Plan Review Details - Permit 06082057
Plan Review Stops For Permit 06082057
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-02-28 Cont ID  
Sent By mjacobs Date 2007-02-28 Time 15:15 Rev Time 0.00
Received By mjacobs Date 2007-02-28 Time 14:28 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-12-18 Cont ID  
Sent By mjacobs Date 2006-12-18 Time 08:37 Rev Time 0.00
Received By mjacobs Date 2006-12-16 Time 17:16 Sent To  
Notes
2006-12-16 17:41:10BUILDING PLAN REVIEW
 PERMIT:06082057
 ADD:1910 PALM BEACH LAKES BLVD.
 CONT: DIGNY YORK ASSOC. LLC.
 TEL: (703)790-528
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1) SHEET A-2WHAT WAS THEPRIOR USE OF THE NEW ADA
 BATHROOM?
  
 2) FBC. EXISTING. SEC 304.1LEVEL 2 ALTERATIONS
 INCLUDE THE RECONFIGURATION OF SPACE, THE ADDITION OR
 ELIMINATION OF ANY DOOR OR WINDOW, THE RECONFIGURATION
 OR EXTENSION OF ANY SYSTEM, OR THE INSTALLATION OF ANY
 ADDITIONAL EQUIPMENT.
  
 3)WPB AMENDMENTS.108.3.FOR PERMITTING PURPOSSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL,ELECTRIC,PLUMBING, MECHANICAL, INTERIOR
 FINISH,ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT EXCLUDING LAND VALUE. THE VALUE ON
 PERMIT APPLICATION SHALL BE THE TOTAL VALUE OF THE
 PROJECT INCLUDING ALL TRADES,MATERIALS AND LABOUR.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-11 Cont ID  
Sent By mjacobs Date 2006-09-11 Time 11:39 Rev Time 0.00
Received By mjacobs Date 2006-09-09 Time 09:49 Sent To  
Notes
2006-09-09 00:00:00 
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1) 11-4.13.6 MANEUVERING CLEARANCES AT
 DOORS.
 MINIMUM MANEUVERING CLEARANCES AT DOORS
 THAT ARE NOT AUTOMATIC OR POWER-ASSISTED
 SHALL BE AS SHOWN IN FIGURE 11-25 . THE
 FLOOR OR GROUND AREA WITHIN THE REQUIRED
 CLEARANCES SHALL BE LEVEL AND CLEAR.
 MINIMUM CLARENCE IS 18". SEE PREP ROOM
 DOOR. SHEET A-2.
  
 2) DOOR ENCROACHMENT
 1005.2 DOOR ENCROACHMENT .
 DOORS OPENING INTO THE PATH OF EGRESS
 TRAVEL SHALL NOT REDUCE THE REQUIRED
 WIDTH TO LESS THAN ONE-HALF DURING THE
 COURSE OF THE SWING. WHEN FULLY OPEN,
 THE DOOR SHALL NOT PROJECT MORE THAN 7
 INCHES (178 MM) INTO THE REQUIRED WIDTH.
  
  
 3) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
  
 A) THE DESIGN OCCUPANT LOAD, SEE 1004.
 -------------------------------------
  
 4) 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED
 BY THE BUILDING OFFICIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE BUILDING OFFICIAL
 (SEE ALSO SECTION 106.3.5). THE SYMBOL
 IN THE LEGEND FOR THE 1-HR RATED
 PARTITION LOOKS THE SAME FOR THE
 EXISTING AND NEW 1-HR RATED WALL. THE
 NEW RATED WALL NEEDS TO BE DESTINTIVE
 FROM THE EXISTING RATED WALL, SO WE CAN
 IDENTIFY THE NEW 1-HR RATED WALLS.
  
 5) ON PAGES A-5 AND A-6 THE NEW WALLS
 NEED TO BE CLEARLY IDENTIFY FROM THE
 EXISTING WALLS.
  
 6) THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SSYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
 EMAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-02-27 Cont ID  
Sent By dpalmer Date 2007-02-27 Time 14:44 Rev Time 0.00
Received By dpalmer Date 2007-02-27 Time 14:31 Sent To B
Notes
2007-02-27 14:45:28FEE BALANCEOF $2,775.00 NOT PAID, PERMIT WILL NOT
 PRINT UNTIL FEE IS PAID.
  
 NEEDS RECORDED NOC BEFORE PERMIT CAN BE PICKED UP.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-11-21 Cont ID  
Sent By dpalmer Date 2006-11-21 Time 08:43 Rev Time 0.00
Received By dpalmer Date 2006-11-21 Time 08:34 Sent To  
Notes
2006-11-21 08:54:38**** UNSAT 2ND REVIEW ***
  
 1) NOTE: PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK
 SHALL BE INCLUDE ON THIS APPLICATION ALL TRADE WORK IS
 BEING SHOWN ON SAID PLANS FOR COMPLETE SCOPE OF WORK.
 PLEASE KNOW, ONCE THE PERMIT ISSUED FOR THIS PERMIT
 (UPON ADJUSTED VALUE) THE SUB CONTRACTORS WILL COME IN
 WITH THEIR APPLICATIONS AND REFERENCE THESE PLANS FOR A
 PERMIT. PLEASE KNOW THAT THE SUB CONTRACTOR WILL ONLY
 PAY A $50 SUB PERMIT FEE AS THEY ARE REFERENCING PLANS
 WHICH CONTAIN SCOPE OF WORK FOR ALL SUB TRADES.
 ONLY WHEN THE SUB CONTRACTOR SUBMIT PLANS AND PERMIT
 APPLICATION ON THEIR OWN DO THEY PAY FULL FEE BASED ON
 THEIR SEPARATE SCOPE OF WORK.
 PLEASE ADJUST TO INCLUDE ALL TRADES AS PLANS SUBMITTED
 INDICATE.
 PLEASE KNOW , ONE MAY BE ASSESSED USING THE MARSHAL'S &
 SWIFT GUIDE AS ADOPTED BY THE CITY OF WEST PALM BEACH
 108.3
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-09 Cont ID  
Sent By dpalmer Date 2006-09-09 Time 16:28 Rev Time 0.00
Received By dpalmer Date 2006-09-09 Time 16:09 Sent To  
Notes
2006-09-09 00:00:00*** UNSAT ****
  
 1) NOTE: PLEASE SEE VALUE FOR COMPLETE
 SCOPE OF WORK SHOWN ON PLANS IS LOW.
 PLEASE SEE VALUE SHALL BE BASED ON ALL
 LABOUR AND MATERIALS, "EVEN IF
 MATERIALS, LT'S ETCIS OWNER SUPPLIED".
 PLEASE KNOW VALUE SHOULD BE ADJUSTED OR
 ONE BE WILL ADJUST USING THE MARSHALL'S
 & SWIFT GUIDE AS ADOPTED BY THE FBC/
 FBC 108.3 ADMIN SECT.
  
 2) NOTE: PLEASE SEE CODES RELEVANT TO
 SCOPE OF WORK, DESIGNS ETC SHALL BE
 SPECIFIED ON PLANS.
 PLEASE SEE THE FOLLOWING SHALL BE
 INDICATED ATA MINIMUM.
 2002 NFPA-70(NEC), 2002 NFPA-72, 2003
 NFPA-101 (LIFE SAFETY CODE).
 PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH ALSO MAY REQUIRE SPECIFIC
 CODES.
 FBC 106.1.2 ADMIN SECT
  
 3) NOTE: PLEASE SEE PLANS INDICATE "MEP" ENGINEERING
 FIRM HOWEVER NONE OF THE MEP
 SHEETS ARE SIGNED, DATED OR SEAL BY THE ENGINEER(S) AND
 NO OTHER SHEETS CONTAIN
 THE REQUIRED TITLE BLOCKS.
 PLEASE VERIFY AS THE ARCHITECT SEEMS TO
 BE SIGNING FOR ALL MEP, WORK WHICH IS
 NOT PERMITTED. PLEASE SEE FS 481.221.
 FS 471.025,471.023, FAC 61G15-23.002
  
 4) NOTE: PLEASE SEE PERMIT APPLICATION,
 PLEASE SEE THE CONTRACTOR'S REP OR
 QUALIFIER WHO SIGNED APPLICATION DID NOT
 ALSO PRINT NAME AS NEEDED AND STATED ON APPLICATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-12-28 Cont ID  
Sent By mawillia Date 2006-12-28 Time 11:23 Rev Time 0.00
Received By mawillia Date 2006-12-28 Time 11:22 Sent To  
Notes
2006-12-28 11:29:48*****PROVISO*****
  
  
 1.) STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.
  
 2.) ACCUMULATIONS OF COMBUSTIBLE WASTE
 MATERIALS AND DUST DEBRIS SHALL BE
 REMOVED FROM THE STRUCTURE AND ITS
 VICINITY AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE
 OPERATIONS.
  
 3.) ALL EXIT COMPONENTS SHALL BE
 MAINTAINED, CLEAR AND UNOBSTRUCTED.
  
 4.) WHERE THE BUILDING IS PROTECTED BY
 FIRE PROTECTION SYSTEMS, SUCH SYSTEMS
 SHALL BE MAINTAINED OPERATIONAL AT ALL
 TIMES DURING OPERATION.
  
 5.) IF IT NECESSARY TO SHUT DOWN A FIRE
 PROTECTION SYSTEM, WPB FIRE RESCUE SHALL
 BE NOTIFIED WHEN THE SYSTEM IS SHUT DOWN
 AND WHEN THE SYSTEM IS RETURNED TO
 SERVICE.
  
 6.) IF THE SCOPE OF THE INTERIOR
 BUILDOUT REQUIRES MODIFICATIONOF THE
 FIRE SPRINKLER AND/OR FIRE ALARM SYSTEM,
 SEPARATE PERMIT AND SHOPDRAWING/PLAN IS
 REQUIRED.
  
 7.) PROVIDE EXISTING AND PROPOSED LIFE
 SAFETY PLAN TO ILLUSTRATE SPRINKLER
 HEADS, FIRE ALARM DETECTION DEVICES,
 EXIT LIGHTS, EMERGENCY LIGHTS, FIRE
 EXTINGUISHERS, ETC.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-09-19 Cont ID  
Sent By mawillia Date 2006-09-19 Time 14:51 Rev Time 0.00
Received By mawillia Date 2006-09-19 Time 14:50 Sent To  
Notes
2006-09-19 00:00:00**PLEASE SUBMIT OR ADDRESS THE FOLLOWING
 NOTES FOR REVIEW.**
  
  
 1.) NFPA 101,2003 EDITION TO BE
 REFERENCED IN ADDITION TO FLORIDA FIRE
 PREVENTION CODE, 2004 EDITION, AS
 RECORDED IN YOUR PROJECT NOTES (SHEET
 A-1).
  
 2.) STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.
  
 3.) ACCUMULATIONS OF COMBUSTIBLE WASTE
 MATERIALS AND DUST DEBRIS SHALL BE
 REMOVED FROM THE STRUCTURE AND ITS
 VICINITY AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE
 OPERATIONS.
  
 4.) ALL EXIT COMPONENTS SHALL BE
 MAINTAINED, CLEAR AND UNOBSTRUCTED.
  
 5.) WHERE THE BUILDING IS PROTECTED BY
 FIRE PROTECTION SYSTEMS, SUCH SYSTEMS
 SHALL BE MAINTAINED OPERATIONAL AT ALL
 TIMES DURING OPERATION.
  
 6.) IF IT NECESSARY TO SHUT DOWN A FIRE
 PROTECTION SYSTEM, WPB FIRE RESCUE SHALL
 BE NOTIFIED WHEN THE SYSTEM IS SHUT DOWN
 AND WHEN THE SYSTEM IS RETURNED TO
 SERVICE.
  
 7.) IF THE SCOPE OF THE INTERIOR
 BUILDOUT REQUIRES MODIFICATIONOF THE
 FIRE SPRINKLER AND/OR FIRE ALARM SYSTEM,
 SEPARATE PERMIT AND SHOPDRAWING/PLAN IS
 REQUIRED.
  
 8.) PROVIDE EXISTING AND PROPOSED LIFE
 SAFETY PLAN TO ILLUSTRATE SPRINKLER
 HEADS, FIRE ALARM DETECTION DEVICES,
 EXIT LIGHTS, EMERGENCY LIGHTS, FIRE
 EXTINGUISHERS, ETC.
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-02-27 Cont ID  
Sent By adarroug Date 2007-02-27 Time 08:17 Rev Time 0.00
Received By adarroug Date 2007-02-27 Time 08:16 Sent To E
Notes
2007-02-27 08:17:22TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-12 Cont ID  
Sent By adarroug Date 2006-11-12 Time 14:21 Rev Time 0.00
Received By adarroug Date 2006-11-12 Time 14:20 Sent To  
Notes
2006-11-14 10:31:34TO "COMM" BD#8
2006-11-12 14:21:17WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-03 Cont ID  
Sent By pkrauss Date 2006-10-03 Time 07:14 Rev Time 0.00
Received By pkrauss Date 2006-08-28 Time 14:36 Sent To  
Notes
2006-09-05 00:00:00TO "COMM" BD#7
2006-08-28 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-12-01 Cont ID  
Sent By pkrauss Date 2006-12-01 Time 13:12 Rev Time 0.00
Received By pkrauss Date 2006-12-01 Time 09:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-02 Cont ID  
Sent By pkrauss Date 2006-10-02 Time 16:12 Rev Time 0.00
Received By pkrauss Date 2006-10-02 Time 15:51 Sent To  
Notes
2006-10-02 00:00:00DENIED:
 1.PLAN SHEET M-1 INDICATES FLEX DUCT
 PENETRATING THROUGH RATED PARTITIONS.
 PER 2004 FMC 603.5.5, FLEXIBLE AIR DUCTS
 & CONNECTORS SHALL NOT PASS THROUGH ANY
 FIRE RESISTANCE RATED ASSEMBLY.
  
 2.PLESE CLARIFY EXUST 10" X 7" EXHAUST
 DUCT RISER CONNECTING TO NEW EF-1.IS
 THIS A SHAFT INTO WHICH THE EF-1
 TERMIATES, PLEASE INDICATE IF THIS IS A
 SUB-DUCT METHOD.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-01-06 Cont ID  
Sent By kstevens Date 2007-01-06 Time 18:42 Rev Time 0.00
Received By kstevens Date 2007-01-06 Time 18:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-09-08 Cont ID  
Sent By kstevens Date 2006-09-08 Time 18:04 Rev Time 0.00
Received By kstevens Date 2006-09-08 Time 18:04 Sent To  
Notes
2006-09-08 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 CITY MUNICIPAL CODE
  
 1. SHT A-1 BUILDING DEPARTMENT NOTES:
 1(C) TO READ FBC-2004 CHAPTER 11
  
 2. SHT A-5 DETAIL 7 SHOW COMPLIANCE WITH
 SECTION 11-4.16.5 FLUSH CONTROLS.
  
 3. SUBMIT A DETAIL FOR THE LAVS SHOWING
 COMPLIANCE WITH SECTION 11-4.19 AND ALL
 SUBSECTIONS.
  
 4. SHOW THE CLEAR FLOOR SPACE FOR ALL
 FIXTURES IN ACCESSIBLE BATHROOMS PER
 SECTIONS 11-4.16.2, 11-4.19.3, AND
 11-4.21.2.
  
 5. SECTION 11-4.2.3 THE BATHROOM DOORS
 SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE REQUIRED FOR ANY FIXTURE.
  
 6. SHT A-7 DETAIL #2 SHOW COMPLIANCE
 WITH THE FOLLOWING:
 FOR WATER CLOSETS,
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
 FOR LAVS,
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
  
 7. SHT P-1 DETAILS 1 & 5. UNDERCOUNTER
 GREASE TRAPS ARE NOT APPROVED IN THE
 FOOD PREP AREA. MUNICIPAL CODE SECTION
 90-124(7)(B). - A MINIMUM 750 GALLON
 GREASE INTERCEPTOR IS REQUIRED.
 INTERCEPTOR SHALL BE SIZED BY LYNN
 MASSON, ENVIRONMENTAL COMPLIANCE MANAGER
 AND CAN BE CONTACTED BY PHONE. (561)
 822-2271, OR FAX (561) 822-2279, OR BY
 E-MAIL [email protected]. WASTE ORD. 3434.
  
 8. SHT P-1 ALL SINKS SHALL BE DRAINED BY
 INDIRECT WASTE IN THE FOOD PREP AREA.
 SECTION 802.1.1.
  
 9. SHT P-2 PLUMBING PRODUCTS: NOTE #3,
 2-1/2" AND SMALLER PIPE SHALL BE SLOPED
 1/4"/FT MINIMUM. TABLE 704.1
  
 10. SHT P-2 PLUMBING GENERAL NOTES: #2
 REFERENCE CODE FBC-2004 PLUMBING.
  
 ***************************************
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  