Plan Review Details - Permit 06082188
Plan Review Stops For Permit 06082188
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-10-16 Cont ID  
Sent By lursu Date 2006-10-16 Time 11:46 Rev Time 0.00
Received By lursu Date 2006-10-16 Time 11:46 Sent To PC
Notes
2006-10-16 11:49:43USE THIS PCN SINCE A UNITY OF TITLE TOOK PLACE BETWEEN
 THE FOLLOWING PCN'S :
 74434309110000080, 74434309110000090 AND
 74434309110000100.THE LOWEST PCN ...0080 WAS KEPT THE
 REST ARE INACTIVE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 20 Status P Date 2008-06-27 Cont ID  
Sent By shill Date 2008-06-27 Time 11:35 Rev Time 0.00
Received By shill Date 2008-06-27 Time 11:35 Sent To  
Notes
2008-06-27 11:35:58REVISED ENERGY CALCS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status F Date 2008-05-27 Cont ID  
Sent By shill Date 2008-05-27 Time 15:00 Rev Time 0.00
Received By shill Date 2008-05-27 Time 15:00 Sent To  
Notes
2008-05-27 15:05:04****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.PER FBPE, ALL ENGINEERS' SIGNATURES ARE TO BE
 ORIGINAL, "WET" SIGNATURES (CANNOT BE A STAMP).
 HOWEVER, IT APPEARS THAT ALL DOCUMENTS WITHIN THE
 BINDER SUBMITTED ARE REPORTS RATHER THAN
 SPECIFICATIONS, PLANS, PRINTS, OR CALCULATIONS.IF ALL
 OF THE DOCUMENTS ARE REPORTS, THE FOLLOWING MAY APPLY
 PER FAC61G15-23.002(2):ENGINEERING REPORTS MUST BE
 SIGNED, SEALED AND DATED ON A SIGNATURE PAGE OR COVER
 LETTER BY EACH PROFESSIONAL ENGINEER WHO IS IN
 RESPONSIBLE CHARGE OF ANY PORTION OF THE REPORT.
  
 THIS MAY BE ACCOMPLISHED BY PROVIDING A SIGNED, SEALED,
 AND DATED COVER LETTER TO BE INCORPORATED INTO THE
 BINDER OF REPORTS.
  
 IF THE DOCUMENTS SUBMITTED INCLUDE SPECIFICATIONS OR
 PLANS (ANYTHING OTHER THAN A REPORT), A SIGNED, SEALED,
 AND DATED INDEX SHEET MAY BE PROVIDED IN LIEU OF
 PROVIDING AN ORIGINAL SIGNATURE FOR EACH SEALED SHEET.
  
 OTHER OPTIONS MAY ALSO BE ACCEPTABLE (SUCH AS SIGNING
 EACH SEALED SHEET) PROVIDED THAT WHATEVER OPTION
 PROPOSED IS IN COMPLIANCE WITH FAC61G15-23.I HAVE
 SUGGESTED THE OPTION WHICH APPEARS TO BE THE SIMPLEST
 BUT THE DECISION AS TO HOW TO COMPLY IS ENTIRELY THE
 ENGINEER'S DECISION.ANY COMPLIANT METHOD IS
 ACCEPTABLE.
  
 2.PLEASE HAVE THE DESIGNER OF RECORD (EITHER
 ARCHITECT OR ENGINEER) REVIEW THE DOCUMENTS PRIOR TO
 RESUBMITTAL.THIS IS REQUIRED FOR ALL SUBMITTALS AND
 MAY BE DONE BY EITHER A SHOP DRAWING REVIEW STAMP OR BY
 LETTER.
  
 3.PLEASE INCLUDE THE CERTIFICATE OF AUTHORIZATION
 NUMBER FOR THE ENGINEERING BUSINESS, ECS FLORIDA LLC,
 ON EACH SHEET WHICH IS REQUIRED TO BE SIGNED AND SEALED
 (INCORPORATED AS TITLE BLOCK INFORMATION).
  
 4.PLEASE NOTE THAT THE REPAIR DETAIL (SHEETS
 SK4.10-05 AND -03) PREPARED BY BLISS & NYITRAY, INC. IS
 A SPECIFICATION, AND BASED ON PREVIOUS PLAN REVIEW
 NOTES, ARE NOT INCORPORATED INTO OUR PLAN SET.PLEASE
 PROVIDE ORIGINALS AS A REVISION UNLESS THIS HAS ALREADY
 BEEN DONE.THIS COMMENT APPLIES TO ANY OTHER SHEETS
 WHICH MAY HAVE BEEN INCLUDED WHICH HAVE THE SAME
 SITUATION BUT WERE NOT SPECIFICALLY LISTED IN THIS
 COMMENT.
  
 5.AS THIS DOCUMENT IS A SUBMITTAL (PER BUILDING
 INSPECTOR'S REQUREST), PLEASE NOTE THAT A COMPLETE PLAN
 REVIEW OF EACH SHEET WAS NOT PERFORMED.THE REPORTS
 SUBMITTED WERE SPOT CHECKED FOR GENERAL COMPLIANCE WITH
 THE CODE AND DESIGNERS' INTENT (ADVISORY, NO ACTION
 REQUIRED).
  
 6.SOME SHEETS REFER TO NONCOMPLIANCE, OTHERS APPEAR
 NONCOMPLIANT.IT APPEARS THAT ALL REPORTS WERE
 SUBMITTED, AND THE NONCOMPLIANCE ADDRESSED IN
 SUBSEQUENT INSPECTIONS.PLEASE PROVIDE A LETTER FROM
 BOTH THE ENGINEERING COMPANY AND THE CONTRACTOR WHICH
 ATTEST GENERALLY TO THE FACT THAT ANY NON COMPLIANCE
 NOTED IN ANY OF THE REPORTS HAS BEEN ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status P Date 2008-05-02 Cont ID  
Sent By shill Date 2008-05-02 Time 17:45 Rev Time 0.00
Received By shill Date 2008-05-02 Time 17:45 Sent To PC
Notes
2008-05-02 17:46:52REVISION #6 DATED 4/22/08; SHEETS S1.1, 1.2, 1.3, 1.4,
 2.1, 2.2., 2.3,3.1,4.1, 4.2, 4.3, 4.4, 4.5, 4.6, 4.7,
 4.8 AND NEW SHEETS 4.9, 4.10, 4.11, 4.12
  
 **PROVISO**REVISE COVER SHEET TO REFLECT CURRENT
 REVISION NUMBER (6) AND NEW SHEETS S4.9 THRU 4.12

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status P Date 2008-04-28 Cont ID  
Sent By shill Date 2008-04-28 Time 14:50 Rev Time 0.00
Received By shill Date 2008-04-28 Time 14:50 Sent To  
Notes
2008-04-28 15:28:49STAIR SHOPS

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status P Date 2008-03-10 Cont ID  
Sent By shill Date 2008-03-10 Time 18:21 Rev Time 0.00
Received By shill Date 2008-03-10 Time 18:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status F Date 2008-03-07 Cont ID  
Sent By shill Date 2008-03-07 Time 16:12 Rev Time 0.00
Received By shill Date 2008-03-07 Time 16:12 Sent To  
Notes
2008-03-07 16:21:26****CORRECTIONS****
 ****STAIR SHOPS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SEE FBC11-4.9.4(2), FBC1009.11.5 REGARDING HANDRAIL
 EXTENSIONS.MOST OF THE RAILS SHOWN ON THE PLAN WHICH
 ARE NOT CONTINUOUS ARE NOT COMPLIANT.
  
 2.SEE FBC FIGURE 8 (C-1).DOES THIS APPLY TO ANY OF
 THE STAIRS?IF IT DOES, AND PROTECTION FROM OVERHEAD
 HAZARDS IS TO BE PROVIDED BY THE SAME COMPANY AS THE
 STAIRS, PLEASE INCLUDE IN THIS SUBMITTAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status P Date 2008-03-07 Cont ID  
Sent By shill Date 2008-03-07 Time 14:56 Rev Time 0.00
Received By shill Date 2008-03-07 Time 14:56 Sent To  
Notes
2008-03-07 14:56:50REVISION, NEW SHEET S4.12

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status F Date 2007-12-28 Cont ID  
Sent By shill Date 2007-12-28 Time 09:36 Rev Time 0.00
Received By shill Date 2007-12-28 Time 09:36 Sent To  
Notes
2007-12-28 09:44:19****CORRECTIONS****
 STAIR RAILING SHOPS
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.HANDRAIL EXTENSIONS IN COMPLIANCE WITH
 FBC11-4.9.4(2), FBC1009.11.5.NO DIMENSIONS ARE SHOWN
 AND, WHEN SCALED, DO NOT COMPLY.
  
 2.HANDRAIL EXTENSIONS ARE TO RETURN TO A WALL, GUARD,
 WALKING SURFACE, OR CONTINUOUS IN ACCORDANCE WITH
 FBC1009.11.5.SEE ALSO FBC11-4.9.4(6).
  
 3.SUBMITTALS/SHOP DRAWINGS ARE TO BE REVIEWED BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL TO THE CITY. NOTE
 THAT IF THE SHOP DRAWINGS DO NOT CORRELATE WITH THE
 PERMIT PLANS, A REVISION WILL BE REQUIRED.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status F Date 2007-12-27 Cont ID  
Sent By shill Date 2007-12-27 Time 18:58 Rev Time 0.00
Received By shill Date 2007-12-27 Time 18:58 Sent To  
Notes
2007-12-27 18:59:51****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.TWO COLLATED SETS REQUIRED.ONLY ONE SET WAS
 SUBMITTED OF SOME OF THE SHEETS.
  
 2.ALL CHANGES TO THE PLAN, INCLUDING DETAILS, SHOULD
 BE SUBMITTED AS REVISIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2007-11-08 Cont ID  
Sent By shill Date 2007-11-08 Time 09:42 Rev Time 0.00
Received By shill Date 2007-11-08 Time 09:42 Sent To  
Notes
2007-11-08 09:50:30****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)THE CERTIFICATE OF AUTHORIZATION FOR THE
 ARCHITECTURE FIRM IS TO BE PRINTED ON EACH SHEET,
 FAC61G16-23.002, 003.
  
 2.)WHEN RESUBMITTING, PLEASE SUBMIT AS A REVISION.
 CHANGES TO THE PLAN, WHETHER THEY BE ACTUAL CHANGES IN
 DESIGN OR DETAILS ORIGINALLY OMITTED BY THE ARCHITECT
 OR ENGINEER, ARE REVISIONS.ONLY SHOP DRAWINGS CAN BE
 SUBMITTED AS SUBMITTALS, AS THEY DO NOT CONTAIN ANY NEW
 INFORMATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2007-10-30 Cont ID  
Sent By shill Date 2007-10-30 Time 12:01 Rev Time 0.00
Received By shill Date 2007-10-30 Time 12:01 Sent To  
Notes
2007-10-30 12:02:48****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.ALL SUBMITTALS ARE TO BE REVIEWED BY DESIGNER OF
 RECORD (ARCHITECT OR ENGINEER) PRIOR TO SUBMITTAL.
  
 2.PLEASE DISCUSS WITH INSPECTOR WHETHER OR NOT THE
 SUBMITTALS ARE REQUIRED TO BE SUBMITTED THROUGH PLAN
 REVIEW.
  
 3.ALL SIGNATURES FOR THE ENGINEER ARE TO BE ORIGINALS
 (NO STAMPS) PER FBPE.
  
 4.ALL INFORMATION REQUIRED BY FAC61G15-23.002 IS TO
 BE ON EACH SHEET (TITLE BLOCK, ENGINEER).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2007-10-29 Cont ID  
Sent By shill Date 2007-10-29 Time 10:25 Rev Time 0.00
Received By shill Date 2007-10-29 Time 10:25 Sent To  
Notes
2007-10-29 10:26:57REISION, S4.9, S4.10, SK4.6-01,SK4.5-04,SK4.5-05 DATED
 10/11/7

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2007-09-26 Cont ID  
Sent By shill Date 2007-09-26 Time 13:39 Rev Time 0.00
Received By shill Date 2007-09-26 Time 13:39 Sent To  
Notes
2007-09-26 13:40:15REVISION (PRODUCT APPROVAL) AND SHOP DRAWINGS OK
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2007-09-14 Cont ID  
Sent By shill Date 2007-09-14 Time 09:41 Rev Time 0.00
Received By shill Date 2007-09-14 Time 09:41 Sent To  
Notes
2007-09-14 09:44:48****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)THE STOREFRONT PRODUCT APPROVAL 05-0317.03 IS NOT
 THE ONE REVIEWED BY DESIGNER OF RECORD (06-1019.08).
 IF YOU WISH TO CHANGE PRODUCTS, SUBMIT AS A REVISION
 AFTER REVIEW BY DESIGNER OF RECORD.
  
 2.)THE NOAS SUBMITTED REQUIRE ENGINEERING ANALYSIS
 DUE TO DESIGN WITH A 33% STRESS INCREASE WHICH IS NO
 LONGER ALLOWED UNDER FBC2004.06-1019.08 PREVIOUSLY
 REVIEWED BY DOR IS COMPLIANT AND DOES NOT REQUIRE THIS
 ANALYSIS.PLEASE HAVE THE ENGINEER REVISE THE SHOP
 DRAWINGS TO INDICATE THAT HE HAS REVIEWED ANCHORING
 WITHOUT THE 33% STRESS INCREASE.SEE THE FLORIDA STATE
 PRODUCT APPROVAL FOR PRODUCT 04-0227.02 AND SEE THE
 NOAS WHICH STATE THAT A STRES INCREASE WAS USED IN
 ANCHOR DESIGN.
  
 3.)SHEET 4A STATES THAT DOOR 202.1 AND FRAME WILL BE
 NONIMPACT.IS THIS AN INTERIOR DOOR?
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-09-14 Cont ID  
Sent By shill Date 2007-09-14 Time 09:32 Rev Time 0.00
Received By shill Date 2007-09-14 Time 09:32 Sent To  
Notes
2007-09-14 09:33:15NEW ENERGY CALCS PROCESSED BY LUIS MARTINEZ 5/21/07
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-06-13 Cont ID  
Sent By shill Date 2007-06-13 Time 08:51 Rev Time 0.00
Received By shill Date 2007-06-13 Time 08:51 Sent To  
Notes
2007-06-13 08:52:10STRUCTURAL CONCRETE CALCS AND SHOPS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-05-03 Cont ID  
Sent By shill Date 2007-05-03 Time 11:19 Rev Time 0.00
Received By shill Date 2007-05-03 Time 11:19 Sent To  
Notes
2007-05-03 11:26:36**PROVISO**
  
 1.)MECHANICAL ENGINEER TO MAIL DOCUMENTS REGARDING SF
 AREA ON ENERGY CALCS.IF THIS DOES NOT SHOW CODE
 COMPLIANCE, NEW ENERGY CALCS WILL BE REQUIRED.
  
  
  
 ***NOTE***
  
 NOC, IMPACT FEES, SOILS WITH FOUNDATION PERMIT
 07030280
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-04-29 Cont ID  
Sent By shill Date 2007-04-29 Time 14:38 Rev Time 0.00
Received By shill Date 2007-04-29 Time 14:38 Sent To  
Notes
2007-04-29 14:43:10****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
  
 FROM PREVIOUS LIST:
  
 1.-4.)ADDRESSED.
  
