Plan Review Details - Permit 06081940
Plan Review Stops For Permit 06081940
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2007-03-01 Cont ID  
Sent By lursu Date 2007-03-01 Time 13:16 Rev Time 0.00
Received By lursu Date 2007-03-01 Time 13:15 Sent To  
Notes
2007-03-01 13:17:06THE UNIT NUMBER IS CORRECT ON THE REVISED SITE PLANS
 .477 S ROSEMARY AVE #169.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-09-12 Cont ID  
Sent By lursu Date 2006-09-12 Time 13:36 Rev Time 0.00
Received By lursu Date 2006-09-12 Time 13:36 Sent To I
Notes
2006-09-12 00:00:00NO UNIT SPECIFIED ON THE APPLICATION
 US EXT #0001 FOR THE UNIT 169 .
2006-09-09 00:00:00NEEDS, NEW SPACE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-08-17 Cont ID  
Sent By shill Date 2007-08-17 Time 17:57 Rev Time 0.00
Received By shill Date 2007-08-17 Time 17:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-08-17 Cont ID  
Sent By shill Date 2007-08-17 Time 10:28 Rev Time 0.00
Received By shill Date 2007-08-17 Time 10:28 Sent To  
Notes
2007-08-17 10:29:16****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)I WAS UNABLE TO LOCATE THE APPLICATION IN THE
 PACKAGE.PLEASE PROVIDE THE PERMIT APPLICATION SO THAT
 THE PERMIT CAN BE ISSUED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-08-06 Cont ID  
Sent By shill Date 2007-08-06 Time 09:01 Rev Time 0.00
Received By shill Date 2007-08-06 Time 09:01 Sent To  
Notes
2007-08-06 09:32:21****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)TYPE IIA DECLARED; THIS REQUIRES A 1 HOUR FOR
 STRUCTURAL COLUMNS FBC TABLE 601.SEE SHEET D1,
 REMOVAL OF DRYWALL AT THE STEEL COLUMNS.ARE THE
 COLUMNS STRUCTURAL?HOW DOES THE REMOVAL OF DRYWALL
 AFFECT THE REQUIRED FIRE RATING?
  
 NEW COMMENT 8/10/7
  
 PLEASE RETAIN DBPR APPROVAL SHEETS IN THE PLAN.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-05-03 Cont ID  
Sent By shill Date 2007-05-03 Time 10:32 Rev Time 0.00
Received By shill Date 2007-05-03 Time 10:32 Sent To  
Notes
2007-05-03 10:33:14****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER 561-805-6724
 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 COMMENTS FROM PREVIOUS REVIEWS, NOT PROPERLY
 ADDRESSED:
  
  
 1.)A1.0 SHOWS "EXISTING FIRE RATED
 WALLS"; SPECIFY FIRE RATING.
  
 3RD REVIEW ? A1.0 SHOWS A 4 HOUR WALL BETWEEN THE
 PROPOSED RESTAURANT AND MACY?S, AND A 2 HOUR WALL AT
 THE SHAFT.A1.1 SHOWS THE 4 HOUR WALL AS A 2 HOUR
 WALL.PLEASE ADDRESS.
  
 2.)IS THIS A CHANGE OF OCCUPANCY?
 DECLARE GOVERNING CODE, FBC EB, AND
 LEVEL OF ALTERATION FBC EB 3, AND CHANGE
 OF OCCUPANCY IF APPLICABLE FBC 8.
  
 3RD REVIEW ? THE ARCHITECT HAS DECLARED LEVEL 1
 ALTERATION.SEE FBC EB CHAPTER 3.DOESN?T THIS
 INVOLVE ADDITION OF WINDOWS, RECONFIGURATION OF SPACE?
 THIS DOES NOT APPEAR TO BE A LEVEL 1 ALTERATION.
  
 3.)PROVIDE A FIRE SPRINKLER PLAN, FBC*106.3.5.1.1(5),
 FS553.79(2).
  
 3RD REVIEW ? THIS IS A STATUTORY REQUIREMENT; SEE
 ATTACHED LETTER.A 4X PLAN REVIEW FEE HAS BEEN
 CHARGED.THIS IS ALSO A STATUTORY REQUIREMENT; MUST BE
 CHARGED WHEN THE SAME COMMENT IS NOT ADDRESSED THREE
 TIMES AND IS REQUIRED TO BE CHARGED EACH TIME AFTER THE
 THIRD TIME.
  
 4.)FBC TABLE 1004.1.2, PLAN STATES MOVEABLE SEATS,
 ARE THE TABLES FIXED?UNCONCENTRATED (TABLES & CHAIRS)
 IS 15 NET.
  
 3RD REVIEW; OCCUPANT LOAD CANNOT BE LESS THAN THE
 TABLE, SO PLEASE ROUND UP RATHER THAN DOWN, INDOORS
 LESS BOOTHS CALCULATION.
  
 5.)3RD REVIEW, FIRE RESISTANCE REQUIREMENTS ARE STILL
 NOT CLEAR.PLEASE SEE A1.1, DETAIL FOR UL U477, 2 HOUR
 BEARING WALL.I WAS UNABLE TO LOCATE THIS ASSEMBLY IN
 THE UL BOOK (HAS U476, U478, BUT NOT U477).THE
 DRAWING SHOWS THAT THIS IS A 1 HOUR WALL (BUT THE UL
 LISTING STATES IT IS A 2 HOUR) WITH 1 LAYER 5/8 TO
 CREATE A NEW 2 HOUR WALL.SEE FBC TABLE 721.2.1.4(2),
 5/8 TYPE X HAS 40 MINUTE RATING, SO THIS WOULD NOT
 CREATE A 2 HOUR WALL.IT IS NOT CLEAR WHERE THIS WILL
 BE INSTALLED.SEE FBC TABLE 302.3.2, AND FBC302.3.2
 EXCEPTION.IT IS ACCEPTABLE TO EXCEED MINIMUM CODE
 REQUIREMENTS, BUT DETAILS ARE TO CLEARLY SHOW CODE
 COMPLIANCE AND ARE TO BE CONSISTENT.
  
 6.)A1.1 HAS A DETAIL WHICH IS NOT LABELED WITH A
 DETAIL MARKER NUMBER AND DOES NOT SPECIFY WHAT IT IS
 FOR OR WHAT THE FIRE RESISTANCE RATING IS.IS THIS A
 PART OF DETAIL 1?IT IS CLOUDED SEPARATELY.
  
 7.)C1, ITEM 8, STATES TABLE 600 REQUIREMENTS. DECLARE
 BUILDING TYPE A OR B AND SHOW REQUIREMENTS BASED ON
 FBC2004, TABLE 601.
  
 8.)PLEASE SIGN THE OWNER/AGENT LINE OF THE ENERGY
 CALCS, FBC 13 103.1.
  
 9.)PROVIDE PRODUCT APPROVALS FOR THE COMPONENTS AND
 CLADDING.A1.0, WINDOW SCHEDULE NOTES WINDOW C AS
 EXISTING, AND IT APPEARS THAT WINDOWS A AND B ARE NEW.
 DOES THIS MEAN THAT ALL OF THE DOORS ARE NEW?IF NOT,
 NOTE THE DOORS AS EXISTING.IF THEY ARE, PROVIDE
 PRODUCT APPROVALS.
  
 10.)DESIGNER OF RECORD IS TO REVIEW PRODUCT
 APPROVALS, FBC*106.3.3.
  
 ONE SET OF THE ARCHITECTURAL DRAWINGS HAS BEEN
 RETAINED.
  
 6/07 - THE RETAINED SET WAS RETURNED TO THE PACKAGE
 (NEEDED DBPR STAMP).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-02 Cont ID  
Sent By shill Date 2007-03-02 Time 07:40 Rev Time 0.00
Received By shill Date 2007-03-02 Time 07:40 Sent To  
Notes
2007-03-02 07:44:14****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)FBC TABLE 1004.1.2, PLAN STATES MOVEABLE SEATS,
 ARE THE TABLES FIXED?UNCONCENTRATED (TABLES & CHAIRS)
 IS 15 NET.
  
 2.)A1.0, LOBBY FOR LOFTS, STILL STATES "EXISTING FIRE
 RATED WALLS TO REMAIN".SEE PREVIOUS LIST IN REGARDS
 TO SPECIFYING FIRE RATING.
  
 3.)SEE PREVIOUS LIST, FIRE SPRINKLER PLAN REQUIRED
 FBC*106.3.5.1.1.(5), FS553.79(2).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-29 Cont ID  
Sent By shill Date 2006-09-29 Time 16:32 Rev Time 0.00
Received By shill Date 2006-09-29 Time 14:56 Sent To  
Notes
2006-09-29 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A1.0 SHOWS "EXISTING FIRE RATED
 WALLS"; SPECIFY FIRE RATING.
  
 2.)IS THIS A CHANGE OF OCCUPANCY?
 DECLARE GOVERNING CODE, FBC EB, AND
 LEVEL OF ALTERATION FBC EB 3, AND CHANGE
 OF OCCUPANCY IF APPLICABLE FBC 8.
  
 3.)PROVIDE A FIRE SPRINKLER PLAN,
 FBC*106.3.5.1.1(5).
  
 4.)PROVIDE DIMENSIONS FOR THE HALLWAY
 AND THE KITCHEN AREA (EGRESS, FBC 10).

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-07-16 Cont ID  
Sent By dpalmer Date 2008-07-16 Time 08:24 Rev Time 0.00
Received By dpalmer Date 2008-07-16 Time 08:24 Sent To PC
Notes
2008-07-16 08:25:39REV FOR SHEETS E0.1,E1 OK, HOWEVER SHEET E-0 WAS NOT
 REVISED AND IS THE SAME SHEET ALREADY ON FILE. THIS
 SHEET WAS NOT STAMPED.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-05-06 Cont ID  
Sent By dpalmer Date 2008-05-06 Time 11:54 Rev Time 0.00
Received By dpalmer Date 2008-05-06 Time 11:54 Sent To PC
Notes
2008-05-06 11:55:30** DENIED REVISIONS/ OK REVISION**
  
 1) NOTE: PLEASE SEE SHEET E-0 INDICATES A REVISION
 HOWEVER THE PLANS DO NOT SEEM TO SHOW ANY REVISION #4.
 THE OTHER REVISED ELECTRICAL SHEETS ARE OK AND
 STAMPED.
 PLEASE SUBMIT ANY REVISED SHEET E-0
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-05-07 Cont ID  
Sent By dpalmer Date 2007-05-07 Time 16:25 Rev Time 0.00
Received By dpalmer Date 2007-05-07 Time 16:25 Sent To  
Notes
2007-05-07 16:26:18NEW ENERGY CALCULATIONS SUBMITTED.
 ELECTRICAL REVIEWED, OK.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-04-18 Cont ID  
Sent By dpalmer Date 2007-04-18 Time 12:56 Rev Time 0.00
Received By dpalmer Date 2007-04-18 Time 12:56 Sent To  
Notes
2007-04-18 12:56:38** UNSAT **
  
 ** TEMPORARY FAILED STATUS
  
  
 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS CONTROL
 METHODS NEED TO BE COORDINATED WITH THE ELECTRICAL
 PLANS AND METHODS OF CONTROLS ON PLANS.
 13-415.1.A, 13-415.1.ABC.1.1.
 A CALLED WAS PLACED TO THE ENGINEER OF RECORD FOR NEW
 INPUT DATA REPORTS TO BE ADJUSTED AND SUBMITTED.
 IF THERE ARE ANY QUESTIONS ON THIS AND HOW THESE ARE TO
 BE SUBMITTED, PLEASE CONTACT THIS REVIEWER.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-01-24 Cont ID  
Sent By dpalmer Date 2007-01-24 Time 12:36 Rev Time 0.00
Received By dpalmer Date 2007-01-22 Time 18:12 Sent To  
Notes
2007-01-24 12:38:41***** UNSAT 2ND REVIEW *****
  
 ITALIAN OVEN
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH IS
 STILL IN NEED OF ADDRESSING.
 PLEASE ALSO DO NOT SUBMIT LOOSE SHEETS NOT ATTACHED IN
 THE SETS OF PLANS. PLEASE SUBMIT COMPLETE SETS SECURED
 TOGETHER.
  
 1) NOTE: OK.
  
 2) NOTE: OK.
  
 3) NOTE: NO, PLEASE SEE THE RESPONSE WAS TO ADD AND
 ADDITIONAL SERVICE, HOWEVER AS THIS DOES NOT AT THIS
 TIME FALL UNDER THE EXCEPTIONS FOR 230.2 THIS AHJ IS
 NOT ABLE TO GRANT THE ADDITIONAL SERVICE BEING
 PROPOSED.
 PLEASE PROVIDE THE LOADS ON THE EXISTING SERVICE ALONG
 WITH THE NEW LOADS. PLEASE KNOW THAT FURTHER
 INFORMATION WOULD BE NEEDED FOR ANY OTHER
 CONSIDERATION.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE PROVIDE LOADS ON EXISTING SERVICE GUTTER WITH
 NEW LOADS BEING ADDED. PLEASE ALSO INDICATE THE SIZE OF
 THE EXISTING SERVICE.
 230.2, 220, 215.5 ETC
 FBC 106.1.2 ADMIN SECT.
  
 4) NOTE: NO? THIS COMMENT IS CURRENTLY *UP IN THE AIR*
 BASED ON THE FACT THAT THE SERVICE RISER HAS NOW
 COMPLETELY CHANGED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING EQUIPMENT GROUNDING CONDUCTOR FROM
 GUTTER TO METER, METER TO MAIN, MAIN TO SUB PANEL,
 PANELS TO TRANSFORMERS, AND TRANSFORMER TO PANELS. **
 PLEASE KNOW, IF MAIN SERVICE FOR BUILDING CONTAINS AS
 MAIN, THEN PROVIDE NOTE ON PLANS FOR "FLOATING NEUTRAL"
 KIT REQUIRED IN METER.
 250.6, 250.24B, 250.110,250.6,250.122 ETC.
  
 5) NOTE: OK.
  
 6) NOTE: OK, THE LOCATIONS ARE NOW BEING SHOWN, HOWEVER
 THE MINIMUM CLEARANCES FOR WORKING CLEARANCE,
 VENTILATION AND POSSIBLE STORAGE AREA THESE ARE BEING
 SHOWN IS NOT CLEAR.
 PLEASE SEEDISCONNECT AS SHOWN ON PLANS ALSO DOES NOT
 MEET MINIMUM CLEARANCE REQUIREMENTS.PLEASE SEE 110.26
 AND THE SAME CODE SECTIONS AS PREVIOUSLY NOTED.
  
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SHOW LOCATIONS OF TRANSFORMERS ON PLANS. PLEASE
 SEE THAT A REVIEW FOR SOME CODE ITEMS CAN NOT BE DONE
 AT THIS TIME AS THESE ARE NOT SHOWN.
 PLEASE SEE INSTALLATION OF THE 112.5KVA TRANSFORMER
 SHALL NOT BE ABOVE CEILING AND MUST MEET ALL THE
 REQUIREMENTS AS
 NEC ARTICLES BELOW REQUIRE.
 PLEASE SEE 450.13B, 450.21, 450.9 ETC.
 ** IF TRANSFORMER(S) ARE GOING TO BE MOUNTED FROM
 CEILING OR WALL, PLEASE PROVIDE STRUCTURAL ENGINEERING
 DETAILS FOR THIS.
  
 7) NOTE: NO, PLEASE SEE THE TAPPED CONDUCTORS DO NOT
 SEEM TO MEET THE CODE SECTION AS PREVIOUSLY GIVEN.
 PLEASE SEE 240.21C6. PLEASE SEE THE DISTANCE ALONG WITH
 THE SIZE OF THE CONDUCTOR TERMINATING INTO OVER CURRENT
 PROTECTION WHICH LIMITS THE LOAD ON ANY CONDUCTOR IS
 NOT MET AT THIS TIME.
 PLEASE SEE THE RISER INDICATES 400AMP OCP ON
 CONDUCTORS RATED AT 285AMPS.
  
 **PREVIOUS REVIEW NOTE**
 PLEASE SEE 240.21 FOR TAPPED CONDUCTORS ON THE
 SECONDARY SIDE OF TRANSFORMERS CAN NOT BE VERIFIED AT
 THIS TIME.
  
 8) NOTE: OK, SEE NOTE ABOVE #7.
  
 9) NOTE: NO/OK, PLEASE SEE THIS WAS NOT DONE, HOWEVER
 AS EQUIPMENT IS REMOVED FROM THE LIGHTING PLANS, IT
 NEED ONLY BE SHOWN ON THE POWER PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE ALL PLANS FOR LOCATIONS OF ALL SERVICE
 EQUIPMENT PANELS. PLEASE SEE PANELS ON LIGHTING SHEETS
 ARE NOT IN THE SAME LOCATIONS AS PANELS ON POWER
 SHEETS.
 106.1.2.FBC 110.26,240.24 ETC.
  
 10) NOTE: OK.
  
 11) NOTE: OK.
  
 12) NOTE: OK.
  
 13) NOTE: OK.
  
 14) NOTE:NO, PLEASE SEE MOST WERE DONE, HOWEVER
 PLEASE SEE PLANS AS THERE ARE SOME FIXTURES BEING
 CIRCUITED TO CIRCUITS WHICH ARE SHOWN AS *BLANK* IN
 PANEL SCHEDULE. PLEASE SEE REDLINED PLANS AND PLEASE
 SEE NEW COMMENTS BASED ON COORDINATION OF CIRCUITING ON
 PLANS, PANEL SCHEDULE, ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 700.12E FOR CIRCUITING OF EMERGENCY AND EXIT
 LTS.
 THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE
 THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES.
  
 15) NOTE:OK, HOWEVER PLEASE SEE THERMOSTATICALLY
 CONTROLLED DEVICES ARE NOW BEING SHOWN AT 125%? THIS IS
 OK AND IS ONLY BEING NOTED AS NOT REQUIRED. THE
 PREVIOUS NOTE IS BEING LEFT AS THE NOTE MENTIONS THIS
 WAS EXEMPT. PLEASE ALSO SEE NOTE AS THE LOADS WILL BE
 CONSIDERED FOR THE EXISTING MAIN SERVICE WHICH IS BEING
 CONNECTED TO.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PANEL SCHEDULES ARE NOT COMPLETE WITH LOAD
 CALCULATIONS AT THIS TIME. PLEASE PROVIDE COMPLETE LOAD
 CALCULATIONS ON HOW LOADS WERE DERIVED.
 PLEASE SEE 220.3,220.10,220.11,220.13 ETC
 PLEASE ALSO INDICATE AND SHOW ALL CONTINUOUS LOADS (3OR
 MORE HRS) AT 125%. (THERMOSTATICALLY CONTROLLED
 UNITS/APPLIANCES ARE IN EXCEPTION)
  
 16) NOTE: OK.
  
 17) NOTE: OK.
  
  
 18) NOTE: OK, THESE ARE BEING ADDED, HOWEVER PLEASE
 CLARIFY HOW LOAD WAS DERIVED. *EXAMPLE* X AMOUNT OF
 LINEAR FT OF WINDOW AT 200VA PER FT = Y*
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE VERIFY NEW OR EXISTING SHOW/STOREFRONT WINDOW
 RECEPTS REQUIRED ABOVE WINDOWS.210.62
 THESE WILL BE REQUIRED IF NOT EXISTING.
 PLEASE ALSO SEE 220.12 FOR LOADS TO BE ADJUSTED.
  
 19) NOTE: OK.
  
 20) NOTE: OK.
  
 21) NOTE:NO,
 A) PLEASE SEE THE LIGHTING CONTROL PANEL DOES NOT
 CONTAIN ANY TIME OF DAY SCHEDULING. (EXAMPLE: 8AM
 -11PM).
 B) PLEASE SEE THE CIRCUITING ON PLANS DOES NOT
 CORRELATE WITH THE CIRCUITING ON PLANS OR PANEL
 SCHEDULE(S).
 C) PLEASE SEE THE METHOD *A* FOR LIGHTING CAN NOT BE
 VERIFIED AT THIS TIME. PLEASE SEE THAT THE ENERGY
 CALCULATIONS SUBMITTED DO NOT CORRELATE WITH THE
 LIGHTING ON PLANS OR LOADS SHOWN ON PLANS FOR LIGHTING.
 PLEASE CORRELATE.
 D) PLEASE SEE BATHROOMS AS THE COVERAGE OF THE DEVICE
 AS SHOWN WOULD NOT COVER THE OTHER CLOSED IN
 AREAS/STALLS OF RESTROOM AREAS. PLEASE SEE THE TYPE OF
 DEVICE MAY BE SPECIFIED WHICH MAY HELP IN COVERAGE;
 HOWEVER DEPENDING ON DEVICE, COVERAGE, WALLS/PARTITIONS
 ETC THESE WILL ALL HAVE AN AFFECT ON THE DESIGN FOR
 LIFE SAFETY OF THESE LIGHTS.
 ** THE INTENT IS NOT TO LEAVE AN OCCUPANT IN ANY AREA
 IN TOTAL DARKNESS IN THE EVENT OF THE FAILURE OR
 TURNING OFF OF THIS ONE DEVICE.
 PLEASE SEE NEW COMMENT BASED ON THE TYPE OF EMERGENCY
 FIXTURE BEING PLACED IN BATHROOM.
  
 ** PLEASE SEE THE PREVIOUS REVIEW NOTE **
 PLEASE SEE THIS IS A NEW OCCUPANCY FOR SPACE. PLEASE
 SEE 2004 FBC CHAPTER 13 FOR COMPLIANCE WITH THE NEW
 FLORIDA ENERGY CODE.
 PLEASE SEE 13-415.1.ABC.1.1, 13-415.1.ABC.1.2, AND
 13-415.1.ABC.1.3
 PLEASE PROVIDE A COMPLETE LIGHTING CONTROL SYSTEM AS
 REQUIRED INCLUDING CONTROLS AND DEVICES FOR ALL
 SEPARATE SPACES CONTAIN FLR TO CEILING HEIGHT
 PARTITIONS.
 PLEASE PROVIDE THE SCHEDULING; PLEASE PROVIDE TYPE OF
 OVER RIDE DEVICES, ALONG WITH THE MAX TIME OVER RIDE AS
 DETERMINED BY THE DEVICE. ( TIMER TYPE4HRS MAX,
 MOTION/OCCUPANT SENSOR TYPE 30MINS MAX).
 PLEASE SEE CONTROLS FOR OVER-RIDING SYSTEM SHALL ALSO
 BE LOCATED AT THE POINTS OF ENTRANCE INTO SPACE. PLEASE
 SEE THAT ANY OVER-RIDES MUST ALSO BE LOCATED SO THE
 OCCUPANT CAN VISUALLY SEE THE LIGHTING BEING
 CONTROLLED.
 PLEASE SUBMIT LIGHTING POWER DENSITIES AS REQUIREDPER
 13-415.1.AB.1,
 13-415.2.ABC.1, AND TABLES 415.2.C.1,
 415.2.B.1, 13-415.2.B.1 ETC ETC.
 PLEASE PROVIDE THE MAX ALLOWED COMPARED TO THE ACTUAL
 DESIGN.
 PLEASE SEE METHODS FOR NEW ENERGY CALCULATIONS MUST
 ALSO BE SUBMITTED.
  
 22) NOTE: OK.
  
 23) NOTE: OK.
  
 ** NEW NOTES **
  
 1) NOTE: PLEASE SEE THE LIGHTING FIXTURE SCHEDULE.
 PLEASE SOME FIXTURES WHICH ARE BEING SHOWN AS
 EMERGENCY, HOWEVER THEY DO NOT CONTAIN ANY BATTERY BACK
 UP. PLEASE SEE THE BATHROOMS ARE ONE LOCATION AS NOTED
 ABOVE WHERE AN EMERGENCY BATTERY BACK UP LIGHT FIXTURE
 OF SOME SORT IS REQUIRED.
 NFPA-101 7.8, 7.9.
 700.12 E, 700.16 NEC.
  
 2) NOTE:PLEASE SEE ARCHITECTURAL COVER SHEET MENTIONS
 THIS AS LEVEL 2 ALTERATION FROM THE EXISTING 2004 FBC.
 THIS IS NOT POSSIBLE FOR A CHANGE IN OCCUPANCY OR THE
 SCOPE OF WORK IN THIS PROJECT. PLEASE ALSO SEE BUIDLING
 REVIEW COMMENTS FOR THIS.
  
 3) NOTE: PLEASE SEE FS 553.80(2)(B) WHICH IS BEING
 GIVEN AS A NOTICE ONLY AT THIS TIME.
  
 ** PLEASE KNOW, AS THERE ARE ITEMS NOT
 YET SUBMITTED FOR REVIEW, THERE MAY BE
 NEW COMMENTS UPON NEXT REVIEW.
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL PLANS/DESIGN.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-22 18:12:46IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-09 Cont ID  
Sent By dpalmer Date 2006-09-09 Time 21:17 Rev Time 0.00
Received By dpalmer Date 2006-09-09 Time 19:18 Sent To  
Notes
2006-09-09 00:00:00***** UNSAT *****
  
 ITALIAN OVEN
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES
 ARE REQUIRED ON PLANS WHICH ARE RELEVANT
 TO THE SCOPE OF WORK AND DESIGNS ON
 PLANS.
 2004 FBC, 2002 NFPA-70 (NEC), 2002
 NFPA-72. 2004 NFPA-96, 2003 NFPA-101.
 THESE ARE REQUIRED AT A MIN.
  
 2) NOTE: PLEASE SEE ADDRESS OF SUITE
 SHALL BE INDICATED ON TITLE BLOCKS ARE
 REQUIRED UNDER THE FLORIDA
 ADMINISTRATIVE CODE.
 61G1-16.004 AND 61G15-23.002
 PLEASE BE SURE TO ALSO CORRELATE WITH
 THE PERMIT APPLICATION AS NO SUITE
 NUMBER IS SHOWN.
  
 3) NOTE: PLEASE PROVIDE LOADS ON
 EXISTING SERVICE GUTTER WITH NEW LOADS
 BEING ADDED. PLEASE ALSO INDICATE THE
 SIZE OF THE EXISTING SERVICE.
 230.2, 220, 215.5 ETC
 FBC 106.1.2 ADMIN SECT.
  
 4) NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM GUTTER TO
 METER, METER TO MAIN, MAIN TO SUB PANEL,
 PANELS TO TRANSFORMERS, AND TRANSFORMER
 TO PANELS.
 ** PLEASE KNOW, IF MAIN SERVICE FOR
 BUILDING CONTAINS AS MAIN , THEN PROVIDE
 NOTE ON PLANSFOR "FLOATING NEUTRAL"
 KIT REQUIRED IN METER.
 250.6,250.24B, 250.110,250.6,250.122
 ETC.
  
 5) NOTE: PLEASE SHOW AND INDICATE THE
 GROUNDING ATTACHMENT LOCATIONS FOR NEW
 AND EXISTING TRANSFORMERS.
 PLEASE SEE 250.30,250.20,250.66, 250.58,
 250.50
  
 6) NOTE: PLEASE SHOW LOCATIONS OF
 TRANSFORMERS ON PLANS. PLEASE SEE THAT A
 REVIEW FOR SOME CODE ITEMS CAN NOT BE
 DONE AT THIS TIME AS THESE ARE NOT
 SHOWN.
 PLEASE SEE INSTALLATION OF THE 112.5KVA TRANSFORMER
 SHALL NOT BE ABOVE CEILING
 AND MUST MEET ALL THE REQUIREMENTS AS
 NEC ARTICLES BELOW REQUIRE.
 PLEASE SEE 450.13B, 450.21, 450.9 ETC.
 ** IF TRANSFORMER(S) ARE GOING TO BE
 MOUNTED FROM CEILING OR WALL, PLEASE
 PROVIDE STRUCTURAL ENGINEERING DETAILS
 FOR THIS.
  
 7) NOTE: PLEASE SEE 240.21 FOR TAPPED
 CONDUCTORS ON THE SECONDARY SIDE OF
 TRANSFORMERS CAN NOT BE VERIFIED AT THIS
 TIME.
  
 8) NOTE: PLEASE SEE PANEL LPH AND LP/LP
 SHOULD BE SHOWN AS 400A RATED AND
 CONTAINING A 300A BRKR IF THIS IS GOING
 TO BE THE DESIGN. PLEASE SEE PANEL NOW
 SHOWS A 400A BRKR WITH A 300A TRIP?
 IF THIS TYPE OF BRKR IS GOING TOBE
 INSTALLED, PLEASE SUBMIT MANUFACTURES
 CUT/SPEC SHEETS ON THIS BREAKER, MUST
 INDICATE A LISTING FROM A NRTL.
 110.3,90.7.
  
 9) NOTE: PLEASE CORRELATE ALL PLANS FOR
 LOCATIONS OF ALL SERVICE EQUIPMENT
 PANELS. PLEASE SEE PANELS ON LIGHTING
 SHEETS ARE NOT IN THE SAME LOCATIONS AS
 PANELS ON POWER SHEETS.
 106.1.2.FBC
 110.26,240.24 ETC.
  
 10) NOTE: PLEASE CORRELATE RISER AND
 PANELS FOR FEEDER SIZES.
 310.16 , 240.4
 PLEASE SEE NEW TRANSFORMER SHOWS 2/0'S
 ON PANEL AND RISER SHOWS 1/0'S. PLEASE
 SEE 310.16 AS THE 1/0'S AS SHOWN ARE
 NOTE RATED FOR OCP BEING PROVIDED.
  
 11) NOTE: PLEASE SEE 240.6 FOR SIZING OF
 STANDARDOCP DEVICES. PLEASE SEE 170A
 BRKR BEING SHOWN FOR THE NEW TRANSFORMER
 WHICH DOES NOT CORRELATE TO ANY OF THE
 STANDARDS.
 240.4, 310.16, 240.6, 450.3
  
 12) NOTE: PLEASE CORRELATE RISER AND
 PANEL SCHEDULES FOR LABELING OF PANELS.
 ( TWO LP1'S)
 FBC 106.1.2
  
 13) NOTE: PLEASE INDICATE THE NEW OR
 EXISTING SIGN CIRCUIT(S). AS REQUIRED
 PER 600.5 PLEASE SEE THAT EACH
 COMMERCIAL BUILDING AND EACH COMMERCIAL
 OCCUPANCY ACCESSIBLE TO PEDESTRIANS
 SHALL BE PROVIDED WITH AT LEAST ONE
 OUTLET IN AN ACCESSIBLE LOCATION AT EACH
 ENTRANCE TO EACH TENANT SPACE FOR SIGN
 OR OUTLINE LIGHTING SYSTEM USE. THE
 OUTLET(S) SHALL BE SUPPLIED BY A BRANCH
 CIRCUIT RATED AT LEAST 20 AMPERES THAT
 SUPPLIES NO OTHER LOAD.
  
 14) NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF EMERGENCY AND EXIT LTS.
 THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
  
 15) NOTE: PLEASE SEE PANEL SCHEDULES ARE
 NOT COMPLETE WITH LOAD CALCULATIONS AT
 THIS TIME. PLEASE PROVIDE COMPLETE LOAD CALCULATIONS ON
 HOW LOADS WERE DERIVED.
 PLEASE SEE 220.3,220.10,220.11,220.13
 ETC
 PLEASE ALSO INDICATE AND SHOW ALL
 CONTINUOUS LOADS (3OR MORE HRS) AT 125%.
 (THERMOSTATICALLY CONTROLLED
 UNITS/APPLIANCES ARE IN EXCEPTION)
  
 16) NOTE: PLEASE SEE TRANSFORMER ARE
 BEING SHOWN WITH WHAT APPEARS TO BE
 "NEUTRALS" IN THE FEEDER CONDUITS GOING
 TO THE TRANSFORMERS? PLEASE KNOW, AS THE TRANSFORMERS
 ARE CONSIDERED SEPARATELY
 DERIVED SYSTEMS/SERVICES, A NEUTRAL
 CONDUCTOR IS NOT INSTALLED.
 PLEASE KEEP IN MIND THE PREVIOUS COMMENT
 ABOVE WHICH PREVIOUSLY MENTIONED MISSING
 EQUIPMENT GROUNDING CONDUCTORS.
  
 17) NOTE: PLEASE SEE2002 NEC, 210.8B3
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
  
 18) NOTE: PLEASE VERIFY NEW OR EXISTING SHOW/STOREFRONT
 WINDOW RECEPTS REQUIRED
 ABOVE WINDOWS.210.62
 THESE WILL BE REQUIRED IF NOT EXISTING.
 PLEASE ALSO SEE 220.12 FOR LOADS TO BE
 ADJUSTED.
  
 19) NOTE: PLEASE SEE COLOR CODING FOR
 120/240V SYSTEM WIRING IS BEING SHOWN ON
 E-0, HOWEVER PLEASE SEE SYSTEM VOLTAGES
 ON PLANS ARE 120/208 AND 277/480V.
 PLEASE SEE COLOR CODING SHALL BE AS
 FOLLOWS.
 120/208,
 BLACK ,RED, BLUE
 &
 277/480V
 BROWN, PURPLE , YELLOW.
 PLEASE KNOW, "ORANGE" IS ONLY IDENTIFIED
 IN THE NEC FOR THE HIGH-LEG OF A OPEN
 DELTA SYSTEM, 120/240V.
 PLEASE ADJUST, 90.4
 ** ALL EXISTING SYSTEMS AT THIS LOCATION
 AT CITY PLACE AND THIS JURISDICATION ARE
 COLOR CODED THIS WAY.
  
 20) NOTE: PLEASE SEE MISSING SHUNT TRIP IDENTIFICATIONS
 FOR ALL ELECTRICAL
 FEEDING OR UNDER HOOD. LTS ETC).
 PLEASE SEE NFPA 2004/1998 BOTH ARE THE
 SAME FOR REQUIRED AUTOMATIC SHUNT UPON
 ACTIVATION OF ANY SURPRESSION SYSTEM.
  
 21) NOTE: PLEASE SEE THIS IS A NEW
 OCCUPANCY FOR SPACE. PLEASE SEE 2004 FBC
 CHAPTER 13 FOR COMPLIANCE WITH THE NEW
 FLORIDA ENERGY CODE.
 PLEASE SEE 13-415.1.ABC.1.1,
 13-415.1.ABC.1.2, AND 13-415.1.ABC.1.3
 PLEASE PROVIDE A COMPLETE LIGHTING
 CONTROL SYSTEM AS REQUIRED INCLUDING
 CONTROLS AND DEVICES FOR ALL SEPARATE
 SPACES CONTAIN FLR TO CEILING HEIGHT
 PARTITIONS.
 PLEASE PROVIDE THE SCHEDULING, PLEASE
 PROVIDE TYPE OF OVER RIDE DEVICES, ALONG
 WITH THE NAX TIME OVE OVER RIDE AS
 DETERMINED BY THE DEVICE. ( TIMER TYPE
 4HRS MAX, MOTION/OCCUPANT SENSOR TYPE
 30MINS MAX).
 PLEASE SEE CONTROLS FOR OVER-RIDING
 SYSTEM SHALL ALSO BE LOCATED AT THE
 POINTS OF ENTRANCE INTO SPACE. PLEASE
 SEE THAT ANY OVER-RIDES MUST ALSO BE
 LOCATED SO THE OCCUPANT CAN VISUALLY SEE
 THE LIGTHING BEING CONTROLLED.
 PLEASE SUBMIT LIGHTING POWER DENSITES AS
 REQUIREDPER 13-415.1.AB.1,
 13-415.2.ABC.1, AND TABLES 415.2.C.1,
 415.2.B.1., 13-415.2.B.1 ETC ETC.
 PLEASE PROVIDE THE MAX ALLOWED COMPARED
 TO THE ACTUAL DESIGN.
 PLEASE SEE METHODS FOR NEW ENERGY
 CALCULATIONS MUST ALSO BE SUBMITTED.
  
 22) NOTE: PLEASE INDICATE IF "LP"
 CONTAINS FEED-THRU LUGS OR IS THERE OCP
 IN LP FEEDING 2ND SECTION OF LP.
  
 23) NOTE: PLEASE SEE 220.12,AN
 ADDITIONAL LOAD OF 150 VOLT-AMPERES
 SHALL BE INCLUDED FOR EVERY 600 MM (2
 FT) OF LIGHTING TRACK OR FRACTION
 THEREOF.
  
 ** PLEASE KNOW, AS THERE ARE ITEMS NOT
 YET SUBMITTED FOR REVIEW, THERE MAY BE
 NEW COMMENTS UPON NEXT REVIEW.
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL PLANS/DESIGN.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-08-14 Cont ID  
Sent By mawillia Date 2007-08-14 Time 17:31 Rev Time 0.00
Received By mawillia Date 2007-08-14 Time 17:09 Sent To B1
Notes
2007-08-14 17:30:55***PROVISO*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEET(S) A1.0, A2.0, AND E-2 WERE
 STAMPED, INITIALED, AND DATED.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 8561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-05-07 Cont ID  
Sent By mawillia Date 2007-05-07 Time 13:27 Rev Time 0.00
Received By mawillia Date 2007-05-07 Time 13:03 Sent To  
Notes
2007-05-07 13:27:47***DENIED*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEWS STILL NEED TO BE ADDRESSED:
  
  
 01.)NFPA 101, 2003 EDITION AND FLORIDA FIRE
 PREVENTION CODE , 2004 EDITION SHALL BE REFERENCED.
  
 02.)STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION,
 AND DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.)ACCUMULATIONS OF COMBUSTIBLE WASTE AND DUST
 DEBRIS SHALL BE REMOVED FROM THE STRUCTURE AND ITS
 IMMEDIATE VICINITY AT THE END OF EACH SHIFT OR MORE
 FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS.
  
 04.)CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES).
  
 06.)WHERE THE BUILDING IS PROTECTED BY FIRE
 PROTECTION SYSTEMS, SUCH SYSTEMS SHALL BE MAINTAINED
 OPERATIONAL AT ALL TIMES DURING ALTERATION.
  
 07.)IF THE SCOPE OF THE INTERIOR BUILDOUT REQUIRES
 MODIFICATION OF THE FIRE SPRINKLER OR FIRE ALARM
 SYSTEM, SEPARATE PERMIT AND PLANS ARE TO BE SUBMITTED
 FOR REVIEW.
  
 08.PLEASE SHOW THE LOCATION OF THE 2A:10BC FIRE
 EXTINGUISHERS SATISFYING THE 75' TRAVEL DISTANCE.
  
 09.)ADDITIONAL PERMIT AND PLANS REQUIRED FOR
 MECHANICAL HOOD/SUPPRESSION SYSTEM.
  
 10.)DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL
 FIRE ALARM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 8561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-02-20 Cont ID  
Sent By mawillia Date 2007-02-20 Time 16:52 Rev Time 0.00
Received By mawillia Date 2007-02-20 Time 16:52 Sent To  
Notes
2007-02-20 17:16:13***DENIED*****
  
 NOTICE:WITH THE EXCEPTION OF COMMENT # 00,ALL
 OTHER COMMENTS WERE THOSE OF THE PREVIOUS FIRE PLAN
 REVIEW OF 10/12/2006
  
  
 00.)THE COMPLETE ADDRESS OF WHERE THE SCOPE OF THE
 WORK IS TO BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF
 EACH SUBMITTED PLAN SHEET.
  
 01.)NFPA 101, 2003 EDITION AND FLORIDA FIRE
 PREVENTION CODE , 2004 EDITION SHALL BE REFERENCED.
  
 02.)STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION,
 AND DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.)ACCUMULATIONS OF COMBUSTIBLE WASTE AND DUST
 DEBRIS SHALL BE REMOVED FROM THE STRUCTURE AND ITS
 IMMEDIATE VICINITY AT THE END OF EACH SHIFT OR MORE
 FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS.
  
 04.)CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES).
  
 05.)ON THE APPROPIATE STOREFRONT AND (OR) ELEVATION
 SHEET, SHOW/DISPLAY THE TENANT SPACE NUMBER FOR THIS
 STRUCTURE.AS PER WEST PALM BEACH CODE, THE CHARACTERS
 (NUMBERS AND/OR LETTERS) SHALL BE NO LESS THAN 3" IN
 HEIGHT AND 1" IN WIDTH.IF SO EQUIPPED, HURRICANE
 SHUTTERS SHALL NOT COVER OR CONCEAL THE ADDRESS.
  
 06.)WHERE THE BUILDING IS PROTECTED BY FIRE
 PROTECTION SYSTEMS, SUCH SYSTEMS SHALL BE MAINTAINED
 OPERATIONAL AT ALL TIMES DURING ALTERATION.
  
 07.)IF THE SCOPE OF THE INTERIOR BUILDOUT REQUIRES
 MODIFICATION OF THE FIRE SPRINKLER OR FIRE ALARM
 SYSTEM, SEPARATE PERMIT AND PLANS ARE TO BE SUBMITTED
 FOR REVIEW.
  
 08.)PLEASE INDICATE/DISPLAY/SHOW THE LOCATION OF EXIT
 LIGHTS, EMERGENCY LIGHTS, FIRE EXTINGUISHERS, AND FIRE
 PROTECTION SYSTEM(S).HOW WILL THEY BE AFFECTED BY THE
 SCOPE OF WORK?
  
 09.)ADDITIONAL PERMIT AND PLANS REQUIRED FOR
 MECHANICAL HOOD/SUPPRESSION SYSTEM.
  
 10.)DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL
 FIRE ALARM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 8561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-12 Cont ID  
Sent By mawillia Date 2006-10-12 Time 12:12 Rev Time 0.00
Received By mawillia Date 2006-10-12 Time 12:11 Sent To  
Notes
2006-10-12 13:08:25*****UNSAT*****
  
  
  
  
 01.)NFPA 101, 2003 EDITION AND FLORIDA FIRE
 PREVENTION CODE , 2004 EDITION SHALL BE REFERENCED.
  
 02.)STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION,
 AND DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.)ACCUMULATIONS OF COMBUSTIBLE WASTE AND DUST
 DEBRIS SHALL BE REMOVED FROM THE STRUCTURE AND ITS
 IMMEDIATE VICINITY AT THE END OF EACH SHIFT OR MORE
 FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS.
  
 04.)CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES).
  
 05.)ON THE APPROPIATE STOREFRONT AND (OR) ELEVATION
 SHEET, SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE
 STRUCTURE.AS PER WEST PALM BEACH CODE, THE CHARACTERS
 (NUMBERS AND/OR LETTERS) SHALL BE NO LESS THAN 6" IN
 HEIGHT AND 1" IN WIDTH.IF SO EQUIPPED, HURRICANE
 SHUTTERS SHALL NOT COVER OR CONCEAL THE ADDRESS.
  
 06.)WHERE THE BUILDING IS PROTECTED BY FIRE
 PROTECTION SYSTEMS, SUCH SYSTEMS SHALL BE MAINTAINED
 OPERATIONAL AT ALL TIMES DURING ALTERATION.
  
 07.)IF THE SCOPE OF THE INTERIOR BUILDOUT REQUIRES
 MODIFICATION OF THE FIRE SPRINKLER OR FIRE ALARM
 SYSTEM, SEPARATE PERMIT AND PLANS ARE TO BE SUBMITTED
 FOR REVIEW.
  
 08.)PLEASE INDICATE/DISPLAY/SHOW THE LOCATION OF EXIT
 LIGHTS, EMERGENCY LIGHTS, FIRE EXTINGUISHERS, AND FIRE
 PROTECTION SYSTEM(S).HOW WILL THEY BE AFFECTED BY THE
 SCOPE OF WORK?
  
 09.)ADDITIONAL PERMIT AND PLANS REQUIRED FOR
 MECHANICAL HOOD/SUPPRESSION SYSTEM.
  
 10.)DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL
 FIRE ALARM.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 8561-805-6722

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-02-12 Cont ID  
Sent By kstevens Date 2007-02-12 Time 12:36 Rev Time 0.00
Received By kstevens Date 2007-02-12 Time 12:36 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-09-08 Cont ID  
Sent By kstevens Date 2006-09-08 Time 09:02 Rev Time 0.00
Received By kstevens Date 2006-09-08 Time 09:02 Sent To  
Notes
2006-09-08 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SHT P-3 THE FOLLOWING INFORMATION IS
 REQUIRED FOR REQUIRED GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. LENGTHS NOT SHOWN.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 E. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 F. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 G. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. UNION NOT
 SHOWN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-08-06 Cont ID  
Sent By adarroug Date 2008-08-06 Time 10:46 Rev Time 0.00
Received By adarroug Date 2008-08-06 Time 10:46 Sent To P
Notes
2008-08-06 10:46:30TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-06-16 Cont ID  
Sent By adarroug Date 2008-06-16 Time 16:20 Rev Time 0.00
Received By adarroug Date 2008-06-16 Time 16:20 Sent To P
Notes
2008-06-16 16:20:32TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-06-11 Cont ID  
Sent By adarroug Date 2008-06-11 Time 15:41 Rev Time 0.00
Received By adarroug Date 2008-06-11 Time 15:41 Sent To  
Notes
2008-06-11 15:46:53TO "COMM" BD#55

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-06-10 Cont ID  
Sent By adarroug Date 2008-06-10 Time 14:44 Rev Time 0.00
Received By adarroug Date 2008-06-10 Time 14:44 Sent To P
Notes
2008-06-10 14:44:46TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-05-02 Cont ID  
Sent By adarroug Date 2008-05-02 Time 12:47 Rev Time 0.00
Received By adarroug Date 2008-05-02 Time 12:47 Sent To P
Notes
2008-05-02 12:47:44TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-05-02 Cont ID  
Sent By adarroug Date 2008-05-02 Time 12:35 Rev Time 0.00
Received By adarroug Date 2008-05-02 Time 12:35 Sent To M
Notes
2008-05-02 12:35:54TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-05-02 Cont ID  
Sent By adarroug Date 2008-05-02 Time 12:00 Rev Time 0.00
Received By adarroug Date 2008-05-02 Time 12:00 Sent To E
Notes
2008-05-02 12:00:37TO "DPALMER' DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-01-02 Cont ID  
Sent By spalmer Date 2008-01-02 Time 16:06 Rev Time 0.00
Received By spalmer Date 2008-01-02 Time 16:06 Sent To B
Notes
2008-01-02 16:06:44TO SAMANTHA HILLS DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-07-30 Cont ID  
Sent By adarroug Date 2007-07-30 Time 09:32 Rev Time 0.00
Received By adarroug Date 2007-07-30 Time 09:32 Sent To  
Notes
2007-08-01 08:15:41TO "COMM" BD#5
2007-07-30 09:32:35WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-18 Cont ID  
Sent By adarroug Date 2007-04-18 Time 09:04 Rev Time 0.00
Received By adarroug Date 2007-04-18 Time 09:04 Sent To  
Notes
2007-04-18 09:06:42TO "COMM" BD#60

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-10 Cont ID  
Sent By adarroug Date 2007-01-10 Time 10:10 Rev Time 0.00
Received By adarroug Date 2007-01-10 Time 10:10 Sent To  
Notes
2007-01-22 08:40:12TO "COMM" BD#13
2007-01-10 10:11:16WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-12 Cont ID  
Sent By mawillia Date 2006-10-12 Time 12:12 Rev Time 0.00
Received By mawillia Date 2006-08-25 Time 10:51 Sent To  
Notes
2006-08-25 00:00:00WAITING FOR "COMM" BD
 TO "COMM" BD#58

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-07-02 Cont ID  
Sent By rregueir Date 2008-07-02 Time 16:53 Rev Time 0.00
Received By rregueir Date 2008-07-02 Time 15:24 Sent To E
Notes
2008-07-02 16:53:48REVISED M-1, M-2, M-3

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-05-21 Cont ID  
Sent By rregueir Date 2008-05-21 Time 11:13 Rev Time 0.00
Received By rregueir Date 2008-05-21 Time 08:55 Sent To PC
Notes
2008-05-21 11:13:12REVIEW #: REVISION
 ACTION: DENIED
  
 CODES:
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGES M-0, M-3 AND M-4 WERE SUBMITTED AS PART OF
 THIS REVISION BUT DO NOT SHOW ANY CHANGES. WHEN
 RESUBMITTING, PLEASE PROVIDE ONLY THOSE PAGES WHICH
 HAVE CHANGES TO BE UPDATED IN THE PERMIT RECORD.
  
 2. PG M-2: HOOD-3 IS BEING REMOVED FROM PLANS. IF THERE
 IS AN OVEN AT THIS LOCATION, IT STILL REQUIRES EITHER A
 TYPE I OR TYPE II HOOD IN ACCORDANCE WITH FBCM 507.2.
 PLEASE SHOW HOW COMPLIANCE WITH THIS CODE SECTION SHALL
 BE ACHIEVED.
  
 3. PG M-2: THE 10X10 GREASE DUCT ASSOCIATED WITH HOOD-3
 IS BEING REPLACED WITH AN 8 INCH ROUND DUCT. KEY NOTE
 #4 CALLS THIS A GREASE DUCT WHILE KEY NOTE #39 CALLS IT
 A PRE-FAB DIRECT-VENT EXHAUST DUCT. PLEASE CLARIFY BY
 ELIMINATING CONFLICTING INFORMATION IN THE KEY NOTES.
 ALSO, IF THE OVEN IS A DIRCT-VENT APPLIANCE AS
 INDICATED BY KEY NOTE #19, IT REQUIRES COMBUSTION AIR
 DIRECTLY FROM THE OUTDOORS. SEE DEFINITION OF
 DIRECT-VENT IN FBCFG SECTION 202. SHOW THE SOURCE OF
 DIRECT COMBUSTION AIR IF THIS IS A DIRECT-VENT
 APPLIANCE.
  
 4. PG M-2: KEY NOTE #4 INDICATES THE 8 INCH ROUND DUCT
 IN THE SHAFT IS EXISTING. THIS IS NOT ACCURATE AS THE
 EXHAUST DUCTS IN THE SHAFT WERE INSTALLED UNDER
 SEPARATE PERMIT #07010023 AND THERE WAS NO 8 INCH ROUND
 DUCT ON PLANS OR ASSOCIATED WITH THAT PERMIT. PLEASE
 CORRECT AND SHOW THE 8 INCH ROUND DUCT AS NEW WORK PART
 OF THIS PERMIT. FBCB 106.1.1.
  
 5. THE KITCHEN HOODS AND GREASE DUCTS ARE ALSO UNDER A
 SEPARATE PERMIT #08010158. IF HOOD-3, RELATED DUCTWORK
 AND FANS ARE TO BE ELIMINATED, PLANS FOR PERMIT
 #08010158 SHALL ALSO BE REVISED. ALL WORK SHALL BE DONE
 IN ACCORDANCE WITH PERMITTED CONSTRUCTION DOCUMENTS AND
 ANY CHANGES SHALL BE SUBMITTED FOR REVIEW IN ACCORDANCE
 WITH FBCB 106.4.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-05-04 Cont ID  
Sent By rregueir Date 2007-05-04 Time 10:35 Rev Time 0.00
Received By rregueir Date 2007-05-04 Time 07:40 Sent To  
Notes
2007-05-04 10:35:04*************PROVISO**************
  
 1. WORK IN SHAFT IS BEING DONE UNDER PERMIT #07010023.
 THE CONDITIONS OF THAT PERMIT SHALL BE SATISFIED PRIOR
 TO FINAL INSPECTION.
 2. GREASE EXHAUST DUCTS AND HOODS SHALL BE UNDER
 SEPARATE "MECHHOOD" PERMIT.
 3. HOOD SUPPRESSION SYSTEMS AND WALK-IN COOLERS REQUIRE
 SEPARATE PERMITS. WORK REQUIRING ADDITIONAL PERMITS
 SHALL NOT BE STARTED ORIOR TO SECURING THOSE PERMITS.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-02-14 Cont ID  
Sent By rregueir Date 2007-02-14 Time 14:36 Rev Time 0.00
Received By rregueir Date 2007-02-14 Time 14:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-11 Cont ID  
Sent By rregueir Date 2006-10-11 Time 18:45 Rev Time 0.00
Received By rregueir Date 2006-10-10 Time 17:51 Sent To  
Notes
2006-10-11 19:01:58------------------DENIED-------------------------
  
 1. EXISTING AHU 1 ACCESS MUST BE LARGE ENOUGH FOR
 REPLACEMENT OF EQUIPMENT PER FBC,M 306
  
 2. KSF 1 REQUIRES DUCT MOUNTED SMOKE DETECTOR AS IT
 EXCEEDS 2,000 CFM.ALL DUCT DETECTORS ARE TO BE TIED
 IN TO THE BUILDING FIRE ALARM SYSTEM PER FBC,M 606
  
 3. VERIFY KSF 1 INTAKE IS IN COMPLIANCE WITH FBC,M
 401.5.1
  
 4. PROVIDE DETAIL FOR GREASE EXHAUST DUCT PENETRATIONS
 THROUGH RATED WALLS AND SHAFTS. SHOW COMPLIANCE WITH
 FBC,M 506.3.10 WITH 2 HOUR LISTED SYSTEMS TO BE USED
 AND INSTALLATION INSTRUCTIONS.
  
 5. HORIZONTAL GREASE EXHAUST DUCT THROUGH LOBBY FOR
 LOFTS REQUIRES CLEAN OUTS PER 506.3.9. HOW WILL ASSESS
 TO CLEAN-OUTS BE PROVIDED IN LOBBY AREA?
  
 6. PAGE M3: A/C ROOF EQUIPMENT MOUNTING DETAIL NOTE
 REFERS TO FBC 2001. PLEASE REFERENCE FBC 2004.
  
 7. PAGE M4: BALANCING GREASE EXHAUST DAMPER DETAIL - IS
 THERE TO BE A BALANCING DAMPER INSIDE THE GREASE
 EXHAUST DUCT? IS THERE A GAP BETWEEN THE HOOD COLLAR
 AND THE DUCT? PLEASE CLARIFY.
  
 8. SEPERATE PERMITS ARE REQUIRED FOR A/C, HOOD SYSTEMS,
 HOOD SUPPRESSION SYSTEMS, WALK-IN COOLERS/FREEZERS.
 ONLY THE A/C AND GREASE EXHAUST DUCT SYSTEMS WERE
 REVIEWED FOR CODE COMPLIANCE. APPLICATIONS AND
 SUBMITTALS FOR ALL OTHER SYSTEMS WILL BE REQUIRED PRIOR
 TO ISSUANCE OF EACH PERMIT.
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop P PLUMBING
Rev No 8 Status P Date 2008-08-08 Cont ID  
Sent By kstevens Date 2008-08-08 Time 16:16 Rev Time 0.00
Received By kstevens Date 2008-08-08 Time 16:16 Sent To  
Notes
2008-08-08 16:17:31REVISIONS OK--SHTS P-1, P-2 & P-3

Review Stop P PLUMBING
Rev No 7 Status P Date 2008-06-17 Cont ID  
Sent By kstevens Date 2008-06-17 Time 10:02 Rev Time 0.00
Received By kstevens Date 2008-06-11 Time 12:49 Sent To  
Notes
2008-06-17 10:03:23REVISIONS OK--SHTS P-I & P-3

Review Stop P PLUMBING
Rev No 6 Status N Date 2008-05-20 Cont ID  
Sent By kstevens Date 2008-05-20 Time 11:22 Rev Time 0.00
Received By kstevens Date 2008-05-20 Time 11:22 Sent To  
Notes
2008-05-20 11:24:01REVISION NOT REQUIRED.--SHT P-0, NO NEW REVISION
 NUMBER INDICATED AND NO CHANGES NOTED ON SHT.

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-05-20 Cont ID  
Sent By kstevens Date 2008-05-20 Time 11:21 Rev Time 0.00
Received By kstevens Date 2008-05-20 Time 11:21 Sent To  
Notes
2008-05-20 11:22:44REVISIONS OK--SHTS P-I, P-2 & P-3

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-08-10 Cont ID  
Sent By kstevens Date 2007-08-10 Time 13:24 Rev Time 0.00
Received By kstevens Date 2007-08-10 Time 13:24 Sent To  
Notes
2007-08-10 13:27:05PASSED PROVISO
  
 REVISIONS REQUIRED FOR SHEETS P-1 & P-3 (SANT. RISER
 DIAGRAM) PRIOR TO SETTING THE GREASE INTERCEPTORS. THE
 GREASE INTERCEPTORS SHALL BE INSTALLED IN PARALLEL, NOT
 SERIES AS INDICATED.

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-06-01 Cont ID  
Sent By kstevens Date 2007-06-01 Time 16:16 Rev Time 0.00
Received By kstevens Date 2007-06-01 Time 16:16 Sent To  
Notes
2007-06-01 16:20:33DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CITY CODE
  
 FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
  
 4. GREASE INTERCEPTOR SHALL BE SIZED BY
 LYNN MASSON, ENVIRONMENTAL COMPLIANCE
 MANAGER. CONTACT LYNN BY PHONE (561)
 822-2271, OR BY FAX (561) 822-2279, OR
 E-MAIL [email protected]. MUNICIPAL CODE
 SECTION 3434.
 ****RESPONSE NOTED, BUT NO FEEDBACK FROM ENVIRONMENTAL
 COMPLIANCE AS OF YET.
 *******RESPONSE FROM RODNEY COMPO IS IN CONFLICT WITH
 INFORMATION SUBMITTED FROM ED SAMOUR. THE TABLES AND
 BENCH SEATING ARE APPROX. 152 SEATS, AND THE OCCUPANCY
 INDICATES APPROX. 200. SEE COPY OF ATTACHED SHEET FROM
 ENVIRONMENTAL COMPLIANCE REQUIRING 3, 1250 GAL GREASE
 INTERCEPTORS.
  
 5. OK
 6. OK
 7. OK
 8. OK
 A. OK
 B. OK
 C. OK
 D. OK
 E. N/A
 F. N/A
 G. OK
  
 **********NEW COMMENT*************
  
 1B. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-02-12 Cont ID  
Sent By kstevens Date 2007-02-12 Time 12:29 Rev Time 0.00
Received By kstevens Date 2007-02-12 Time 12:29 Sent To  
Notes
2007-02-12 12:36:30DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CITY CODE
  
 FROM PREVIOUS REVIEW:
  
 1. PLANS SHALL BE ROUTED TO DBPR
 RESTURANT AND HOTEL DIVISION FOR REVIEW
 PRIOR TO RESUBMITTING. PLANS SHALL BE
 STAMPED AND TWO PAGE "WORKSHEETS"
 ATTACHED TO EACH SET OF PLANS TO BE
 SUBMITTED. SECTION 102.2.1.
 ****NO RESPONSE, NOT ADDRESSED
  
 2. OK
 3. OK
  
 4. GREASE INTERCEPTOR SHALL BE SIZED BY
 LYNN MASSON, ENVIRONMENTAL COMPLIANCE
 MANAGER. CONTACT LYNN BY PHONE (561)
 822-2271, OR BY FAX (561) 822-2279, OR
 E-MAIL [email protected]. MUNICIPAL CODE
 SECTION 3434.
 ****RESPONSE NOTED, BUT NO FEEDBACK FROM ENVIRONMENTAL
 COMPLIANCE AS OF YET.
  
 5. OK
 6. OK
 7. OK
 8. OK
 A. OK
 B. OK
 C. OK
 D. OK
 E. N/A
 F. N/A
 G. OK
  
 **********NEW COMMENT*************
  
 1B. SHTS P-1 & P-3 THE DISHWASHER SHALL CONNECT TO THE
 SANITARY, NOT THE GREASE SYSTEM. MUNICIPAL
 90-124(7)(B). (MISSED ON FIRST REVIEW)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-09-08 Cont ID  
Sent By kstevens Date 2006-09-08 Time 08:04 Rev Time 0.00
Received By kstevens Date 2006-09-07 Time 18:52 Sent To  
Notes
2006-09-08 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. PLANS SHALL BE ROUTED TO DBPR
 RESTURANT AND HOTEL DIVISION FOR REVIEW
 PRIOR TO RESUBMITTING. PLANS SHALL BE
 STAMPED AND TWO PAGE "WORKSHEETS"
 ATTACHED TO EACH SET OF PLANS TO BE
 SUBMITTED. SECTION 102.2.1
  
 2. SUBMIT CALCULATIONS FOR MINIMUM
 FIXTURE REQUIREMENTS. TABLES 1004.1.2
 AND 403.1.
  
 3. SUBMIT AN EXISTING FLOOR PLAN TO
 DETERMINE THE EXTENT OF THE DEMO WORK TO
 BE DONE. SECTION 106.1.1.
  
 4. GREASE INTERCEPTOR SHALL BE SIZED BY
 LYNN MASSON, ENVIRONMENTAL COMPLIANCE
 MANAGER. CONTACT LYNN BY PHONE (561)
 822-2271, OR BY FAX (561) 822-2279, OR
 E-MAIL [email protected]. MUNICIPAL CODE
 SECTION 3434.
  
 5. SHT A1.1 EQUIPMENT LIST INDICATES TWO
 #19 HAND SINKS, BUT ONLY ONE WAS FOUND.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 6. SHT P-0 PLUMBING SPECIFICATIONS.
 FLOOR DRAINS ARE NOT AN APPROVED
 INDIRECT WASTE RECEPTOR. FLOOR SINKS OR
 HUB DRAINS SHALL BE USED. SECTIONS 802.3
 AND 802.3.2.
  
 7. SHT P-3 DOMESTIC WATER ISOMETRIC.
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES, IN AN "EFFECTIVE
 RANGE", NOT IN THE CEILING AS SHOWN.
 PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
  
 8. SHT P-3 THE FOLLOWING INFORMATION IS
 REQUIRED FOR REQUIRED GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. LENGTHS NOT SHOWN.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 E. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 F. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 G. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. UNION NOT
 SHOWN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2007-08-07 Cont ID  
Sent By eschneid Date 2007-08-07 Time 13:24 Rev Time 0.00
Received By eschneid Date 2007-08-07 Time 13:24 Sent To  
Notes
***NONE***