| 2006-09-08 00:00:00 | ***UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE PLANS SHALL INDICAT |
| | ETHE CURRENT CODE IN AFFECT. |
| | 2002 NEC/ NFPA-70 |
| | |
| | 2) NOTE: PLEASE SEE VALUE SHALL BE BASED |
| | ON LABOUR AND MATERIALS EVEN IF ANY |
| | MATERIALS ARE OWNER SUPPLIED. |
| | FBC 108.3. |
| | |
| | 3) NOTE: PLEASE SEE PLANS ARE REQUIRED |
| | TO BE SIGNED WIHT SIGNATURE AS |
| | RECOGNIZED ANDON FILE WITH THIS OFFICE |
| | FOR THE ENGINEER OF RECORD. |
| | FS 471.025 |
| | |
| | 4) NOTE: PLEASE PROVIDE THE GROUNDIGN |
| | ELECTRODE SYSTEM DETAIL, MUST ATTACH TO |
| | NEW FOOTER STEEL OF BLDG PER 250.50, |
| | MUST ALSO PROVIDE INFORMATION FOR GROUND |
| | RODS AS SHOWN. |
| | PLEASE KNOW, AS ANY COLD WATER FIRE |
| | SPRINKLER STAND PIPES WILL BE ON SITE, |
| | THIS SHALL ALSO BE SHOWN BODNED AS |
| | REQUIRED. |
| | 250.104, 250.50. |
| | |
| | 5) NOTE: PLEASE PROVIDE A GROUNDING |
| | ELECTRODE RISER FOR TRANSFORMERS ETC. |
| | 250.30,250.20,250.58. |
| | SHOW ATTACHEMNTS AND SIZING FOR |
| | TRANSFORMERS. |
| | 250.66 |
| | GRN RISER SHALL BE COPPER. |
| | |
| | 6) NOTE: PLEASE INDICATE THAT THE MDP AS |
| | SHOWN ONLY CONTAIN A MAX OF 6 SPACES AS |
| | PERMITTED PER 230.71. PLEAS KNOW, IF |
| | EQUIPMENT DOES CONTAIN MORE THAN 6 |
| | SPACES EVEN FOR SP BRKERS, A MAIN WILL |
| | BE REQUIRED. |
| | |
| | 7) NOTE: PLEASE PROVIDE AN OVERVIEW OF |
| | SITE WHERE EQUIPMENT WILL BE LOCATED ON |
| | GROUND LEVEL. |
| | |
| | 8) NOTE: PLEASE PROVIDE INFORMATION FOR |
| | TRAILER HOOK UP FEEDERS, GROUNDING |
| | DISCONNECTS ETC AS THESE ARE NOT PART OF |
| | OTHER PERMITS AND THIS INFORMATION HAS |
| | NOT BEEN SHOWN HERE. |
| | FBC106.1.2, 2002 NEC. |
| | |
| | 9) NOTE: PLEASE SUBMIT ALL INFORMATION |
| | FOR PROSED FIRE PUMP. IF THIS TEMPORARY? |
| | PLEASE INDICATE LOCKED ROTOR CURRENT |
| | ETC. |
| | PLEASE SUBMIT MANUFACTURE SPECS / CUT |
| | SHEETS FOR FIRE PUMP CONTROLLER / FIRE |
| | PUMP. |
| | PLANS MENTIONS FPC BY OTHERS HOWEVER IF |
| | HOOK UP IS BEING DONE UNDER THIS PERMIT |
| | , THIS INFORMATION MUST BE PROVIDED AT |
| | THIS TIME. |
| | ** PLEASE ALSO KNOW, THE INSTALLATION OF |
| | THE FIRE PUMP SHALL BE PERMITTED BY THE |
| | LICENSED CONTRACTOR QUALIFIED FOR THIS |
| | TYPE OF INSTALLATION. |
| | |
| | 10) NOTE: PLEASE SEE PLANS INDICATE ALL |
| | ELECTRICAL FEEDERS, SEC'S ETC BEING |
| | INSTALLED IN CONDUIT?? PLEASE VERIFY AND |
| | CONFIRM ON PLANS TYPE OF CONDUIT. PLEASE |
| | KNOW AS THIS IS ON AN CONSTRUCTION SITE, |
| | FOR CONSTRUCTION PURPOSE AND IF USING |
| | PVC, SCH 80 WILL BE REQUIRED. |
| | IF USING ANY KIND OF CORDS/CABLES TYPE |
| | SHALL BE INDICATED FOR EXTRA HARD |
| | SERVICE. |
| | 527, 352 ETC. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |