Plan Review Details - Permit 06082089
Plan Review Stops For Permit 06082089
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-09-11 Cont ID  
Sent By lursu Date 2006-09-11 Time 11:51 Rev Time 0.00
Received By lursu Date 2006-09-11 Time 11:51 Sent To I
Notes
2006-09-11 00:00:00ATTACH PERMIT TO EXT #0015 FOR THIS UNIT
 240

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-04-12 Cont ID  
Sent By shill Date 2007-04-12 Time 17:37 Rev Time 0.00
Received By shill Date 2007-04-12 Time 17:37 Sent To  
Notes
2007-04-12 17:37:50REVISION DATED 4/9
 SHEETS A1.1, 3.1, 4.2,5.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-04-02 Cont ID  
Sent By shill Date 2007-04-02 Time 16:00 Rev Time 0.00
Received By shill Date 2007-04-02 Time 16:00 Sent To  
Notes
2007-04-02 16:10:10****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA
  
 1.)THE PLANTATION SHUTTER DOORS AT THE PRIVATE DINING
 AREA DO NOT COMPLY WITH FBC11-4.13,FBC1008.1.2.
  
 2.)A4.2, RAMP HANDRAIL IS TO COMPLY WITH
 FBC11-4.8.5(2).H6 SHOWS 1'1" EXTENSION AT THE TOP.
  
 3.)SEE C6-A4.2, FBC11-4.8.5(6).COMPLIANCE IS NOT
 CLEAR; PROVIDE A DETAIL.ALSO SEE FBC11 FIGURE 17.
  
 4.)POS, A1.1, PROVIDE A DETAIL.SEE FBC11-7.2.
  
 5.)N/A (REMOVED)
  
 6.)FBC11-4.8.4(2), SHOW THE DIMENSION OF THE LANDING
 AT THE TOP OF THE RAMP.
  
 7.)A1.1, C7-A3.1, THESE DINING AREAS ON THE RAISED
 PLATFORM ARE NOT ACCESSIBLE, FBC11-5.1,
 FBC11-4.1.2(2).
  
 8.)WHAT IS AT COLUMN LINE BETWEEN B-8, B8.1?THIS
 APPEARS TO BE A RAMP WITH NONCOMPLIANT RAILINGS.SEE
 FBC11-4.1.2(2).PROVIDE DETAILS FOR THE RAMP,
 HANDRAILS.
  
 9.)A5.1, SHOW MANEUVERING CLEARANCE FOR THE DOOR AT
 THE KITCHEN.AS THE DOORS ARE NOT LABELED, AND THERE
 AREN'T ANY CROSS COLUMN LINES IN THIS AREA, IT IS
 DIFFICULT TO DESCRIBE WHICH DOOR THIS CORRECTION
 APPLIES TO SO TO AVOID CONFUSION PLEASE SHOW FOR ALL.
 NOTE THAT A1.1 SHOWS THIS AREA AS CLEAR, A5.1 SHOWS
 THIS AREA OBSTRUCTED WITH SQUARES.WHAT IS THIS?
  
 10.)SEE FBC11-4.32, AND FBC11-5.1-11-5.3, FBC11
 FIGURE 46.SHOW COMPLIANCE ON THE PLAN; NO
 ACCESSIBLITITY DETAILS, PATH, ETC. WERE PROVIDED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-12-07 Cont ID  
Sent By shill Date 2006-12-07 Time 09:21 Rev Time 0.00
Received By shill Date 2006-12-07 Time 09:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-04 Cont ID  
Sent By shill Date 2006-10-04 Time 14:51 Rev Time 0.00
Received By shill Date 2006-10-04 Time 11:46 Sent To  
Notes
2006-10-04 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)DECLARE LEVEL OF ALTERATION, FBC EB
 CHAPTER 3.
  
 2.)PROVIDE VALUATION OF THIS PROJECT
 ON THE PERMIT APPLICATION.
  
 3.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS,
 FS713.13.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-06-21 Cont ID  
Sent By dpalmer Date 2007-06-21 Time 17:34 Rev Time 0.00
Received By dpalmer Date 2007-06-21 Time 17:17 Sent To PC
Notes
2007-06-21 17:36:56REVISED LOADS CALCULATIONS.
 ENGINEER WAS INFORMED THAT THE INCREASED LOADS FROM
 ORIGINAL DESIGN WAS VERY CLOSE BY LESS THAN 1KVA TO MAX
 LOAD ON TRANSFORMER HOWEVER IT DOES APPEAR TOMEET THE
 "MINIMUM CODE".

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-05-17 Cont ID  
Sent By dpalmer Date 2007-05-17 Time 16:47 Rev Time 0.00
Received By dpalmer Date 2007-05-17 Time 15:46 Sent To PC
Notes
2007-05-17 16:47:59** UNSAT **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE GO OVER LOAD CALCULATIONS ON SHEET AND
 LOADS ON PANELS AS THESE DO NOT CORRELATE.
 PLEASE COORDINATE THESE LOADS AND VERIFY THE LOAD ON
 THE TRANSFORMER AS IT SEEM TO BE NOW SHOWN RIGHT AT ITS
 MAXIMUM RATING WITHOUT ANY ROOM FOR EXPANSION. PLEASE
 SEE LOADS AS SHOWN ON THIS DOES NOT LEAVE ROOM FOR THE
 ADDITION OF ONE CIRCUIT OR ANY LOAD AS REQUIRED PER
 90.8.
 PLEASE SEE 220 AND GO OVER ALL LOAD CALCULATIONS PER
 NEC AND COORDINATE.
  
 2) NOTE: PLEASE SEE THE VALUE FROM THE ORIGINAL APPLIED
 SCOPE OF WORK HAS SUBSTANTIALLY INCREASED AND FEES ARE
 DUE FOR INCREASED CONTRACT VALUE PER FBC 108.3
 THIS VALUE INCREASE IS BASED ON THE LAST SET OF
 BUILDING REVISIONS WHICH INCREASED SCOPE OF WORK.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-02-21 Cont ID  
Sent By dpalmer Date 2007-02-21 Time 19:11 Rev Time 0.00
Received By dpalmer Date 2007-02-21 Time 19:04 Sent To I
Notes
2007-03-01 17:34:30PROCESSED PLANS .
2007-02-21 19:10:57REMOVED FROM INCOMING. IN ELECTRIC FOR REVIEW, PLANS
 ARE TO BE ROUTED BACK TO INCOMING WHEN COMPLETED.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-01-13 Cont ID  
Sent By dpalmer Date 2007-01-13 Time 20:08 Rev Time 0.00
Received By dpalmer Date 2007-01-13 Time 18:35 Sent To  
Notes
2007-01-13 20:08:12*** UNSAT 3RD REVIEW ***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW(S) WHICH
 STILL NEED TO BE ADDRESSED.
 PLEASE SEE THE RESPONSE LETTER MENTIONS: "WILL COMPLY
 AND SEE REVISED SHEETS", HOWEVER COMPLIANCE HAS NOT
 BEEN DONE AND ELECTRICAL PLANS AND RISER FOR SERVICE
 HAVE NOW BEEN COMPLETELY CHANGED FROM THE PREVIOUS
 SUBMITTED PLANS.
 PLEASE SEE THERE ARE ALSO SOME NEW COMMENTS BASED ON
 THE REVISED RISER DIAGRAM AND PANEL SCHEDULES
 SUBMITTED.
  
  
 1) NOTE: PLEASE SEE THE SERVICE HAS NOW BEEN COMPLETELY
 BEEN REVISED. PLEASE SEE RISER NO SHOWS H1A AS A 400AMP
 PANEL. PLEASE KNOW THAT THE LOAD CALCULATIONS FOR
 SERVICE HAVE NOT YET BEEN UPDATED THROUGH-OUT THE
 SERVICE PROVIDED TO THE SPACE. PLEASE SEE "H1A" WHICH
 FEEDS ALL OTHER PANELS. PLEASE SEE THAT THERE ARE LOADS
 ON THIS PANEL WHICH ARE BLANK WITH ZERO LOADS SHOWN??
 HOW IS IT POSSIBLE THAT NO RECEPTACLE LOADS ARE PRESENT
 ON H1A, OR LOADS FOR LIGHTING ETC?
 PLEASE SEE PANEL SCHEDULE K-1 WHICH IS STILL NOT
 COMPLETE WITH THE LOAD CALCULATIONS AND SECTIONS ARE
 BLANK. PLEASE SEE OTHER LOADS THAT ARE SHOWN ON THE
 BOTTOM OF THE SCHEDULE FOR MANY ITEMS WHICHDO NOT
 CORRELATE WITH THE LOADS SHOWN AT THE RIGHT HAND SIDE
 OF THE SHEET WHICH STATE THEY ARE FOR K-1. ??
 SOME OF THIS VERBIAGE IS TAKEN FROM THE PREVIOUS REVIEW
 AS THE SAME COMMENT EXISTS.
 PLEASE UPDATE AS REQUESTED ON PREVIOUS REVIEW. WHEN
 ADDING OR INCREASING LOAD TO SERVICE, THIS WOULD AFFECT
 THE LOAD OF THE ENTIRE SERVICE WHICH IS EXISTING. 220,
 220.3, 220.10, 220.11, 220.13, CONTINUOUS LOADS PER
 215.3, 230.42
 FBC ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF
 WEST PALM BEACH, SECTIONS, 106.1.2, 106.3.5.1.2
  
 2) NOTE: PLEASE SEE NOW WITH THE NEW RISER BEING SHOWN;
 PLEASE CONFIRM THE 112.5 KVA TRANSFORMER BEING FED WITH
 A 200AMP BREAKER. PLEASE SEE 450.3 AS THE MAXIMUM OVER
 CURRENT PROTECTION SHALL BE SIZED AT 125%. PLEASE KNOW
 THAT ONLY IF MEETING THE EXCEPTION #3 WOULD A HIGHER
 OVER CURRENT PROTECTION BE PERMITTED. PLEASE SEE THAT
 THE MAXIMUM OCP SHOULD BE 175AMPS.IF MEETING THE
 EXCEPTION, PLEASE IDENTIFY THE TRANSFORMER WITH THE
 REQUIRED DETAILS FOR MEETING THIS.
  
 3) NOTE: PLEASE KNOW THAT DUE TO THE NUMBER OF CHANGES
 WHICH HAVE BEEN MADE TO THIS SERVICE AND INFORMATION
 SHOWN AND NOT SHOWN, PLEASE SUBMIT ALL FEEDERS ON
 RISER. PLEASE SHOW THE CONDUCTORS FROM THE PANEL H1A TO
 THE TRANSFORMER AND THE CONDUCTORS FROM THE TRANSFORMER
 TO THE PANEL K-1. PLEASE INCLUDE ALL CONDUCTOR SIZES
 FOR ALL NEW BRANCH CIRCUITS.
 240.4, 310.16, 240.21, 215.5, 215.3 ETC
 FBC 106.3.5.1.2, 106.1.2 ETC
  
 4) NOTE: PLEASE SEE NO DETAIL IS YET SHOWN FOR THE OC
 SENSOR DEVICE WHICH IS BEING SHOWN ON PLANS. THE ONLY
 MENTIONS IS THAT IS SHALL TURN OFF WITHIN 30MINS AFTER
 THE LAST SENSING OF THE OCCUPANT.
 PLEASE SEE THAT DUE TO THE CIRCUITS ON PLANS BEING
 SHOWN AND THE LOADS AS SHOWN, THE AMOUNT OF DEVICES AS
 SHOWN DO NOT APPEAR TO BE ABLE TO DO AS STATED. PLEASE
 SEE NO SPECIFIC ELECTRICAL DETAIL HAS BEEN SUBMITTED
 SHOWING IF NEW POWER PACKS ARE BEING INSTALLED? ARE
 THESE ARE 120V UNITS? MOTION, HEAT, ULTRASONIC? PLEASE
 KNOW ADDING NOTES ON PLANS IN LIEU OF SPECIFIC DETAIL
 AS REQUIRED FOR CODE COMPLIANCE IS NOT PERMITTED.
 PLEASE PROVIDE A DETAIL FOR THE "SYSTEM" WHICH IS BEING
 PROPOSED. PLEASE INDICATE THE TIMES, AND MAXIMUM
 OVER-RIDES TIME
 IF THE INTENT IS MEETING FBC CHAPTER 13, PLEASE SEE
 13-415.1.ABC.1.1, .1.2, .1.3
  
 5) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO THE DESIGN PROFESSIONAL(S) AND REPEAT
 COMMENTS FOR CODE COMPLIANCE. PLEASE SEE THAT A 4X FEE
 FOR THE PLAN REVIEW PORTION OF THE BASE PERMIT FEE HAS
 NOW BEEN ASSESSED DUE TO REPEAT COMMENTS FOR CODE
 COMPLIANCE. THIS FEE OF $2,388 WILL BE DUE BEFORE PLANS
 ARE RESUBMITTED FOR REVIEW. PLEASE SEE THE ATTACHED
 SECTION WHICH IS TAKEN DIRECTLY FROM THE FLORIDA
 STATUTES.
  
 "(B)WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS' DOCUMENTS, IF A LOCAL GOVERNMENT FINDS
 IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW".
  
 PLEASE KNOW THAT AT THIS TIME ONE COPY OF ALL THREE
 SETS OF ELECTRICAL PLANS ARE NOW BEING RETAINED BY THIS
 OFFICE FOR POSSIBLE PIER REVIEW FROM THE FLORIDA BOARD
 OF PROFESSIONAL ENGINEERS.
 ** IF ANY PORTION OF THESE COMMENTS IS NOT UNDERSTOOD
 OR THERE ARE COMMENTS ON THIS REVIEW, IT IS IMPERATIVE
 TO CONTACT THIS OFFICE TO GO OVER COMMENTS. THISMAY
 HELP TO ALLEVIATE SUCH ACTIONS.
  
  
 ** PLEASE KNOW AT THIS TIME A COMPLETE REVIEW FOR CODE
 COMPLIANCE CAN NOT BE DONE DUE TO INFORMATION MISSING
 AND/OR INFORMATION WHICH HAS REPEATEDLY CHANGED FROM
 EACH REVISED SET OF PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-11-16 Cont ID  
Sent By dpalmer Date 2006-11-16 Time 10:37 Rev Time 0.00
Received By dpalmer Date 2006-11-16 Time 08:47 Sent To  
Notes
2006-11-16 10:43:33*** UNSAT 2ND REVIEW ***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH
 STILL NEEDS TO BE ADDRESSED.
  
 1) NOTE: PLEASE SEE LOAD CALCULATIONS FOR SERVICE HAS
 NOT YET BEEN UPDATED THROUGH-OUT THE SERVICE PROVIDED
 TO THE SPACE. PLEASE SEE "H1A" WHICH FEEDS ALL OTHER
 PANELS. PLEASE SEE THE LOADS ON THIS PANEL ARE BLANK
 WITH ZERO LOADS SHOWN??
 PLEASE UPDATE AS REQUESTED ON PREVIOUS REVIEW. WHEN
 ADDING OR INCREASING LOAD TO SERVICE, THIS WOULD AFFECT
 THE LOAD OF THE ENTIRE SERVICE WHICH IS EXISTING.
 220.3, 220.10, 220.11, 220.13, CONTINUOUS LOADS PER
 215.3, 230.42
 FBC ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF
 WEST PALM BEACH, SECTIONS, 106.1.2, 106.3.5.1.2
  
 2) NOTE: PLEASE SEE THE RESPONSE ON LIGHTING CONTROLS
 FOR DINING AREA WAS DONE BY ADDING A NOTE ON PLANS FOR
 A TIMER AND AUTO-SHUT REQUIRED.
 PLEASE KNOW ADDING NOTES ON PLANS IN LIEU OF SPECIFIC
 DETAIL AS REQUIRED FOR CODE COMPLIANCE IS NOT
 PERMITTED.
 PLEASE PROVIDE A DETAIL FOR THE "SYSTEM" WHICH IS BEING
 PROPOSED. PLEASE INDICATE THE TIMES,AND MAXIMUM
 OVER-RIDES TIME
 IF THE INTENT IS MEETING FBC CHAPTER 13, PLEASE SEE
 13-415.1.ABC.1.1, .1.2, .1.3
  
 3) NOTE: PLEASE SEE POSSIBLE MISPRINT WHEN ADDING THE
 RELEVANT CODE ON SHEET G1.1.
 PLEASE SEE NFPA-72 IS BEING REFERENCED AS THE NATIONAL
 ELECTRICAL CODE, WHEN 72 IS ACTUALLY THE NATION FIRE
 ALARM CODE.(.2002)
 THIS COULD HAVE BEEN RED-LINED; HOWEVER PLANS ARE
 COMING BACK FOR CORRECTIONS.
  
 4) NOTE: PLEASE SEE RESPONSE LETTER FROM DESIGN TEAM
 FOR MEP'S REFLECT OCI AND ASSOCIATES, YET PLANS DO NOT
 CONTAIN ANY TITLE BLOCKS FOR OCI??
 THIS ONLY IN QUESTION AT THIS TIME AND PLANS MAY BE
 DIRECTLY DONE AS LISTED BY THE SOLE ENGINEER OF
 RECORD.
  
 FAC 61G15-23.002/ FS 471.023
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. **IF
 THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF THE
 NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE DO
 NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-10 Cont ID  
Sent By dpalmer Date 2006-09-10 Time 20:13 Rev Time 0.00
Received By dpalmer Date 2006-09-10 Time 19:51 Sent To  
Notes
2006-09-10 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE BE SURE THE PERMIT
 APPLICATION CONTAINS THE APPLIED VALUW
 WHICH IS REQUIRED TO BE FILLED OUT BY
 THE CONTRACTOR. PLEASE SEE THAT THE
 RELEVANT SQ FOOTAGE SHOULD ALSO BE
 STATED ON APPLICATION.
  
 2) NOTE: PLEASE SEE THE FOLLOWING
 RELEVANT CODE BE PLACED ONELECTRICAL
 PLANS.
 2002 NFPA-70(NEC ALREADY ON A-COVER
 SHEET), 2002 NFPA-72 AND 2003 NFPA-101
  
 3) NOTE: PLEASE VERIFY THE LOAD AS SHOWN
 ON PANEL LP, PLEASE SEE LOAD SEEMS TO BE
 RIGHT ON THE BORDER OVER OVER LOADING
 THE PANEL FEEDER AND NO ROOM FOR ANY
 FUTURE EXPANSION IS PRESENT. PLEASE SEE
 90.8, AS THE LOADS HAVE BEEN INCREASED
 AND THE FEEDER NEEDS TO BE INCREASED
 FROM K-2.
 215.5,310.16,240.4
  
 4) NOTE: PLEASE SEE NEW ELECTRICAL ITEMS
 HAVE BEEN INCLUDED ON EXISTING PANELS,
 HOWEVER COMPLETED UPDATED LOAD
 CALCULATIONS NEED TO BE DONE.
 PLEASE SEE KITCHEN PANEL NEEDS TO
 INCLUDE NEW AND EXISTING LOADS ALONG
 WITH K-2.
 220, 215.5
 FBC 106.1.2
  
 5) NOTE: PLEASE CLARIFY LIGTING CONTROLS
 PER 13-415.1.ABC.1.1 FORNEW DINING ARE
 LIGHTING.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-04-12 Cont ID  
Sent By mawillia Date 2007-04-12 Time 10:35 Rev Time 0.00
Received By mawillia Date 2007-04-12 Time 10:32 Sent To  
Notes
2007-04-12 10:35:26*****APPROVED*****
  
  
  
 REVIEWED REVISED PLAN SHEETS A1.1, A3.1, A4.2,AND A5.1;
 NO FIRE STAMPING NEEDED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-02-27 Cont ID  
Sent By mawillia Date 2007-02-27 Time 18:13 Rev Time 0.00
Received By mawillia Date 2007-02-27 Time 18:13 Sent To  
Notes
2007-02-27 18:31:28*****APPROVED*****
  
  
 ALL PREVIOUS FIRE PLAN REVIEW COMMENTS HAVE BEEN
 ADDRESSED.. PLAN SHEETS LS1.1, F1.1, E1.1, AND E1.2 WER
 STAMPED, INITIALED, AND DATED

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-02-06 Cont ID  
Sent By mawillia Date 2007-02-06 Time 16:39 Rev Time 0.00
Received By mawillia Date 2007-02-06 Time 16:39 Sent To  
Notes
2007-02-06 17:57:41*****UNSAT******
  
 RESPONSES TO THE PREVIOUS FIRE PLAN REVIEW OF 12/01/06
 RECEIVED AS FOLLOWS:
  
  
 2.) STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.NFPA 241 WAS ADDED TO THE
 SHEET G1.1 UNDER APPLICABLE CODES, HOWEVER IT IS NOT A
 LIFE SAFETY CODE
  
 3.) ACCUMULATIONS OF COMBUSTIBLE WASTE
 MATERIALS, DUST, AND DEBRIS SHALL BE
 REMOVED FROM THE STRUCTURE AND ITS
 IMMEDIATE VICINITY AT THE END OF EACH
 SHIFT OR MORE FREQUENTLY AS NECESSARY
 FOR SAFE OPERATIONS.YOUR RESPONSE TO MY COMMENT WAS
 "SHALL INSTRUCT CONTRACTOR TO COMPLY."BETTER YET, ADD
 IT TO THE PLAN
  
 *****REMINDER******
  
 IN REFERENCE TO ADDRESS SIGNAGE (SEE SHEET LS1.1)
 NUMERALS SHALL NOT BE LESS THAN 6 INCHES IN HEIGHT AND
 NO LESS THAN 1 INCH IN WIDTH
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCL;UDE A
 RESPONSE LETTER INDICATING HOW/WHERE EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-12-01 Cont ID  
Sent By mawillia Date 2006-12-01 Time 11:13 Rev Time 0.00
Received By mawillia Date 2006-12-01 Time 11:13 Sent To  
Notes
2006-12-01 11:31:31*****UNSAT******
  
 RESPONSES TO THE PREVIOUS FIRE PLAN REVIEW OF 10/05/06
 RECEIVED AS FOLLOWS:
  
 1.) NFPA 101 - 2003 EDITION, AND FLORIDA
 FIRE PREVENTION CODE - 2004 EDITION
 SHALL BE REFERENCED. NFPA 101 IS A LIFE SAFETY CODE,
 NOT AN ELECTRICAL CODE.ALSO MAKE REFERENCE TO FL.
 FIRE PREVENTION CODE UNDER APPLICABLE CODES, SHEET
 G1.1
  
 2.) STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.SHOULD BE ADDED TO THE
 SHEET G1.1 UNDER APPLICABLE CODES
  
 3.) ACCUMULATIONS OF COMBUSTIBLE WASTE
 MATERIALS, DUST, AND DEBRIS SHALL BE
 REMOVED FROM THE STRUCTURE AND ITS
 IMMEDIATE VICINITY AT THE END OF EACH
 SHIFT OR MORE FREQUENTLY AS NECESSARY
 FOR SAFE OPERATIONS. SHOULD BE ADDED IN THE PLANS
  
 4.)OK
  
 5.)OK
  
 6.) PANIC HARDWARE IS REQUIRED ON EXIT
 DOORS SERVING AN OCCUPANT LOAD GREATER
 THAN ONE HUNDRED.SHOULD BE ADDED IN THE PLANS
  
 7.)OK
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCL;UDE A
 RESPONSE LETTER INDICATING HOW/WHERE EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-05 Cont ID  
Sent By mawillia Date 2006-10-05 Time 13:44 Rev Time 0.00
Received By mawillia Date 2006-10-05 Time 12:40 Sent To  
Notes
2006-10-05 00:00:00*****DENIED*****
  
  
  
  
 1.) NFPA 101 - 2003 EDITION, AND FLORIDA
 FIRE PREVENTION CODE - 2004 EDITION
 SHALL BE REFERENCED.
  
 2.) STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.
  
 3.) ACCUMULATIONS OF COMBUSTIBLE WASTE
 MATERIALS, DUST, AND DEBRIS SHALL BE
 REMOVED FROM THE STRUCTURE AND ITS
 IMMEDIATE VICINITY AT THE END OF EACH
 SHIFT OR MORE FREQUENTLY AS NECESSARY
 FOR SAFE OPERATIONS.
  
 4.) IF THE SCOPE OF THE INTERIOR
 BUILDOUT REQUIRES MODIFICATION OF THE
 FIRE ALARM OR FIRE SPRINKLER SYSTEM,
 SEPARATE PERMIT AND SHOP DRAWINGS/PLANS
 ARE REQUIRED.
  
 5.) ON SHEET E1.0 AT BAR AREA #1, PLEASE
 EXPLAIN HOW THE SUPPORT COLUMN WILL
 MAINTAIN ITS FIRE PROTECTION RATING IF
 THE EXISTING BRICK AROUND THE COLUMN IS
 REMOVED.
  
 6.) PANIC HARDWARE IS REQUIRED ON EXIT
 DOORS SERVING AN OCCUPANT LOAD GREATER
 THAN ONE HUNDRED.
  
 7.) ON SHEET LS1.1, THE AISLE CLEARANCE
 OF 3'-0" (LOCATED AROUND DINING AREA
 "C") EXITING BETWEEN BAR SEAT #20-21 AND
 THE SUPPORT COLUMN IS TO NARROW.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 6 Status P Date 2007-04-20 Cont ID  
Sent By kstevens Date 2007-04-20 Time 09:46 Rev Time 0.00
Received By kstevens Date 2007-04-20 Time 09:46 Sent To  
Notes
2007-04-20 09:47:09GAS REVISION OK - SHTS P1.1 & P1.2 - CHANGED EXISTING
 GAS PIPE SIZE TO 3" & CHANGED SOME PIPE SIZES

Review Stop G GAS REVIEW
Rev No 5 Status F Date 2007-04-17 Cont ID  
Sent By kstevens Date 2007-04-17 Time 10:43 Rev Time 0.00
Received By kstevens Date 2007-04-17 Time 10:43 Sent To  
Notes
2007-04-17 10:49:22REVISION DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. A UNION IS REQUIRED FOR THE REGULATOR. THE UNION CAN
 NOT BE IN THE CEILING IF IT IS A DROPPED CEILING OR
 HARD CEILING.
  
 2, TALKED TO CONTRACTOR. A REGULATOR IS NOT REQUIRED IF
 THE SECTION OF PIPE UPSTREAM OF THE SIX CHAMBER WOK
 RANGE MAINTAINS 3" PIPE SIZE.TABLE 402.4(6). THE
 CONTRACTOR INDICATED HE WILL DELETE THE REGULATOR AND
 SHUT OFF VALVE AND MAINTAIN 3" PIPE TO THE WOK RANGE.
 ITEM #41.
  
