Plan Review Details - Permit 06082019
Plan Review Stops For Permit 06082019
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-06-29 Cont ID  
Sent By jwitmer Date 2007-06-29 Time 12:58 Rev Time 1.10
Received By jwitmer Date 2007-06-29 Time 12:58 Sent To  
Notes
2007-06-29 13:21:30FOUNDATION REVISION FROMMONOLITHIC TO STEM WALL REV#
 4OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-12-20 Cont ID  
Sent By rnuquist Date 2006-12-20 Time 05:22 Rev Time 0.00
Received By rnuquist Date 2006-12-20 Time 05:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-17 Cont ID  
Sent By alange Date 2006-11-17 Time 10:27 Rev Time 0.00
Received By alange Date 2006-11-17 Time 10:27 Sent To  
Notes
2006-11-17 10:31:52DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
  
 6.STATE PRODUCT APPROVALS SUBMITTED ARE THE WRONG
 PAGES.PROCEED FURTHER AND SELECT THE APPROVAL FOR THE
 SELECTED PRODUCT.IT SHOULD SHOW FOR EXAMPLE,PGT,
 MODEL 701 AND APPROVAL STATUS.
 ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 10.SHOW THE FOLLOWING ON PLANS.
 R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A
 STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION SO AS TO NOT CREATE
 A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE AWAY FROM FOUNDATION
 WALLS SHALL FALL A MINIMUM OF 6 INCHES
 WITHIN THE FIRST 10 FEET.
  
 IMPORTANT:
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-03 Cont ID  
Sent By alange Date 2006-10-03 Time 08:51 Rev Time 2.50
Received By alange Date 2006-10-03 Time 08:51 Sent To  
Notes
2006-10-03 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.PAGE 3 NOT SIGNED AND SEALED.
  
 3. STRUCTURAL DESIGN CRITERIA.SHOULD
 BE ASCE 7-02 NOT ASCE 7-98.
  
 4.SIGN OWNER AGENT ON ENERGY CALCS.
  
 5.PRODUCT APPROVALS REQUIRED FOR
 HARDIE PLANK SIDING.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
 TRUSS DRAWING REQUIRED TO BE APPROVED
 PRIOR TO INSTALLATION.
  
 9.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 10.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A
 STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION SO AS TO NOT CREATE
 A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE AWAY FROM FOUNDATION
 WALLS SHALL FALL A MINIMUM OF 6 INCHES
 WITHIN THE FIRST 10 FEET.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-04-24 Cont ID  
Sent By btrobaug Date 2007-04-24 Time 09:21 Rev Time 0.50
Received By btrobaug Date 2007-04-24 Time 06:41 Sent To PC
Notes
2007-04-24 09:21:28 
  
 REVISION FOR MOVING SERVICE,REDLINED SMOKE ALARMS,
 KITCHEN GFI AND 210.63@CU./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-09-12 Cont ID  
Sent By btrobaug Date 2006-09-12 Time 16:35 Rev Time 0.75
Received By btrobaug Date 2006-09-12 Time 13:58 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-06-03 Cont ID  
Sent By adarroug Date 2008-06-03 Time 11:18 Rev Time 0.00
Received By adarroug Date 2008-06-03 Time 11:18 Sent To M
Notes
2008-06-03 11:18:22TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-12-19 Cont ID  
Sent By adarroug Date 2007-12-19 Time 16:16 Rev Time 0.00
Received By adarroug Date 2007-12-19 Time 16:16 Sent To M
Notes
2007-12-19 16:17:19TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-04-23 Cont ID  
Sent By adarroug Date 2007-04-23 Time 15:20 Rev Time 0.00
Received By adarroug Date 2007-04-23 Time 15:20 Sent To E
Notes
2007-04-23 15:20:41TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-12-01 Cont ID  
Sent By adarroug Date 2006-12-01 Time 14:09 Rev Time 0.00
Received By adarroug Date 2006-12-01 Time 14:09 Sent To B
Notes
2006-12-01 14:10:12TO "LMARTINEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-11-12 Cont ID  
Sent By adarroug Date 2006-11-12 Time 13:02 Rev Time 0.00
Received By adarroug Date 2006-11-12 Time 13:02 Sent To M
Notes
2006-11-12 13:02:38TO"TGORDON" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-04 Cont ID  
Sent By adarroug Date 2006-11-04 Time 18:47 Rev Time 0.00
Received By adarroug Date 2006-11-04 Time 18:47 Sent To Z
Notes
2006-11-04 18:48:01TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-05 Cont ID  
Sent By adarroug Date 2006-09-05 Time 09:31 Rev Time 0.00
Received By adarroug Date 2006-09-05 Time 09:31 Sent To E
Notes
2006-09-05 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-03 Cont ID  
Sent By alange Date 2006-10-03 Time 08:54 Rev Time 0.00
Received By alange Date 2006-08-28 Time 10:20 Sent To  
Notes
2006-08-28 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-06-03 Cont ID  
Sent By tgordon Date 2008-06-03 Time 16:27 Rev Time 0.30
Received By tgordon Date 2008-06-03 Time 16:27 Sent To  
Notes
2008-06-03 16:27:49REVISION TO MECH. PLAN M.1.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-12-20 Cont ID  
Sent By tgordon Date 2007-12-20 Time 13:36 Rev Time 0.30
Received By tgordon Date 2007-12-20 Time 13:36 Sent To  
Notes
2007-12-20 13:46:36PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** MECHANICAL REVISION **
 *** DENIED ***
 1) MECHANICAL PLANS ON FILE ARE SIGNED AND SEALED BY AN
 ARCHITECT (STEPHEN M. ROY) AND ONLY HE MAY MAKE
 REVISIONS TO THEM. PLEASE SUBMIT REVISED PLANS SIGNED
 AND SEALED BY THE ARCHITECT.
  
 2) PLEASE SHOW WERE THE CLOTHES DRYER VENT IS
 TERMINATING AT ON THE MECHANICAL PLAN, SEE 2004 FBC/R
 M303.4.2.
  
 3) DUCT LAYOUT ON REVISED PLAN IS FADED AND DIFFICULT
 TO READ. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, SEE F.B.C. 106.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-11-13 Cont ID  
Sent By tgordon Date 2006-11-13 Time 08:17 Rev Time 0.30
Received By tgordon Date 2006-11-13 Time 08:17 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-09-27 Cont ID  
Sent By tgordon Date 2006-09-27 Time 16:28 Rev Time 0.30
Received By tgordon Date 2006-09-27 Time 16:28 Sent To B
Notes
2006-09-27 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS ARE CALLING FOR
 TWO 12 SEER A/C SYSTEMS, AND THE MECH.
 PLANS ARE CALLING FOR TWO 12 SEER A/C
 SYSTEMS, THE TWO MUST COINCIDE, PLEASE
 CORRECT.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT ALSO, PER 2004 FBC
 13-600.3.ABC.2 .
  
 3) PLEASE NOTE ON MECHANICAL PLANS,
 CLOTHES DRYER VENT TERMINATION MUST BE A
 MIN. OF 4 FT. FROM A/C CONDENSER UNIT,
 PER 2004 FBC/M 501.2 .
  
 4) PLEASE REMOVE NOTE ON MECH. PLANS
 UNDER EQUIPMENT LISTING REGARDING 1 CFM
 PER SQ. FT..
  
 5) PLEASE SHOW THE SIZE OF THE RETURN
 AIR GRILL FOR AHU #1 ON MECH. PLANS.
  
 6) PLEASE LABEL AHU #1 LOCATION ON MECH.
 PLANS.
  
 7) SEE HIGH LIGHTS ON MECH. PLANS,
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-09-23 Cont ID  
Sent By jleech Date 2006-09-23 Time 14:34 Rev Time 0.00
Received By jleech Date 2006-09-23 Time 14:34 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-11-11 Cont ID  
Sent By mmclean Date 2006-11-11 Time 13:26 Rev Time 0.00
Received By mmclean Date 2006-11-11 Time 13:26 Sent To I
Notes
2006-11-11 13:31:19PROVISO: A SEPARATE PERMIT WILL BE PULLED FOR THE
 POOL/SPA.
 PROVISO: A SEPARATE PERMIT WILL BE PULLED FOR THE SHED.
 SHED MUST MEET THE SIDE & REAR SETBACK OF 5FT AND 6FT
 SEPARATION FROM THE ANY STRUCTURE.
 PROVISO: THE PROPOSED A/C UNITS SHALL NOT BE CLOSER
 THAN 1FT FROM SIDE PROPERTY LINE.
 PROVISO: THE NEW STRUCTURE WILL BE BUILT AT THE
 REQUIRED 5FT MINIMUM SIDE SETBACK WITH BOTH SIDES
 TOTALLING 15FT OR MORE.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-09-04 Cont ID  
Sent By mmclean Date 2006-09-04 Time 08:21 Rev Time 0.00
Received By mmclean Date 2006-09-04 Time 08:21 Sent To I
Notes
2006-09-04 00:00:00DENIED,
 1. NEED TO PROVIDE THE DIMENSION OF THE
 PROPOSED WALKWAY AND DRIVEWAY (LENGTH &
 WIDTH)ON TWO COPIES OF SITEPLAN.
 2. NEED TO PROVIDE THE DIMENSION OF THE
 EXISTING WALKWAY ON TWO COPIES OF
 SITEPLAN.
  
 NOTE:MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE, WHICHEVER IS LESS WITHIN THE
 FIRST 25FT FRONT SETBACK.
  
 3. ONLY ALLOWED TO HAVE 216.5SQ OF BRICK
 WITHIN THE FIRST 25FT FRONT SETBACK.
 4. PLEASE PROVIDE A SITEPLAN THAT CLEARLY
 SHOWS THE SIDE SETBACKS OF THE PROPOSED
 ADDITION (CANNOT READ THE SETBACKS).
  
 NOTE: SEPARATE PEMIT WILL BE PULLED FOR
 THE SHED (MUST MEET THE CURRENT
 SIDE/REAR SETBACK AND MUST BE 6FT FROM
 THE MAIN STRUCTURE).
  
 NOTE: SEPARATE PERMIT WILL BE PULL FOR
 POOL/SPA WITH FENCE.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720