Plan Review Details - Permit 06082098
Plan Review Stops For Permit 06082098
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-10-06 Cont ID  
Sent By alange Date 2006-10-06 Time 14:30 Rev Time 0.00
Received By alange Date 2006-10-06 Time 14:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-10-04 Cont ID  
Sent By alange Date 2006-10-04 Time 10:26 Rev Time 0.50
Received By alange Date 2006-10-04 Time 10:26 Sent To  
Notes
2006-10-04 00:00:00DENIED
  
 1.SUBMIT TWO ORIGINAL COPIES OF ROOF
 FASTENING CALCULATIONS.ONLY ONE
 SUBMITTED.
  
 2.CERTIFICATE OFAUTHORIZATION NUMBER
 REQUIRED FOR OKEECHOBEE ARCHITECTS
 COLLABORATIVE, INC.FS 481.221 (8)
  
 3.PRESSURES ARE THE SAME FOR PERIMETER
 AND CORNER ZONES YET THE FASTENING IS
 DIFFERENT.
 PLEASE VERIFY AND SUBMIT WITH
 CALCULATIONS AS REQUIRED PER LIMITATION
 NUMBER 7.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-25 Cont ID  
Sent By alange Date 2006-09-25 Time 10:39 Rev Time 0.33
Received By alange Date 2006-09-25 Time 10:39 Sent To  
Notes
2006-09-25 00:00:00DENIED
  
 1.SEE GENERAL LIMITATION NUMBER 7 FOR
 JOHNS MANVILLE CORP. BITUMEN ROOF.
 ROOF ENHANCED FASTENING CALCULATIONS
 REQUIRED.
  
 2.PRODUCT APPROVALS SUBMITTED WITH
 PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-31 Cont ID  
Sent By alange Date 2006-08-31 Time 09:40 Rev Time 0.50
Received By alange Date 2006-08-31 Time 09:40 Sent To  
Notes
2006-08-31 00:00:00DENIED
  
 1.SELECT THE ROOF ASSEMBLY USED FOR
 THE JOHNS MANVILLE BITUMEN ROOF.MARK
 ON PRODUCT APPROVAL.
  
 2.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR JOHNS MANVILLE BITUMEN
 ROOF.
 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672