 3. A NEW REVISION WILL BE REQUIRED SHOWING CHANGES.
 (SHOWS EXISTING CHANGED FROM 4" TO 3" PIPE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2007-03-01 Cont ID  
Sent By kstevens Date 2007-03-01 Time 08:46 Rev Time 0.00
Received By kstevens Date 2007-02-28 Time 18:56 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-02-02 Cont ID  
Sent By kstevens Date 2007-02-02 Time 10:59 Rev Time 0.00
Received By kstevens Date 2007-02-02 Time 10:59 Sent To  
Notes
2007-02-02 11:08:08DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 FROM PREVIOUS REVIEW:
  
 10. SHT FP1.2 THE FOLLOWING INFORMATION
 IS REQUIRED FOR GAS PERMIT:
  
 A. OK
 B. OK
 C. OK
 D. OK
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE FROM ENGINEER NOTED, BUT NO MANUF.
 SPECIFICATION SHEETS SHOWING THE LISTING, THE MODEL
 NUMBER, OR THE BTU LOAD INDICATED HAS BEEN SUBMITTED.
 ******RESPONSE NOTED, BUT ITEM 41 CHAMBER WOK. INDICATE
 WHICH MODEL "RINGS, TIP, TIP VERTICAL SHIELD/TIP ANGLE
 SHIELD, TIP NO CLOG WILL BE USED TO ADD UP TO 450,000
 BTU.--ITEM 45 INDICATES 6 BURNER RANGE/CONVECTION
 OVENS ON THE KITCHEN EQUIPMENT CONNECTION SCHEDULE, BUT
 MANUF. SPECIFICATION SHEET INDICATES STAKEHOUSE
 BROILERS, AND THE BTU'S DO NOT REFLECT THE EQUIPMENT
 CONNECTION SCHEDULE. PLEASE CORRELATE INFORMATION.
  
 F. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****RESPONSE NOTED, BUT ONLY ONE VALVE IS SHOWN ON THE
 RISER DIAGRAM. IT IS NOT INDICATED IF IT IS THE MANUAL
 SHUT OFF VALVE OR THE EMERGENCY SHUT OFF VALVE. BOTH
 VALVES ARE REQUIRED. ALSO NO UNION IS INDICATED
 DOWNSTREAM OF THE MANUAL AS REQUIRED. ******RESPONSE
 NOTED, BUT THE MANUAL SHUT OFF VALVE SHOWN IN THE
 CEILING IS NOT REQUIRED. BECAUSE THE EXISTING MANUAL
 SHUT OFF VALVE BELOW THE CEILING UPSTREAM OF THE
 SOLENOID WAS NOT INDICATED ON THE PREVIOUS SUBMITTALS,
 THE REQUIREMENT FOR THE MANUAL SHUT OFF VALVE WAS
 INDICATED.
  
 G. OK - USING 402.4(6) BECAUSE 402.4(2) ONLY GOES UP TO
 200 FT, AND THE DEVELOPED LENGTH IS 238.5 FT. MINIMUM
 2-1/2" IS REQUIRED UP TO THE FIRST ITEM #29 PER THE
 TABLE. 2" IS INDICATED. PLEASE CHANGE PIPE SIZE.
  
 I. (NEW GAS COMMENT)BTU LOAD OF EACH APPLIANCE AND
 THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 J. (NEW GAS COMMENT) THE DRIPS INSTALLED AT THE ENDS OF
 THE GAS LINES SHOULD BE INSTALLED, (1), AT THE BOTTOM
 OF THE DROP WHERE THE GAS LINE SPLITS INTO TWO LINES TO
 KEEP THE MOISTURE OUT OF THE GAS EQUIPMENT. SECTION
 408.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-12-14 Cont ID  
Sent By kstevens Date 2006-12-14 Time 10:38 Rev Time 0.00
Received By kstevens Date 2006-12-14 Time 10:38 Sent To  
Notes
2006-12-14 10:41:06DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SHT FP1.2 THE FOLLOWING INFORMATION
 IS REQUIRED FOR GAS PERMIT:
  
 A. OK
 B. OK
 C. OK
 D. OK
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE FROM ENGINEER NOTED, BUT NO MANUF.
 SPECIFICATION SHEETS SHOWING THE LISTING, THE MODEL
 NUMBER, OR THE BTU LOAD INDICATED HAS BEEN SUBMITTED.
  
 F. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****RESPONSE NOTED, BUT ONLY ONE VALVE IS SHOWN ON THE
 RISER DIAGRAM. IT IS NOT INDICATED IF IT IS THE MANUAL
 SHUT OFF VALVE OR THE EMERGENCY SHUT OFF VALVE. BOTH
 VALVES ARE REQUIRED. ALSO NO UNION IS INDICATED
 DOWNSTREAM OF THE MANUAL AS REQUIRED.
  
 G. OK - USING 402.4(6) BECAUSE 402.4(2) ONLY GOES UP TO
 200 FT, AND THE DEVELOPED LENGTH IS 238.5 FT. MINIMUM
 2-1/2" IS REQUIRED UP TO THE FIRST ITEM #29 PER THE
 TABLE. 2" IS INDICATED. PLEASE CHANGE PIPE SIZE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-09-09 Cont ID  
Sent By kstevens Date 2006-09-09 Time 09:50 Rev Time 0.00
Received By kstevens Date 2006-09-09 Time 09:50 Sent To  
Notes
2006-09-09 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SHT FP1.2 THE FOLLOWING INFORMATION
 IS REQUIRED FOR GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. SHOW ALL CUT SECTION
 LENGHTS. INDICATE VALVE SIZE. (TO BE
 FULL SIZE AS REQUIRED PIPE SIZE TO
 APPLIANCE).
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. SHT
 FP1.1 INDICATES 1PSI OR LESS. IF NATURAL
 GAS, PROVIDER PROVIDES 1/2PSI, 2PSI OR
 5PSI ONLY. PLEASE CONFIRM INLET PRESSURE
 PRIOR TO RESUBMITTING. IF 2PSI, INDICATE
 THE LOCATION OF THE 2PI TO 1/2PSI
 REGULATORS, AND SUBMIT THE MANUF.
 SPECIFICATION SHEETS FOR THE REGULATORS
 AND INDICATE THE MODEL NUMBER.
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 F. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 G. SUBMIT GAS TABLE USED FOR SIZING GAS
 PIPE PER FBC-2004 FUEL GAS, OR INDICATE
 THE SOURCE OF THE GAS TABLE USED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-06-20 Cont ID  
Sent By adarroug Date 2007-06-20 Time 14:23 Rev Time 0.00
Received By adarroug Date 2007-06-20 Time 14:23 Sent To E
Notes
2007-06-20 14:24:03TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-05-16 Cont ID  
Sent By adarroug Date 2007-05-16 Time 11:37 Rev Time 0.00
Received By adarroug Date 2007-05-16 Time 11:35 Sent To E
Notes
2007-05-16 11:37:58TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-04-19 Cont ID  
Sent By adarroug Date 2007-04-19 Time 09:56 Rev Time 0.00
Received By adarroug Date 2007-04-19 Time 09:56 Sent To G
Notes
2007-04-19 09:57:01TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-04-12 Cont ID  
Sent By adarroug Date 2007-04-12 Time 10:41 Rev Time 0.00
Received By adarroug Date 2007-04-12 Time 10:41 Sent To FIRE
Notes
2007-04-12 10:42:11TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-04-11 Cont ID  
Sent By adarroug Date 2007-04-11 Time 09:17 Rev Time 0.00
Received By adarroug Date 2007-04-11 Time 09:17 Sent To P
Notes
2007-04-11 09:17:31TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-04-11 Cont ID  
Sent By adarroug Date 2007-04-11 Time 09:13 Rev Time 0.00
Received By adarroug Date 2007-04-11 Time 09:13 Sent To  
Notes
2007-04-12 10:25:19 
 4/12/07SENT TO MIKE WILLIAMS DESK FOR REVIEW.RB
  
2007-04-11 09:13:59WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-28 Cont ID  
Sent By spalmer Date 2007-03-28 Time 18:19 Rev Time 0.00
Received By spalmer Date 2007-03-28 Time 18:19 Sent To B
Notes
2007-03-28 18:19:46TO SAMANTHA HILL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-14 Cont ID  
Sent By adarroug Date 2007-02-14 Time 16:46 Rev Time 0.00
Received By adarroug Date 2007-02-14 Time 16:46 Sent To  
Notes
2007-02-26 11:41:38TO "COMM" BD#63
2007-02-14 16:46:40WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-27 Cont ID  
Sent By adarroug Date 2006-12-27 Time 11:28 Rev Time 0.00
Received By adarroug Date 2006-12-27 Time 11:28 Sent To  
Notes
2007-01-11 11:03:39TO "COMM" BD#40
2006-12-27 11:28:48WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-13 Cont ID  
Sent By adarroug Date 2006-11-13 Time 09:30 Rev Time 0.00
Received By adarroug Date 2006-11-13 Time 09:30 Sent To  
Notes
2006-11-15 11:00:51TO "COMM" BD#60
2006-11-13 09:31:16WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-05 Cont ID  
Sent By mawillia Date 2006-10-05 Time 12:40 Rev Time 0.00
Received By mawillia Date 2006-09-01 Time 09:35 Sent To  
Notes
2006-09-05 00:00:00TO "COMM" BD#19
2006-09-01 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-11-15 Cont ID  
Sent By rregueir Date 2006-11-15 Time 18:05 Rev Time 0.00
Received By rregueir Date 2006-11-15 Time 18:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-09-30 Cont ID  
Sent By rregueir Date 2006-09-30 Time 15:30 Rev Time 0.00
Received By rregueir Date 2006-09-30 Time 15:30 Sent To  
Notes
2006-09-30 00:00:00----------------DENIED------------------
  
 1. PROVIDE DETAILED DRAWINGS SHOWING
 SIZES/LOCATIONS/SPECS OF EXISTING
 EQUIPMENT AND DUCTWORK ALONG WITH WORK
 BEING PERFORMED TO FACILITATE RELOCATION
 OF DIFFUSERS AS INDICATED ON PAGE M1.1
 KEYNOTE #2 - PER FBC 106.1.1
  
 2. PROVIDE FRESH AIR CALCULATIONS BASED
 ON OCCUPANCY CLASSIFICATION AND OCCUPANT
 LOAD PER FBC,M 403.3
  
 3. IF TOILET ROOMS ARE TO BE MODIFIED
 PER PLUMBING REVIEW COMMENT #1, VERIFY
 AND PROVIDE INFORMATION NEEDED TO SHOW
 EXHAUST OF TOILET ROOMS IN COMPLIANCE
 WITH FBC,M TABLE 403.3
  
 4. PAGE M1.1 KEYNOTE #5: ANY MOVEMENT OR
 ADJUSTMENT OF TYPE I KITCHEN HOODS WILL
 REQUIRE SEPERATE PERMITS FOR BOTH THE
 HOODS AND HOOD SUPPRESSION SYSTEMS.
  
 5. DRAWING SC-1 SHEET FS500 SHOWS 6" PVC
 CHASES FOR SODA FOUNTAINS TO BE
 INSTALLED ABOVE CEILING. DO THESE CHASES
 TRAVEL THROUGH ANY RETURN AIR PLENUMS?
 NO COMBUSTIBLE MATERIALS CAN BE EXPOSED
 IN RETURN AIR PLENUMS.THIS APPLIES TO
 ALL COMBUSTIBLES, NOT JUST THE SODA
 CHASES. FBC,M 602.2.1
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU
 HAVE ANY QUESTIONS.
  
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-03-01 Cont ID  
Sent By kstevens Date 2007-03-01 Time 08:46 Rev Time 0.00
Received By kstevens Date 2007-02-28 Time 18:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-02-02 Cont ID  
Sent By kstevens Date 2007-02-02 Time 10:42 Rev Time 0.00
Received By kstevens Date 2007-02-02 Time 10:42 Sent To  
Notes
2007-02-02 11:10:30DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 *****FROM PREVIOUS REVIEW*****
  
 1. OK - EXISTING TOILET ROOMS
 2. OK SHEET NOT RESUBMITTED (N0 FP SHEETS)
 3. OK
  
 4. PLANS SHALL BE ROUTED TO DBPR HOTEL
 AND RESTURANT DIVISION FOR REVIEW.
 MINIMUM TWO SETS OF STAMPED PLANS WITH
 TWO PAGE "WORK SHEETS" ATTACHED SHALL BE RESUBMITTED
 FOR REVIEW. SECTION 102.2.1.
 ****RESPONSE FROM ENGINEER NOTED, BUT ARCHITECT DID NOT
 RESPOND AND COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED, BUT TWO SETS OF PLANS SHALL BE
 SUBMITTED. THE SHEETS SUBMITTED WITH THE DBPR STAMP
 SHALL BE ADDED TO THE SETS OF PLANS AND THE 2 PAGE
 WORKSHEETS SHALL BE ATTACHED TO THE DBPR SHEETS ADDED
 TO THE SETS. IF THE SHEETS ARE NOT SIGNED, SEALED,
 DATED BY A DESIGN PROFESSIONAL, THE SHEETS ARE REQUIRED
 TO HAVE THE PRINTED NAME AND SIGNATURE OF THE PERSON
 DESIGNING THE SHEETS.
  
 5. SUBMIT AN EXISTING FLOOR PLAN FOR THE
 KITCHEN AREA TO DETERMINE ACTUAL CHANGES
 TO THE KITCHEN AND EQUIPMINT. SECTION
 106.1.1.
 ****RESPONSE FROM ENGINEER NOTED, BUT COMMENT NOT
 ADDRESSED BY KITCHEN EQUIPMENT CONTRACTOR.
 ******RESPONSE NOTED, BUT AN EXISTING FLOOR PLAN HAS
 NOT BEEN SUBMITTED.
  
 6. OK
 7. OK - SHEET NUMBER CHANGED WITHOUT NOTICE.
 8. OK - SHEET NUMBER CHANGED WITHOUT NOTICE.
 9. OK
  
 10. SHT FP1.2 THE FOLLOWING INFORMATION
 IS REQUIRED FOR GAS PERMIT:
  
 A. OK
 B. OK
 C. OK
 D. OK
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE FROM ENGINEER NOTED, BUT NO MANUF.
 SPECIFICATION SHEETS SHOWING THE LISTING, THE MODEL
 NUMBER, OR THE BTU LOAD INDICATED HAS BEEN SUBMITTED.
 ******RESPONSE NOTED, BUT ITEM 41 CHAMBER WOK. INDICATE
 WHICH MODEL "RINGS, TIP, TIP VERTICAL SHIELD/TIP ANGLE
 SHIELD, TIP NO CLOG WILL BE USED TO ADD UP TO 450,000
 BTU.--ITEM 45 INDICATES 6 BURNER RANGE/CONVECTION
 OVENS ON THE KITCHEN EQUIPMENT CONNECTION SCHEDULE, BUT
 MANUF. SPECIFICATION SHEET INDICATES STAKEHOUSE
 BROILERS, AND THE BTU'S DO NOT REFLECT THE EQUIPMENT
 CONNECTION SCHEDULE. PLEASE CORRELATE INFORMATION.
  
 F. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****RESPONSE NOTED, BUT ONLY ONE VALVE IS SHOWN ON THE
 RISER DIAGRAM. IT IS NOT INDICATED IF IT IS THE MANUAL
 SHUT OFF VALVE OR THE EMERGENCY SHUT OFF VALVE. BOTH
 VALVES ARE REQUIRED. ALSO NO UNION IS INDICATED
 DOWNSTREAM OF THE MANUAL AS REQUIRED. ******RESPONSE
 NOTED, BUT THE MANUAL SHUT OFF VALVE SHOWN IN THE
 CEILING IS NOT REQUIRED. BECAUSE THE EXISTING MANUAL
 SHUT OFF VALVE BELOW THE CEILING UPSTREAM OF THE
 SOLENOID WAS NOT INDICATED ON THE PREVIOUS SUBMITTALS,
 THE REQUIREMENT FOR THE MANUAL SHUT OFF VALVE WAS
 INDICATED.
  
 G. OK - USING 402.4(6) BECAUSE 402.4(2) ONLY GOES UP TO
 200 FT, AND THE DEVELOPED LENGTH IS 238.5 FT. MINIMUM
 2-1/2" IS REQUIRED UP TO THE FIRST ITEM #29 PER THE
 TABLE. 2" IS INDICATED. PLEASE CHANGE PIPE SIZE.
  
 I. (NEW GAS COMMENT)BTU LOAD OF EACH APPLIANCE AND
 THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 J. (NEW GAS COMMENT) THE DRIPS INSTALLED AT THE ENDS OF
 THE GAS LINES SHOULD BE INSTALLED, (1), AT THE BOTTOM
 OF THE DROP WHERE THE GAS LINE SPLITS INTO TWO LINES TO
 KEEP THE MOISTURE OUT OF THE GAS EQUIPMENT. SECTION
 408.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-12-14 Cont ID  
Sent By kstevens Date 2006-12-14 Time 10:03 Rev Time 0.00
Received By kstevens Date 2006-12-13 Time 19:05 Sent To  
Notes
2006-12-14 10:31:37DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 *****FROM PREVIOUS REVIEW*****
  
 1. OK - EXISTING TOILET ROOMS
 2. OK SHEET NOT RESUBMITTED (N0 FP SHEETS)
 3. OK
  
 4. PLANS SHALL BE ROUTED TO DBPR HOTEL
 AND RESTURANT DIVISION FOR REVIEW.
 MINIMUM TWO SETS OF STAMPED PLANS WITH
 TWO PAGE "WORK SHEETS" ATTACHED SHALL BE RESUBMITTED
 FOR REVIEW. SECTION 102.2.1.
 ****RESPONSE FROM ENGINEER NOTED, BUT ARCHITECT DID NOT
 RESPOND AND COMMENT NOT ADDRESSED.
  
 5. SUBMIT AN EXISTING FLOOR PLAN FOR THE
 KITCHEN AREA TO DETERMINE ACTUAL CHANGES
 TO THE KITCHEN AND EQUIPMINT. SECTION
 106.1.1.
 ****RESPONSE FROM ENGINEER NOTED, BUT COMMENT NOT
 ADDRESSED BY KITCHEN EQUIPMENT CONTRACTOR.
  
 6. SHT FP1.1 KITCHEN EQUIPMENT
 CONNECTION SCHEDULE. THE FOLLOWING ITEMS
 WERE NOT FOUND OR INDICATED ON THE FLOOR
 PLAN. NUMBERS 8, 12, 31, 32, 75, B02,
 B10 AND B11. PLEASE INDICATE LOCATION ON
 THE FLOOR PLAN. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT NOW FLOOR PLAN DOES NOT SHOW
 ITEMS #4, & #8. EXISTING ITEM #87 NOT SHOWN ON THE
 SCHEDULE.PLEASE CLARIFY.- SHEET NUMBER CHANGED
 WITHOUT NOTICE.
  
 7. OK - SHEET NUMBER CHANGED WITHOUT NOTICE.
 8. OK - SHEET NUMBER CHANGED WITHOUT NOTICE.
  
 9. SHT FP1.2 WATER RISER IN THE NEW COOK
 AREA DOES NOT REFLECT THE FLOOR PLAN.
 PLEASE CORRELATE RISER AND FLOOR PLAN.
 SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE RISER W4 DOES NOT REFLECT
 THE FLOOR PLAN FOR ITEMS 92 & 73. - SHEET CHANGED
 NUMBER WITHOUT NOTICE.
  
 10. SHT FP1.2 THE FOLLOWING INFORMATION
 IS REQUIRED FOR GAS PERMIT:
  
 A. OK
 B. OK
 C. OK
 D. OK
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE FROM ENGINEER NOTED, BUT NO MANUF.
 SPECIFICATION SHEETS SHOWING THE LISTING, THE MODEL
 NUMBER, OR THE BTU LOAD INDICATED HAS BEEN SUBMITTED.
  
 F. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****RESPONSE NOTED, BUT ONLY ONE VALVE IS SHOWN ON THE
 RISER DIAGRAM. IT IS NOT INDICATED IF IT IS THE MANUAL
 SHUT OFF VALVE OR THE EMERGENCY SHUT OFF VALVE. BOTH
 VALVES ARE REQUIRED. ALSO NO UNION IS INDICATED
 DOWNSTREAM OF THE MANUAL AS REQUIRED.
  
 G. OK - USING 402.4(6) BECAUSE 402.4(2) ONLY GOES UP TO
 200 FT, AND THE DEVELOPED LENGTH IS 238.5 FT. MINIMUM
 2-1/2" IS REQUIRED UP TO THE FIRST ITEM #29 PER THE
 TABLE. 2" IS INDICATED. PLEASE CHANGE PIPE SIZE.
  
 **************NEW COMMENTS*************
  
 1B. SHT P1.1 KEY NOTES #11 INDICATES "NOT USED", BUT
 THERE ARE TWO NUMBER 11'S IN THE BAR AREA. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 2B. SHT P1.1 KEY NOTES #10 INDICATES "EXISTING URINAL",
 BUT IT SHOWS #10 TWICE AND BOTH ARE NOT URINALS. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 3B. SHT P1.1 W1/FP1.2 THRU W5/FP1.2 REFERENCES FOR THE
 WATER RISER DIAGRAMS REFER TO A SHEET THAT HAS NOT BEEN
 SUBMITTED. PLEASE CORRELATE THE REFERENCE TO THE
 CORRECT SHEET WITH THE WATER RISERS ON THEM. SECTION
 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE RESUBMIT ONE COPY OF THE PLANS SUBMITTED FOR
 THIS REVIEW FOR REFERENCE AND COMPARISON.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-09-09 Cont ID  
Sent By kstevens Date 2006-09-09 Time 07:58 Rev Time 0.00
Received By kstevens Date 2006-09-08 Time 18:53 Sent To  
Notes
2006-09-09 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 1. SHT G1.1 PER TABLE 403.1 & SECTION
 403.1.1 ASSEMBLY OCCUPANCIESD REQUIRE A
 3:2 RATIO OF W/C'S PROVIDED FOR WOMEN AS
 COMBINED W/C'S AND URINALS PROVIDED FOR
 MEN. SINCE 2 W/C'S & 1 URINAL, (3), ARE
 PROVIDED FOR MEN, 3X1.66 (3:2 RATIO), 5
 W/C'S ARE REQUIRED FOR WOMEN.
  
 2. SHT FP1.0 DEMO NOTES 7 AND 11 WERE
 NOT FOUND ON THE FLOOR PLAN. PLESASE
 CLARIFY. SECTION 106.1.1.
  
 3. ALL SHEETS KEY PLAN INDICATES SCOPE
 OF WORK TO BE OUTSIDE THE KITCHEN AREA.
 WORK IS INDICATED IN THE KITCHEN AREA.
 CHANGE KEY PLAN TO REFLECT SCOPE OF WORK
 TO ALL AREAS WHERE WORK IS BEING DONE.
 SECTION 106.1.1.
  
 4. PLANS SHALL BE ROUTED TO DBPR HOTEL
 AND RESTURANT DIVISION FOR REVIEW.
 MINIMUM TWO SETS OF STAMPED PLANS WITH
 TWO PAGE "WORK SHEETS" ATTACHED SHALL BE RESUBMITTED
 FOR REVIEW. SECTION 102.2.1.
  
 5. SUBMIT AN EXISTING FLOOR PLAN FOR THE
 KITCHEN AREA TO DETERMINE ACTUAL CHANGES
 TO THE KITCHEN AND EQUIPMINT. SECTION
 106.1.1.
  
 6. SHT FP1.1 KITCHEN EQUIPMENT
 CONNECTION SCHEDUL. THE FOLLOWING ITEMS
 WERE NOT FOUND OR INDICATED ON THE FLOOR
 PLAN. NUMBERS 8, 12, 31, 32, 75, B02,
 B10 AND B11. PLEASE INDICATE LOCATION ON
 THE FLOOR PLAN. SECTION 106.1.1.
  
 7. SHT FP1.1 NOTE 12 NOT FOUND. NUMBERED
 WRONG AS NUMBER 2? PLEASE CLARIFY.
 SECTION 106.1.1.
  
 8. SHT FP1.1 FLOOR PLAN SHOW A FLOOR
 SINK TO REMAIN THAT IS NOT LOCATED UNDER
 A PLUMBING FIXTURE. FLOOR SINKS ARE
 NORMALLY INSTALLED 1" ABOVE FINISHED
 FLOOR. WILL THE FLOOR BE BUILD UP FOR
 THIS TO BE USED AS A FLOOR DRAIN?
 SECTION 106.1.1.
  
 9. SHT FP1.2 WATER RISER IN THE NEW COOK
 AREA DOES NOT REFLECT THE FLOOR PLAN.
 PLEASE CORRELATE RISER AND FLOOR PLAN.
 SECTION 106.1.1.
  
 10. SHT FP1.2 THE FOLLOWING INFORMATION
 IS REQUIRED FOR GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. SHOW ALL CUT SECTION
 LENGHTS. INDICATE VALVE SIZE. (TO BE
 FULL SIZE AS REQUIRED PIPE SIZE TO
 APPLIANCE).
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. SHT
 FP1.1 INDICATES 1PSI OR LESS. IF NATURAL
 GAS, PROVIDER PROVIDES 1/2PSI, 2PSI OR
 5PSI ONLY. PLEASE CONFIRM INLET PRESSURE
 PRIOR TO RESUBMITTING. IF 2PSI, INDICATE
 THE LOCATION OF THE 2PI TO 1/2PSI
 REGULATORS, AND SUBMIT THE MANUF.
 SPECIFICATION SHEETS FOR THE REGULATORS
 AND INDICATE THE MODEL NUMBER.
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 F. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 G. SUBMIT GAS TABLE USED FOR SIZING GAS
 PIPE PER FBC-2004 FUEL GAS, OR INDICATE
 THE SOURCE OF THE GAS TABLE USED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status N Date 2007-01-03 Cont ID  
Sent By mflis Date 2007-01-03 Time 15:15 Rev Time 0.00
Received By mflis Date 2007-01-03 Time 15:15 Sent To  
Notes
2007-01-03 15:16:17ZONING: REVIEW; NOT REQUIRED
  
 RESTAURANT INTERIOR REMODEL
 NO CHANGES TO ARCHITECTURAL
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status P Date 2006-09-18 Cont ID  
Sent By mflis Date 2006-09-18 Time 16:54 Rev Time 0.00
Received By mflis Date 2006-09-18 Time 16:54 Sent To  
Notes
2006-09-18 00:00:00INTERIOR BUILDOUT - REVIEWED FOR USE.
 -MJF