 5.)SEPARATE PERMIT REQUIRED FOR THE
 DUMPSTER ENCLOSURE.PLEASE COMPLETE A
 PERMIT APPLICATION; SEPARATE PLANS ARE
 NOT REQUIRED.
  
 6-10.)ADDRESSED.
  
 11-28.)ADDRESSED.
  
 29.)SEE ELECTRIC COMMENTS REGARDING THE ENERGY CALCS.
 ALSO PLEASE CLARIFY CONFLICT BETWEEN THE SQUARE FOOT
 AREA ON THE PLAN AND THE ENERGY CALC SQUARE FOOT AREA.
  
 3RD REVIEW - THE RESPONSE LETTER STATES THAT CROSS
 WALLS ARE EXCLUDED.SEE DEFINITION OF BUILDING AREA IN
 CHAPTER 13.AREA IS TO MEASURED FROM OUTSIDE FACE TO
 OUTSIDE FACE OF EXTERIOR WALLS; WHERE IN THE CODE DOES
 IT ALLOW EXCLUSION OF WALLS?ALSO THE ENERGY CALCS
 HAVE A "FAILED" STATUS, MUST SAY "PASSED".
  
 30.)NEW COMMENT:DUE TO POLICY CHANGE, PLEASE SUBMIT
 ALL REQUIRED PRODUCT APPROVALS FOR ALL COMPONENTS &
 CLADDING.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO EVALUATION REPORTS, FAC9B72,
 WWW.FLORIDABUILDING.ORG
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-02-26 Cont ID  
Sent By shill Date 2007-02-26 Time 09:00 Rev Time 0.00
Received By shill Date 2007-02-21 Time 10:04 Sent To  
Notes
2007-02-26 09:45:43****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
  
 1.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025 FOR MORE
 INFORMATION.
  
 2.-4.)ADDRESSED.
  
 5.)SEPARATE PERMIT REQUIRED FOR THE
 DUMPSTER ENCLOSURE.PLEASE COMPLETE A
 PERMIT APPLICATION; SEPARATE PLANS ARE
 NOT REQUIRED.
  
 6-10.)ADDRESSED.
  
 11.)SEE FBC313, FBC406.1.FROM PREVIOUS LIST,
 PENETRATIONS TO BE IN COMPLIANCE WITH FBC M712
 (M1-01-101).THE EXHAUST FAN LOUVER IS NOT IN
 COMPLIANCE.HOWEVER, AFTER FIRTHER DISCUSSION WITH
 HAROLD MOSER, CHIEF MECHANICAL INSPECTOR, THE EXHAUSE
 SHOULD DISCHARGE TO THE OUTSIDE, FBC MECHANICAL 501.2.
  
  
 1 HOUR OCCUPANCY VERTICAL SEPARATION IS SHOWN BETWEEN
 THE GARAGE AND BUSINESS AREA; PLEASE SHOW HORIZONTAL
 SEPARATION BETWEEN THE FIRST AND SECOND FLOOR, EITHER
 TESTED ASSEMBLY OR CALCULATED FIRE RESISTANCE.
  
 12-16.)ADDRESSED.
  
 17.)SECTION 2-A6-00-101, THE STAIR
 RAIL IS TO EITHER BE ROUNDED OR RETURN
 TO THE FLOOR, WALL, OR POST.A STRAIGHT
 EXTENSION IS SHOWN.
  
 SECOND REVIEW; THE STAIR RAILING DETAIL ISN'T CLEAR.
 HANDRAIL AND GUARDRAIL ARE REQUIRED FBC1012.1,
 FBC1009.11.ONLY ONE RAIL IS SHOWN.IT APPEARS THAT
 THE RAILING EXTENSION IS NOT ROUNDED, SEE FBC11 FIGURE
 19.
  
 18.)SECTION 2-A6-00-101, THE AREA
 UNDER THE STAIR LACKS THE HEADROOM
 REQUIRED BY FBC11-4.4.2, BARRIER
 REQUIRED.
  
 19.-22.)ADDRESSED.
  
 23.)STRUCTURALS STATE THAT MRH IS
 24FT.NOTE THAT THE STAIR ROOF IS AT APPROXIMATELY
 37FT.DESIGN PRESSURES
 APPEAR COMPLIANT AS THE HIGHER SECTION
 IS A PITCHED ROOF, BUT PLEASE ADDRESS ON
 THE PLAN.
  
 THE RESPONSE LETTER STATES THAT THERE IS A
 CLARIFICATION LETTER IN THE PACKAGE.PER DISCUSSION
 WITH THE ENGINEER, THE LETTER WILL BE PROVIDED TO
 PREVENT FIELD ISSUES (INSPECTIONS).
  
 24.)ON THE YHS 50 STOREFRONT PRODUCT
 APPROVAL, INDICATE WHICH PRODUCT YOU ARE
 USING AS NOT ALL MEET WORST CASE FOR
 WIND LOADS.
  
 THE YHS 50 STOREFRONT PRODUCT APPROVALS WERE NOT
 RESUBMITTED.ANY PRODUCT APPROVALS NOT REVIEWED PRIOR
 TO PERMIT ISSUANCE WILL REQUIRE SEPARATE PERMITS.
  
 25-26.)ADDRESSED.
  
 27.)ANY PRODUCT APPROVALS REQUIRED BY
 FAC9B72 AND NOT SUBMITTED PRIOR TO
 PERMIT ISSUANCE WILL REQUIRE SEPARATE
 PERMITS; FOR INSTANCE, THE FLAT DECK
 ROOF AND THE EXTERIOR METAL DOORS.FOR
 THE FLAT DECK, INDICATE WHICH APPROVED
 ASSEMBLY YOU WILL BE USING.
  
 28.)ADDRESSED.
  
 NEW COMMENTS:
  
 29.)SEE ELECTRIC COMMENTS REGARDING THE ENERGY CALCS.
 ALSO PLEASE CLARIFY CONFLICT BETWEEN THE SQUARE FOOT
 AREA ON THE PLAN AND THE ENERGY CALC SQUARE FOOT AREA.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-05 Cont ID  
Sent By shill Date 2006-10-05 Time 11:12 Rev Time 0.00
Received By shill Date 2006-10-04 Time 16:02 Sent To  
Notes
2006-10-05 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
  
 1.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025 FOR MORE
 INFORMATION.
  
 2.)PRODUCT APPROVALS TO BE REVIEWED BY
 DESIGNER OF RECORD, FBC*106.3.3.
  
 3.)A PRELIMINARY SURVEY WAS SUBMITTED,
 BUT APPEARS TO HAVE BEEN REPLACED BY A
 FINAL SURVEY.REMOVE THE PRELIMINARY
 FROM THE PACKAGE OR CLARIFY AS TO ITS
 PURPOSE AS THE INFORMATION ON IT IS
 INCOMPLETE.
  
 4.)SHEET C7, PARKING IS TO COMPLY WITH
 CITY OF WEST PALM BEACH STANDARD, SEE
 ATTACHED.
  
 5.)SEPARATE PERMIT REQUIRED FOR THE
 DUMPSTER ENCLOSURE.PLEASE COMPLETE A
 PERMIT APPLICATION; SEPARATE PLANS ARE
 NOT REQUIRED.
  
 6.)PROVIDE MAXIMUM SLOPES FOR THE
 ACCESSIBLE ROUTE SHEET SP1 OR C5,
 FBC11-4.1.2(1).
  
 7.)CODE DATE, SHEET G0-00-001, INCLUDE
 SPRINKLER INFORMATION (APPEARS TO BE
 FULLY SPRINKLED), BUILDING AREA
 (EXISTING, PROPOSED ADDITION, NEW
 TOTAL).
  
 8.)A0-00-601 STATES THAT THE BUILDING
 IS 30FT FROM THE PROPERTY LINE, SP1
 SHOWS A DISTANCE OF 27.97 ON THE SOUTH
 SIDE.IT APPEARS THAT NO FIRE
 RESISTANCE IS REQUIRED PER FBC TABLE
 602, BUT PLEASE REVISE THE NOTE.
  
 9.)SHOW SIDEWALK WIDTH AT ACCESSIBLE
 PARKING SPACE ON SHEET A0-00-601,
 FBC11-4.6.2(1).44IN MINIMUM REQUIRED.
 A DETAIL IS SHOWN ELSEWHERE ON THE PLAN
 BUT WHEN SCALED THE SIDEWALK APPEARS TO
 BE 24IN.
  
 10.)SHEET A0-00-601 REFERS TO
 ASCE7-98, CORRECT REFERENCE IS 7-02,
 FBC35.
  
 11.)SEE FBC313, FBC406.1.SHOW
 OCCUPANCY CLASSIFICATION FOR THE GARAGE,
 TOTAL SF FOR GARAGE AREA.IF OCCUPANCY
 SEPARATION IS USED, IT MUST BE IN
 COMPLIANCE WITH FBC TABLE 302.3.2,
 FBC406.2.7, PENETRATIONS IN COMPLIANCE
 WITH FBC712 (M1-01-101).REVISE
 BUILDING ALLOWABLE AREA CALCULATIONS,
 FBC 5.
  
 12.)SEE FBC1013.2.THE LIFE SAFETY
 PLAN A0-00-601 SHOWS THE STAIR 2
 TERMINATING IN THE COVERED PARKING AREA.
 NO DOORS SHOWN FROM THE GARAGE TO THE
 OUTSIDE, GATE DOES NOT COMPLY WITH
 FBC1008.1.2 EXCEPTIONS.THIS MAY SERVE
 AS EGRESS FROM THE PARKING GARAGE, SEE
 EXCEPTION 1, BUT NOT FROM THE BUSINESS
 AREA.ALSO SEE FBC1013.2 REGARDING
 EGRESS THROUGH INTERVENING SPACES.
  
 13.)DETAIL 4-A2-02-001, THE SINK IS TO
 BE MOUNTED NO HIGHER THAN 34IN
 FBC11-4.24.2.PROVIDE A DETAIL FOR THE
 SINK, SEE FBC11-4.24.NOTE THAT CABINET
 DOORS NOT PERMITTED AS IT PREVENTS THE
 KNEE CLEARANCE REQUIRED BY FBC11-4.24.3.
  
 14.)DETAILS 21 AND 13, SHEET
 A7-02-101, CABINET DOORS NOT PERMITTED
 AS IT PREVENTS THE SINK KNEE CLEARANCE
 REQUIRED BY FBC11-4.24.3
  
 15.)THE BUILDING APPEARS TO BE THREE
 STORIES IN THE STAIRWAY.SEE SHEET
 A6-00-101.TWO STORY BUILDING DECLARED
 ON A0-00-601.
  
 16.)DECLARE AN OCCUPANT LOAD FOR THE
 ROOF TERRACE AND ROOF GARDEN AREAS.
  
 17.)SECTION 2-A6-00-101, THE STAIR
 RAIL IS TO EITHER BE ROUNDED OR RETURN
 TO THE FLOOR, WALL, OR POST.A STRAIGHT
 EXTENSION IS SHOWN.
  
 18.)SECTION 2-A6-00-101, THE AREA
 UNDER THE STAIR LACKS THE HEADROOM
 REQUIRED BY FBC11-4.4.2, BARRIER
 REQUIRED.
  
 19.)A9-01-201 INDICATES THAT BATHROOM
 WALL FINISHES ARE TO BE DETERMINED.SEE
 FBC1210.2, HARD NONABSORBENT SURFACE
 REQUIRED.
  
 20.)NO PENETRATIONS ALLOWED IN THE
 EXIT ENCLOSURE (STAIRS), FBC1-019.1.2,
 SEE MECHANICAL SHEETS.
  
 21.)SPECIFY FIRE RATING FOR FIRE RATED
 DOORS, FC TABLE 715.3, SHEET A8-00-101.
  
  
 22.)SPECIFY ANCHORING FOR THE
 GENERATOR, FBC1606.1.3, UNLESS THIS WILL
 BE ON A SEPARATE PERMIT.
  
 23.)STRUCTURALS STATE THAT MRH IS
 24FT.NOTE THAT THE STAIR ROOF IS AT
 APPROXIMATELY 37FT.DESIGN PRESSURES
 APPEAR COMPLIANT AS THE HIGHER SECTION
 IS A PITCHED ROOF, BUT PLEASE ADDRESS ON
 THE PLAN.
  
 24.)ON THE YHS 50 STOREFRONT PRODUCT
 APPROVAL, INDICATE WHICH PRODUCT YOU ARE
 USING AS NOT ALL MEET WORST CASE FOR
 WIND LOADS.
  
 25.)FOR THE MULLION PRODUCT APPROVAL,
 INDICATE WHICH PRODUCT YOU ARE
 INSTALLING.
  
 26.)FOR THE PICTURE WINDOW PRODUCT
 APPROVAL, INDICATE WHICH PRODUCT YOU ARE
 INSTALLING.
  
 27.)ANY PRODUCT APPROVALS REQUIRED BY
 FAC9B72 AND NOT SUBMITTED PRIOR TO
 PERMIT ISSUANCE WILL REQUIRE SEPARATE
 PERMITS; FOR INSTANCE, THE FLAT DECK
 ROOF AND THE EXTERIOR METAL DOORS.FOR
 THE FLAT DECK, INDICATE WHICH APPROVED
 ASSEMBLY YOU WILL BE USING.
  
 28.)SHOW COMPLIANCE WITH FBC1014.2.1,
 EXCEPTION 2, EXITS TO BE LOCATED MORE
 THAN 1/3 THE DIAGONAL APART.

Review Stop E ELECTRICAL
Rev No 12 Status N Date 2008-09-03 Cont ID  
Sent By lmartine Date 2008-09-03 Time 15:20 Rev Time 0.00
Received By lmartine Date 2008-09-03 Time 15:20 Sent To  
Notes
2008-09-03 15:22:05AS-BUILTS WERE GIVEN BACK TO ROSE . ELECTRICAL REVIEW
 IS NOT REQUIRED.

Review Stop E ELECTRICAL
Rev No 11 Status F Date 2008-07-30 Cont ID  
Sent By dpalmer Date 2008-07-30 Time 09:35 Rev Time 0.00
Received By dpalmer Date 2008-07-30 Time 09:35 Sent To PC
Notes
2008-07-30 09:36:16** DENIEDREVIEW **
  
  
 1) NOTE:ELECTRICAL PERMIT IS CLOSED OUT AND ALREADY
 HAS FINAL. NO PLAN REVIEW TO BE DONE.
  
  

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2008-06-16 Cont ID  
Sent By dpalmer Date 2008-06-16 Time 13:36 Rev Time 0.00
Received By dpalmer Date 2008-06-16 Time 13:36 Sent To M
Notes
2008-06-16 13:36:32ENERGY CALCS.

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2008-05-29 Cont ID  
Sent By dpalmer Date 2008-05-29 Time 12:57 Rev Time 0.00
Received By dpalmer Date 2008-05-29 Time 12:57 Sent To PC
Notes
2008-05-29 12:57:39** DENIED/HOLD REVISIONS**
 REVISED ENERGY CALCULATIONS AND PLANS SUBMITTED 5/15.
  
 1) NOTE:PLEASE SEE THE INFORMATION ON THE
 CERTIFICATION SHEETS FOR PREPARER OF ENERGY
 CALCULATIONS AND OTHER DESIGNERS IS NOT COMPLETE. FOR
 EXAMPLE: PLEASE SEE THE PERSON PREPARING DOCUMENTS FOR
 THIS SCOPE OF WORK SHALL BE A LICENSED PE ALONG WITH
 THE OTHER DESIGNERS LISTED ON SHEET. SOME OF THE
 INDIVIDUALS LISTED DO CONTAIN LICENSE INFORMATION, SOME
 DO NOT.
 AN E-MAIL WAS SENT AS OF THIS REVIEW REQUESTING
 INFORMATION FROM MR. CHRIS CONROY.
  
 2) NOTE: PLEASE BE SURE TO SEE NOTES DATED AS OF THIS
 DATE WHICH AFFECT ELECTRICAL REVISIONS. REVISED
 ELECTRICAL PLANS WERE SUBMITTED WITH DOZENS OF HAND
 DRAWN CHANGES TO PHOTO-COPIED ENGINEERED PLANS WHICH IS
 NOT PERMITTED.
 PLEASE BE SURE TO COORDINATE THIS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2008-05-29 Cont ID  
Sent By dpalmer Date 2008-05-29 Time 12:50 Rev Time 0.00
Received By dpalmer Date 2008-05-29 Time 12:50 Sent To  
Notes
2008-05-29 12:51:12** DENIEDREVIEW FOR REVISIONS**
  
 1) NOTE:PLEASE SEE ARCHITECTURAL SHEETS, ELECTRICAL
 SHEETS AND PLUMBING SHEETS SUBMITTED 5/20/08 ARE ALL
 *PHOTO-COPIES OF SIGNED AND SEALED PLANS. THESE SHEETS
 ALSO CONTAIN NUMEROUS ITEMS WHICH HAVE BEEN HAND DRAWN
 ON SHEETS WHICH IS NOT PERMITTED.
 PLEASE KNOW ALL LOW VOLTAGE SYSTEMS BEING ADDED MUST BE
 REVISED BY THE BASE BUILDING ELECTRICAL ENGINEER OF
 RECORD ALONG WITH PERMIT FOR SUCH WORK.
 PLEASE SEE THAT ANY REVISED LIGHTING MODULES ETC WHICH
 WERE ADDED TO PLANS MUST ALOS BE INCLUDED AND REVISED
 IN THE BASE BUILDING PLANS.
 FS481.221 AND 471.025
 FBC 106.3.5.1.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2008-05-06 Cont ID  
Sent By dpalmer Date 2008-05-06 Time 10:37 Rev Time 0.00
Received By dpalmer Date 2008-05-06 Time 10:37 Sent To PC
Notes
2008-05-06 10:38:12** DENIED REVISIONS **
  
 1) NOTE: PLEASE SEE THE VERSION OF THE ENERGY
 CALCULATIONS SHALL BE UNDER THE VERSION WHICH PERMIT
 APPLICATION WAS MADE. PLEASE KNOW THE VERSION SUBMITTED
 AS 2.5 WAS NOT ADOPTED UNTIL 12/8/06. PERMIT WAS
 APPLIED FOR BEFORE THIS DATE. VERSION 2.11 WAS IN
 AFFECT AT THE APPLICATION DATE.
 13-400.3.A (2005 REVISIONS TO THE 2004 FBC)
  
 2) NOTE: PLEASE SEE THE PLANS DO NOT CORRELATE WITH THE
 CALCULATIONS OR INPUT DATA REPORT. PLEASE SEE THE
 FIXTURES ON PHOTO-METRICS DO NOT COORDINATE WITH THE
 LIGHTING FIXTURES ON THE FIXTURE LEGEND.
 PLEASE SEE
 FOR EXAMPLE:
 PLEASE SEE THE FIXTURES SL2 WHICH ARE ON FIXTURE LEGEND
 ON E0-00-001 WHICH ARE NOT THE SAME AS SHEET
 E1-01-301.
 THESE SAME FIXTURES COULD NOT BE LOCATED FOR THE TOTAL,
 WATTAGE ETC IN THE IDR. THE IDR CONTAINS FIXTURES FOR
 EXTERIOR BUT NOT ALL.
 PLEASE SEE THE IDR ALSO CONTAINS A *NON-A/C* ZONE
 HOWEVER THESE SL2 FIXTURES ARE NOT IN THIS ZONE.
 THE GARAGE ALONE SHOWS A MINIMUM OF 8-SL2 FIXTURES.
 THERE ARE NO SL2 FIXTURES ON IDR. SL2 FIXTURES INDICATE
 4-42W COMPACT BULBS. PLEASE GOT THROUGH ALL AND
 COORDINATE.
 THESE WERE SPECIFICALLY NOTED ON THE PREVIOUS REVIEW
 HOWEVER THE SAME FIXTURES ARE THE SAME COMMENTS. ONE
 COPY OF THE CALCULATIONS WILL BE RETAINED BY THIS
 OFFICE.
 **** IT IS IMPORTANT TO KNOW THIS IS NOT AN EXHAUSTED
 LIST AS THERE ARE OTHER FIXTURES WHICH DO NOT
 COORDINATE. THE EXAMPLES ARE GIVEN AS A BENEFIT ONLY.
  
 PLEASE SUBMIT COMPLETED REVISED LIGHTING PLANS FOR ALL
 REVISED LIGHTING. THIS WOULD INCLUDE ALL OUTSIDE
 LIGHTS, EVEN 2ND FLOOR ARE.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2008-02-09 Cont ID  
Sent By dpalmer Date 2008-02-09 Time 08:39 Rev Time 0.00
Received By dpalmer Date 2008-02-09 Time 08:38 Sent To  
Notes
2008-02-11 08:39:39** DENIED REVISIONS **
  
 1) NOTE: PLEASE SEE PROVISO NOTES FROM MAY 07 HAVE NOT
 YET BEEN SUBMITTED FOR CORRECTIONS. PLEASE SEE NOTES
 ATTACHED TO THIS REVIEW.
  
 2) NOTE: PLEASE SEE THE REVISED ENERGY CALCULATIONS
 HAVE ITEMS WHICH NEED TO BE ADDRESSED. IN THE FOLLOWING
 NOTES THE INPUT DATA REPORT WILL BE NOTED AS IDR.
  
 A) ** PLEASE SEE THE SIGNATURE OF THE OWNER AGENT NEEDS
 TO BE SIGNED ON CERTIFICATION SHEETS. 13-103.1.1.1
  
 B) ** PLEASE SEE THE LIGHTING AS SHOWN ON PLANS NEEDS
 TO COORDINATE WITH THE LIGHTING ON THE IDR.
 PLEASE SEE THE EXTERIOR LIGHTING ON THE IDR DOES NOT
 MATCH WITH THE FIXTURE LEGEND ON PLANS, THE NUMBER OF
 FIXTURES OR THE WATTAGE OF FIXTURES. A FEW EXAMPLES
 WILL BE NOTED BELOW.
 PLEASE SEE FIXTURE SL3 WHICH IS 500WATTS ON IDR, IS
 ONLY 250WATTS ON FIXTURE LEGEND.
 PLEASE SEE THIS SAME SL3 FIXTURE ON THE IDR SHOWS ONLY
 THREE FIXTURES YET THE PLANS SHOW AT LEAST SEVEN.
 PLEASE SEE THE SL2 FIXTURES ON PLANS ARE NOT EVEN ON
 THE IDR.
 PLEASE SEE THE SL2 FIXTURE ALSO NEEDS TO SHOW WATTAGE
 OF FIXTURE ON FIXTURE LEGEND.
 PLEASE SEE THE CATEGORY FOR SL3 AND SL4 STATES
 *LIGHTING THAT IS SPECIFICALLY DESIGNATED AS REQUIRED
 BY A HEALTH, OR LIFE SAFETY STATUTE OR ORDINANCE*.
 PLEASE KNOW THERE IS NO SPECIFIC STATUTE, ORDINANCE, OR
 CODE WHICH THIS TYPE OF OUTSIDE LIGHTING IS REQUIRED.
 THERE IS SOME LIGHTING THAT IS REQUIRED BY STATUTES,
 HOWEVER THIS OCCUPANCY AND LOCATIONS DOES NOT FALL
 UNDER THIS.
 ** THIS WAS A FEW EXAMPLES, PLEASE BE SURE TO
 COORDINATE OTHERS AS WELL.
  
 3) NOTE: PLEASE SUBMIT REVISED PHOTO-METRICS FOR
 REVISIONS IN THE LIGHTING PLANS. PLEASE KNOW THAT THE
 REVISED OUTSIDE LIGHTS DO NOT COORDINATE WITH THE
 LIGHTING FIXTURES AS SHOWN ON PHOTO-METRICS. NOT ALL
 BUT SOME ARE IN NEED OF BEING REVISED.
 FBC 106.1.2 FOR ADDITIONAL INFORMATION/COORDINATION.
  
 PLEASE SUBMIT REVISED ITEMS. PLEASE BE SURE TO CALL IF
 THERE ARE ANY QUESTIONS OR IF THE COMMENTS ARE NOT
 UNDERSTOOD IN ANY FASHION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-06-21 Cont ID  
Sent By dpalmer Date 2007-06-21 Time 09:40 Rev Time 0.00
Received By dpalmer Date 2007-06-21 Time 07:46 Sent To PC
Notes
2007-06-21 09:43:39REVISIONS ADDRESSING PREVIOUS *PROVISO* ARE OK. STAMPED
 SHEETS.
  
 SHEETS SUBMITTED WITHOUT REVISIONS OR CHANGES ARE BEING
 RETURNED AS THEY ARE THE SAME AS PLANS ALREADY ON
 RECORD.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-05-15 Cont ID  
Sent By dpalmer Date 2007-05-15 Time 16:39 Rev Time 0.00
Received By dpalmer Date 2007-05-15 Time 11:38 Sent To B
Notes
2007-05-15 16:39:48** PROVISO/REVISIONS REQUIRED **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
 ** PLEASE SEE THE BELOW COMMENTS ARE BASED ON CHANGES
 ON PLANS. THERE ARE ITEMS ON THE ELECTRICAL RISER
 DIAGRAM/PANELS WHICH WERE CHANGED FROM PREVIOUS PLANS
 AND NOT PART OF PREVIOUS REVIEWED PLANS. NEW COMMENTS
 ARE NOW BASED ON THESE CHANGES.
  
 1) NOTE:PLEASE SEE THE ELECTRICAL RISER. PLEASE
 COORDINATE FEEDERS/CONDUCTORS WITH THAT OF THE FEEDER
 LEGEND AND THE PANEL(S).
 A) PLEASE SEE RISER SHOWS 250MCM FROM PANEL *H* TO
 *MH*, HOWEVER PANEL *MH* INDICATES 500MCM.
 ** THIS FEEDER WAS REVISED FROM PREVIOUS PLANS.
  
 B) PLEASE SEE THE FEEDERS FROM *QQ* TO *MQ* WHICH NOW
 INDICATE 4/300, WHICH TRANSLATED TO THE FEEDER SCHEDULE
 SHOULD BE 4-350MCM AND EQUIPMENT GROUND, HOWEVER THE
 FEEDER LEGEND ONLY INDICATES 3-350MCM AND EQUIPMENT
 GROUND WHICH IS MISSING ONE PHASE OR NEUTRAL CONDUCTOR.
  
 ( 4-WIRE COLUMN CONTAINS OTHERS NOTED AS 3-WIRE,
 HOWEVER THESE DO NOT APPLY TO RISER)
 **THIS FEEDER WAS REVISED FROM PREVIOUS PLANS.
  
 C) PLEASE SEE THE NEW METER CENTER ELEVATION WHICH DOES
 NOT COORDINATE WITH THE RISER BELOW ELEVATION AS
 SHOWN.
 PLEASE SEE THE ELEVATION SHOWS 225AMP MAIN CIRCUIT
 BREAKERS FOR MAIN FOR THE HOUSE AND AMERICAN LUNG
 HOWEVER THE ELECTRICAL RISER SHOWS 250AMP MAIN CIRCUIT
 BREAKERS WHICH DO NOT CORRELATE.
 **THIS ELECTRICAL RISER AND METER CENTER ELEVATION WAS
 REVISED FROM PREVIOUS PLANS.
  
 2) NOTE: PLEASE SEE RISER, AS THE TAPPED CONDUCTORS ARE
 NOT SHOWN FROM GUTTER TO EACH METER OR FIRST MEANS OF
 DISCONNECT, THE RISER WAS REDLINED TO NOTE THAT *NO
 EQUIPMENT GROUNDING CONDUCTOR* BEFORE THE FIRST MEANS
 OF DISCONNECT.
  
 3) NOTE: PLEASE COORDINATE THE SHEET DESIGNATION OF
 E1-01-301 AS THE FIRST FLOOR IS CALLED LIGHT DENSITY
 AND SECOND FLOOR IS PHOTO-METRICS.
  
 4) NOTE:PLEASE KNOW THE ABOVE CORRECTIONS MUST BE
 SUBMITTED FOR REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN OR 30DAYS WHICH EVER COMES
 FIRST. THIS CONDITION OF ISSUANCE WILL PLACE PERMIT ON
 HOLD WITHIN 30DAYS IF REVISIONS ARE NOT SUBMITTED.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-04-09 Cont ID  
Sent By dpalmer Date 2007-04-09 Time 18:10 Rev Time 0.00
Received By dpalmer Date 2007-04-08 Time 13:59 Sent To  
Notes
2007-04-09 18:10:33 
 ** UNSAT3RD REVIEW **
  
 11) NOTE: PLEASE SEE THAT COMPLIANCE WITH THE ENERGY
 CALCULATIONS HAS NOT BEEN MET.
 ** PLEASE SEE THAT THIS IS THE FIRST TIME THAT ENERGY
 CALCULATIONS ARE BEING SUBMITTED FOR REVIEW. PLEASE SEE
 THERE ARE SEVERAL ITEMS ON CALCULATIONS WHICH DO NOT
 CORRELATE WITH PLANS.
 PLEASE SEE THE WATTAGES FOR MANY OF THE SAME FIXTURES
 ON PLANS ARE BEING SHOWN ON ENERGY CALCULATIONS AS
 DIFFERENT WATTAGES EVEN THOUGH IT'S THE SAME FIXTURE.
 ONE FIXTURE IS SHOWN WITH AS MANY AS THREE DIFFERENT
 FIGURES FOR WATTAGE. 26, 55, AND 62.
 PLEASE CLARIFY MISSING AREAS ON PLANS, WHICH ARE NOT IN
 CALCULATIONS.
 PLEASE SEE SOME AREAS ON PLANS DO NOT CORRELATE WITH
 THE SAME AMOUNT OF FIXTURES ON CALCULATIONS. PLEASE SEE
 THE NUMBER OF LIGHT FIXTURES IN SOME ROOMS ON PLANS
 SHOW FOR EXAMPLE THREE FIXTURES AND ENERGY CALCULATIONS
 SHOW TWO OR TWO ON PLANS AND ONE IN CALCULATIONS ETC.
 PLEASE SEE STORAGE ROOMS, STAIRS, SOME OFFICES WHICH
 CONTAIN THE EXACT SAME FIXTURES, YET SHOWN WITH
 DIFFERENT FIGURES ON CALCULATIONS.
 PLEASE CLARIFY WATTAGE USE IN CALCULATIONS WITH THAT OF
 THE FIXTURES. PLEASE SEE THE PLANS AND FIXTURE LEGEND
 CONTAINS FIXTURES AT ONE LEVEL OF WATTAGE AND THE
 ENERGY CALCULATIONS INDICATE A DIFFERENT WATTAGE?
 PLEASE GO THROUGH ALL ENERGY CALCULATIONS AS THERE ARE
 MANY OF THESE ITEMS WHICH CAN NOT BE LISTED ONE FOR
 ONE.
  
 PLEASE SEE 2004 FBC CHAPTER 13, 13-415.1.AB.1.1,
 13-415.2
  
 2) NOTE: PLEASE SEE THE ELECTRICAL LIGHTING PLANSFOR
 FIRST AND SECOND FLOORS AND LIGHTING POWER DENSITY
 SHEETS DO NOT CORRELATE.
 PLEASE SEE SOME OF THE ROOM LAYOUTS AND LIGHTING
 LAYOUTS AND THE AMOUNT OF FIXTURES ON THESE SHEETS DO
 NOT CORRELATE.
 PLEASE SEE E1-01-101, E1-01-302, ETC.
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE SOME SHEETS INDICATE THE ELECTRICAL
 ROOM ALSO BEING PART OF THE WATER METER ROOM IN THE
 SAME ROOM AND SOME SHEETS INDICATE THESE BEING IN TWO
 SEPARATE ROOMS?
 PLEASE SEE 110.26 AND ROOMS AND AREAS WHICH ARE
 REQUIRED TO BE DEDICATED ELECTRICAL SPACE.
 PLEASE COORDINATE SHEETS AND LAYOUTS FOR ROOMS/WALLS.
 PLEASE SEE E1-01-101, 302, 201 ETC
  
 4) NOTE: PLEASE SEE THE PHOTO-METRIC TABLES ON THE SITE
 PLANS WHICH ARE NOT READABLE AT THIS TIME, PLEASE
 ADJUST THE SCALE ON PLANS FOR THIS.
 106.1.2, 106.3.1
  
 5) NOTE:PLEASE SEE THE PANEL *A* IS BEING SHOWN WITH
 FEED-THRU LUGS TO PANEL *MA* WHICH INDICATES 200AMP
 OVER CURRENT PROTECTION ON 2/0 WHICH ARE ONLY RATED FOR
 175AMPS.
 PLEASE SEE 310.16, 240.4.
 PLEASE SEE THE RISER SEEMS TO INDICATE THE CORRECT SIZE
 TO LEGEND ON PLANS.
  
 6) NOTE: PLEASE SEE THAT LOAD CALCULATIONS ARE NOW
 BEING SUBMITTED FOR REVIEW FOR THE FIRST TIME. THESE
 COMPLETED CALCULATIONS WERE NOT SUBMITTED ON PREVIOUS
 PLANS. THE GENERAL VA PER SQ FT FOR RECEPTACLES MAY
 ONLY BE USED WHEN THE KNOWN NUMBER OF DEVICES IS NOT
 KNOWN. PLEASE SEE THAT THE PLANS DO HOWEVER INDICATE
 THE TOTAL NUMBER OF DEVICES THEREFORE THE MINIMUM
 REQUIRED VA IS TO BE BASED ON THE AMOUNT OF RECEPTACLES
 AT 180VA PER DEVICE.
 PLEASE SEE 220.13 AND ADJUST CALCULATIONS.
  
 7) NOTE: PLEASE SEE THE LOADS SHOWN ON THE PANEL
 SCHEDULES FOR *Q, H AND A*ARE NOT THAT OF THE CONNECTED
 LOAD BEING SHOWN IN THE LOAD CALCULATIONS ON SHEET
 E0-00-01.
 PLEASE SEE THE LOAD ON THE *A* PANEL SEEMS TO BE VERY
 CLOSE TO LOAD PERMITTED ON THIS PANEL AND MAINS. PLEASE
 SEE 90.8 AS THERE DOES NOT SEEM TO BE MUSH ROOM FOR
 FUTURE LOADS OR CHANGES IN DESIGN. PLEASE REVIEW LOADS
 AND BE SURE LOADS DO NOT EXCEED RATING OF SERVICE AND
 CONSIDERATION IS TAKEN FOR ANY FUTURE LOADS. PLEASE
 ALSO SEE THE LOAD CALCULATIONS FOR WHAT APPEARS TO BE
 THE LOAD FOR THE ENTIRE SERVICE AS THESE ARE BEING
 LABELED FOR THE *QUANTUM* SERVICE.
 THIS SEEMS TO BE A MISPRINT FOR SERVICE.
 PLEASE SEE NEC 220.
 FBC 106.3.5.1.2
  
 8) NOTE: PLEASE SEE THE PANEL SCHEDULES WILL BE
 REQUIRED TO BE SPECIFIC TO LIST ALL CIRCUITS TO ROOMS
 AND AREAS IN WHICH THEY FEED.
 PLEASE SEE THE USE OF *GENERAL LIGHTING OR GENERAL
 RECEPTACLES* IS NOT ACCEPTABLE ANDWILL BE REQUIRED TO
 LIST ROOMS OR AREAS FOR WHICH THEY FEED. THIS MAY BE
 DONE BY OFFICE DESIGNATION BY NAME OR NUMERICAL
 IDENTIFICATION.
 A *PROVISO* (CONDITION OF ISSUANCE) MAY BE SET UP FOR
 THIS ITEM OR THIS MAY BE ADDRESSED AT THIS TIME. PLEASE
 SEE THE FOLLOWING TEXT WHICH IS TAKEN FROM THE CODE
 COMMENTARY*
 *PROVISO* (CONDITION OF ISSUANCE) MAY BE SET UP FOR
 THIS ITEM.
  
 *CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* 408.4,
 310.16, 240.4 ETC
  
 9) NOTE: PLEASE SEE THAT ONE SET OF ELECTRICAL PLANS
 AND ENERGY CALCULATIONS ARE BEING RETAINED BY THIS
 OFFICE AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-04-08 13:59:49IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-01-15 Cont ID  
Sent By dpalmer Date 2007-01-15 Time 14:25 Rev Time 0.00
Received By dpalmer Date 2007-01-14 Time 19:10 Sent To  
Notes
2007-01-15 14:25:18 
  
 *** UNSAT 2ND REVIEW***
  
 AMERICAN LUNG ASSOCIATION
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED ALONG WITH SOME NEW COMMENTS BASED
 ON CHANGES MADE TO PLANS.
 PLEASE KNOW THAT THERE NEW COMMENTS BASED ON PLANS AND
 CHANGES MADE.
  
 ** PLEASE KNOW THAT BASED ON THE LAST MEETING HELD, THE
 ARCHITECT WAS PRESENT HOWEVER NO CONTACT TO DATE HAS
 BEEN MADE BY THE ENGINEERING DESIGNER(S) TO GO OVER
 COMMENTS.
  
 ** PLEASE SEE THE COMMENTS BELOW ARE TAKEN DIRECTLY
 FROM PREVIOUS REVIEW IN THE SAME NUMERICAL ORDER. THEY
 WILL CONTAIN A NO, OK, OR NO/OK.
 A) NO WILL BE FOLLOWED BY FURTHER EXPLANATION OF THE
 PREVIOUS COMMENT.
 B) OK, MAY REFERENCE TO ANY NEW NOTES, HOWEVER WILL
 HAVE PREVIOUS NOTE REMOVED.
 C) NO/OK, WILL BE FOLLOWED BY FURTHER EXPLANATION AS
 PART OF THE COMMENT MAY NOT HAVE BEEN ADDRESSED FULLY
 AND PART OF THE PREVIOUS COMMENT MAY BE OK.
 D) OK/N/A, AS THE PREVIOUS NOTE DOES NOT APPLY ANY
 FURTHER AS PLANS HAVE DELETED OR CHANGED.
  
 ** ANY NEW NOTES WILL BE AT THE BOTTOM AND IDENTIFIED
 AS *** NEW NOTES ***.
  
  
  
  
 1) NOTE: NO/OK. PLEASE SEE THE ENGINEERING BUSINESS
 NUMBER WAS VERIFIED WITH THE STATE, HOWEVER PLEASE SEE
 THE ADDRESS FOR FIRM ON THE STATE'S WEBSITE AND PLANS
 DIFFER. A FAR AS WE HAVE BEEN INFORMED FROM THE STATE,
 THIS INFORMATION IS REQUIRED TO MATCH.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING REQUIRED LICENSE INFORMATION ON
 TITLE BLOCKS.
 PLEASE SEE FAC 61G15-23.002 AND FS
 471.023.
 PLEASE KNOW PER THE FLORIDA STATUES AS NOTED ABOVE AND
 PER THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS, ANY
 FIRM PRACTICING ENGINEERING AND OFFERING ENGINEERING
 SERVICES MUST ALSO OBTAIN A CERTIFICATE OF
 AUTHORIZATION NUMBER FOR THE ENGINEERING PART OF THE
 BUSINESS.
 PLEASE SEE THE FIRM NUMBER AS SHOWN IS ONLY LICENSED
 FOR THE ARCHITECTURAL FIRM.
 PLEASE ALSO SEE ADDRESS ON TITLE BLOCK DO NOT CORRELATE
 WITH THE ADDRESS AS LISTED ON THE STATE'S DEPARTMENT OF
 BUSINESS AND PROFESSIONAL REGULATION.
 PLEASE SEE THE ATTACHED PRINT OUT ATTACHED TO
 ELECTRICAL NOTES.
 ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S).
  
 2) NOTE: OK/NO, PLEASE SEE THIS WAS DONE HOWEVER THIS
 INFORMATION WAS HAND WRITTEN ON SHEETS WHICH IS OK. THE
 COMMENT WILL REMAIN AS NEW SHEETS WILL ALSO BE REQUIRED
 TO CONTAIN THIS INFORMATION. THIS IS SOMETHING THAT
 SHOULD BE ADDED INTO THE FIRMS CADD OR COMPUTER SYSTEMS
 SO THAT THIS INFORMATION DOES NOT HAVE TO BE
 HANDWRITTEN ON ALL SHEETS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER
 FOR THE ENGINEER OF RECORD ON SAID TITLE BLOCKS AS
 REQUIRED UNDER FAC 61G15-23.002
  
 3) NOTE: OK.
  
 4) NOTE: OK.
  
 5) NOTE: OK, N/A
  
 6) NOTE: OK, AS THE GEN HAS BEEN REMOVED AND NOTES
 BEING DONE AS FUTURE, HOWEVER PLEASE SEE THESE SECTIONS
 AND PREVIOUS NOTES ARE BEING LEFT FOR INFORMATIONAL
 REASONS FOR THE PANEL E WHICH IS BEING SHOWN AS FUTURE
 WHICH DOES NOT SEEM TO MEET THESE SECTIONS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 225.31-225.39 FOR MISSING REQUIRED MEANS OF
 DISCONNECT FOR THE FEEDERS FROM THE GENERATOR UNIT.
 PLEASE SEE GROUPING ETC AS REQUIRED.
  
  
 7) NOTE: OK, HOWEVER SEE NEW NOTES WITH RESPECT TO GAP,
 FACP AND FAAP.
  
 8) NOTE: OK, N/A. SEE NEW NOTES HOWEVER FOR PANEL H.
  
  
 9) NOTE: OK.
  
 10) NOTE: OK, N/A.
  
 11) NOTE: OK, N/A.
  
 12) NOTE: OK/NO, PLEASE SEE THESE ITEMS WERE ADDED,
 HOWEVER PLEASE SEE MISSING CIRCUITING FOR THE ROOF TOP
 GFI'S.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING DISCONNECTS FOR RTU'S WHICH COULD
 NOT BE LOCATED ON PLANS. CAN BE TYPICAL IF THE SAME.
 440.11
 PLEASE ALSO SEE MISSING ROOF TOP GFI'S WHICH COULD NOT
 BE LOCATED ON PLANS FOR ROOF.
 230.63, 210.8
  
 13) NOTE: NO, PLEASE SEE PLANS AS THE INTENTION SEEMS
 TO HAVE BEEN MADE, BUT PLEASE SEE THAT THERE ARE LINES
 FOR CIRCUITING WHICH STILL PLACES THE LIGHTING ON WITH
 OTHER HOUSE CIRCUITS AND OTHER AREAS WHICH IS NOT
 PERMITTED. PLEASE SEE SECTIONS AS NOTED REQUIRE
 DEDICATED CIRCUITS WHICH MAY NOT FEED OTHER AREAS.
 PLEASE SEE NOTE FOR CONTROL OF PIT LTS.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE MISSING THE REQUIRED DEDICATED CIRCUITS FOR
 THE ELEVATOR MACHINE ROOM.
 620.23, 620.24
  
 14) NOTE:OK, HOWEVER SEE NEW NOTES FOR EMERGENCY
 LIGHTING.
  
 15) NOTE:NO, PLEASE SEE ALL DEVICES AS NOTED AND
 SHOWN ON PLANS SHALL INDICATE ALL OF THE MAXIMUM TIMES.
 ONLY ONE SYMBOL ON LEGEND CONTAINS THE INFORMATION AS
 NEEDED.
 PLEASE SEE ELEVATOR PIT LIGHTS WHICH APPEAR TO BE
 MISSING CONTROL(S).
 PLEASE CALL F THERE ARE ANY QUESTIONS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SPECIFY THE MAX OVER RIDE TIMES FOR THE OCCUPANT
 SENSORS.
 30MIN MAX FOR SENSORS AND 4HRS MAX FOR TIMER TYPE OVER
 RIDES.
 PLEASE ALSO SEE SEPARATE SPACES/ROOMS WHICH SEEM TO BE
 MISSING OVER RIDE CONTROLS.
 PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2,
 .1.3
  
 16) NOTE:NO, PLEASE SEE THAT IT APPEARS BASED ON THE
 RESPONSE FROM THE DESIGN TEAM THAT THIS COMMENT WAS NOT
 UNDERSTOOD.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED SHOWING
 METHOD A, INDICATES ALL LIGHTING BEING CONTROLLED AS
 "MANUAL ON/OFF". THIS IS NOT POSSIBLE IF THERE ARE
 AUTOMATED CONTROL LIGHTING SYSTEMS AND AUTOMATED
 DEVICES/OCCUPANCY SENSORS ETC.
 13-415.1.ABC.1.1, .1.2, AND .1.3. 13-415.2. ETC.
  
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE VERIFY HOW THE ENERGY CALCULATIONS SUBMITTED ALL
 MENTIONS AND CONTAIN "MANUAL ON/OFF" CONTROLS FOR
 LIGHTING??
 PLEASE SEE METHODS REQUIRED PER 13-415.1.AB.1.
  
 17) NOTE:NO, PLEASE SEE BASED ON THE RESPONSE IT
 MENTIONS TO SEE LIGHTING PHOTO-METRICS?? PLEASE KNOW
 THAT PHOTO-METRICS AND LIGHTING POWER DENSITIES AND
 PERFORMANCE CALCULATIONS A RE COMPLETELY DIFFERENT
 ITEMS.
 PLEASE SUBMIT PER SECTIONS GIVEN IN PREVIOUS REVIEW
 NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT LIGHTING POWER DENSITY CALCULATIONS AS
 REQUIRED. 13-415.1.AB.1,13 ,415.2.ABC.1 AND TABLES
 415.2.C.1 AND 415.2.B.1 (WHERE APPLICABLE)
  
 18) NOTE: OK.
  
 20) NOTE: OK, HOWEVER THIS NOTE WILL REMAIN AS BASED ON
 THE SIZE OF THE SERVICE ENTRANCE CONDUCTORS, THE LOAD
 CALCULATIONS SUBMITTED THIS MAY BE CHANGED AND/OR
 INCREASED. SEE COMMENTS AS THIS PREVIOUS NOTE WILL
 REMAIN AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 250.66 FOR MIN SIZING OF THE GEC. APPEARS
 THIS SHOULD BE 2/0 MIN.
  
 21) NOTE: NO, PLEASE SEE AS NOTED ABOVE THIS STILL
 SEEMS TO BE IN QUESTION. PLEASE SEE SOME COMMON AREAS
 WHICH ARE NOT FED FROM HOUSE PANELS, PLEASE SEE OTHER
 AREAS LIKE THE ROOF TOP WHICH IS BEING FED FROM HOUSE
 PANEL AND QQ PANELS FOR STAIRS. PLEASE SEE NOTES FOR
 ELEVATOR ROOMS WHICH ARE BEING FED FROM HOUSE AND
 TENANT PANELS.
 THIS SCENARIO ON PLANS AS SHOWN IS NOT CLEAR. PLEASE
 SEE THERE SEEMS TO BE AN ELECTRICAL ROOM ON FIRST FLOOR
 WHICH REVIEW OF 240.24 SHOULD BE NOTED AND ADJUST PLANS
 AS NEEDED.
 PLEASE MAKE OTHER ADJUSTMENTS AS ROOF TOP ACCESS SEEMS
 TO BE ONLY ACCESSIBLE THROUGH WHAT IT BEING SHOWN AS
 STAIRWAYS FOR THE 2ND FLR TENANT ONLY. IF THESE
 STAIRWAYS OR A STAIRWAY IS BEING USED FOR COMMON USE,
 THEN THE ONE OR MORE BEING USED SHALL BE CIRCUITED FORM
 THE HOUSE COMMON AREA PANEL/EQUIPMENT.
 PLEASE ALSO SEE BOLLARDS BEING SHOWN ON ROOF?, AND
 BEING SHOWN FROM HOUSE WHICH IS OK, HOWEVER NOT CLEAR
 WHY THERE ARE BOLLARD TYPE FIXTURES ON ROOF? PLEASE
 KNOW THAT AS PLANS ARE NOT CLEAR AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY THE SEPARATION OF TENANTS. PLEASE SEE
 PLANS AS SHOWN HAS CIRCUITING FROM EACH TENANT SERVICE
 CROSSING OVER INTO OTHER TENANT'S AREAS AND ROOMS. IF
 THE BUILDINGS GOING TO HAVE "HOUSE" POWER THESE MAY NOT
 FEED INTO TENANT SPACES. PLEASE ALSO SEE
 CIRCUITS FOR UPPER TENANT MAY NOT FEED AREAS IN LOWER
 TENANTS. PLEASE SEE PROPER TENANT SEPARATION AND
 CROSSING OVER OF CIRCUITS AND COMMON AREAS. PLEASE
 ADJUST CIRCUITING ON PLANS.
 PLEASE SEE "HOUSE" PANELS LOCATED ON FIRST FLR TENANTS
 SPACE?
 THIS IS UNCLEAR WHAT IS BEING PROPOSED IN THIS DESIGN
  
 22) NOTE: NO, PLEASE SEE NEW COMMENTS AS THE RISER HAS
 COMPLETELY CHANGED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE AS KNOW "SCHEDULE WAS SUBMITTED FOR THE
 800A BUS/METER CENTER, PLEASE INDICATE THE CONDUCTORS
 FROM THE MAIN BUS TO EACH OF THE ATS UNITS.
 215.5, 240.4,310.16
  
 23) NOTE: OK, HOWEVER SEE NEW NOTES.
  
 24) NOTE: OK/NO, CIRCUITS ARE BEING SHOWN, HOWEVER
 COMING FROM HOUSE PANEL? PLEASE SEE 600.5 AND THE
 REQUIRED DEDICATED CIRCUITS. THIS CIRCUIT AS SHOWN ON
 PLANS COMES NOT ONLY FROM THE HOUSE PANEL; IT IS ALSO
 SHOWN FEEDING OTHER AREAS OF LIGHTING. PLEASE SEE 600.5
 REFERENCES TO 220.3(B)6
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE VERIFY NEW OR EXISTING REQUIRED SIGN CIRCUIT PER
 600.5
  
 25) NOTE: NO, PLEASE SEE LOAD CALCULATIONS ARE NOT
 COMPLETE PER NEC AND CODE SECTIONS GIVEN.
 PLEASE ALSO SEE NEW NOTES BASED ON THE LOADS ALREADY
 SHOWN WHICH EXCEED THE RATING OF THE SERVICE ENTRANCE
 CONDUCTORS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE VERIFY AND SHOW LOAD CALCULATIONS FOR SERVICE
 AND GENERATOR.
 PLEASE SEE 220.3,220.10,220.11,220.13, ETC
 PLEASE SHOW ALL CONTINUOUS LOADS AT 125%.215.3,230.42
  
 26) NOTE: OK,N/A.
  
 27) NOTE: OK, N/A.
  
 28) NOTE: NO, SEE NEW NOTES FROM THIS REVIEWER.
  
 PLEASE SEE POSSIBLE FIRE AND BUILDING REVIEW COMMENTS
 AS IT DID NOT SEEM PLANS WERE SUBMITTED FOR ANY
 BUILDING FIRE ALARM SYSTEM?
  
 **** NEW NOTES ******
  
  
 29) NOTE: PLEASE SEE PANELS MH, MA, H, MQ ETC ALL LIST
 FEEDS TO AUTOMATIC TRANSFER SWITCHES WHICH ARE NOT ON
 RISER. THESE ARE NOT THE ATS DEVICES WHICH ARE SHOWN ON
 RISER WHICH ARE NOTED AS FUTURE ON THE LINE SIDE OF
 THESE PANELS.
 PLEASE ALSO SEE ONE IS STILL BEING SHOWN AS LS /ATS FOR
 LIFE SAFETY. PLEASE SEE IF THERE ARE LEGALLY REQUIRED
 SYSTEMS OR LIFE SAFETY SYSTEMS, PLEASE REVISE PLANS.
 PLEASE CLARIFY ALL OF THESE. REVIEW FOR ANY CODE
 COMPLIANCE CAN NOT BE DONE AT THIS TIME AS PLANS ARE
 CONFUSING AND ARE NOT CLEAR OF INTENTIONS, CODES AND
 DESIGNS AS SHOWN.
 PLEASE SUBMIT ALL MANUFACTURE'S SPEC/CUT SHEETS FOR ANY
 PROPOSED SWITCHES TO BE INSTALLED AT THIS TIME. 110.3,
 90.7.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION FOR ADDITIONAL
 INFORMATION.
  
 30) NOTE: PLEASE SEE THAT THE MEN'S AND WOMEN'S
 BATHROOM WHICH ARE NOT SINGLE OCCUPANT OR SINGLE POINT
 OF USE SHALL CONTAIN A BATTERY BACK UP LIGHT FIXTURE OF
 SOME KIND.
 PLEASE ALSO SEE UPPER STAIRS WHICH DO NOT INDICATE
 BATTERY BACK UP FIXTURES.
 PLEASE SEE PARKING GARAGE AREA FOR EGRESS TO THE PUBLIC
 RIGHT OF WAY.
 PLEASE SEE LS 101 7.8.1.3, AND 7.9.2.2.
 PLEASE KNOW THE LIGHTING LEVELS ON STAIRS SHALL MEET
 10FT UNDER NORMAL AND 1FT CANDLED UNDER EM.
  
 31) NOTE: PLEASE SEE THAT THESE PLANS SHALL CONTAIN A
 BASE LAYOUT FOR ALL FIRE ALARM DEVICES TO REVIEW FOR
 ADA COMPLIANCE. PLEASE SEE THE NOTE BEING PLACED ON THE
 PLANS CAN NOT BE ACCEPTED. PLEASE KNOW THAT EVEN THOUGH
 THE FIRE ALARM AND ANY FIRE SPRINKLER WILL BE REQUIRED
 UNDER A SEPARATE PERMIT THESE BASE SYSTEMS ARE STILL
 REQUIRED ON BASE BUILDING PLANS.
 THIS WAS NOT A COMMENT ON THIS REVIEWER'S PREVIOUS
 REVIEW; HOWEVER IT HAS NOW BECOME PART OF THE
 ELECTRICAL REVIEW SINCE THESE PLANS WERE PREVIOUSLY
 REVIEWED. PLEASE SEE COMPLIANCE FOR MINIMUM STROBE AND
 SOUNDING DEVICE LEVELS SHALL BE STATED AND LOCATIONS
 SHOWN.
 PLEASE SEE 11-4.28.1, .2, AND.3(4).
 FBC ADMIN SECTION 106.3.5.1.2
  
 32) NOTE: PLEASE CLARIFY PANELS H, A AND Q AS BEING
 NOTED AS SERVICE ENTRANCE RATED. HOW IS THIS POSSIBLE
 WHEN THESE ARE ALL BEING SHOWN AS MLO?
 PLEASE ALSO EXPLAIN.
 106.1.2, 106.3.5.1.2, NEC 230.70, 110.3, 90.7
  
 33) NOTE: PLEASE SUBMIT MANUFACTURE'S SPEC/CUT SHEETS
 ON THE PROPOSED SERVICE AS SHOWN ON RISER. THIS 800A
 RATED BUS WHICH SHOWS NO MAIN, YET SHOWS SEPARATE
 METERS AND MAINS FOR EACH TENANT AND HOUSE IS NOT
 CLEAR.
 IT MAY SEEM THAT THIS EQUIPMENT MAY BE REQUIRED TO
 CONTAIN A MAIN? (IF APPLICABLE)
 PLEASE SUBMIT MORE INFORMATION. FBC 106.1.2,
 106.3.5.1.2
 NEC 110.3, 90.7, 230.70, ETC
  
 34) NOTE: PLEASE SEE BASED ON THE LOAD CALCULATIONS
 SUBMITTED AND NOTED ABOVE IN NOTE #25, THE SEC'S ARE
 NOT LARGE ENOUGH FOR THE LOADS AS SHOWN. PLEASE ALSO
 KNOW BASED ON THESE LOADS SHOWN AND SOME LOADS WHICH
 ARE REQUIRED WHICH HAVE NOT YET BEEN ADDED OR SHOWN THE
 SIZING OF THESE CAN NOT BE VERIFIED FOR CODE COMPLIANCE
 AT THIS TIME.
 PLEASE ALSO SEE NOTE ABOVE AS IF THE EQUIPMENT CHANGES
 SOME OTHER CODE SECTIONS MAY ALSO APPLY FOR DEVICES
 RATED OVER 800AMPS.
 PLEASE SEE 240.4, 310.16, 230.70, 230.76, 230.79,
 230.90, 230.91 ETC
  
 35) NOTE: PLEASE SUBMIT WIND LOADS FOR NEW SITE
 LIGHTING POLES AS SHOWN. THESE SHALL INDICATE THE
 MINIMUM LEVELS PER FBC 140MPH 3-SEC GUST (120
 SUSTAINED) AND INDICATE THE EPA OF FIXTURES FOR THE
 POLE BEING STATED.
 PLEASE KNOW THIS WILL BE REVIEWED FURTHER BY THE
 BUILDING REVIEWER.
  
 36) NOTE: PLEASE KNOW CONTACT WITH THE FIRE MARSHAL'S
 OFFICE SHOULD BE MADE FOR COORDINATION OF THE LOCATIONS
 OF THE FACP, GAP(FUTURE) AND FAAP.
  
 37) NOTE: PLEASE KNOW THIS IS BEING NOTED ONLY AS PANEL
 E IS NOT UNDER THIS PERMIT. THE BREAKER IS BEING SHOWN
 FOR ATS-LS.?
 THIS IS ONLY BEING NOTED.
  
 38) NOTE: PLEASE SEE ATTACHED REFERENCE TO FS
 553.80(2)(B) WITH RESPECT TO DESIGN PROFESSIONALS AND
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
  
 ** PLEASE KNOW AS THERE MAY BE COMMENTS ON THE NEXT
 REVIEW BASED ON INFORMATION NOT SHOWN OR CHANGES WHICH
 WILL BE TAKING PLACE ON PLANS.
  
 ** PLEASE BE AWARE OF ANY COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT THE
 ELECTRICAL PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-15 11:23:552007-01-15 11:23:55
 REVIEW IN PROGRESS
2007-01-14 19:10:49PLANS REMOVED FROM INCOMING TABLE. IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-10 Cont ID  
Sent By dpalmer Date 2006-09-10 Time 18:18 Rev Time 0.00
Received By dpalmer Date 2006-09-10 Time 15:53 Sent To  
Notes
2006-09-10 00:00:00*** UNSAT ***
  
 AMERICAN LUNG ASSC
  
 1) NOTE: PLEASE SEE MISSING REQUIRED
 LICENSE INFORMATION ON TITLE BLOCKS.
 PLEASE SEE FAC 61G15-23.002 AND FS
 471.023.
 PLEASE KNOW PER THE FLORIDA STATUES AS
 NOTED ABOVE AND PER THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS, ANY FIRM
 PRACTICING ENGINEERING AND OFFERING
 ENGINEERING SERVICES MUST ALSO OBTAIN A CERTIFICATE OF
 AUTHORIZATION NUMBER FOR
 THE ENGINEERING PART OF THE BUSINESS.
 PLEASE SEE THE FIRM NUMBER AS SHOWN IS
 ONLY LICENSED FOR THE ARCHITECTURAL
 FIRM.
 PLEASE ALSO SEE ADDRESS ON TITLE BLOCK
 DO NOT CORRELATE WITH THE ADDRESS AS
 LISTED ON THE STATE'S DEPARTMENT OF
 BUSINESS AND PROFESSIONAL REGULATION.
 PLEASE SEE THE ATTACHED PRINT OUT
 ATTACHED TO ELECTRICAL NOTES.
 ** THIS IS REQUIRED FOR ALL SHEETS AND
 FOR ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2) NOTE: PLEASE SEE MISSING THE PRINTED
 NAME AND LICENSE NUMBER FOR THE ENGINEER
 OF RECORDON SAID TITLE BLOCKS AS
 REQUIRED UNDER FAC 61G15-23.002
  
 3) NOTE: PLEASE SEE A LETTER WAS
 ATTACHED FROM THE ENGINEER OF RECORD FOR VERIFICATION
 OF LEGAL SIGNATURE. PLEASE
 KNOW THE WORDING OF LETTER IS FINE,
 HOWEVER LETTER MUST BE ORIGINAL.
 (PHOTO-COPY SUBMITTED). MUST ALSO BE
 SIGNED, DATED AND SEALED BY SAID
 ENGINEER.
 PLEASE ALSO SEE THE STATUES IN WHICH
 STATE THE DOCUMENT IS BEING NOTARIZED,
 IF IN FLORIDA PLEASE SEE FS 117.05 AS IN
 THE STATE OF FLORIDA A STAMP AND
 SIGNATURE OF NOTARY IS NOT ALL THAT IS
 REQUIRED FOR A LEGAL DOCUMENT.
  
 4) NOTE: PLEASE SEE SURVEY SUBMITTED IN
 INDEED A PHOTO-COPY OF THE SIGNATURE
 WITH A RAISED SEAL OVER PHOTO-COPIED
 SIGNATURE WHICH IS NOT PERMITTED UNDER
 FAC 61G17, FS 472.025
 PLEASE ALSO SEE THAT THE RAISED SEAL
 MUST BE CLEAR AND VISIBLE WITH ALL
 INFORMATION ON SAID SEAL. (NOT VISIBLE AT
 THIS TIME).
 PLEASE CORRELATE THE SURVEY WITH THE
 ELECTRICAL PLANS, AS THE E-SHEETS
 INDICATE ANEW GENERATOR.(PLEASE SEE
 ZONING COMMENTS FOR THIS.
  
 5) NOTE: PLEASE SUBMIT ALL MANUFACTURES
 SPECS/CUT SHEETS FOR THE NEW GENERATOR,
 NEW SUB-BASE FUEL TANK AND EACH OF THE
 PROPOSED ATS SWITCHES.
 PLEASE SEE THAT ALL SPEC SHEETS FOR THE
 ATS UNITS CONTAINS A LISTING FROM A
 (NRTL). NATIONALLY RECOGNIZED TESTING
 LABORATORY.
 PLEASE ALSO BE SURE ALL AIC RATING FOR
 ALL ATS UNITS AND MAINS ARE INDICATED ON
 PLANS/SPECS.700.5, 701.6,702.5 NFPA-110
 6.5
 110.3,90.7
 FBC 106.1.2 ADMIN SECT.
  
 6) NOTE: PLEASE SEE 225.31-225.39 FOR
 MISSING REQUIRED MEANS OF DISCONNECT FOR
 THE FEEDERS FROM THE GENERATOR UNIT.
 PLEASE SEE GROUPING ETC AS REQUIRED.
  
  
 7) NOTE: PLEASE SEE A NOTE FOR SIGNAGE
 IS REQUIRED INCLUDING SIGNAL DEVICES.
 700.7,700.8,701.8,701.9
  
 8) NOTE: PLEASE SEE 700.1 AND 701.1
 EMERGENCY AND LEGALLY REQUIRED SYSTEMS
 MAY NOT OCCUPY THE SAME ELECTRICAL
 DISTRIBUTION EQUIPMENT RACEWAYS ETC.
 PLEASE SEE PANEL "E" IS THE SAME DIST
 EQUIPMENT WHICH FEEDS EM/LEGALLY AND
 OPTIONAL STAND-BY SYSTEMS.700.9,
 701.10ETC
 ** PLEASE CLARIFY SYSTEMS AS SHOWN AS IT
 IS UNCLEAR WHY ALL ARE BEING SHOWN AS
 REQUIRED LS OR EM SYSTEM.
  
 9) NOTE: PLEASEKNOW THAT ALL CODES
 RELEVANT TO THE DESIGN AND SCOPE PF WORK
 SHALL BE STATED ON PLANS. PLEASE SEE
 THAT THE FOLLOWING IS REQUIRED AT A
 MINIMUM. PLEASE KNOW AS OF JULY 1ST 2003
 THE 2002 NEC WAS ADOPTED BY THE STATE.
 PLEASE SEE "A" SHEET WHICH SHOWS 99.
 2002 NFPA-70, 2002 NFPA-72, 2003
 NFPA-101, 2002 NFPA-110, 2004 FBC
  
 10) NOTE: PLEASE SEE NFPA-110 7.2.2.1 AS
 TWICE THECLEARANCE DISTANCE FOR ATS
 IS REQUIRED IN MAIN ELECTRICAL ROOM AS
 REQUIRED PER 110.26
  
 11) NOTE: PLEASE SEE NFPA-110 CHAPTER 7
 AS THE ELEVATION OF THE GENERATOR IS NOT
 STATED. PLEASE SEE MOUNTING ETC AS
 REQUIRED. PLEASE SEE THE ELEVATION IS
 REQUIRED AT A MIN OF 6" ABOVE THE
 FLOODING LEVEL (BFE) IF IN A FLOOD ZONE.
 PLEASE SEE 7.4 AND BUILDING REVIEW
 COMMENTS FOR REQUIRED SLAB DETAIL.
  
 12) NOTE: PLEASE SEE MISSING DISCONNECTS
 FOR RTU'S WHICH COULD NOT BE LOCATED ON
 PLANS. CAN BE TYPICAL IF THE SAME.
 440.11
 PLEASE ALSO SEE MISSING ROOF TOP GFI'S
 WHICH COULD NOT BE LOCATED ON PLANS FOR
 ROOF.
 230.63, 210.8
  
 13) NOTE: PLEASE SEE MISSING THE
 REQUIRED DEDICATED CIRCUITS FOR THE
 ELEVATOR MACHINE ROOM.
 620.23,620.24
  
 14) NOTE: PLEASE SEE THAT AN EMERGENCY
 LT FIXTURE OF SOME SORT WITH BATTERY
 BACK UP WILL BE REQUIRED IN THE MAIN
 ELECTRICAL ROOM AND THE ELEVATOR MACHINE
 ROOM.
 7.9.2.2, 700.16, 90.4
  
 15) NOTE: PLEASE SPECIFY THE MAX OVER
 RIDE TIMES FOR THE OCCUPANT SENSORS.
 30MIN MAX FOR SENSORS AND 4HRS MAX FOR
 TIMER TYPE OVER RIDES.
 PLEASE ALSO SEE SEPARATE SPACES/ROOMS
 WHICH SEEM TO BE MISSING OVER RIDE
 CONTROLS.
 PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2,
 .1.3
  
 16) NOTE: PLEASE VERIFY HOW THE ENERGY CALCULATIONS
 SUBMITTED ALL MENTIONS AND
 CONTAIN "MANUAL ON/OFF" CONTROLS FOR
 LIGHTING??
 PLEASE SEE METHODS REQUIRED PER
 13-415.1.AB.1.
  
 17) NOTE: PLEASE SUBMIT LIGHTING POWER
 DENSITY CALCULATIONS AS REQUIRED.
 13-415.1.AB.1,13.415.2.ABC.1 AND TABLES
 415.2.C.1 AND 415.2.B.1
  
 18) NOTE: PLEASE SEE MISSING GROUNDING
 ELECTRODE DETAIL FOR THE GROUNDING
 ELECTRODE SYSTEM. PLEASE SEE MISSING NEW
 FOOTER STEEL ETC
 250.50
  
 20) NOTE: PLEASE SEE 250.66 FOR MIN
 SIZING OF THE GEC. APPEARS THIS SHOULD
 BE 2/0 MIN.
  
 21) NOTE: PLEASE CLARIFY THE SEPARATION
 OF TENANTS. PLEASE SEE PLANS AS SHOWN
 HAS CIRCUITING FROM EACH TENANT SERVICE
 CROSSING OVER INTO OTHER TENANT'S AREAS
 AND ROOMS. IF THEBUILDINGS GOING TO
 HAVE "HOUSE" POWER THESE MAY NOT FEED
 INTO TENANT SPACES. PLEASE ALSO SEE
 CIRCUITS FOR UPPER TENANT MAY NOT FEED
 AREAS IN LOWER TENANTS. PLEASE SEE PROPER
 TENANT SEPARATION AND CROSSING OVER OF
 CIRCUITS AND COMMON AREAS. PLEASE ADJUST CIRCUITING ON
 PLANS.
 PLEASE SEE "HOUSE" PANELS LOCATED ON
 FIRST FLR TENANTS SPACE?
 THIS IS UNCLEAR WHAT IS BEING PROPOSED
 IN THIS DESIGN
  
 22) NOTE: PLEASE SEE AS KNOW "SCHEDULE
 WAS SUBMITTED FOR THE 800A
 BUS/METER CENTER, PLEASE INDICATE THE
 CONDUCTORS FROM THE MAIN BUS TO EACH OF
 THE ATS UNITS.
 215.5, 240.4,310.16
  
 23) NOTE: PLEASE KNOW , DEPENDING ON
 OUTCOME OF SERVICE, PLEASE BE SURE TO
 LABEL MAINS.
 230.2E ETC
  
 24) NOTE: PLEASE VERIFY NEW OR EXISTING
 REQUIRED SIGN CIRCUIT PER 600.5
  
 25) NOTE: PLEASE VERIFY AND SHOW LOAD
 CALCULATIONS FOR SERVICE AND GENERATOR.
 PLEASE SEE 220.3,220.10,220.11,220.13,
 ETC
 PLEASE SHOW ALL CONTINUOUS LOADS AT 125%.215.3,230.42
  
 26) NOTE: PLEASE INDICATE THE GROUNDING
 ELECTRODE SYSTEM AT THE GENERATOR.
 250.30,250.20, 250.50
  
 27) NOTE: PLEASE INDICATE THE OCP AT THE GENERATOR.
 106.1.2, 700,701, 702
  
 28) NOTE: PLEASE SEE POSSIBLE FIRE AND
 BUILDING REVIEW COMMENTS AS IT DID NOT
 SEEM PLANS WERE SUBMITTED FOR ANY
 BUILDING FIRE ALARM SYSTEM?
  
 ** PLEASE BE AWARE OF ANY COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT THE
 ELECTRICAL PLANS.
  
 ** PLEASE KNOW AS THERE ARE ITEMS WHICH
 WERE NOT SUBMITTED FOR REVIEW AND
 POSSIBLE CHANGES IN DESIGN, THERE MAY BE
 OTHER COMMENTS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2006-10-31 Cont ID  
Sent By rchokshi Date 2006-10-31 Time 15:04 Rev Time 0.00
Received By rchokshi Date 2006-10-31 Time 14:50 Sent To  
Notes
2006-10-31 15:04:00MATTHEW HAROLD SENT SHEETS C-4 & C-5AT 45TH STREET
 WITH ALL ENG CORRECTIONS PREVIOUSLY ASKED FOR.MR
 HAROLD ALSO SAID THAT HE IS GOING TO SEND REVISED PLANS
 WITH ALL OTHER DISCIPLINE'S CORRECTIONS TO CITY HALL
 CONST. SERVICES.IT IS APPROVED FOR ENG. REVIEW WHILE
 AT 45TH STREET.RASIK CHOKSHI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2006-10-02 Cont ID  
Sent By rchokshi Date 2006-10-02 Time 13:18 Rev Time 0.00
Received By rchokshi Date 2006-10-02 Time 13:03 Sent To  
Notes
2006-10-02 00:00:00AGAIN FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE TELL US WHAT IS YOUR
 MAINTENANCE PLAN FOR EX-FILTRATION
 PIPES,TRENCH ETC., TO KEEP CLEAN &
 UNPLUG HOLES. MAY BE A GOOD IDEA TO KEEP
 SWALE IN GRASS AREA AROUND THE SITE,
 OTHERWISE WATER FROM THIS SITE WILL GO
 TO AUSTRALIAN AVE OR BACK IN THE LAKE
 WHICH WE DO NOT WANT.
 2. YOU HAVE NOT SHOWN ANY CATCH BASINS
 NEXT TO YOUR SITE ON EITHER
 DIRECTION.PLEASE SHOW.
 3. PLEASE SHOW PLACE FOR A DUMPSTER
 ENCLOSURE WHICH MUST MEET STANDARDS OF
 CITY OF WPB.
 4. DRAWINGS ARE NOT SEALED & SIGNED
  
 PLEASE RESPOND EACH ITEM ASKED FOR.
  
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2006-09-15 Cont ID  
Sent By rchokshi Date 2006-09-15 Time 10:54 Rev Time 0.00
Received By rchokshi Date 2006-09-15 Time 09:29 Sent To  
Notes
2006-09-15 00:00:00FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE SHOW HOW WAS EXFILTERATION
 TRENCH LENGTH DETERMINED? NEED CAL.
 CRITERIA FOR RUNOFF CAL., PLEASE SHOW
 CONTROL STRUCTURES DETAILS, ( C-4,
 CA,ETC,ON SHEET C-5) SFWMD PERMIT,
  
 2. PLEASE SHOW ALL CATCH BASINS IN
 SURROUNDING AREA OF THE SITE. PLEASE
 SHOW ROAD, SIDEWALK, PARKING LOT, FIRST
 FLOOR ELEVATION, MAKE SURE AREA DO NOT
 GET FLOODED.
  
 3. SHOW ALL WATER/SEWER MAINS,DRAINAGE
 WATER CONNECTIONS ON THE DRAWINGS.
 UTILITY (45TH STREET) MUST APPROVE
 BEFORE WE APPROVE.
  
 4. SHOW NOTES ANDSHOW DUMPSTER
 ENCLOSURE DETAILS,SIDE WALK
 DETAIL,PARKINGS, MUST MEET CITY OF WPB
 STANDARDS. ADA ETC.,
  
 PLEASE RESPOND EACH ITEMS, SEPARATELY
  
 RASIK CHOKSHI 805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status N Date 2008-06-17 Cont ID  
Sent By mawillia Date 2008-06-17 Time 16:17 Rev Time 0.00
Received By mawillia Date 2008-06-17 Time 15:58 Sent To  
Notes
2008-06-17 16:04:00*****NO REVIEW*****
  
 PLAN REVIEW FOR THE FIRE ALARM AND FIRE SPRINKLER
 AS-BUILTS CAN NOT BE CONDUCTED UNDER BUILDING PERMIT.
 ANY REVISIONS SHALL BE MADE UNDER THE APPROPIATE SUB
 PERMIT.PLEASE BE ADVISED THAT PERMIT 07051013 (FIRE
 SPRINKLER) WAS FINALED 5/29/08, AND ON 5/23/08 PERMIT
 07090086 WAS FINALED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-02-19 Cont ID  
Sent By mwennerg Date 2008-02-19 Time 15:49 Rev Time 0.00
Received By mwennerg Date 2008-02-19 Time 15:49 Sent To  
Notes
2008-02-19 15:51:15REVISION DATED 11/28/07 STAMPED SHEETS F1-01-101 AND
 F1-02-101.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-05-02 Cont ID  
Sent By mwennerg Date 2007-05-02 Time 14:12 Rev Time 0.00
Received By mwennerg Date 2007-05-02 Time 14:11 Sent To  
Notes
2007-05-02 14:17:53***PROVISO***
  
 1) IT APPEARS THAT PREVIOUS FIRE COMMENTS HAVE BEEN
 ADDRESSED.
  
 2) YOUR RESPONSE TO THE FIRST FIRE REVIEW #14 REFERS
 THIS WRITER TO ELECTRICAL COMMENTS. THE PLANS WILL BE
 STAMPED WITH THE REQUIREMENT FOR UL LISTING FOR CENTRAL
 STATION SERVICE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-02-15 Cont ID  
Sent By mwennerg Date 2007-02-15 Time 10:49 Rev Time 0.00
Received By mwennerg Date 2007-02-15 Time 10:49 Sent To  
Notes
2007-02-15 10:56:03***DENIED***
  
 1 OK
  
 2) OK
  
 3) OK
  
 4) SEE ELECTRICAL COMMENTS.
  
 5) RESPONSE INDICATES FBC. IN ADDITION, PLEASE ADD NOTE
 REFERENCING NFPA 241.
  
 6) OK
  
 7) OK
  
 8) NO SHEET FOUND IN EACH SET OF PLANS.
  
 9) OK
  
 10) OK
  
 11) OK
  
 12) OK
  
 13) OK
  
 14) FIRE COMMENTS HAVE BEEN REFERRED TO ELECTRICAL.
 PLEASE ACKNOWLEDGE AND ADD TO PLANS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 (561) 805-6722 OR 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-17 Cont ID  
Sent By mwennerg Date 2006-10-17 Time 13:57 Rev Time 0.00
Received By mwennerg Date 2006-10-17 Time 13:57 Sent To  
Notes
2006-10-17 14:25:52***DENIED***
  
 1) FIREAND SMOKE DAMPER INSTALLATIONS TO BE DROP
 TESTED PRIOR TO FINAL INSPECTION.
  
 2) FIRE DEPARTMENT CONNECTIONS SHALL BE SECURED WITH
 KNOX LOCKING CAPS.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM SYSTEMS.
  
 4) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR
 GENERATOR AND EQUIPMENT. PLEASE SUBMIT MANUFACTURER
 SPEC SHEETS.
  
 5) CONSTRUCTION, ALTERATION AND DEMOLITION SHALL COMPLY
 WITH NFPA 241.
  
 6) PLEASE PROVIDE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING.
  
 7) PLANS SHOW ACCESS TO ROOF. PLEASE PROVIDE FURTHER
 INFORMATION REGARDING THIS ARRANGEMENT.
  
 8) AN ADDRESS IS REQUIRED ON BUILDING AND SHALL BE
 MINIMUM OF 6" IN HEIGHT, 1" IN WIDTH AND CONTRASTING TO
 BACKGROUND. PLEASE SHOW ON ELEVATIONS.
  
 9) PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENT FOR
 HANDRAILS AND GUARDS.
  
 10) STAIRS TO COMPLY WITH NFPA 101, SECTION 7.2.2.2.1
 (A).
  
 11) PLEASE ILLUSTRATE FIRE RATING OF DOORS IN MINUTES.
 SHT A-800-101 (DOOR SCHEDULE).
  
 12) FIRE RATED DOORS SHALL CLOSE AND LATCH UTILIZING UL
 LISTED CLOSERS.
  
 13) FIRE PROTECTION SHEETS SHOW THE FDC AT SOUTH SIDE
 OF BUILDING AND E SHEETS SHOW THE CONNECTION AT NORTH
 SIDE OF BUILDING. PLEASE CLARIFY CORRECT LOCATION.
  
 14) FIRE ALARM SYSTEM TO BE UL CERTIFIED FOR CENTRAL
 STATION SERVICE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 29 Status N Date 2008-08-15 Cont ID  
Sent By adarroug Date 2008-08-15 Time 10:04 Rev Time 0.00
Received By adarroug Date 2008-08-15 Time 10:04 Sent To E
Notes
2008-08-15 10:05:11TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2008-08-07 Cont ID  
Sent By adarroug Date 2008-08-07 Time 09:11 Rev Time 0.00
Received By adarroug Date 2008-08-07 Time 09:11 Sent To P
Notes
2008-08-07 09:12:58TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 27 Status N Date 2008-07-11 Cont ID  
Sent By adarroug Date 2008-07-11 Time 10:54 Rev Time 0.00
Received By adarroug Date 2008-07-11 Time 10:54 Sent To E
Notes
2008-07-11 10:55:01TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2008-07-11 Cont ID  
Sent By adarroug Date 2008-07-11 Time 10:52 Rev Time 0.00
Received By adarroug Date 2008-07-11 Time 10:52 Sent To P
Notes
2008-07-11 10:52:31TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2008-06-25 Cont ID  
Sent By adarroug Date 2008-06-25 Time 10:25 Rev Time 0.00
Received By adarroug Date 2008-06-25 Time 10:25 Sent To B
Notes
2008-06-25 10:26:09TO "HMOSER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2008-06-03 Cont ID  
Sent By adarroug Date 2008-06-03 Time 12:20 Rev Time 0.00
Received By adarroug Date 2008-06-03 Time 12:20 Sent To E
Notes
2008-06-03 12:20:56TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2008-05-30 Cont ID  
Sent By adarroug Date 2008-05-30 Time 15:32 Rev Time 0.00
Received By adarroug Date 2008-05-30 Time 15:32 Sent To FIRE
Notes
2008-05-30 15:33:13TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2008-05-20 Cont ID  
Sent By adarroug Date 2008-05-20 Time 12:24 Rev Time 0.00
Received By adarroug Date 2008-05-20 Time 12:24 Sent To  
Notes
2008-05-22 13:21:47TO "COMM" BD#19
2008-05-20 12:28:03WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2008-05-16 Cont ID  
Sent By adarroug Date 2008-05-16 Time 11:11 Rev Time 0.00
Received By adarroug Date 2008-05-16 Time 11:11 Sent To E
Notes
2008-05-16 11:12:16TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2008-05-15 Cont ID  
Sent By adarroug Date 2008-05-15 Time 12:36 Rev Time 0.00
Received By adarroug Date 2008-05-15 Time 12:36 Sent To B
Notes
2008-05-15 12:36:31TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2008-04-29 Cont ID  
Sent By adarroug Date 2008-04-29 Time 10:43 Rev Time 0.00
Received By adarroug Date 2008-04-29 Time 10:43 Sent To B
Notes
2008-04-29 10:44:19TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2008-04-29 Cont ID  
Sent By adarroug Date 2008-04-29 Time 10:25 Rev Time 0.00
Received By adarroug Date 2008-04-29 Time 10:25 Sent To E
Notes
2008-04-29 10:27:36TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2008-04-18 Cont ID  
Sent By adarroug Date 2008-04-18 Time 14:16 Rev Time 0.00
Received By adarroug Date 2008-04-18 Time 14:16 Sent To B
Notes
2008-04-18 14:16:43TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2008-03-14 Cont ID  
Sent By adarroug Date 2008-03-14 Time 10:02 Rev Time 0.00
Received By adarroug Date 2008-03-14 Time 10:02 Sent To M
Notes
2008-03-14 10:02:49TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2008-02-29 Cont ID  
Sent By adarroug Date 2008-02-29 Time 08:58 Rev Time 0.00
Received By adarroug Date 2008-02-29 Time 08:58 Sent To B
Notes
2008-02-29 08:58:37TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2008-02-29 Cont ID  
Sent By adarroug Date 2008-02-29 Time 08:40 Rev Time 0.00
Received By adarroug Date 2008-02-29 Time 08:40 Sent To B
Notes
2008-02-29 08:40:50TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-02-04 Cont ID  
Sent By shill Date 2008-02-04 Time 16:55 Rev Time 0.00
Received By shill Date 2008-02-04 Time 16:55 Sent To  
Notes
2008-02-04 16:58:41TO "COMM" BD#33

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-12-12 Cont ID  
Sent By adarroug Date 2007-12-12 Time 09:24 Rev Time 0.00
Received By adarroug Date 2007-12-12 Time 09:23 Sent To B
Notes
2007-12-12 09:25:05TO "SHILL" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-11-08 Cont ID  
Sent By adarroug Date 2007-11-08 Time 09:06 Rev Time 0.00
Received By adarroug Date 2007-11-08 Time 08:37 Sent To B
Notes
2007-11-08 09:07:12TO "SHILL' DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-10-26 Cont ID  
Sent By adarroug Date 2007-10-26 Time 10:14 Rev Time 0.00
Received By adarroug Date 2007-10-26 Time 10:14 Sent To B
Notes
2007-10-26 10:14:32TO "SHILL" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-09-25 Cont ID  
Sent By adarroug Date 2007-09-25 Time 10:06 Rev Time 0.00
Received By adarroug Date 2007-09-25 Time 10:06 Sent To B
Notes
2007-09-25 10:06:21TO "SHILL' DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-09-12 Cont ID  
Sent By adarroug Date 2007-09-12 Time 16:45 Rev Time 0.00
Received By adarroug Date 2007-09-12 Time 16:44 Sent To B
Notes
2007-09-12 16:45:20TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-06-06 Cont ID  
Sent By adarroug Date 2007-06-06 Time 11:47 Rev Time 0.00
Received By adarroug Date 2007-06-06 Time 11:47 Sent To B
Notes
2007-06-06 11:48:17TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-06-06 Cont ID  
Sent By adarroug Date 2007-06-06 Time 11:36 Rev Time 0.00
Received By adarroug Date 2007-06-06 Time 11:36 Sent To E
Notes
2007-06-06 11:36:30TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-05-14 Cont ID  
Sent By adarroug Date 2007-05-14 Time 16:48 Rev Time 0.00
Received By adarroug Date 2007-05-14 Time 16:48 Sent To E
Notes
2007-05-14 16:48:25TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-04-02 Cont ID  
Sent By spalmer Date 2007-04-02 Time 17:18 Rev Time 0.00
Received By spalmer Date 2007-04-02 Time 17:18 Sent To  
Notes
2007-04-02 17:18:18TO COMM BOARD # 61 RACK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-29 Cont ID  
Sent By dpalmer Date 2007-03-29 Time 18:42 Rev Time 0.00
Received By dpalmer Date 2007-03-29 Time 18:42 Sent To  
Notes
2007-03-29 18:42:36WAITING FOR COMM BOARD.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-29 Cont ID  
Sent By adarroug Date 2006-12-29 Time 10:21 Rev Time 0.00
Received By adarroug Date 2006-12-29 Time 10:02 Sent To  
Notes
2007-01-29 08:35:37TO "COMM" BD#39
2006-12-29 10:22:02WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-17 Cont ID  
Sent By mwennerg Date 2006-10-17 Time 14:27 Rev Time 0.00
Received By mwennerg Date 2006-09-01 Time 16:39 Sent To  
Notes
2006-09-07 00:00:00TO "COMM" BD#48
2006-09-01 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2008-06-27 Cont ID  
Sent By rregueir Date 2008-06-27 Time 10:45 Rev Time 0.00
Received By rregueir Date 2008-06-27 Time 10:36 Sent To  
Notes
2008-06-27 10:37:19REVISED ENERGY CALCULATIONS

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-06-26 Cont ID  
Sent By hmoser Date 2008-06-26 Time 10:08 Rev Time 0.00
Received By hmoser Date 2008-06-26 Time 10:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-03-14 Cont ID  
Sent By tgordon Date 2008-03-14 Time 16:15 Rev Time 0.30
Received By tgordon Date 2008-03-14 Time 16:15 Sent To  
Notes
2008-03-14 16:16:40REVISION TO MECH. PLAN PAGE M1-02-101.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-02-19 Cont ID  
Sent By tgordon Date 2008-02-19 Time 11:20 Rev Time 1.30
Received By tgordon Date 2008-02-19 Time 11:20 Sent To  
Notes
2008-02-19 11:22:11REVISION TO MECH. PLANS PAGES M1-01-101, M1-02-101,
 M6-00-101, AND COOLING LOAD CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-04-26 Cont ID  
Sent By rregueir Date 2007-04-26 Time 07:51 Rev Time 0.00
Received By rregueir Date 2007-04-25 Time 19:06 Sent To  
Notes
2007-04-26 07:51:34*************PROVISO************
  
 EF-5: AIR REMOVED BY MECHANICAL EXHAUST SHALL BE
 DISCHARGED OUTDOORS (NOT INTO PARKING GARAGE) PER FBC,M
 501.2. ALSO, OPENING PROTECTIVE (FIRE DAMPER) IS
 REQUIRED AT WALL PENETRATION INTO GARAGE PER FBC,M
 607.5. REVISION REQUIRED TO SHOW THESE CORRECTIONS
 PRIOR TO ROUGH INSPECTION.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-02-12 Cont ID  
Sent By rregueir Date 2007-02-12 Time 10:58 Rev Time 0.00
Received By rregueir Date 2007-02-12 Time 10:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-16 Cont ID  
Sent By rregueir Date 2006-10-16 Time 17:01 Rev Time 0.00
Received By rregueir Date 2006-10-14 Time 11:53 Sent To  
Notes
2006-10-16 17:20:01-------------------DENIED-------------------
 1. PG.M1-02-101 SHOWS 1 HOUR RATED SHAFT WITH DUCTS TO
 FIRST FLOOR. PLEASE PROVIDE DETAIL FOR SHAFT
 TERMINATION AT 2ND FLOOR LEVEL IN COMPLIANCE WITH FBC
 707.11
  
 2. PG.M1-02-101 PENETRATIONS INTO A MEANS-OF-EGRESS
 STAIRWELL ARE PROHIBITED PER FBC 1019.1.2
  
 3. PG.M1-02-101 SHAFT ENCLOSURES PERMITTED TO BE
 PENETRATED BY DUCTS SHALL BE PROTECTED BY APPROVED FIRE
 AND SMOKE DAMPERS INSTALLED IN ACCORDANCE WITH THEIR
 LISTING PER FBC,M 607.5.5.1
  
 4. PG M1-01-101 ROOMS 121 AND EM2 SHOW FIRE DAMPERS ON
 TRANSFER OPENINGS BUT NOT AT SUPPLY DUCTS. DUCT
 PENETRATIONS IN FIRE BARRIERS SHALL BE PROTECTED WITH
 APPROVED FIRE DAMPERS IN ACCORDANCE WITH THEI RLISTING
 PER FBC,M 607.5.2
  
 5. PG.M7-00-101 DETAIL #8 FIRE DAMPERS ARE TO BE UL555
 LISTED AND INSTALLED PER MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AND LISTING PER FBC,M 607.2
  
 6. PG M1-0R-101 PLEASE SHOW MEANS OF CONDENSATE
 DISPOSAL TO BE IN COMPLIANCE WITH FBC,M 307.2.1 AND FBC
 1503.6.AUXILIARY DRAIN PROTECTION IS ALSO REQUIRED
 PER FBC,M 307.2.3
  
 7. PG.M7-00-101 ROOFTOP EQUIPMENT REQUIRES AN
 ENGINEERED SYSTEM TO SHOW COMPLIANCE WITH WIND LOAD
 REQUIREMENTS PER FBC,M 301.13. PLEASE PROVIDE DETAIL
 SHOWING ROOF-TO-CURB AND CURB-TO-EQUIPMENT ATTACHMENTS.
 NOTE: THE CITY OF WEST PALM BEACH IS IN THE 140MPH WIND
 ZONE PER FBC CHAPTER 16.
  
 8. PG.M1-01-101 SEE BUILDING PLAN REVIEW COMMENT #11
 REGARDING DUCT PENETRATIONS INTO GARAGE. THERE ARE ALSO
 TWO DUCTS PENETRATING RATED WALL AT ROOM EM1.
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop P PLUMBING
Rev No 7 Status P Date 2008-08-20 Cont ID  
Sent By kstevens Date 2008-08-20 Time 10:33 Rev Time 0.00
Received By kstevens Date 2008-08-20 Time 10:33 Sent To  
Notes
2008-08-20 10:34:23REVISIONS OK--SHTS P1-01-101 & P1-02-101

Review Stop P PLUMBING
Rev No 6 Status F Date 2008-07-23 Cont ID  
Sent By kstevens Date 2008-07-23 Time 15:10 Rev Time 0.00
Received By kstevens Date 2008-07-23 Time 15:10 Sent To  
Notes
2008-07-23 15:14:41REVISIONS DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHTS P1-01-101, P1-02-101 & P7-00-001 INDICATE
 REVISION #4 IN THE REVISION INDEX, BUT NO CLOUD OR
 REVISION NUMBER IS SHOWN. SECTION 106.1.3. PLEASE CLOUD
 ALL REVISIONS AND INDICATE REVISION NUMBER FOR EACH
 REVISION SUBMITTED.
  
 2. SHTS P1-0R-101 & P7-00-002 INDICATE REVISION #3 IN
 THE REVISION INDEX, BUT NO CLOUD OR REVISION NUMBER IS
 SHOWN. SECTION 106.1.3. PLEASE CLOUD ALL REVISIONS AND
 INDICATE REVISION NUMBER FOR EACH REVISION SUBMITTED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status F Date 2008-06-05 Cont ID  
Sent By kstevens Date 2008-06-05 Time 10:25 Rev Time 0.00
Received By kstevens Date 2008-06-05 Time 10:25 Sent To  
Notes
2008-06-05 10:44:26DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS P1-01-101 & P1-02-101 HAVE BEEN SUBMITTED AS
 PHOTO COPIES AND WITH HAND DRAWN CHANGES TO ORIGINAL
 SIGNED, SEALED, DATED PLANS. ALL CHANGES TO SIGNED,
 SEALED & DATED PLANS SHALL BE SUBMITTED AS NEW
 REVISIONS, CLOUDED AND INDICATED WITH A REVISION NUMBER
 AND SHALL BE SIGNED, SEALED AND DATED BY THE ENGINEER
 OF RECORD. SECTION 106.1, FAC 61G15-23.002(2) & FS
 471.025.
  
 2. ALL CHANGES TO THE PLUMBING SANITARY, WATER, STORM,
 CONDENSATE, OR GAS SYSTEMS SHALL BE REFLECTED WITH
 REVISIONS TO THE ISOMETRIC RISER DIAGRAMS OF EACH
 SYSTEM THAT IS REVISED. SECTION 106.3.5.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-03-03 Cont ID  
Sent By kstevens Date 2008-03-03 Time 15:35 Rev Time 0.00
Received By kstevens Date 2008-03-03 Time 15:35 Sent To  
Notes
2008-03-03 15:36:28REVISIONS APPROVED. SHTS P1-OR-101, P1-01-101,
 P1-02-101, P7-00-001

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-05-09 Cont ID  
Sent By kstevens Date 2007-05-09 Time 14:15 Rev Time 0.00
Received By kstevens Date 2007-05-09 Time 14:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-02-07 Cont ID  
Sent By kstevens Date 2007-02-07 Time 09:29 Rev Time 0.00
Received By kstevens Date 2007-02-06 Time 09:16 Sent To  
Notes
2007-02-07 10:22:54DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. DELETED
 2. OK
 3. OK
 4. OK
 5. OK
 6. DELETED
 7. OK
  
 8. SHT A7-01-101 ELEVATION 1 KITCHEN
 SINK TO COMPLY WITH SECTION 11-4.24 AND
 ALL SUBSECTIONS. SHOW ON DETAIL.
 ****RESPONSE NOTED, INFORMATION STILL REQUIRED. SHOW
 COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE - FORWARD APPROACH
 REQUIRED. SHOW ON THE FLOOR PLAN OF SHT A9-03-101 TO
 SEE IF FURNITURE WILL CONFLICT WITH THE CLEAR FLOOR
 SPACE.
 E. 11-4.24.7 FAUCETS.
  
 9.OK
 10. OK
  
 11. SHT A7-02-101 ELEVATION 13, STAFF
 SINK SHALL COMPLY WITH SECTION 11-4.24
 AND ALL SUBSECTIONS. SUBMIT INFORMATION
 ON DETAIL.
 ****RESPONSE NOTED, BUT SUCH INFORMATION SHALL BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. SHOW COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE - FORWARD APPROACH
 REQUIRED. SHOW ON THE FLOOR PLAN OF SHT A9-03-101 TO
 SEE IF FURNITURE WILL CONFLICT WITH THE CLEAR FLOOR
 SPACE.
 D. 11-4.24.7 FAUCETS.
  
 12. SHTS A9-01-201 & AP-02-201 ROOMS
 108, 126, 127, 205, 206, 214. TOILET
 ROOM FLOORS & WALLS SHALL BE SMOOTH,
 HARD AND NONABSORBENT PER SECTIONS
 1210.1 & 1210.2. THE BASE IS INDICATED
 AS T2 WHICH IS NOT SHOWN UNDER THE BASE INFORMATION,
 BUT AS "TBD" UNDER THE
 FLOOR INFORMATION. WALLS ARE INDICATED
 AS P5 OR P6. PLEASE SUBMIT INFORMATION
 SHOWING HOW A PAINTED WALL CAN COMPLY
 WITH REQUIREMENTS OF "HARD &
 NONABSORBENT". SHOW BASE MATERIAL.
 ****RESPONSE NOTED, BUT ROOM 108 STILL SHOWS PAINT ON
 THE EAST WALL. SECTION 1210.2 STATES "WALLS WITHIN 2'
 OF URINALS AND WATER CLOSETS".--THE FINISH SCHEDULE
 DOES NOT SHOW T1 IN THE BASE INFORMATION, NOR DOES IT
 SHOW T1/T3 IN THE WALL INFORMATION.--ROOM 205 SHOWS
 T1/T3 ON THE NORTH & SOUTH WALLS, BUT IT IS REQUIRED ON
 THE SOUTH, EAST, & WEST WALLS.--ROOM 206 SHOWS
 T1/T3 ON THE NORTH & SOUTH WALLS, BUT IT IS REQUIRED ON
 THE NORTH, EAST & WEST WALLS.--ROOM 214 SHOWS T1/T3
 ON THE EAST WALL ONLY, BUT IT IS ALSO REQUIRED ON THE
 SOUTH WALL. PLEASE INDICATE THE REQUIRED FINISH ON THE
 REQUIRED WALLS.--PLEASE UPDATE THE FINISH SCHEDULES
 TO INCLUDE THE FINISH SHOWN ON THE BASE & WALLS.
  
 13. OK
 14. OK
 15. OK
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
  
 **************NEW COMMENT*************
  
 1B. SHT P1-01-101 INDICATES A SHOWER TRAP IN THE
 CEILING OF THE ELECTRIC METER ROOM. THIS IS NOT
 APPROVED PER NFPA 70 SECTION 110.26.--THIS SHEET
 ALSO INDICATES A DRAIN PAN UNDER THE PIPING DISCHARGING
 TO THE GARAGE. THIS WILL BE WASTE WATER AND CAN NOT
 DRAIN TO THE GARAGE. ALL PLUMBING FIXTURES, DRAINS,
 APPURTENANCES AND APPLIANCES USED TO RECEIVE OR
 DISCHARGE LIQUID WASTES OR SEWAGE SHALL BE DIRECTLY
 CONNCETED TO THE SANITARY DRAINAGE SYSTEM. SECTION
 301.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-09-11 Cont ID  
Sent By kstevens Date 2006-09-11 Time 18:22 Rev Time 0.00
Received By kstevens Date 2006-09-09 Time 15:28 Sent To  
Notes
2006-09-11 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL CIVIL SHEETS, THE BUSINESS NUMBER (CERTIFICATE
 OF AUTHORIZATION) IS
 REQUIRED IN THE TITLE BLOCK ON EACH
 SHEET. FAC 61G1-16.004(2), FAC
 61G15-23.002(2), FS 481.219. & FS
 481.2055. BOTH CA#'S ARE REQIRED FOR THE ENGINEERING
 AND THE SURVEYO PORTION OF
 THE BUSINESS IN THE TITLE BLOCK PER
 DBPR.
  
 2. ALL ARCHITECTURAL SHEETS. THE TITLE
 BLOCK SHALL SHOW THE DATE PREPARED,
 DATED SEAL, PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT.
 61G1-16.004(4)(5)(6) & FS 481.2055.
  
 3. SHT A0-00-001 THE FOLLOWING
 INFORMATION IS REQUIRED TO SHOW
 COMPLIANCE WITH ACCABILITY REQUIREMENTS:
 A. 11-4.18.2 HEIGHT (SHOWS 19")
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.19.5 FAUCETS (LAV)
  
 4. SHT A0-01-301 DEMO KEY NOTES #3.
 INDICATE THAT DEAD ENDS ARE PROHIBITED
 PER SECTION 704.5.
  
 5. SHT A1-0R-001 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS. SHOW THE SQUARE FOOTAGE
 BEING DRAINED BY EACH ROOF DRAIN.
 CALCULATIONS SHALL SHOW ROOF AREA PLUS
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS, ALONG WITH ALL AREAS OF ROOF
 THAT DRAIN ONTO THE ROOF FROM ABOVE.
  
 6. SHT A2-02-001 DETAIL #4 SHOWS THE
 COUNTERTOP AT 36". MAX 34" TO SINK PER
 11-4.24.2.
  
 7. SHT A5-00-103 DETAIL #7 OVERFLOW
 SCUPPERS TO BE 2" TO 4" ABOVE THE ROOF
 TO THE FLOW LINE. (SHOW AS EVEN WITH
 ROOF). ALSO THE MINIMUM HEIGHT IS 4".
 (SHOWN AS 3"). SECTION 1503.4.3 AND
 SECTION 1107.3.
  
 8. SHT A7-01-101 ELEVATION 1 KITCHEN
 SINK TO COMPLY WITH SECTION 11-4.24 AND
 ALL SUBSECTIONS. SHOW ON DETAIL.
  
 9. SHT A7-01-101 ELEVATIONS 7, 13, 17.
 FLUSH CONTROLS TO BE LOCATED ON THE WIDE
 SIDE TO THE W/C TANK. SECTION 11-4.16.5.
  
 10. SHT A7-02-101 ELEVATIONS 2, 8 , 11
 FLUSH CONTROLS SHALL BE LOCATED ON THE
 WIDE SIDE OF THE W/C TANK. SECTION
 11-4.16.5.
  
 11. SHT A7-02-101 ELEVATION 13, STAFF
 SINK SHALL COMPLY WITH SECTION 11-4.24
 AND ALL SUBSECTIONS. SUBMIT INFORMATION
 ON DETAIL.
  
 12. SHTS A9-01-201 & AP-02-201 ROOMS
 108, 126, 127, 205, 206, 214. TOILET
 ROOM FLOORS & WALLS SHALL BE SMOOTH,
 HARD AND NONABSORBENT PER SECTIONS
 1210.1 & 1210.2. THE BASE IS INDICATED
 AS T2 WHICH IS NOT SHOWN UNDER THE BASE INFORMATION,
 BUT AS "TBD" UNDER THE
 FLOOR INFORMATION. WALLS ARE INDICATED
 AS P5 OR P6. PLEASE SUBMIT INFORMATION
 SHOWING HOW A PAINTED WALL CAN COMPLY
 WITH REQUIREMENTS OF "HARD &
 NONABSORBENT". SHOW BASE MATERIAL.
  
 13. SHTP1-01-101 ELEVATOR SUMP PUMPS.
 PLUMBING SYSTEMS SHALL NOT BE LOCATED IN
 AN ELEVATOR SHAFT, OR IN AN ELEVATOR
 EQUIPMENT ROOM. SECTION 301.6. OIL FROM
 THE ELEVATOR SHAFT SHALL NOT BE
 DEPOSITED INTO THE SEWER SYSTEM. SECTION
 302.1. THIS IS CONSIDERED HAZARDOUS
 MATERIAL AND SHALL BE CONTAINED AND
 RECYCLED.
  
 14. SHT P1-01-101 DEAD ENDS ARE
 PROHIBITED PER SECTION 704.5. ALL
 SANITARY PIPING SHALL BE DEMO'D AT THE
 MAIN LINE. ALL CAPPED PIPING SHALL BE
 INSPECTED PRIOR TO COVERING.
  
 15. SHT P1-01-101 INDICATE WHAT "SW"
 FIXTURE IS. DESIGNATION NOT SHOWN ON THE
 PLUMBING CONNECTION FIXTURE SCHEDULE.
  
 16. SHT P7-00-001 SUBMIT THE SANITARY
 RISER DIAGRAM IN ISOMETRIC FORM THAT
 REFLECTS THE FLOOR PLAN. SHOW ALL DFU'S
 AS THEY ACCUMULATE IN THE SYSTEM.
 SECTIONS 106.1.1 AND 106.3.5.1.3. (SEE
 ATTACHED SHEET FOR AN EXAMPLE OF A
 PORTION OF THE SANT. RISER ISOMETRIC
 DIAGRAM THAT REFLECTS THE FLOOR PLAN).
 RISER DIAGRAMS AS DRAWN ARE NOT
 ACCEPTABLE AND DO NOT REFLECT THE FLOOR
 PLAN.
  
 17. SHT P7-00-001 W/C NOT VENTED AS
 DRAWN. (TOILET ROOM BY OFFICE ROOM 107).
 (SEE ATTACHED EXAMPLE OF ISOMETRIC FOR
 CORRECT VENTING OF W/C).
  
 18. SHT P7-00-002 DETAIL #2 WATER HEATER
 PAN REQUIRES A PAN DRAIN. SECTION
 504.7.1.
  
 19. SHT P7-00-002 DETAIL #3 SUBMIT
 MANUF. SPECIFICATION SHEETS FOR TANKLESS
 WATER HEATER. MUST SHOW LISTING. SECTION
 303.4.
  
 20 ALL PME SHEETS ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME, ADDRESS,
 AND LICENSE NUMBER ON EACH SHEET. SEAL
 HAS NOT BEEN DATED (WHEN SEAL IS AFFIXED
 TO PLANS), NOR IS THE PRINTED NAME OF
 THE ENGINEER INDICATED. FAC
 61G15-23.002(2) AND FS 471.025.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2007-04-17 Cont ID  
Sent By lfranco Date 2007-04-17 Time 18:41 Rev Time 0.00
Received By lfranco Date 2007-04-16 Time 11:23 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2007-02-06 Cont ID  
Sent By lfranco Date 2007-02-06 Time 15:15 Rev Time 0.00
Received By lfranco Date 2007-02-06 Time 15:42 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-10-12 Cont ID  
Sent By eschneid Date 2006-10-12 Time 19:26 Rev Time 0.00
Received By LFRANCO Date 2006-10-12 Time 19:26 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy