Plan Review Details - Permit 06081976
Plan Review Stops For Permit 06081976
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2007-04-05 Cont ID  
Sent By rmcdouga Date 2007-04-05 Time 17:24 Rev Time 0.00
Received By rmcdouga Date 2007-04-05 Time 17:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-03-22 Cont ID  
Sent By rmcdouga Date 2007-03-22 Time 07:07 Rev Time 0.00
Received By rmcdouga Date 2007-03-22 Time 06:39 Sent To  
Notes
2007-03-22 06:50:27REVISED SHEETS A5.0, A7.0 AND A7.3 ARE OK FOR BUILDING
 REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-01-17 Cont ID  
Sent By rmcdouga Date 2007-01-17 Time 16:38 Rev Time 0.00
Received By rmcdouga Date 2007-01-17 Time 16:38 Sent To  
Notes
2007-01-17 16:39:10CHANGE OF CONTRACTOR AND ISSUE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-01-16 Cont ID  
Sent By rmcdouga Date 2007-01-16 Time 08:43 Rev Time 0.00
Received By rmcdouga Date 2007-01-16 Time 08:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-12-18 Cont ID  
Sent By rmcdouga Date 2006-12-18 Time 08:01 Rev Time 0.00
Received By rmcdouga Date 2006-12-18 Time 07:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-10-27 Cont ID  
Sent By rmcdouga Date 2006-10-27 Time 14:23 Rev Time 0.00
Received By rmcdouga Date 2006-10-27 Time 14:23 Sent To  
Notes
2006-10-27 15:09:08DENIED BY BUILDING
  
 1) RECORDED COPY OF THE NOC WILL BE REQUIRED.
  
 2) PLANS ARE REQUIRED TO HAVE THE CITY PLACE APPROVAL
 STAMP ON THEM.
  
 3) THE CERTIFICATE OF AUTHORIZATION NUMBER IS REQUIRED
 FOR THE ENGINEERING BUSINESS OF MICHAUD, COOLEY,
 ERICKSON WHICH APPEARS IN THE TITLE BLOCK. SEE FAC
 61G15-23.002 AND FS CHAPTER 471.
  
 4) SUBMIT PRODUCT APPROVALS FOR THE STOREFRONT DOORS
 AND THE HOLLOW METAL EXTERIOR DOOR.
  
 5) THE FLORIDA PRODUCT APPROVAL COVER SHEET SUBMITTED
 FOR THE STOREFRONT IS FOR VISTAWALL GROUP AND THE NOA
 IS FOR VISTAWALL ARCHITECTURAL PRODUCTS. THESE ARE NOT
 THE SAME MANUFACTURERS. THERE IS NO FL PRODUCT APPROVAL
 FOR VISTAWALL ARCHITECTURAL PRODUCTS. HOWEVER, THE
 MIAMI DADE NOA IS ACCEPTABLE WITHOUT FL APPROVAL .
  
 6)THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT PER CITY ADMINISTRATIVE CODE 106.3.
  
 7) THE STOREFRONT SYSTEM IS SPECIFIED INCORRECTLY ON
 THE PLANS AS FG-500. THE PRODUCT APPROVAL IS FOR
 FG-5000. PLEASE CORRECT. SEE SHEETS A6.0, A6.10,
 A6.11.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-20 Cont ID  
Sent By rmcdouga Date 2006-09-20 Time 15:48 Rev Time 0.00
Received By rmcdouga Date 2006-09-20 Time 07:03 Sent To  
Notes
2006-09-21 00:00:00DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE TITLE BLOCK IS MISSING THE FIRM
 NUMBER FOR THE ARCHITECT BUSINESS. SEE
 FAC 61G1-16.004.
  
 3) FBC 13-400.3.ABC.1THE FLA/COM
 PERFORMANCE CALCULATION PROCEDURES
 DEMONSTRATING CODE COMPLIANCE FOR
 METHODS A AND B, AND FORM 400C
 DEMONSTRATING CODE COMPLIANCE FOR METHOD
 C SHALL BE PREPARED, SIGNED AND SEALED
 BY AN ARCHITECT OR ENGINEER REGISTERED
 IN THE STATE OF FLORIDA. THE FORMS
 REQUIRE THE RAISED SEAL AND ORIGINAL
 SIGNATURE OF THE ARCHITECT OR ENGINEER.
 NOTE: ONLY ONE OF THE METHODS LISTED
 ABOVE IS REQUIRED TO BE SUBMITTED (TWO
 COPIES).
  
 4) FBC 13-400.3.ABC.2 THE BUILDING?S
 OWNER, THE OWNER?S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY
 THE OWNER SHALL CERTIFY TO THE BUILDING
 OFFICIAL THAT THE BUILDING IS IN
 COMPLIANCE WITH THE REQUIREMENTS OF
 CHAPTER 13 OF THIS CODE PRIOR TO
 RECEIVING THE PERMIT TO BEGIN
 CONSTRUCTION OR RENOVATION.
  
 5) SPECIFY THE LEVEL OF ALTERATION, AS
 SPECIFIED IN THE 2004 FBC EXISTING
 BUILDING CODE, FOR THE PROJECT ON THE
 PLANS.
  
 6) SPECIFY THE BUILDINGS CONSTRUCTION
 TYPE USING THE 2004 FBC DESIGNATIONS.
 SPECIFY A OR B.
  
 7) ON SHEET A0.0 THE EGRESS WIDTH INCHES
 PER OCCUPANT FOR THE DOOR AND STAIR
 WIDTHS ARE INCORRECT. THEY ARE 0.2 FOR
 DOORS AND 0.3 FOR STAIRWAYS. SEE FBC
 TABLE 1005.1.
  
 8) SUBMIT PRODUCT APPROVALS FOR EXTERIOR
 DOORS, STOREFRONTS, WINDOWS, ETC.
 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 9 )W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 10) INDICATE THE REQUIRED CLEAR FLOOR
 SPACES FOR ALL FIXTURES ON THE PLANS
 WITH LINES. FBC 11-4.2.4 & 11-4.22.3.
  
 11) FBC 11-4.22.2ALL DOORS TO
 ACCESSIBLE TOILET ROOMS SHALL COMPLY
 WITH SECTION 11-4.13 . DOORS SHALL NOT
 SWING INTO THE CLEAR FLOOR SPACE
 REQUIRED FOR ANY FIXTURE.
  
 12) CONSTRUCTION BARRICADE MUST COMPLY
 WITH FBC 3306.5 AND 3306.6.
  
 13) SUBMIT INFORMATION INDICATING THE
 FLAME RESISTANCE OF THE FABRIC AWNING
 MATERIAL. FBC 3105.3.1
  
 14) FABRIC SHALL BE QUICK REMOVAL OR
 BREAKAWAY DESIGN. SEE FBC 3105.4.2.1.
  
 15) ALL EXTERIOR SIGNS WILL REQUIRE
 SEPARATE PERMITS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-03-14 Cont ID  
Sent By dpalmer Date 2007-03-14 Time 09:21 Rev Time 0.00
Received By dpalmer Date 2007-03-13 Time 16:48 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-01-13 Cont ID  
Sent By dpalmer Date 2007-01-13 Time 15:07 Rev Time 0.00
Received By dpalmer Date 2007-01-13 Time 14:36 Sent To  
Notes
2007-01-13 15:09:06LV SECURITY REDLINED ON PLANS TO BE A SEPARATE
 PERMIT..
 ELECTRICAL PLANS STAMPED.
 VOIDED OLD ENERGY CALCULATIONS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-12-09 Cont ID  
Sent By dpalmer Date 2006-12-09 Time 18:56 Rev Time 0.00
Received By dpalmer Date 2006-12-09 Time 18:05 Sent To I
Notes
2006-12-09 18:58:50** UNSAT 3RD REVIEW**
  
 1) NOTE: PLEASE SEE METHOD "B" CALCULATIONS FOR
 LIGHTING ALLOWANCES AND DESIGN WATTAGE AS SHOWN IS NOT
 YET CLEAR. PLEASE SEE MAXIMUM WATTAGE AS SHOWN FOR
 COMPLETE DESIGN IS STATED AS 7691.6 BASED ON TABLES IN
 THE FBC AND AS STATED ON PLANS. PLEASE EXPLAIN HOW THE
 DESIGN WATTAGE IS 11,354?
 PLEASE KNOW BASED ON METHOD "B" AND SQ FT ENTERED AS
 4310 THIS WILL SHOW AND INDICATE A "PASS" RESULT.
 PLEASE KNOW AS PER OUR CONVERSATIONS OVER THE PHONE
 AREAS OF TRADES OFFS WERE PERMITTED AS STATED IN
 13-415.2.B.1 ITEM (4), HOWEVER AS SHOWN THE WATTAGE
 STILL EXCEEDS ALLOWANCES AS NO AREAS SHOW AN DESIGN
 SUBSTANTIALLY LESS WHICH WOULD PERMIT ADDITIONAL
 WATTAGE IN OTHER AREAS. AS PER CONFERENCE CALLS, THE
 DESIGN WATTAGE TOTALS WOULD NOT EXCEED TOTAL ALLOWED.
 PLEASE SEE 13-415.2.B.2. PLEASE SEE IF THESE ARE BEING
 USED, THEN PLEASE KNOW THIS WILL NEED TO BE SHOWN ON
 PLANS UNLESS FIGURED AND SHOWN INTO METHOD "B". IT IS
 OUR UNDERSTANDING THAT METHOD "B" DOES NOT PERMIT THIS
 BREAK DOWN AS LISTED FOR ADDITIONAL POWER ALLOWANCES,
 THEREFORE A TABLE MAY BE USED ANDWILL BE REQUIRED TO
 BE PLACED ON PLANS WHICH PROVIDES A DETAILED BREAKDOWN
 OF AREAS ETC. ( SHEET E-4 , LOWER RIGHT HAND CORNER)
 PLEASE SEE SECTIONS: 1. , 2. , 3. (1)(2).
  
 2) NOTE: PLEASE BE SURE ALL RESPONSE LETTERS FROM
 DESIGN TEAM ARE DATED TO ALLEVIATE ANY CONFUSION OF
 WHICH NOTES ARE BEING REPLIED TO.
 THIS WILL SUBSTANTIALLY HELP IN THE REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-12-09 18:05:37PLANS REMOVED FROM INCOMING, WILL BE ROUTED BACK TO
 INCOMINGWAITING FOR BOB BOARD ONCE REVIEW IS DONE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-10-24 Cont ID  
Sent By dpalmer Date 2006-10-24 Time 20:17 Rev Time 0.00
Received By dpalmer Date 2006-10-24 Time 19:01 Sent To  
Notes
2006-10-24 20:17:14**** UNSAT2ND REVIEW***
  
 ** IMPORTANT**
 PLEASE KNOW, ANY AND ALL PLANS FOR ANY WORK BEING
 PERFORMED ON "CITY PLACE" PROPERTY IS REQUIRED TO
 CONTAIN THE "CITY PLACE" APPROVAL STAMP , SIGNED BEFORE
 PLANS ARE SUBMITTED OR CAN BE ISSED FOR PERMIT.
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW WHICH ARE
 STILL IN NEED OF ADDRESSING.
 PLEASE ALSO SEE NEW COMMENTS BASED ON CHANGES ON
 PLANS.
  
 PLEASE ALSO SEE NEW NOTES FOR ELECTRICAL ITEMS WHICH
 WERE MISSED BY THIS REVIEWER ON PREVIOUS REVIEW,
 HOWEVER THESE ARE NOW COMMENTED ON THIS REVIEW. CODE
 COMPLIANCE IS STILL REQUIRED WHETHER OR NOT COMMENT WAS
 MADE ON PREVIOUS REVIEW.
  
 ** PLEASE SEE COMMENTS BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW AND NEW NOTES ADDED TO BOTTOM.
  
  
 1) NOTE: NO/ OK. PLEASE SEE "A" SHEETS IF PRACTICING AS
 AN INDIVIDUAL THEN A CA# IS NOT REQUIRED. PLEASE SEE
 HOWEVER ALL SHEETS ARE REQUIRED TO CONTAIN THE PRINTED
 LICENSE NUMBER FOR SAID INDIVIDUAL. THIS IS REQUIRED ON
 ALL SHEETS AND FOR ALL TRADES WHICH CONTAIN THE TITLE
 BLOCK FOR ARCHITECT.
 PLEASE SEE BASED ON PREVIOUS REVIEWIT WAS NOT TYPED
 FOR THE MISSING CERTIFICATE OF AUTHORIZATION NUMBER FOR
 ENGINEERING FIRM. IN ERROR IT WAS TYPED UP FOR THE
 ARCHITECTURAL FIRM. PLEASE SEE THE SECTIONS WHICH
 SHOULD HAVE BEEN NOTED ARE FAC 61G15-23.002 ANDFS
 471.023 FOR ENGINEERS AND FIRMS. PLEASE SEE MISSING
 CERTIFICATE OF AUTHORIZATION NUMBER AND PLEASE SEE
 MISSING THE PRINTED NAME OF THE INDIVIDUAL AND LICENSE
 NUMBER FOR EACH OF THE SIGNED AND SEALED DOCUMENTS.
 THIS IS REQUIRED ON ALL ENGINEERING SHEETS AND SHEETS
 CONTAINING THE TITLE BLOCK FOR ENGINEERING
 FIRM.(INCLUDING THE CA # ON "A" SHEETS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING REQUIRED
 INFORMATION ON TITLE BLOCK FOR
 ARCHITECTURAL FIRM. PLEASE SEE MISSING
 REQUIRED LICENSE NUMBER FOR THE FIRM.
 (CERTIFICATE OF AUTHORIZATION NUMBER).
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G1-16.004 AND FLORIDA STATUES 481.219.
 **THIS IS REQUIRED ON ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
  
 2) NOTE: OK, HOWEVER SEE NEW NOTES PER PLANS
 SUBMITTED.
  
 3) NOTE: OK, NEW SEAL PROVIDED, HOWEVER SEE NEW NOTES
 PER PLANS SUBMITTED.
  
 4) NOTE:NO,PLEASE SEE MULTIPLE SETS OF CALCULATIONS
 ARE SUBMITTED. PLEASE ONLY SUBMITTED THE RELEVANT CALCS
 FOR SCOPE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FLORIDA ENERGY EFF.
 FORMS SENT IN ARE NOT SIGNED, DATED AND
 SEALED BY THE ENGINEER/RESPONSIBLE
 DESIGNER OF RECORD./ PLEASE KNOW, THESE
 MAY NOT CONTAIN PHOTO-COPIED SIGNATURES
 AS SUBMITTED.
 PLEASE ALSO SEE THREE SETS OF ENERGY
 CALCULATIONS WERE SUBMITTED. METHODS A ,
 B AND C???
 PLEASE SEE FBC CHAPTER 13 FOR PERMITTED
 METHOD ONLY PERMITTED IN THE SCOPE OF
 WORK BEING DONE.
 13-101.1.3, 13-415.1.AB.1
  
 5) NOTE:NO,PLEASE SEE SCHEDULING WAS NOT INDICATED.
 PLEASE SEE NO MAX OVER TIMES SHOWN FOR THE DEVICES
 CHOSEN AND SHOWNON PLANS. PLEASE SEE "OCCUPANT
 SENSOR" TYPE DEVICES REQUIRES A MAX OF 30MINS WHERE
 NOTE #8 MENTIONS 4HRS. PLEASE ALSO BE SURE TO CORRELATE
 THE SYMBOLS ON PLANS WITH THE SYMBOL LEGEND FOR TYPE OF
 DEVICE.
 PLEASE SEE NO PERFORMANCE CALCULATIONS WERE SUBMITTED
 BASED ON TABLES AND PERMITTED MAXIMUM WATTAGE PERMITTED
 FOR ACTUAL SPACE. PLEASE SEE SPACE DETERMINATION FOR
 SOME AREAS AS"FINE STORAGE" DOES NOT FIT FOR USE AND
 ITEMS IN STORAGE. PLEASE PROVIDE A SPACE BY SPACE
 CONSIDERATION. THIS MAY BE PLACED ON PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE THE DETAILS FOR
 THE LIGHTING CONTROL SYSTEM BEING
 PROPOSED AND COMPLIANCE WITH
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE SEPARATE SPACES CONTAINING
 FLOOR TO CEILING HEIGHT PARTITIONS AND
 SEPARATE CONTROLS/OVER-RIDES REQUIRED.
 PLEASE KNOW, THE OVER RIDES SHALL BE
 LOCATED SUCH AS THE OCCUPANT VISUALLY
 SEE THE LIGHTING BEING CONTROLLED.
 PLEASE SPECIFY THE TYPE AND TIMES
 PERMITTED ON THE OVER RIDE DEVICES.
 (4HRS MAX TIMER TYPE AND 30MINS MAX ON
 OCCUPANT SENSOR TYPE).
 PLEASE PROVIDE SCHEDULING FOR SYSTEM.
 PLEASE SEE POINTS OF INGRESS AND EGRESS
 FOR CONTROL.
 PLEASE PROVIDE LIGHTING POWER DENSITIES
 PER THE TABLES IN CHAPTER
 13.415.2.ABC.1, 415.2.C.1, 415.2.B.1
  
 6) NOTE: OK.
  
 7) NOTE:NO, RESPONSE MENTIONS PLANS DESIGN PER
 CODES, HOWEVER THE CODES ARE REQUIRED TO BE STATED ON
 PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE THE FOLLOWING
 CODES ARE REFLECTED AS RELEVANT TO PLANS
 AND DESIGN.
 2002 NFPA-70, 2002 NFPA-72, 2003
 NFPA-101 AND 2004 FBC.
  
 8) NOTE: OK.
  
 9) NOTE: OK.
  
 10) NOTE: OK, HOWEVER SEE NEW NOTES.
  
 11) NOTE: OK.
  
 12) NOTE: OK.
  
 ** NEW NOTES ***
  
 13) NOTE: PLEASE SEE WHEN SIGNING AND SEALING PLANS
 THEY ARE ALSO REQUIRED TO BE DATED PER FS 471.025.
 PLEASE SEE OTHER SHEETS AND TRADES ALSO.
  
 14) NOTE: PLEASE CORRELATE RISER WITH PANELS. PLEASE
 SEE PANEL "A" IS BEING SHOWN AS 225A MCB YET RISER
 SHOWS 400A MCB.
  
 15) NOTE: PLEASE KNOW, IF INDEED THIS PANEL "A" IS 400A
 MCB?, PLEASE SEE 240.21C AS THE CONDUCTORS ARE RATED
 FOR 380A'S PER 310.16 FOR 500MCM'S. WHEN ON THE
 SECONDARY SIDE OF A TRANSFORMER , IT MUST TERMINATE IN
 OCP WHICH LIMITS THE AMPERAGE ON THE CONDUCTOR. PLEASE
 SEE 310.16,240.21,110.14 ETC. IT APPEARS HOWEVER THAT
 BASED ON PANEL "A" BEING SHOWN AS 225A'S, THE 500'S AS
 SHOWN WOULD BE OVER.
  
 16) NOTE: PLEASE SEE MAX OCP FOR THE FEEDING THE
 TRANSFORMER IS BASED ON 450.3 TABLES (125%). PLEASE SEE
 NEXT SIZE UP WOULD BE 175A PER 240.6. PLEASE SEE THE
 200A OCP IS TOO HIGH. (PLEASE SEE THERE ARE EXCEPTIONS,
 HOWEVER TRANSFORMER AS SHOWN DOES NOT MEET THEM).
  
 17) NOTE: PLEASE VERIFY THE FEED AND OCP AT THE
 EXISTING MAIN WHICH FEEDS PANEL "H". PLEASE SEE THIS
 PANEL LOAD EXCEEDS WHAT APPEARS TO BE A 150A OCP
 DEVICE, ALTHOUGH 200A RATED FEEDERS ARE FEEDING THIS.
 PLEASE CLARIFY THIS?
 240.4,240,310.16,408. ETC
  
  
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENT FROM OTHER TRADES WHICH MAY
 AFFECT THE ELECTRICAL PLANS/ DESIGN.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-10-24 19:01:25IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-11 Cont ID  
Sent By dpalmer Date 2006-09-11 Time 11:11 Rev Time 0.00
Received By dpalmer Date 2006-09-10 Time 20:32 Sent To  
Notes
2006-09-11 00:00:00REVIEW IN PROGRESS
 **** UNSAT ****
  
 1) NOTE: PLEASE SEE MISSING REQUIRED
 INFORMATION ON TITLE BLOCK FOR
 ARCHITECTURAL FIRM. PLEASE SEE MISSING
 REQUIRED LICENSE NUMBER FOR THE FIRM.
 (CERTIFICATE OF AUTHORIZATION NUMBER).
 PLEASE SEE FLORIDA ADMINISTRATIVE OCDE
 61G1-16.004 AND FLORIDA STATUES 481.219.
 **THIE IS REQUIRED ON ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
  
 2) NOTE: PLEASE SEE MEP AND F SHEETS.
 PLEASE SEE MECHANICAL, PLUMBING AND FIRE
 WHICH ALL CONTAIN A "RUBBER STAMP"
 INSTEAD OF THE REQUIRED "RAISED SEAL"
 PLEASE SEE FS 471.025, AN FAC
 61G15-23.001.
 ** THIS IS REQUIRED FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S).
  
 3) NOTE: PLEASE SEE FAC 61G15-23.001. AS
 THE SEAL USED BY THE ENGINEER ON THE
 ELECTRICAL SHEETS IS NO LONGER VALID.
 PLEASE SEE THE RULING ABOVE CHNAGED IN
 FEB OF 2004 WHICH REQUIRED ALL ENGINEERS
 TO OBTIAN NEW SEALS WHICH CONTAIN THE
 WORDING OF "LICENSE" INSTEAD OF THE
 PREVIOUS WORDING OF "CERTIFICATE".
 PLEASE KNOW THAT AN EXTENSION FOR ALMOST
 2YRS WAS GRANTED TO THE DATE DEC 31ST,
 2005 ONLY.
  
 4) NOTE: PLEASE SEE FLORIDA ENERGY EFF.
 FORMS SENT IN ARE NOT SIGNED, DATED AND
 SEALED BY THE ENGINEER/REPOSIBLE
 DESIGNER OF RECORD./ PLEASE KNOW, THESE
 MAY NOT CONTAIN PHOTO-COPIED SIGNATURES
 AS SUBMITTED.
 PLEASE ALSO SEE THREE SETS OF ENGERGY
 CALCULATIONS WERE SUBMITTED. METHODS A ,
 B AND C???
 PLEASE SEE FBC CHAPTER 13 FOR PERMITTED
 METHOD ONLY PERMITTED IN THE SCOPE OF
 WORK BEING DONE.
 13-101.1.3, 13-415.1.AB.1
  
 5) NOTE: PLEASE PROVIDE THE DETAILS FOR
 THE LIGHTING CONTROL SYSTEM BEING
 PROPOSED AND COMPLIANCE WITH
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE SEPARATE SPACES CONTAINING
 FLOOR TO CEILING HEIGHT PARTITIONS AND
 SEPARATE CONTROLS/OVER-RIDES REQUIRED.
 PLEASE KNOW, THE OVER RIDES SHALL BE
 LOCATED SUCH AS THE OCCUPANT VISUALLY
 SEE THE LIGHTING BEING CONTROLLED.
 PLEASE SPECIFY THE TYPE AND TIMES
 PERMITTED ON THE OVER RIDE DEVICES.
 (4HRS MAX TIMER TYPE AND 30MINS MAX ON
 OCCUPANT SENSOR TYPE).
 PLEASE PROVIDE SCHEDULING FOR SYSTEM.
 PLEASE SEE POINTS OF INGRESS AND EGRESS
 FOR CONTROL.
 PLEASE PROVIDE LIGHTING POWER DENSITIES
 PER THE TABLES IN CHAPTER
 13.415.2.ABC.1, 415.2.C.1, 415.2.B.1
  
 6) NOTE: PLEASE BE SURE ALL PLANS ARE
 "ATTACHED" INTO TWO COMPLETE SETS.
 PLEASE SEE PLANS SUBMITTED ARE LOOSE AND
 ARE NOT ATTACHED IN ANY FASHION. PLEASE
 DO SO.
 106.1 FBC ADMIN SECT
  
 7) NOTE:PLEASE BE SURE THE FOLLOWING
 CODES ARE REFLECTED AS RELEVANT TO PLANS
 AND DESIGN.
 2002 NFPA-70, 2002 NFPA-72, 2003
 NFPA-101 AND 2004 FBC.
  
 8) NOTE: PLEASE VERIFY AND PROVIDE AN
 EXTENDED NOTE FOR "LOCK OFF" DEVICES.
 PLEASE KNOW, THAT THE "LOCK OFF" DEVICE
 SHALL BE AN INTEGRAL PART OF THE CIRCUIT
 BREAKER. THE "LOCK OFF" DEVICES BEING
 PROPOSED IN LEIU OF DISCONNECTS REQUIRED
 BY CODE SHALL CONTAIN THIS TYPE OF BRKR.
 PLEASE KNOW THIS AHJ DOES NOT ACCEPT
 "SNAP ON" TYPE WHICH CAN BE EASILY
 REMOVED OR "FALL OFF" WHEN A PANEL COVER
 IS REMOVED.
 110.3, 90.7, 90.4
  
 9) NOTE: PLEASE SEE THAT THE COLOR
 CODING FOR 277/480V SYSTEMS SHALL BE AS
 FOLLOWS.
 BROWN, PURPLE, YELLOW.
 PLEASE ADJUST AS "ORANGE" AS STATED IN
 THE NEC IS FOR OPEN DELTA, 120/240V
 "HIGH-LEG" ONLY.
 PLEASE KNOW EXISTING WIRING IN SYSTEMS
 IN THIS JURISDICTION AND THE ALL OTHER JURISDICTIONS
 LOCATED PALM BEACH COUNTY
 CONTAIN THE ABOVE COLOR CODING FROM
 PREVIOUS LOCAL AMENDMENTS.
 215, 90.4, 310.12
  
 10) NOTE: PLEASE SEE MISSING THE
 "EQUIPMENT GROUNDING CONDUCTOR" ON THE
 PRIMARY SIDE OF THE TRANSFORMER.
 250.110,250.122, ETC
  
 11) NOTE: PLEASE INCLUDE ALL CONDUCTOR
 SIZES ON PANEL SCHEDULE. PLEASE
 CORRELATE WITH ALL OCP DEVICES. 240.4,310.16,408.4
  
 12) NOTE: PLEASE VERIFY THE SHOW WINDOW
 RECEPTS SPACING. AS SHOWN ON PLANS THERE
 SEEMS TO BE WINDOWS MISSING REQUIRED
 RECEPTS AND OTHERS WHERE THE SPACING
 DOES NOT SEEM TO MEET CODE.
 210.62
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENT FROM OTHER TRADES WHICH MAY
 AFFECT THE ELECTRICAL PLANS/ DESIGN.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2006-09-10 00:00:00IN ELEC FOR REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-04-05 Cont ID  
Sent By mawillia Date 2007-04-05 Time 12:38 Rev Time 0.00
Received By mawillia Date 2007-04-05 Time 12:29 Sent To  
Notes
2007-04-05 12:36:34*****APPROVED*****
  
  
  
 REVISED SHEETS A5.0,A7.0, AND A7.3REVIEWED;SINCE
 LIFE AND FIRE SAFETY CONCERNS WERE NOT AFFECTED, NO
 FIRE STAMPING NEEDED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-01-16 Cont ID  
Sent By mawillia Date 2007-01-16 Time 14:21 Rev Time 0.00
Received By mawillia Date 2007-01-16 Time 14:21 Sent To B
Notes
2007-01-16 14:23:00*****APPROVED*****
  
  
 PLAN SHEETS E-1 AND FS-1 WERE STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-12-18 Cont ID  
Sent By mawillia Date 2006-12-18 Time 10:24 Rev Time 0.00
Received By mawillia Date 2006-12-18 Time 10:24 Sent To  
Notes
2006-12-18 10:27:18*****PROVISO*****
  
  
  
  
 TO BE STAMPED WHEN ALL OTHER PLAN REVIEW HAVE BEEN
 SATISFIED

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-11-01 Cont ID  
Sent By mwennerg Date 2006-11-01 Time 10:05 Rev Time 0.00
Received By mwennerg Date 2006-11-01 Time 10:05 Sent To  
Notes
2006-11-01 10:12:58***PROVISO***
  
 PLEASE SEE OTHER REVIEW COMMENTS REGARDING REQUIREMENTS
 AND COMPLY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-09-22 Cont ID  
Sent By mawillia Date 2006-09-22 Time 13:49 Rev Time 0.00
Received By mawillia Date 2006-09-22 Time 13:40 Sent To  
Notes
2006-09-22 00:00:00*****UNSAT******
  
  
  
  
  
 1.) STRUCTURES UNDERGOING CONSTRUCTION,
 ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.
  
 2.) ACCUMULATIONS OF COMBUSTIBLE WASTE
 MATERIAL AND DUST DEBRIS SHALL BE
 REMOVED FROM THE STRUCTURE AND ITS
 IMMEDIATE VICINITY AT THE END OF THE
 SHIFT OR MORE FREQUENTLY AS NECESSARY
 FOR SAFE OPERATIONS.
  
 3.) WHERE THE BUILDING IS PROTECTED BY
 FIRE PROTECTION SYSTEMS, SUCH SYSTEMS
 SHALL BE MAINTAINED OPERATIONAL AT ALL
 TIMES DURING ALTERATION.
  
 4.) WHEN IT IS NECESSARY TO SHUT DOWN A
 FIRE PROTECTION SYSTEM, THE FIRE
 DEPARTMENT WILL BE NOTIFIED WHEN THE
 SYSTEM IS SHUT DOWN AND WHEN IT IS
 RETURNED TO SERVICE.
  
 5.) IF THE SCOPE OF THE INTERIOR
 BUILDOUT REQUIRES MODIFICATION OF FIRE
 SPRINKLER OR FIRE ALARM SYSTEM, SEPARATE
 PERMIT AND SHOP DRAWINGS/PLANS ARE TO BE
 SUBMITTED.
  
 6.) EXPLAIN HOW EMERGENCY FIRE DEPARMENT
 RESPONSE CAN BE ACCOMPLISHED WHEN THE
 BARRICADE IS ERECTED. WILL ACCESS TO
 FIRE HYDRANT(S) OR OTHER FIRE DEPARTMENT
 CONNECTIONS BE HAMPERED/OBSTRUCTED?
  
 7.) NFPA 101,2003 EDITION, AND FLORIDA
 FIRE PREVENTION CODE, 2004 EDITION,
 SHALLBE REFERENCED.
  
 8.) ON THE APPROPIATE STOREFRONT &
 ELEVATION SHEET, SHOW/DISPLAY THE
 NUMERICAL ADDRESS ON THE STRUCTURE AS
 WELL AS THE STORE'S SUITE NUMBER. IF
 USED, HURRICANE SHUTTERS SHALL NOT BE
 PERMITTED TO COVER OR CONCEAL ADDRESS.
  
 9.) INTERIOR FINISH FOR WALLS AND
 CEILING IN EXIT CORRIDOR SHALL BE CLASS
 "A" OR CLASS "B".
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-03-10 Cont ID  
Sent By adarroug Date 2007-03-10 Time 13:12 Rev Time 0.00
Received By adarroug Date 2007-03-10 Time 13:12 Sent To B
Notes
2007-03-10 13:12:55TO "COMM" BD#21

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-10 Cont ID  
Sent By adarroug Date 2007-03-10 Time 13:07 Rev Time 0.00
Received By adarroug Date 2007-03-10 Time 13:07 Sent To E
Notes
2007-03-10 13:08:11TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-01-09 Cont ID  
Sent By adarroug Date 2007-01-09 Time 11:33 Rev Time 0.00
Received By adarroug Date 2007-01-09 Time 11:33 Sent To  
Notes
2007-01-12 16:29:24TO "BOB"#4
2007-01-09 11:33:55WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-15 Cont ID  
Sent By mmiller Date 2006-11-29 Time 18:52 Rev Time 0.00
Received By rmcdouga Date 2006-11-29 Time 18:52 Sent To  
Notes
2006-12-14 16:18:40TO "BOB"#1
2006-11-29 18:52:31WAITING FOR BOB BOARD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-14 Cont ID  
Sent By adarroug Date 2006-10-14 Time 13:52 Rev Time 0.00
Received By adarroug Date 2006-10-14 Time 13:52 Sent To  
Notes
2006-10-23 08:31:37TO "BOB"#7
2006-10-14 13:53:13WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-23 Cont ID  
Sent By jleech Date 2006-09-23 Time 10:20 Rev Time 0.00
Received By jleech Date 2006-08-26 Time 14:28 Sent To  
Notes
2006-09-07 00:00:00TO "BOB"#18
2006-08-26 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-03-12 Cont ID  
Sent By tgordon Date 2007-03-12 Time 12:27 Rev Time 0.30
Received By tgordon Date 2007-03-12 Time 12:27 Sent To  
Notes
2007-03-12 12:28:24REVISION TO MECH. PLANS PAGE M-2.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-01-16 Cont ID  
Sent By tgordon Date 2007-01-16 Time 10:01 Rev Time 0.25
Received By tgordon Date 2007-01-16 Time 10:01 Sent To  
Notes
2007-01-16 10:03:48PLANS RE-SUBMITTED PASSED REVIEW ON 12-16-06.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-12-15 Cont ID  
Sent By tgordon Date 2006-12-15 Time 11:29 Rev Time 1.30
Received By tgordon Date 2006-12-15 Time 11:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-10-23 Cont ID  
Sent By tgordon Date 2006-10-23 Time 11:07 Rev Time 1.00
Received By tgordon Date 2006-10-23 Time 11:07 Sent To  
Notes
2006-10-23 11:30:29*** DENIED ***
 1) THE PLANS NEED THE CITY PLACE STAMP ON THEM.
  
 2) SEE MECHANICAL PLANS, THE ENGINEER'S SEAL NEEDS THE
 DATE IT WAS SEALED ON THEM, PER FAC 61G15-23.002.
  
 3) SEE MECH. PLANS, THE ENGINEER DOUGLAS COOLEY NEEDS
 HIS PRINTED NAME AND LICENSE NUMBER IN THE TITLE BLOCK,
 PER FAC 61G15-23.002(2).
  
 4) SEE MECH. PLANS, THE FIRM MICHAUD, COOLY, ERICKSON
 NEEDS THEIR CERTIFICATE OF AUTHORIZATION NUMBER IN THE
 TITLE BLOCK, PER FAC 61G15-23.002(2).
  
 5) SEE MECH.PLANS, THE ARCHITECT KENNETH PARK NEEDS HIS
 LICENSE NUMBER IN THE TITLE BLOCK, PER FAC
 61G1-16.004(2).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-09-11 Cont ID  
Sent By tgordon Date 2006-09-11 Time 14:37 Rev Time 1.00
Received By tgordon Date 2006-09-11 Time 14:37 Sent To  
Notes
2006-09-11 00:00:00*** DENIED ***
 1) PLANS SHOW USABLE SPACE AS 4310 SQ.
 FT., ENERGY CAL'S. SHOW CONDITIONED AREA
 AS 5304 SQ. FT., THE TWO MUST COINCIDE
 PLEASE CORRECT.
  
 2) PLANS SHOW 20.5 TONS OF A/C, ENERGY
 CAL'S. SHOW 5.5 TON OF A/C, THE TWO MUST
 COINCIDE PLEASE CORRECT.
  
 3) SEE ENERGY CAL'S. FORM 'A' SYSTEM
 REPORT COMP. FCU-1 IS LESS THAN 65,000
 BTU'S., PLANS SHOW THAT FCU-1 IS 134,900
 TOTAL BTU'S. PLEASE CORRECT.
  
 4) SEE ELECTRICAL REVIEW NOTES 1,2,3,
 AND *4* PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-12-21 Cont ID  
Sent By jleech Date 2006-12-21 Time 08:21 Rev Time 0.00
Received By jleech Date 2006-12-21 Time 08:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-10-30 Cont ID  
Sent By jleech Date 2006-10-30 Time 11:52 Rev Time 0.00
Received By jleech Date 2006-10-30 Time 11:52 Sent To  
Notes
2006-10-30 12:13:11DENIED;
 1. CITY PLACE STAMP , ENG. TO DATE, AND MISSING LICENSE
 NUMBERS REQUIRED SEE ELECTRIC AND MECHANICAL PLAN
 REVIEW NOTES.
 2. PAGE A-7.4 DETAIL 14 THE KICK PLAT AND BASE OF BREAK
 SINK CABINET IS STILL SHOWN IN DETAIL. THE 19" KNEE
 CLEARANCE CAN NOT BE ACHIEVED
 WITH OUT REMOVING. PLEASE REVISE DRAWING.
 3. PLEASE ADD NOTE TO PLUMBING PLAN THAT PUBLIC
 BATHROOMS FACILITIES EXIST WITHIN 500' OF STORE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-09-23 Cont ID  
Sent By jleech Date 2006-09-23 Time 09:44 Rev Time 0.00
Received By jleech Date 2006-09-23 Time 09:44 Sent To  
Notes
2006-09-23 00:00:00DENIED;
 1.PLANS TO BE SEALED AND SIGNED, COPYS
 NOT PERMITED.
 2.PAGE A1.0 DEMO PLAN; PLEASE ADD NOTE
 TO PLAN (NO DEAD ENDS PERMITED IN THE
 PLUMBING SYSTER SECTION 704.5. PLUMBING
 DEMO INSPEDTION REQUIRED)
 3.SEPARATE TOILET FACILITIES REQUIRED.
 SEE FBC-2004 PLUMBING SECTION 403.2
 EXCEPTION 4. THE RETAIL SPACE IS OVER
 300 SQ. FT. BATHROOM MUST BE ACCESSABLE
 TO THE PUBLIC ALSO UNLESS THERE ARE
 PUBLIC FACILITIES TO COMPLY WITH SECTION
 403.6.
 4.PAGE A7.4 DETAIL 14; DRAWING SHOWS
 KICK PLAT AND DOORS WITH GARBAGE
 DISPOSAL. A FRONTAL APPROACH APPROACH IS
 REQUIRED SEE SECTION 11-4.21.3 KNEE
 CLEARANCE UNDER SINK ISA MIN. OF 19".
 SHOW CLEAR FLOOR SPACE ON FLOOR PLAN.
 5.PAGE P-1 PLUMBING FIXTURE SCHEDULE;
 TOILET SEAT TO BE OPEN FRONT WITHOUT LID
 IS REQUIRED FOR A PUBLIC TOILET.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695