Plan Review Details - Permit 06082036
Plan Review Stops For Permit 06082036
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-09-26 Cont ID  
Sent By jleahy Date 2006-09-26 Time 06:37 Rev Time 0.45
Received By jleahy Date 2006-09-26 Time 06:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-13 Cont ID  
Sent By jleahy Date 2006-09-13 Time 16:32 Rev Time 0.45
Received By jleahy Date 2006-09-13 Time 15:55 Sent To  
Notes
2006-09-13 00:00:001) FROM THE DRAWINGS I CAN'T TELL WHICH
 IS THE FRONT AND WHICH IS THE BACK OF
 THE HOUSE.210.52 (E) REQUIRES AN
 OUTLET AT THE FRONT AND BACK OF THE
 RESIDENCE.
  
 2) 210.70 2B REQUIRES LIGHTING OUTLETS
 AT THE EGRESS DOOR LOCATIONS.
  
 3) ALL BEDROOM OUTLETS REQUIRE ARC FAULT
 PROTECTION210.12 B
  
 4) 210.50 D REQUIRES BATHROOM CIRCUITS
 TO BE 20 AMPERE RATED.
  
 5) NEED TO SHOW BATHROOM AND ARC FAULT
 CIRCUITS ON PANEL SCHEDULR.
  
 7) PANEL SCHEDULE SHOWS HWH ON A 2 POLE
 60 AMP. BREAKER WITH NUMBER #12 WIRE.
  
 8) YOU NEED TO LABEL ALL ROOMS ON PLAN,
 ON THE LEFT HAND SIDE THERE IS A ROOM
 THAT HAS A CLOSET CHECK CLEARANCES ON
 LIGHTS IN THIS CLOSET,

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-20 Cont ID  
Sent By adarroug Date 2006-09-20 Time 16:22 Rev Time 0.00
Received By adarroug Date 2006-09-20 Time 16:22 Sent To E
Notes
2006-09-20 00:00:00TO "JLEAHY" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-13 Cont ID  
Sent By adarroug Date 2006-09-13 Time 16:21 Rev Time 0.00
Received By adarroug Date 2006-08-28 Time 11:49 Sent To  
Notes
2006-08-28 00:00:00TO "E" BOX