Plan Review Details - Permit 06081918
Plan Review Stops For Permit 06081918
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-09-14 Cont ID  
Sent By mawillia Date 2006-09-14 Time 09:13 Rev Time 0.00
Received By mawillia Date 2006-09-14 Time 09:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-11 Cont ID  
Sent By pkrauss Date 2006-09-11 Time 07:19 Rev Time 0.00
Received By pkrauss Date 2006-09-08 Time 07:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-08 Cont ID  
Sent By pkrauss Date 2006-09-08 Time 07:18 Rev Time 0.00
Received By pkrauss Date 2006-08-25 Time 09:18 Sent To  
Notes
2006-08-25 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-09-11 Cont ID  
Sent By pkrauss Date 2006-09-11 Time 07:05 Rev Time 0.00
Received By pkrauss Date 2006-09-11 Time 07:05 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-08-31 Cont ID  
Sent By tgordon Date 2006-08-31 Time 10:49 Rev Time 0.20
Received By tgordon Date 2006-08-31 Time 10:49 Sent To FIRE
Notes
2006-08-31 00:00:00*** DENIED ***
 1) ENGINEER'S LICENSE NUMBER MUST BE ON
 ALL PLANS SEALED BY HIM, PER FAC
 61G15-23.002 .
  
 2) PLEASE SHOW HOW DUCT SUPPORT LEGS ARE
 TO BE ANCHORED TO ROOF.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.