Plan Review Details - Permit 06081925
Plan Review Stops For Permit 06081925
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2007-09-25 Cont ID  
Sent By lursu Date 2007-09-25 Time 16:14 Rev Time 0.00
Received By lursu Date 2007-09-25 Time 09:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2007-12-05 Cont ID  
Sent By shill Date 2007-12-05 Time 10:07 Rev Time 0.00
Received By shill Date 2007-12-05 Time 10:07 Sent To  
Notes
2007-12-05 10:14:05****CORRECTIONS****
 ****REVISION****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS REVIEW:
  
 1.)ALL INFORMATION REQUIRED BY FAC61G15-23.002 IS
 REQUIRED ON EACH SHEET, INCLUDING CERTIFICATE OF
 AUTHORIZATION.
  
 2-4.)ADDRESSED.
  
 5.)THE WIND DESIGN CRITERIA, FBC1603.1.4, IS TO STAY
 WITH THE PLANS.THIS WAS BROUGHT IN AS A LETTER;
 EITHER INCORPORATE INTO THE PLAN OR SUBMIT THE LETTER
 WITH THE PLANS WHEN RESUBMITTING.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-10-01 Cont ID  
Sent By shill Date 2007-10-01 Time 11:48 Rev Time 0.00
Received By shill Date 2007-10-01 Time 11:48 Sent To  
Notes
2007-10-01 11:55:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)ALL INFORMATION REQUIRED BY FAC61G15-23.002 IS
 REQUIRED ON EACH SHEET, INCLUDING CERTIFICATE OF
 AUTHORIZATION.
  
 2.)IN THE ORIGINAL PLAN, YOU HAVE A SERIES OF
 STRUCTURAL DETAILS 1 THROUGH 11.IN THIS SET, YOU HAVE
 ONE SERIES OF DRAWINGS 1 - 10, AND ANOTHER WHICH IS 1 -
 11.IT IS NOT CLEAR HOW THESE TWO SETS OF DRAWINGS
 CORRELATE WITH THE ORIGINAL SET.PLEASE REVISE YOUR
 SHEET NAMING CONVENTION SO THAT THERE IS NO DUPLICATION
 OF NUMBERS.IF THESE THREE SETS ARE ADDED TO THE
 ORIGINAL SET, YOU NOW HAVE THREE "SHEET 1", TWO WHICH
 ARE MARKED "SHEET 1 OF 11".FOR CLARITY, PROVIDE AN
 INDEX.
  
 3.)THE ORIGINAL DRAWINGS IS A SET OF 11 SHEETS.YOU
 HAVE SUBMITTED A SET OF TEN SHEETS WHICH HAS REVISION
 NUMBERS (ALTHOUGH NOTHING IS CLOUDED).YOU HAVE ALSO
 SUBMITTED A SET OF 11 DRAWINGS, NO REVISION NUMBERS.
 DO THESE TWO DRAWING SETS COMPLETELY REPLACE AND VOID
 THE ORIGINAL DRAWING SET OF 11?
  
 4.)ALL CHANGES TO THE PLAN ARE TO BE CLOUDED WITH
 REVISION NUMBERS/DATES.A TRANSMITTAL LETTER IS
 HELPFUL.
  
 5.)DECLARE GOVERNING CODE AND WIND DESIGN CRITERIA,
 FBC1603.1.4.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-07-19 Cont ID  
Sent By lmartine Date 2007-07-19 Time 16:21 Rev Time 0.00
Received By lmartine Date 2007-07-19 Time 16:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-07-17 Cont ID  
Sent By shill Date 2007-07-17 Time 10:43 Rev Time 0.00
Received By shill Date 2007-07-17 Time 10:42 Sent To  
Notes
2007-07-17 10:45:24****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)THE SCOPE HAS BEEN REDUCED,THERE ARE MANY SHEETS
 IN THE PLAN WHICH HAVE BEEN CROSSED OFF.PLEASE REMOVE
 ALL UNNECESSARY SHEETS.SHEETS SHOWING WORK TO BE DONE
 ALONG WITH WORK NOW CROSSED OFF ARE ACCEPTABLE TO BE
 LEFT IN THE PACKAGE.HOWEVER, SHEETS SUCH AS G4, G5,
 G6 HAVE THE ENTIRE SHEET CLOUDED AS NOT IN THE SCOPE OF
 THIS PERMIT.THEREFORE, THE SHEETS SHOULD BE
 UNNECESSARY.KEEP ONLY SHEETS PERTINENT TO THIS
 PERMIT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-16 Cont ID  
Sent By shill Date 2007-03-16 Time 08:57 Rev Time 0.00
Received By shill Date 2007-03-16 Time 08:12 Sent To  
Notes
2007-03-16 09:02:51****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1-6.)ADDRESSED.
  
 7.)GUARDS REQUIRED, FBC1012.1.ALSO
 SEE FBC1012.1 EXCEPTION 1.SHOW
 LOCATIONS OF REQUIRED GUARDS AND PROVIDE
 A DETAIL IN COMPLIANCE WITH FBC1012.2,
 1012.3, 1607.9.
  
 THE RAMP DETAIL PROVIDED IS NOT COMPLIANT WITH THE
 GUARDRAIL REQUIREMENTS FBC1012.1.
  
 8-9.)ADDRESSED.
  
 10.) PERMITS ARE REQUIRED FROM USACE AND
 DEP.PLANS MAY BE RESUBMITTED PRIOR TO
 FINAL USACE AND DEP APPROVAL, BUT THE
 WPB BUILDING PERMIT WILL NOT BE ISSUED
 UNTIL A COPY OF THE PERMITS ARE
 PROVIDED.
  
 11.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS,
 FS713.13.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-21 Cont ID  
Sent By shill Date 2006-09-21 Time 12:59 Rev Time 0.00
Received By shill Date 2006-09-21 Time 11:22 Sent To  
Notes
2006-09-21 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)ALL INFORMATION REQUIRED BY
 FAC61G16-23.002 IS TO BE ON EACH SHEET
 (TITLE BLOCK FOR ENGINEER, STRUCTURAL
 PLAN).
  
 2.)P1 OF 2, DESIGN CRITERIA, DECLARE
 GOVERNING CODE.
  
 3.)P1 OF 2, DESIGN CRITERIA, DECLARE
 EXPOSURE ("C"), FBC1603.1.4.
  
 4.)THE SITE IS REQUIRED TO BE
 ACCESSIBLE, FBC11-4.1(1)(A).SHOW
 ACCESSIBLE ROUTE, FBC11-4.1.2.INCLUDE
 SLOPE AND CROSS SLOPES.
  
 5.)GROUND SURFACES TO COMPLY WITH
 FBC11-4.5.PROVIDE INFORMATION/DETAILS
 TO SHOW COMPLIANCE.
  
 6.)SEE ATTACHED ADAAG FOR INFORMATION
 REGARDING DESIGN OF ACCESSIBLE BOATING
 FACILITIES. THIS IS AVAILABLE AT
 HTTP://WWW.ACCESS-BOARD.GOV/
 RECREATION/GUIDES/BOATING.HTM
  
 7.)GUARDS REQUIRED, FBC1012.1.ALSO
 SEE FBC1012.1 EXCEPTION 1.SHOW
 LOCATIONS OF REQUIRED GUARDS AND PROVIDE
 A DETAIL IN COMPLIANCE WITH FBC1012.2,
 1012.3, 1607.9.
  
 8.)SEE FBC11-4.8.5.SHOW LOCATIONS OF
 ANY HANDRAILS REQUIRED AND PROVIDE A
 DETAIL, FBC11-4.26.
  
 9.)TWO GANGWAYS ARE SHOWN AS "ADA".
 HOW WILL THE OTHER AREAS BE ACCESSIBLE?
 PROVIDE GANGWAY DETAILS.
  
 10.) PERMITS ARE REQUIRED FROM USACE AND
 DEP.PLANS MAY BE RESUBMITTED PRIOR TO
 FINAL USACE AND DEP APPROVAL, BUT THE
 WPB BUILDING PERMIT WILL NOT BE ISSUED
 UNTIL A COPY OF THE PERMITS ARE
 PROVIDED.
  
 11.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS,
 FS713.13.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-11-29 Cont ID  
Sent By btrobaug Date 2007-11-29 Time 16:29 Rev Time 0.00
Received By btrobaug Date 2007-11-29 Time 15:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-10-25 Cont ID  
Sent By btrobaug Date 2007-10-25 Time 11:22 Rev Time 0.00
Received By btrobaug Date 2007-10-22 Time 15:06 Sent To PC
Notes
2007-10-25 10:28:36 
  
 REVISION DENIED
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PLEASE CLOUD OR OTHERWISE NOTE REVISION FOR CLARITY
 AND RECORD RETENTION. 106.1.3, AS AMENDED.
  
 2} NOTE #8 SHEET E1 INDICATES THE USE OF "NMPT". NOTE
 THE SCOPE PER UL WOULD PROHIBIT USE OF THAT TUBING:
 NONMETALLIC MECHANICAL PROTECTION TUBING (NMPT)
 UL 1696
  
 1 SCOPE
 1.1 THIS STANDARD APPLIES TO NONMETALLIC MECHANICAL
 PROTECTION TUBING (NMPT) AND FITTINGS IN 10 TO 53 (1/4
 TO 2) TRADE SIZES FOR USE AS SUPPORT AND PROTECTION OF
 INSULATED CONDUCTORS IN EQUIPMENT INTENDED FOR USE IN
 NON-HAZARDOUS LOCATIONS. FOR TUBING AND FITTING SIZES
 IN THIS STANDARD, THE METRIC DESIGNATOR IS GIVEN FIRST,
 WITH THE TRADE SIZE IN INCHES FOLLOWING IN
 PARENTHESES.
  
  
 1.2 TUBING SPECIFIED BY THIS STANDARD IS INTENDED FOR
 USE WITH FITTINGS IN COMPLIANCE WITH CLAUSE 4.3. THE
 FITTINGS MAY BE FOR WET OR DRY LOCATIONS.
  
 1.3 THIS STANDARD DOES NOT INCLUDE TUBING USED TO
 SUPPLY POWER FROM THE FIXED WIRING OF STRUCTURES TO
 UTILIZATION EQUIPMENT.
  
 3} SHEETS E5 AND E6 ARE NOT REVISIONS OF THOSE SAME
 NUMBERED SHEETS ON THE PERMITTED SET. CORRELATE REVISED
 SHEET NUMBERS TO THE SHEET BEING REVISED FOR RECORD
 KEEPING AND CLARITY IN THE FIELD. 106.1.3 FBC AS
 AMENDED.
  
 NOTE: SEE FIRE PLAN REVIEW FOR COMMENTS ON ADDRESS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-02-20 Cont ID  
Sent By btrobaug Date 2007-02-20 Time 15:47 Rev Time 2.00
Received By btrobaug Date 2007-02-20 Time 11:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-13 Cont ID  
Sent By btrobaug Date 2006-10-13 Time 16:03 Rev Time 3.00
Received By btrobaug Date 2006-10-06 Time 12:31 Sent To  
Notes
2006-10-13 16:02:59NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE ENGINEER OF RECORD SHALL INDICATE THE
 CERTIFICATE OF AUTHORIZATIONNUMBER ALONG WITH OTHER
 INFORMATION REQUIRED BY 61G15-23.002FLORIDA
 ADMINISTRATIVE CODE.
  
 2} PROVIDE A DETAIL INDICATING COMPLIANCE WITH ARTICLE
 501 NECAND 30A NFPA FOR THE ELECTRICAL CONNECTIIONS
 AT THE FUEL DISPENSING SYSTEM ON THE DOCKS.
  
 3} PLEASE SUBMIT DETAILS OF THE "DATACOM" PEDESTALS
 LIKE THE ONES SUBMITTED FOR THE POWER PEDESTALS.
 INDICATE IF THE CONDUIT SYSTEM IS INDEPENDENT OF THE
 BELLINGHAM SYSTEM OR PART OF SAME SYSTEM. THERE DOESN'T
 APPEAR TO BE HANDHOLES OR PULLING POINTS. PLEASE
 CLARIFY.
  
 4} THERE WERE DRAWINGS SUBMITTED FROM MEISNER ELECTRIC,
 WHICH MUST CONTAIN THE PRINTED NAME AND WRITTEN
 SIGNATURE OF THE DESIGNER PER 106.3.4.2 FBC AS AMENDED,
 OR CHAPTER 471 FS IF APPLICABLE. THERE WERE ALSO
 DRAWINGS ON SHEET E5 OF THE ELECTRICAL PLANS FOR THIS
 SYSTEM. PLEASE INDICATE WHICH ONE WILL BE SUBMITTED FOR
 PERMITTING, WHICH DESIGNER IS TAKING RESPONSIBILITY.
  
 5} SUBMIT DETAILS FOR THE MOUNTING AND WIRING FOR THE
 CCTV CAMERAS SHOWN ON THE PLANS.
  
 6} SUBMIT A COMPLETE RACEWAY SYSTEM FOR THE POWER POINT
 PEDESTAL FEEDERS. SUBMITTED WERE CONDUITS , CABLES AND
 THWN, ALL OF WHICH WILL BE EXPOSED AND NOT PART OF ANY
 SYSTEM BETWEEN DOCK SECTIONS. SEE NEC.300.4 PROTECTION
 AGAINST PHYSICAL DAMAGE.
 WHERE SUBJECT TO PHYSICAL DAMAGE, CONDUCTORS SHALL BE
 ADEQUATELY PROTECTED.
  
 7} THE SPECIFICATION SECTION ON E2 INCORRECTLY
 REFERENCES THE 2005 EDITION OF THE NEC, THE CODE
 CURRENTLY ADOPTED BY THE FLORIDA LEGISLATURE IS 2002.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2007-09-28 Cont ID  
Sent By rchokshi Date 2007-09-28 Time 16:00 Rev Time 0.00
Received By rchokshi Date 2007-09-28 Time 16:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-12-20 Cont ID  
Sent By mawillia Date 2007-12-20 Time 13:35 Rev Time 0.00
Received By mawillia Date 2007-12-20 Time 12:53 Sent To E
Notes
2007-12-20 13:35:15*****REVISION APPROVED*****
  
 THE COMMENT FROM THE PREVIOUS FIRE PLAN REVIEW
 (10/09/07) HAS BEEN ADDRESSED;REVISED PLAN SHEET P1
 OF P2 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2007-10-09 Cont ID  
Sent By mawillia Date 2007-10-09 Time 12:05 Rev Time 0.00
Received By mawillia Date 2007-10-09 Time 11:48 Sent To  
Notes
2007-10-09 12:05:32*****UNSAT*****
  
  
 1.THE ACTUAL/CORRECT ADDRESS OF THE PROJECT SITE
 SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET.BE ADVISED THAT:*NO ADDRESS SHOWN ON THE
 SHEET E1 THRU E6;*THE ADDRESS OF 4000 NORTH FLAGLER
 IS SHOWN ON SHEET P1 AND P2;*THE ADDRESS OF 4300
 NORTH FLAGLER IS ON YOUR SUBMITTAL FORM;* THE ADDRESS
 4210 NORTH FLAGLER IS RECORDED IN THE PERMIT SYSTEM.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-07-18 Cont ID  
Sent By mawillia Date 2007-07-18 Time 17:17 Rev Time 0.00
Received By mawillia Date 2007-07-18 Time 17:09 Sent To  
Notes
2007-07-18 17:14:09*****PROVISO*****
  
  
 THE APPROPIATE SHEET(S) TO BE FIRE-STAMPED WHEN ALL
 OTHER REVIEWERS HAVE BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-03-07 Cont ID  
Sent By mawillia Date 2007-03-07 Time 16:26 Rev Time 0.00
Received By mawillia Date 2007-03-07 Time 16:16 Sent To  
Notes
2007-03-07 16:26:29*****APPROVED*****
  
  
 ALL COMMENTS FROM PREVIOUS FIRE PLAN REVIEW HAVE BEEN
 ADDRESSED.PLAN SHEET P1 STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-11-02 Cont ID  
Sent By mwennerg Date 2006-11-02 Time 14:51 Rev Time 0.00
Received By mwennerg Date 2006-11-02 Time 14:51 Sent To  
Notes
2006-11-02 15:01:06***DENIED***
  
 1) WORK SHALL COMPLY WITH NFPA 303, FIRE PROTECTION
 STANDARD FOR MARINAS AND BOATYARDS.
  
 2) PLEASE PROVIDE MORE DETAILS REGARDING FUELING
 OPERATIONS, THAT SHALL COMPLY WITH NFPA 30A.
  
 3) PLEASE NOTE THAT ALL REQUIRED SIGNAGE SHALL BE
 APPROPRIATELY DISPLAYED. IN ADDITION, PLEASE INDICATE
 EMERGENCY FUEL SHUT OFF ON PLANS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW (561) 805-6722 OR 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-01-02 Cont ID  
Sent By spalmer Date 2008-01-02 Time 11:59 Rev Time 0.00
Received By spalmer Date 2008-01-02 Time 11:59 Sent To B
Notes
2008-01-02 11:59:40TO SAMANTHA HILLS DESK

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-12-19 Cont ID  
Sent By adarroug Date 2007-12-19 Time 16:34 Rev Time 0.00
Received By adarroug Date 2007-12-19 Time 16:34 Sent To B
Notes
2007-12-19 16:34:41TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-11-15 Cont ID  
Sent By adarroug Date 2007-11-15 Time 08:17 Rev Time 0.00
Received By adarroug Date 2007-11-15 Time 08:17 Sent To  
Notes
2007-11-27 14:32:11TO "COMM" BD#54
2007-11-15 08:17:33WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-12 Cont ID  
Sent By adarroug Date 2007-09-05 Time 11:20 Rev Time 0.00
Received By adarroug Date 2007-09-05 Time 11:20 Sent To  
Notes
2007-09-28 08:23:24TO "COMM" BD#18
2007-09-12 11:20:59WAITING FOR "COMM" BD--REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-05 Cont ID  
Sent By adarroug Date 2007-06-05 Time 11:51 Rev Time 0.00
Received By adarroug Date 2007-06-05 Time 11:51 Sent To  
Notes
2007-06-18 09:11:17TO "COMM" BD#46
2007-06-05 11:51:36WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-24 Cont ID  
Sent By adarroug Date 2007-01-24 Time 17:12 Rev Time 0.00
Received By adarroug Date 2007-01-24 Time 17:12 Sent To  
Notes
2007-02-02 09:47:10TO "COMM" BD#52
2007-01-24 17:12:51WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-06 Cont ID  
Sent By mwennerg Date 2006-11-06 Time 13:09 Rev Time 0.00
Received By mwennerg Date 2006-08-26 Time 12:08 Sent To  
Notes
2006-08-28 00:00:00TO "COMM" BD#24
2006-08-26 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-10-14 Cont ID  
Sent By hmoser Date 2006-10-14 Time 10:39 Rev Time 0.00
Received By hmoser Date 2006-10-14 Time 10:39 Sent To  
Notes
2006-10-14 10:40:41NO MECHANICAL PLANS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 4 Status N Date 2007-12-14 Cont ID  
Sent By kstevens Date 2007-12-14 Time 17:28 Rev Time 0.00
Received By kstevens Date 2007-12-14 Time 17:28 Sent To  
Notes
2007-12-14 17:29:00NO PLUMBING REVISIONS SUBMITTED

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-10-19 Cont ID  
Sent By mperson Date 2007-10-19 Time 15:10 Rev Time 0.00
Received By mperson Date 2007-10-19 Time 14:21 Sent To PC
Notes
2007-10-19 14:29:22REVISION DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 1. ALL CHANGES TO THE PLAN ARE TO BE CLOUDED WITH
 REVISION NUMBERS/DATES PER FBC-2004 CHAPTER 1, SECTION
 106.1.3 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM.
 NOTE: A TRANSMITTAL LETTER IS HELPFUL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-02-24 Cont ID  
Sent By kstevens Date 2007-02-24 Time 11:27 Rev Time 0.00
Received By kstevens Date 2007-02-24 Time 11:27 Sent To  
Notes
2007-02-24 11:29:32PASSED/PROVISO--RPZV BACKFLOWS REQUIRED AT THE
 POINTS OF CONNECTION UNLESS THERE IS A DEDCATED LINE
 FOR THE DOCKS, IN THAT CASE ONE BACKFLOW FOR POTABLE
 WATER TO DOCK REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-09-16 Cont ID  
Sent By kstevens Date 2006-09-16 Time 07:41 Rev Time 0.00
Received By kstevens Date 2006-09-16 Time 07:41 Sent To  
Notes
2006-09-16 00:00:00BACKFLOW PREVENTION REQUIRED

Review Stop Z ZONING
Rev No 6 Status P Date 2007-12-21 Cont ID  
Sent By jroach Date 2007-12-21 Time 11:16 Rev Time 0.00
Received By jroach Date 2007-12-21 Time 11:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status P Date 2007-09-25 Cont ID  
Sent By jroach Date 2007-09-25 Time 10:34 Rev Time 0.00
Received By jroach Date 2007-09-25 Time 10:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2007-07-16 Cont ID  
Sent By jroach Date 2007-07-16 Time 08:20 Rev Time 0.00
Received By jroach Date 2007-07-16 Time 08:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2007-02-08 Cont ID  
Sent By jroach Date 2007-02-08 Time 17:43 Rev Time 0.00
Received By jroach Date 2007-02-08 Time 17:43 Sent To  
Notes
2007-02-08 17:53:51***FAILED***
  
 1) A MAJOR AMENDMENT TO THE RYBOVICH SPENCER COMMERCIAL
 MARINED PLANNED DEVELOPMENT (CMPD) SHALL BE APPROVED BY
 THE CITY COMMISSION PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT.
  
 2) A COPY OF THE APPROVED U.S. ARMY CORPS OF ENGINEERS
 (USACOE) AND FLORIDA DEPARTMENT OF ENVIRONMENTAL
 PROTECTION (FDEP) PERMITS SHALL BE PROVIDED.
  
 3) SUFFICIENT PARKING SHALL BE PROVIDED PRIOR TO FINAL
 INSPECTION AND/OR CO OF THE DOCKS.THE NEW MARINA
 SHALL NOT BE UTILIZED UNTIL THE PARKING LOT PROPOSED
 FOR THE PENINSULA HAS RECEIVED A FINAL INSPECTIONA
 AND/OR CO.
  
 4) PLEASE NUMBER THE SLIPS.THE NUMBER OF SLIPS SHALL
 BE IN ACCORDANCE WITH, AND SHALL NOT EXCEED THE TOTAL
 NUMBER OF, THAT APPROVED BY THE USACOE, FDEP, AND THE
 CITY COMMISSION.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT JOHN ROACH, SENIOR
 PLANNER, AT (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-09-22 Cont ID  
Sent By jroach Date 2006-09-22 Time 19:48 Rev Time 0.00
Received By jroach Date 2006-09-22 Time 19:48 Sent To  
Notes
2006-09-22 00:00:009/22/06 ***FAILED***
  
 A MAJOR AMENDMENT TO THE RYBOVICH
 SPENCER COMMERCIAL MARINE PLANNED
 DEVELOPMENT SHALL BE APPROVED PRIOR TO
 THE ISSUANCE OF A BUILDING PERMIT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 SENIOR PLANNER, AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-09-07 Cont ID  
Sent By jroach Date 2006-09-07 Time 18:35 Rev Time 0.00
Received By jroach Date 2006-09-07 Time 18:35 Sent To  
Notes
***NONE***