Plan Review Details - Permit 06081871
Plan Review Stops For Permit 06081871
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2006-10-23 Cont ID  
Sent By lursu Date 2006-10-23 Time 08:07 Rev Time 0.00
Received By lursu Date 2006-10-23 Time 08:07 Sent To  
Notes
2006-10-23 08:07:45ADDRESS READS ON THE REVISED ISTE PLANS SUITE # 138

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-09-11 Cont ID  
Sent By lursu Date 2006-09-11 Time 11:59 Rev Time 0.00
Received By lursu Date 2006-09-11 Time 11:59 Sent To I
Notes
2006-09-11 00:00:00PLS VERIFY WHICH IS THE CORRECT UNIT
 ,173 OR 138 .
2006-09-09 00:00:00PLANS SHOWS SUITE #173 AND APPLICATION
 SHOWS #138.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-12-04 Cont ID  
Sent By shill Date 2006-12-04 Time 11:47 Rev Time 0.00
Received By shill Date 2006-12-04 Time 11:47 Sent To  
Notes
2006-12-04 11:51:50****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)WHEN PRODUCT APPROVALS ARE NOT INCLUDED IN THE
 ORIGINAL REVIEW, SEPARATE PERMITS REQUIRED.PLEASE
 APPLY.
  
 THE SUBMITTAL IS OTHERWISE CODE COMPLIANT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-10-23 Cont ID  
Sent By shill Date 2006-10-23 Time 11:53 Rev Time 0.00
Received By shill Date 2006-10-23 Time 11:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-12 Cont ID  
Sent By shill Date 2006-09-12 Time 12:27 Rev Time 0.00
Received By shill Date 2006-09-12 Time 10:22 Sent To  
Notes
2006-09-12 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)THE SALES COUNTER IS TO COMPLY WITH
 FBC 11-7.2(1).
  
 2.)THE PLANS STATE THAT THE FIRE
 SPRINKLER RENOVATION IS THE
 RESPONSIBILITY OF THE FIRE SPRINKLER
 COMPANY.FIRE SPRINKLER INFORMATION IS
 REQUIRED AT THIS TIME, SEE ATTACHED
 LETTER FROM THE STATE.ALSO REQUIRED BY
 FBC*106.3.5.1.1(5).
  
 3.)PROVIDE A WALL SECTION FOR THE
 FRONT WALL.NO STRUCTURAL INFORMATION
 WAS PROVIDED.
  
 4.)PRODUCT APPROVALS REQUIRED FOR THE
 NEW FRONT WALL AND DOOR.PRODUCT
 APPROVALS ARE TO BE REVIEWED BY THE
 DESIGNER OF RECORD FBC*106.3.3.
  
 5.)DECLARE GOVERNING CODE AND LEVEL OF
 ALTERATION FBC EB CHAPTER 3.
  
 6.)PROVIDE WIND DESIGN CRITERIA
 FBC1603.1.4.
  
 7.)IMPACT PROTECTION REQUIRED FOR THE
 STOREFRONT, FBC16091.4.USE OF
 REMOVABLE SHUTTERS ON COMMERCIAL
 BUILDINGS MUST BE APPROVED BY THE
 BUILDING OFFICIAL.SEE ATTACHED POLICY,
 ITEM 13.IF YOU ARE NOT USING IMPACT
 GLASS PLEASE SUBMIT AN INSTALLATION PLAN
 FOR REVIEW.THIS MAY BE DONE PRIOR TO
 RESUBMITTAL.
  
 8.)AN ARCHITECT BUSINESS LICENSE IS
 REQUIRED FOR THE COMPANY, JEROME
 BAUMOEHL ARCHITECTS AND PLANNERS INC.
 THIS HAS BEEN CORRECTED IN THE PAST ON
 PREVIOUS PROJECTS AND WAS RESOLVED BY
 REMOVAL OF THE NAME FROM THE PLANS.IT
 APPEARS THAT YOU ARE STILL USING THE
 NAME, AND APPARENTLY HAVE BEEN
 PRACTICING ARCHITECTURE THROUGH THIS
 COMPANY SINCE 1998.THE MATTER HAS BEEN
 FORWARDED TO THE FLORIDA BOARD OF
 ARCHITECTS.PLEASE EITHER REVISE THE
 PLANS TO INCLUDE THE COMPANY NAME WITH
 AN ARCHITECT BUSINESS LICENSE NUMBER OR
 REMOVE THE COMPANY NAME FROM THE PLANS.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-10-29 Cont ID  
Sent By dpalmer Date 2006-10-29 Time 06:20 Rev Time 0.00
Received By dpalmer Date 2006-10-29 Time 05:58 Sent To I
Notes
2006-10-29 06:32:18*****REDLINED PLANS *****
  
  
 1) DISCONNECT FOR TRANSFORMER REDLINED ON E-1.1 TO SEE
 RISER FOR DISCONNETC PER 240.21
  
 2) DEVICES NOW BEING NOTED ON E-2.1 NOTE TO THE SOUTH
 FLORIDA BUILFING CODE?, CHANGED TO "FBC".SFBC IS NO
 LONGER IN EFFECT.
 ALSO REDLINED THE MAXIMUM OF 30MINS OVER RIDE TIMES FOR
 OCC SENSOR TYPE DEVICES AS REQUIRED PER
 13-415.1.ABC.1.1
 PREVIOUS NOTE.
  
  
 NO CHANGES ARE REQUIRED TO BE MADE TO PLANS, ONLY MAKE
 ADJUSTMENTS IF REVISING PLANS DURINGCONSTRUCTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-10-29 05:59:21IN ELEC FOR REVIEW, WILL PROCESS BACK TO INCOMING WHEN
 COMPLETED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-10-20 Cont ID  
Sent By dpalmer Date 2006-10-20 Time 19:57 Rev Time 0.00
Received By dpalmer Date 2006-10-20 Time 18:28 Sent To  
Notes
2006-10-20 19:57:29****UNSAT2ND REVIEW ****
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW INCLUDING
 NEW NOTES DUE TO SOME CHANGES IN PLANS.
 PLEASE SEE NEW NOTES BELOW ADDED TO BOTTOM OF REVIEW.
  
 1) NOTE:OK, ADDRESS CHANGED TO # 138
  
 2) NOTE: OK.
  
 3) NOTE:OK, HOWEVER PLEASE SEE NEW NOTES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY THE LOCATION OF
 THE EXISTING TRANSFORMER ON PLANS. RISER
 SEEMS TO SHOW THIS ELEVATED WHICH IS OK,
 HOWEVER THIE SHALL NOT BE INSTALLED
 ABOVE CEILING(S)/HOLLOW SPACES PER
 450.13B
 ** PLEASE BE AWARE, THE ORIGINAL PLANS
 FOR THE BUILT OUT OF THIS SPACE DID NOT
 SHOW THE UNIT ABOVE THE CEILING OR
 INSTALLED IN ANY HOLLOW SPACE.
  
 4) NOTE:NO, PLEASE SEE PLANS ON "A" SHEET NOWS
 INDICATES A 2004 NEC. PLEASE KNOW, THIS SHEET DOES NOT
 NEED TO BE CHANGEDAS THIS CAN BE REDLINED BY THE
 REVIEWER IF GRANTED PERMISSION BY THE ARCHITECT OF
 RECORD.(2002 NEC)
  
 ** PREVIOUSREVIEW NOTE **
 PLEASE SEE "A" SHEETS SHALL
 INDICATE THE LATEST ADOPTED CODES
 RELEVANT TO DESIGN AND SCOPE OF WORK.
 106.1.2 FBC ADMIN SECT.
  
 5) NOTE: OK.
  
 6) NOTE: NO, PLEASE CLARIFY WHERE THE OVER RIDE DEVICE
 IS LOCATED AT THE NEAREST POINT OF ENTRANCE INTO THE
 SPACE AND SO THAT THE OCCUPANT CAN VISUALLY SEE THE
 LIGHTING WHICH IS BEING CONTROLLED.
 PLEASE SEE EXSITNG ROOMS CONTAINING FLR TO CEILING
 HEIGHT PARTIONS/WALLS.
 PLEASE VERIFY THESE DEVICES.
 13-415.10ABC0101, .1.2
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE THAT EXISTING AREAS
 OF OFFICE, BATHRMS, AND AREAS IN THE
 REAR OF SPACE WILL ALSO BE REQUIRED TO
 HAVE CONTROLSFOR LIGHTING MEETING FBC
 2004 CHAPTER 13.
 PLEASE ADJUST.
 PLEASE SEE THAT SPEARATE SPACES WHICH
 REQUIRE CONTROLS WHICH OVER RIDE THE
 LIGHTING CONTROL SYSTEM, AS WELL AS THE
 POINT OF ENTRANCE INTO THE SPACE.
  
  
 ** NEW NOTE ***
  
 7) NOTE: PLEASE SEE THE LOCATION OF THE TRANSFORMER IS
 NOW BRING MOVED TO CORRECT THE EXSITING CODE VIOLATION,
 HOWEVER PLEASE SEE THE LOCATION IS SHOWN FARTHER AWAY
 FROM THE PANEL"LB"WHICH NOW APPEARS TO CREATE AN
 ISSUE WITH 240.21C. PLEASE SEE LENGTH OF TAPPED
 CONDUCTORS ON THE SECONDARY SIDE OF THE TRANSFORMER
 SHALL TERMINATE IN OCP DEVICE WITHIN THE MAXIMUM LIMITS
 OF THE "CONDUCTOR" LENGTH.
  
 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS. THIS IS ONLY
 A NOTICE GIVEN AT THIS TIME.
 AS REQUIRED.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-09 Cont ID  
Sent By dpalmer Date 2006-09-09 Time 14:37 Rev Time 0.00
Received By dpalmer Date 2006-09-09 Time 13:58 Sent To  
Notes
2006-09-09 00:00:00****UNSAT ****
  
 1) NOTE: PLEASE SEE PLANS INDICATE SUITE
 #173 ON ALL SHEETS AND IN NOTES, HOWEVER
 PERMIT APPLICATIONSHOWS SUITE #138??
 PLEASE ADJUST AND CORRELATE.
  
 2) NOTE: PLEASE SEE TITLE BLOCKS FOR
 ARCHITECTURAL FIRM LIST "ARCHITECTS".
 IF A CERTIFICATE OF AUTHORIZATION NUMBER
 IS OBTAINED , PLEASE INDICATE, HOWEVER
 IF THE NUMBER HAS NOT YET BEEN ISSUED
 THROUGH DBPR, PLEASE REVISE TITLE BLOCKS
 ONLY TO INCLUDE "ARCHITECT" AS AN
 INDIVIDUAL.
 FAC 61G1-16.004, FS 481.219
  
 3) NOTE: PLEASE CLARIFY THE LOCATION OF
 THE EXISTING TRANSFORMER ON PLANS. RISER
 SEEMS TO SHOW THIS ELEVATED WHICH IS OK,
 HOWEVER THIE SHALL NOT BE INSTALLED
 ABOVE CEILING(S)/HOLLOW SPACES PER
 450.13B
 ** PLEASE BE AWARE, THE ORIGINAL PLANS
 FOR THE BUILT OUT OF THIS SPACE DID NOT
 SHOW THE UNIT ABOVE THE CEILING OR
 INSTALLED IN ANY HOLLOW SPACE.
  
 4) NOTE: PLEASE SEE "A" SHEETS SHALL
 INDICATE THE LATEST ADOPTED CODES
 RELEVANT TO DESIGN AND SCOPE OF WORK.
 106.1.2 FBC ADMIN SECT.
  
 5) NOTE: PLEASE SEE 210.8B3, FOR 15/20A
 120 RECEPTS IN KITCHEN AREAS TO BE
 GFI/GFI PROTECTED.
  
 6) NOTE: PLEASE SEE THAT EXISTIGN AREAS
 OF OFFICE, BATHRMS, AND AREAS IN THE
 REAR OF SPACE WILL ALSO BE REQUIRED TO
 HAVE CONTROLSFOR LIGHTING MEETING FBC
 2004 CHAPTER 13.
 PLEASE ADJUST.
 PLEASE SEE THAT SPEARATE SPACES WHICH
 REQUIRE CONTROLS WHICH OVER RIDE THE
 LIGHTING CONTROL SYSTEM, AS WELL AS THE
 POINT OF ENTRANCE INTO THE SPACE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-10-31 Cont ID  
Sent By mawillia Date 2006-10-31 Time 15:38 Rev Time 0.00
Received By mawillia Date 2006-10-31 Time 15:38 Sent To  
Notes
2006-10-31 15:41:23*****APPROVED*****
  
  
  
  
 PREVIOUS FIRE REVIEW COMMENTS HAVE BEEN ADDRESSED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-10-23 Cont ID  
Sent By mwennerg Date 2006-10-23 Time 13:34 Rev Time 0.00
Received By mwennerg Date 2006-10-23 Time 13:34 Sent To  
Notes
2006-10-23 13:37:37***DENIED***
  
 1) PLEASE NOTE THAT A RESPONSE LETTER WAS SUBMITTED
 WITH NO RESPONSE TO FIRE REVIEW.
  
 2) PLEASE SEE LAST FIRE REVIEW COMMENTS ARE INCLUDED
 WITH THIS REVIEW FOR YOUR CONVENIENCE.SHEET E-4.1, NOTE
 13 HAS NOT BEEN CORRECTED.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-12 Cont ID  
Sent By mwennerg Date 2006-10-12 Time 13:36 Rev Time 0.00
Received By mwennerg Date 2006-10-12 Time 13:36 Sent To  
Notes
2006-10-12 13:48:21***DENIED***
  
 1) PLEASE CLARIFY CORRECT ADDRESS SUITE NUMBER AND SHOW
 ON PLANS.
  
 2) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. SHT E-4.1,
 NOTE 13.
  
 3)CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status   Date 2006-11-29 Cont ID  
Sent By mmiller Date 2006-11-29 Time 19:02 Rev Time 0.00
Received By mmiller Date 2006-11-29 Time 19:02 Sent To B
Notes
2006-11-29 19:03:04SENT TO SAMANTHA HILL'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-10-28 Cont ID  
Sent By adarroug Date 2006-10-28 Time 09:52 Rev Time 0.00
Received By adarroug Date 2006-10-28 Time 09:52 Sent To  
Notes
2006-11-01 09:53:28TO "BOB"#2

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-20 Cont ID  
Sent By dpalmer Date 2006-10-20 Time 18:27 Rev Time 0.00
Received By dpalmer Date 2006-10-20 Time 18:27 Sent To  
Notes
2006-10-20 18:27:54TO BOB #4NEIL/ROBERT . DV PALMER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-16 Cont ID  
Sent By adarroug Date 2006-10-16 Time 11:37 Rev Time 0.00
Received By adarroug Date 2006-10-16 Time 11:37 Sent To  
Notes
2006-10-16 11:37:51WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-12 Cont ID  
Sent By mwennerg Date 2006-10-12 Time 14:13 Rev Time 0.00
Received By mwennerg Date 2006-08-23 Time 10:05 Sent To  
Notes
2006-08-25 00:00:00TO "COMM" BD#54
2006-08-23 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-10-23 Cont ID  
Sent By rregueir Date 2006-10-23 Time 17:40 Rev Time 0.00
Received By rregueir Date 2006-10-23 Time 17:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-06 Cont ID  
Sent By pkrauss Date 2006-10-06 Time 14:16 Rev Time 0.00
Received By pkrauss Date 2006-10-06 Time 14:02 Sent To  
Notes
2006-10-06 00:00:00DENIED:
 PLANS ARE CODE COMPLIANT WITH THE
 EXCEPTION OF THE ARCHITECTS TITLE BLOCK.
 PLEASE ADDRESS BUILDING & ELECTRICAL
 COMMENTS WITH REGARDS TO THE TITLE
 BLOCK.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected].

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-11-01 Cont ID  
Sent By pschmitz Date 2006-11-01 Time 12:04 Rev Time 0.00
Received By pschmitz Date 2006-11-01 Time 12:04 Sent To  
Notes
2006-11-01 12:07:19DBPR WILL DO A FINAL INSPECTION.
 NO PLAN REVIEW REQUIRED, NO CHANGE OF OCCUPANCY.
 CASE #206105

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-10-26 Cont ID  
Sent By jleech Date 2006-10-26 Time 10:25 Rev Time 0.00
Received By jleech Date 2006-10-26 Time 10:25 Sent To  
Notes
2006-10-26 10:34:40FROM PREVIOUS PLUMBING PLAN REVIEW;
 1.OK
 2. NOPAGE A-3 WALL FINISH; FBC-2004 BUILDING SECTION
 1210.2 WALL MATERIAL. A HARD SURFACE IS REQUIRED.
 PAINT CAN BE CHIPPED OR SCRATCHED. (NOT A HARD
 SURFACE).
 3. OKDBPR WILL DO A FINAL INSPECTION ONLY. PLAN
 REVIEW NOT REQUIRED BECAUSE OCCUPANCY HAS NOT
 CHANGED. CASE # 206105. CONTACT PERSON STEPHNIE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-09-07 Cont ID  
Sent By kstevens Date 2006-09-07 Time 06:25 Rev Time 0.00
Received By kstevens Date 2006-09-06 Time 18:35 Sent To  
Notes
2006-09-07 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS, THE TITLE BLOCK STATES
 "ARCHITECTS", WHICH INDICATES A
 PARTNERSHIP AT THE VERY LEAST. A
 CERTIFICATE OF AUTHORIZATION IS
 REQUIRED. BUSINESS NUMBER NOT SHOWN. FAC
 61G1-16.004(2) & FS 481.219. - ALSO
 WHITE OUT IS NOT ALLOWED ON SIGNED,
 SEALED, DATED PLANS. SECTION 106.1.3
  
 2. SHT P3 ROOM FINISH SCHEDULE. INDICATE
 HOW PAINTED WALLS COMPLIES WITH THE
 REQUIREMENT FOR A HARD, NON ABSORBENT
 WALL AS REQUIRED IN SECTION 1210.2.
  
 3. PLANS SHALL BE ROUTED TO DBPR HOTEL
 AND RESTURANT DIVISION FOR REVIEW.
 MINIMUM TWO SETS OF REVIEWED PLANS
 STAMPED BY DBPR WITH TWO PAGE "WORK
 SHEETS" ATTACHED SHALL BE SUBMITTED FOR
 REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved