| 2006-09-20 00:00:00 | |
| | |
| | BUILDING REVIEW 2ND CHECKLIST |
| | (INFORMATION PROVIDED ON FIRST CHECKLIST |
| | WAS NOT PROVIDED): |
| | |
| | ***NOTE: COMMENTS IN CAPITAL LETTERS ARE |
| | ORIGINAL COMMENTS. COMMENTS IN LOWER |
| | CASE LETTERS ARE THE RESPONSE TO |
| | CONTRACTOR'S SUBMITTAL. |
| | |
| | 1- PROVIDE KEY PLAN AND WINDOWS AND |
| | DOORS SIZES. TO VERIFY EGRESS |
| | COMPLIANCE. SEC. 106.1.2 CITY AMENDMENTS |
| | TO FBC 2004. |
| | |
| | * NO DONE. |
| | |
| | 2- PROVIDE OPENING PROTECTION (SHUTTERS |
| | OR ANY OTHER MEANS OF GLAZING |
| | PROTECTION) AS REQUIRED BY SECTION 507.3 |
| | FBC 2004, EXISTING BUILDING. |
| | PROVIDE PRODUCT APPROVAL, KEY PLAN AND A |
| | COMPLETE INSTALLATION SCHEDULE. SEE |
| | ATTACHED SAMPLE OF INSTALLATION SCHEDULE |
| | FROM THE CITY IMPLEMENTATION STANDARD |
| | FOR WIND-BORNE DEBRIS IMPACT PROTECTION. |
| | |
| | * NO DONE. |
| | |
| | 3- ACCORDING TO INSPECTOR'S |
| | PRE-INSPECTION AND PICTURES BUILDING HAS |
| | ROTTEN AREAS AT OPENINGS FRAMING. NEED |
| | TO REPLACE FRAMING AS REQUIRED. PROVIDE |
| | COMPLETE STRUCTURAL FRAMING DETAILS FOR |
| | DOORS AND WINDOWS INSTALLATION. SEC. |
| | 106.1.2 OF CITY AMENDMENTS TO FBC 2004. |
| | |
| | * NO DONE. |
| | |
| | 4- THIS PERMIT APPLICATION IS FOR DOORS |
| | AND WINDOWS REPLACEMENT ONLY. ACCORDING |
| | TO THE INSPECTOR'S PICTURES THERE IS |
| | CONSIDERABLE STRUCTURAL DAMAGE TO THE |
| | HOUSE. PROVIDE COMPLETE ENGINEERING AND |
| | STRUCTURAL PLANS TO PERFORM ALL |
| | STRUCTURAL REPAIRS. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | * NO DONE. NO INFORMATION SUBMITTED FOR |
| | STRUCTURAL REPAIRS EXCEPT FOR RAFTER |
| | REPAIRS WHICH WAS DONE UNDER ANOTHER |
| | PERMIT. THIS HOUSE NEED COMPLETE |
| | ENGINEERING DRAWINGS TO PROVIDE |
| | STRUCTURAL STABILITY OF THE BUILDING. |
| | SECTION 106.1.2 CITY AMENDMENTS TO FBC |
| | 2004. |
| | |
| | 5- THERE ARE 2 DIFFERENT PRODUCT |
| | APPROVALS FOR DOORS SUBMITTED. SUBMIT |
| | ONLY THE ONE FOR THE SPECIFIC DOOR TO BE |
| | INSTALLED. |
| | |
| | * ONLY ONE COPY OF DOOR PRODUCT APPROVAL |
| | WAS SUBMITTED. NEED 2 COPIES. |
| | |
| | ** NOW THERE ARE 3 DIFFERENT PRODUCT |
| | APPROVALS SUBMITTED FOR SINGLE HUNG |
| | WINDOWS. ONE IS NOA 05-0729.03 FL 6585 |
| | FOR TRACO WINDOWS. |
| | THE OTHER ONE IS FL 6111 FOR H-R |
| | WINDOWS, BUT THE DRAWINGS SUBMITTED ARE |
| | FOR SIMONTON WINDOWS. FL 6111 IS FOR H-R |
| | WINDOWS, NOT FOR SIMONTON WINDOWS. |
| | IF USING ALL 3 DIFFERENT WINDOW |
| | MANUFACTURERS, THEN PROVIDE COMPLETE |
| | PRODUCT APPROVAL PACKAGE FOR EACH ONE. |
| | (NOTE: TRACO WINDOWS PRODUCT APPROVAL |
| | PACKAGE IS COMPLETE. H-R WINDOWS AND |
| | SIMONTON WINDOWS ARE THE ONES WHO NEED |
| | COMPLETE PACKAGE). |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |