Plan Review Details - Permit 06081875
Plan Review Stops For Permit 06081875
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-03-15 Cont ID  
Sent By lmartine Date 2007-03-15 Time 12:47 Rev Time 0.00
Received By lmartine Date 2007-03-15 Time 12:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-11-12 Cont ID  
Sent By rnuquist Date 2006-11-12 Time 21:37 Rev Time 0.00
Received By rnuquist Date 2006-11-12 Time 21:36 Sent To  
Notes
2006-11-12 21:37:40REVISED PLAN

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-09-23 Cont ID  
Sent By rnuquist Date 2006-09-23 Time 13:54 Rev Time 0.00
Received By rnuquist Date 2006-09-23 Time 13:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-09-13 Cont ID  
Sent By btrobaug Date 2007-09-13 Time 16:40 Rev Time 0.00
Received By btrobaug Date 2007-09-13 Time 15:48 Sent To PC
Notes
2007-09-13 16:40:07 

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-02-16 Cont ID  
Sent By btrobaug Date 2007-02-16 Time 13:00 Rev Time 0.75
Received By btrobaug Date 2007-02-16 Time 12:00 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-11-03 Cont ID  
Sent By btrobaug Date 2006-11-03 Time 15:59 Rev Time 0.75
Received By btrobaug Date 2006-11-02 Time 12:05 Sent To M
Notes
2006-11-03 15:59:24 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} SHOW THE GROUNDING ELECTRODE SYSTEM CONNECTIONS PER
 250.66. SEE THAT THE LOCATION OF THE ATS NOW MAKES IT
 THE FIRST MEANS OF DISCONNECT., SHOW MAIN BONDING
 JUMPER AND NOTE THAT THE NEUTRAL AND GROUND MUST BE
 ISOLATED BEYOND THAT. ALSO NOTE THAT NO EQUIPMENT
 GROUND IS SHOWN FROM THE SERVICE TO THE GENERATOR WITH
 THAT FEED.
  
 2} THERE MUST BE TWO COPIES OF ALL DOCUMENTS SUBMITTED
 FOR REVIEW, I CAN ONLY FIND ONE OF THE ATS.
  
 3} SECTION 3.2 OF THE ATS MANUAL INDICATES A
 DISCONNECTING MEANS IS REQUIRED AHEAD OF THE ATS FOR
 THE GENERATOR AND UTILITY POWER PRIOR TO MANUAL
 OPERATION. IT DOES NOT APPEAR THIS SWITCH IS RATED AS A
 SERVICE DISCONNECTING MEANS, AND THEREFORE SHOULD NOT
 BE POSITIONED IN THE SERVICE AS SHOWN.
  
 4} PLEASE CALCULATE THE SERVICE LOAD PER 220 SECTION I,
 STANDARD, OR 220 SECTION III, OPTIONAL. DEMANDS CANNOT
 BE REVIEWED FOR COMPLIANCE UNDER THE FORMAT THAT WAS
 SUBMITTED ON THIS PLAN.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-14 Cont ID  
Sent By btrobaug Date 2006-09-14 Time 12:54 Rev Time 0.50
Received By btrobaug Date 2006-09-14 Time 11:17 Sent To M
Notes
2006-09-14 00:00:00 
  
 NONCOMPLIANT.
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE LOCATE ALL SERVICE EQUIPMENT
 ON THE PLAN, METER ENCLOSURE,
 DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN
 BE REVIEWED.
  
 2} PROVIDE A RISER DIAGRAM SHOWING
 ELECTRICAL CONNECTION OF ALL SERVICE AND
 GENERATOR EQUIPMENT.
  
 3} PROVIDE MANUFACTURERS
 SPECIFICATIONS/RECOMMENDATION, REGARDING
 CLEARANCES.
  
 4} PROVIDE SPECIFICATIONS FOR THE
 TRANSFER SWITCH.
  
 5} PROVIDE A CALCULATION FOR THE LOAD
 BEING SERVED BY THE GENERATOR.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 7 Status P Date 2007-08-08 Cont ID  
Sent By mperson Date 2007-08-08 Time 10:04 Rev Time 0.33
Received By mperson Date 2007-08-08 Time 10:04 Sent To PC
Notes
2007-08-08 10:06:45REVISION: UPGRADING TO A 2 LB. NAT/GAS SYSTEM.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 6 Status F Date 2007-07-24 Cont ID  
Sent By mperson Date 2007-07-24 Time 10:55 Rev Time 0.15
Received By mperson Date 2007-07-24 Time 10:55 Sent To PC
Notes
2007-07-24 11:13:38REVISION DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 1. NOTE: ONLY ONE (1) SHEET P-1 WAS SEALED BY THE
 ARCHITECT KELLY D. YATES, FLORIDA AR #13706.
 A} 106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION
 DOCUMENTS, SPECIAL INSPECTION AND
 STRUCTURAL OBSERVATION PROGRAMS, AND
 OTHER DATA SHALL BE SUBMITTED IN TWO OR
 MORE SETS WITH EACH APPLICATION FOR A
 PERMIT.
 B} 106.1 SUBMITTAL DOCUMENTS. IF THE DESIGN
 PROFESSIONAL IS AN ARCHITECT
 LEGALLY REGISTERED UNDER THE LAWS OF
 THIS STATE REGULATING THE PRACTICE OF
 ARCHITECTURE AS PROVIDED FOR IN CHAPTER
 481, FLORIDA STATUTES, PART 1 THEN HE OR SHE
 SHALL AFFIX HIS OR HER SEAL, SIGNATURE
 AND DATE TO SAID DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA, AS
 REQUIRED BY FLORIDA STATUTES.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS REVIEWER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  

Review Stop G GAS REVIEW
Rev No 5 Status F Date 2007-06-28 Cont ID  
Sent By mperson Date 2007-06-28 Time 09:25 Rev Time 0.33
Received By mperson Date 2007-06-28 Time 09:25 Sent To PC
Notes
2007-06-28 10:38:02REVISION DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION IS REQUIRED FOR
 GAS PLAN REVIEW FOR THE REVISION TO MEET CODE
 COMPLIANCE:
  
 1. NOTE: THE ORIGINAL NATURAL GAS ISOMETRIC RISER
 DIAGRAM ON SHEET P-1 WERE SIGNED AND SEALED BY
 ARCHITECT KELLY D. YATES, ANY REVISED DRAWING TO THE
 GAS SYSTEM PER CHAPTER 481, FLORIDA STATUTES, PART 1,
 MUST ALSO BE SIGNED AND SEALED BY SAID DESIGN
 PROFESSIONAL. ALSO A TITLE BLOCK IS REQUIRED PER,
 FAC-61G1-16.004 TITLE BLOCK:
 A TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTURAL OR INTERIOR DESIGN
 DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE
 FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED
 SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
 (7) FIRMS CERTIFICATE OF AUTHORIZATION NUMBER PER FS
 481.219
  
 2. PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. PLEASE INDICATE
 THIS ON THE RESUBMITTED REVISION.
  
 3. PLEASE CLEARLY INDICATE THE ABOVE GROUND AND
 UNDERGROUND PIPING MATERIAL OF THE GAS SYSTEM. THERE
 WAS A REVISION ON THE ORIGINAL DOCUMENTS DATED 3-20-07
 (PLAN REVIEW COMMENTS) IN THE PLUMBING NOTES #5 GAS
 PIPING: POLYETHELENE PLASTIC PIPE (PE). PLEASE CLARIFY
 THIS ON THE RESUBMITTED REVISION.
  
 4. NOTE: THE DRIP LEG DETAIL INDICATED ON THE REVISION
 IS WRONG. PLEASE CORRECT THE REVISION PER FBC-2004 FUEL
 GAS SECTION 408.4 A SEDIMENT TRAP SHALL BE INSTALLED
 DOWNSTREAM OF THE EQUIPMENT SHUTOFF VALVE AS CLOSE TO
 THE INLET OF THE EQUIPMENT AS PRACTICAL. A **PROVISO**
 WAS PUT ON THE PERMIT COPIES REFLECTING THIS.
  
 5. PLEASE PROVIDE TWO COPIES MANUFACTURER'S
 SPECIFICATION OF THE MP REGUALTORS WITH THE FOLLOWING
 INFORMATION.
 A} MAKE.
 B} MODEL NUMBER.
 C} MAXIMUM INDIVIDUAL LOAD CAPACITY (LARGEST
 SINGLE APPLIANCE SERVED BY THE REGULATOR)
 D} CAPACITY OF REGULATOR (TOTAL LOAD OF ALL
 APPLIANCES COMBINED)
 E} SHOW A LISTING FROM A NATIONALLY RECOGNIZED
 TESTING LABORATORY (NRTL).
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2007-04-18 Cont ID  
Sent By mperson Date 2007-04-18 Time 14:32 Rev Time 0.33
Received By mperson Date 2007-04-18 Time 14:32 Sent To PC
Notes
2007-04-18 14:37:09****************PROVISO****************
 PER FBC-2004 FUEL GAS, SECTION 408.4 A SEDIMENT TRAP
 SHALL BE INSTALLED DOWNSTREAM OF THE EQUIIPMENT SHUTOFF
 VALVE AS CLOSE TO THE INLET OF THE EQUIPMENT AS
 PRACTICAL.

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-02-20 Cont ID  
Sent By mperson Date 2007-02-20 Time 10:27 Rev Time 0.45
Received By mperson Date 2007-02-20 Time 10:27 Sent To B
Notes
2007-02-20 11:46:34DENIED
 REFERENCE: FBC-2004 FUEL GAS AND CITY OF WEST PALM
 BEACH GAS PERMIT APPLICATION REQUIREMENTS:
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. OK
  
 2. NO.
 ** SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: SHEET P-1 INDICATES PIPING MATERIAL TO BE
 SCHEDULE 40 BLACK STEEL.
  
 A} PER FBC-2004 FUEL GAS, SECTION 404.8 PROTECTION
 AGAINST CORROSION. FERROUS METAL EXPOSED IN EXTERIOR
 LOCATIONS SHALL BE PROTECTED FROM CORROSION IN A MANNER
 SATISFACTORY TO THE CODE OFFICIAL.
 NOTE: PLEASE ADD TO RESUBMITTED NOTES.
  
 B} PER FBC-2004 FUEL GAS, SECTION 404.8.1 PROHIBIED
 USE, UNCOATED THREADED OR SOCKET WELDED JOINTS SHALL
 NOT BE USED IN PIPING IN CONTACT WITH SOIL OR WHERE
 INTERNAL OR EXTERNAL CREVICE CORROSION IS KNOWN TO
 OCCUR.
 NOTE: PLEASE ADD TO RESUBMITTED NOTES.
  
 C} PER FBC-2004 FUEL GAS, SECTION 404.8.2 PROTECTIVE
 COATINGS AND WRAPPING. PIPE PROTECTIVE COATINGS AND
 WRAPPINGS SHALL BE APPROVED FOR THE APPLICATION AND
 SHALL BE FACTORY APPLIED.
 NOTE: PLEASE ADD TO RESUBMITTED NOTES.
  
 ** NOTE: IT IS SUGGESTED THAT ANY NEW UNDERGROUNG
 PIPING MATERIAL FOR THE GAS SYSTEM BE POLYETHYLENE
 PLASTIC PIPE (PE). ALSO IF PE PIPE IS USED FOR THE
 GENERATOR THE PIPE SIZE WILL NEED TO BE INCREASED TO
 2-1/2" FOR THE GENERATOR. PLEASE BE AWARE THAT
 UNDERGROUND GALVANIZED PIPE IS UNACCEPTABLE TO THE CODE
 OFFICIAL PER FBC-2004 FUEL GAS, SECTION 404.8.
  
 3. OK
  
 4. OK
  
 5. NO
 ** INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 NOTE: THE REFERENCE TO THE FUEL GAS TABLE 402.4 (2) IS
 NOT ACCEPTABLE AS A DELIVERY PRESSURE. DELIVERY
 PRESSURE CAN NOT BE ASSUMED, IT MUST BE CLEARLY
 INDICATED ON THE RESUBMITTAL.
  
 6. OK
  
 7. OK
  
 8. OK
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-11-07 Cont ID  
Sent By mperson Date 2006-11-07 Time 09:16 Rev Time 0.45
Received By mperson Date 2006-11-07 Time 09:15 Sent To B
Notes
2006-11-07 09:55:33UNSAT
 REFERENCE: FBC-2004 FUEL GAS AND FBC-2004 CHAPTER 1
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE SUBMITTED DRAWING IS NOT AN ISOMETRIC AND
 DOES NOT SHOW ALL CUT SECTIONS OF PIPE AND
 CORRESPONDING LENGTHS.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: ON THE RESUBMITTED ISOMETRIC PLEASE INDICATE ALL
 PIPING MATERIAL AND PIPE SIZES.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: ON THE RESUBMITTED ISOMETRIC PLEASE INDICATE THE
 BTU LOAD OF THE GENERATOR AND THE EXISTING BTU LOAD OF
 SAID ADDRESS.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE:THIS INCLUDES THE EXISTING SYSTEM AS WELL AS
 THE PROPOSED GENERATOR.
  
 5. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 NOTE: PLEASE SUBMIT MANUFACTURER SHEETS OF MP
 REGULATORS.
  
 7. PROVIDE NOTICE OF COMMENCEMENT RECORDED WITH THE
 CLERK OF COURT BEFORE A PERMIT CAN BE ISSUEDNOTE: THE
 ORIGINAL NOC SUBMITTED WITH THE GENERATOR APPLICATION
 DOES NOT INCLUDE GAS SYSTEM OR CONTRACTOR.
  
 8. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-09-18 Cont ID  
Sent By mperson Date 2006-09-18 Time 15:58 Rev Time 0.15
Received By mperson Date 2006-09-18 Time 15:58 Sent To B
Notes
2006-09-18 00:00:00CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.
  
 ******IMPORTANT INFORMATION******
 AS OF 8/25/06 GENERATOR (GEN/RES AND
 GEN/COM) PERMIT APPLICATIONS SHALL NOT
 BE ACCEPTED UNLESS THE ELECTRICAL INFOR-
 MATION AND GAS (OR DIESEL) INFORMATION
 IS ALL SUBMITTED AT THE SAME TIME. THE
 GENERATOR, ELECTRICAL AND GAS/DIESEL IN-
 FORMATION WILL BE ROUTED TOGETHER. THIS
 WILL ENSURE THAT ALL OF THE INFORMATION
 (PARTICULARLY THE MANUFACTURER'S SPECI-
 FICATIONS AND INSTALLATION INSTRUCTIONS)
 ARE AVAILABLE TO ALL PLAN REVIEWERS.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-09-11 Cont ID  
Sent By adarroug Date 2007-09-11 Time 12:43 Rev Time 0.00
Received By adarroug Date 2007-09-11 Time 12:43 Sent To E
Notes
2007-09-11 12:43:33TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-08-06 Cont ID  
Sent By adarroug Date 2007-08-06 Time 17:08 Rev Time 0.00
Received By adarroug Date 2007-08-06 Time 17:08 Sent To G
Notes
2007-08-06 17:09:11TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-07-10 Cont ID  
Sent By adarroug Date 2007-07-10 Time 10:02 Rev Time 0.00
Received By adarroug Date 2007-07-10 Time 10:02 Sent To P
Notes
2007-07-10 10:02:54TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-06-08 Cont ID  
Sent By adarroug Date 2007-06-08 Time 14:50 Rev Time 0.00
Received By adarroug Date 2007-06-08 Time 14:50 Sent To G
Notes
2007-06-08 14:51:11TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-04-05 Cont ID  
Sent By spalmer Date 2007-04-05 Time 17:19 Rev Time 0.00
Received By spalmer Date 2007-04-05 Time 17:19 Sent To G
Notes
2007-04-05 17:20:03TO MIKE PERSON

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-02-15 Cont ID  
Sent By adarroug Date 2007-02-15 Time 09:59 Rev Time 0.00
Received By adarroug Date 2007-02-15 Time 09:59 Sent To E
Notes
2007-02-15 09:59:51TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-02-02 Cont ID  
Sent By adarroug Date 2007-02-02 Time 16:40 Rev Time 0.00
Received By adarroug Date 2007-02-02 Time 16:40 Sent To Z
Notes
2007-02-02 16:41:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-11-01 Cont ID  
Sent By adarroug Date 2006-11-01 Time 18:48 Rev Time 0.00
Received By adarroug Date 2006-11-01 Time 18:48 Sent To E
Notes
2006-11-01 18:48:43TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-24 Cont ID  
Sent By adarroug Date 2006-10-24 Time 13:22 Rev Time 0.00
Received By adarroug Date 2006-10-24 Time 13:22 Sent To Z
Notes
2006-10-24 13:23:04TO "Z" BOX/RESUB--NEW SHEETS SUBMITTED FOR ALL TRADES.
 GAS APPL. ATTACHED TO THIS RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-05 Cont ID  
Sent By adarroug Date 2006-09-05 Time 09:37 Rev Time 0.00
Received By adarroug Date 2006-09-05 Time 09:37 Sent To E
Notes
2006-09-05 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-23 Cont ID  
Sent By rnuquist Date 2006-09-23 Time 13:55 Rev Time 0.00
Received By rnuquist Date 2006-08-23 Time 15:16 Sent To PC
Notes
2006-08-23 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-11-03 Cont ID  
Sent By tgordon Date 2006-11-03 Time 16:29 Rev Time 0.20
Received By tgordon Date 2006-11-03 Time 16:29 Sent To G
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-09-18 Cont ID  
Sent By tgordon Date 2006-09-18 Time 13:42 Rev Time 0.15
Received By tgordon Date 2006-09-18 Time 13:42 Sent To P
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2007-02-14 Cont ID  
Sent By jroach Date 2007-02-14 Time 10:51 Rev Time 0.00
Received By jroach Date 2007-02-14 Time 10:51 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-10-31 Cont ID  
Sent By mmclean Date 2006-10-31 Time 14:33 Rev Time 0.00
Received By mmclean Date 2006-10-31 Time 14:33 Sent To I
Notes
2006-10-31 14:33:31PROPOSED GENERATOR - RE-STAMP NEW PLANS.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-09-02 Cont ID  
Sent By mmclean Date 2006-09-02 Time 10:51 Rev Time 0.00
Received By mmclean Date 2006-09-02 Time 10:50 Sent To I
Notes
***NONE***