAME TIME. THE
 GENERATOR, ELECTRICAL AND GAS/DIESEL IN-
 FORMATION WILL BE ROUTED TOGETHER. THIS
 WILL ENSURE THAT ALL OF THE INFORMATION
 (PARTICULARLY THE MANUFACTURER'S SPECI-
 FICATIONS AND INSTALLATION INSTRUCTIONS)
 ARE AVAILABLE TO ALL PLAN REVIEWERS.
  
 NOTE: THE GAS PERMIT ISSUED 7/17/06 DOES
 NOT INCLUDE THE GENERATOR, PLEASE
 REFERENCE THE ATTACHED COPY OF THE
 APPROVED GAS ISOMETRIC FOR 533 S.
 MANGONIA CIRCLE. A REVISION CAN BE MADE
 TO THE OPEN GAS PERMIT FROM FLORIDA
 PUBLIC UTILITIES CO. ADDING THE
 GENERATOR WITH THE FOLLOWING INFORMATION
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505. (IF APPLICABLE)
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-06 Cont ID  
Sent By adarroug Date 2006-12-06 Time 11:05 Rev Time 0.00
Received By adarroug Date 2006-12-06 Time 11:05 Sent To E
Notes
2006-12-06 11:05:41TO "BTROBAUGH "DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-05 Cont ID  
Sent By adarroug Date 2006-09-05 Time 09:28 Rev Time 0.00
Received By adarroug Date 2006-09-05 Time 09:28 Sent To E
Notes
2006-09-05 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-29 Cont ID  
Sent By alange Date 2006-09-29 Time 16:37 Rev Time 0.00
Received By alange Date 2006-09-01 Time 10:48 Sent To  
Notes
2006-09-01 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-09-18 Cont ID  
Sent By tgordon Date 2006-09-18 Time 14:04 Rev Time 0.15
Received By tgordon Date 2006-09-18 Time 14:04 Sent To P
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-09-04 Cont ID  
Sent By mmclean Date 2006-09-04 Time 10:52 Rev Time 0.00
Received By mmclean Date 2006-09-04 Time 10:52 Sent To I
Notes
2006-09-04 00:00:00THE PROPOSED GENERATOR SHALL NOT BE
 CLOSER THAN 6FT FROM SIDE PROPERTY LINE.