Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-11-12 Cont ID  
Sent By rnuquist Date 2006-11-12 Time 21:51 Rev Time 0.00
Received By rnuquist Date 2006-11-12 Time 21:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-22 Cont ID  
Sent By amorse Date 2006-08-22 Time 14:50 Rev Time 0.00
Received By amorse Date 2006-08-22 Time 14:50 Sent To PC
Notes
2006-08-22 00:00:00 
  
 DENIED
  
 1) A CONTRACTOR SHALL SUBCONTRACT
 ROOFING, EXCEPT FOR THE INSTALLATION OF
 WOOD SHINGLES OR SHAKES AND ASPHALT OR
 FIBERGLASS SHINGLES WHEN ON A NEW
 BUILDING OF THEIR OWN CONSTRUCTION, OR
 REPAIRS UNDER WARRANTY FOR SUCH BUILDING
 PER 489.113 (3),(3B)
 EXCEPTION FOR REPAIRS UNDER EXECUTIVE
 ORDER
 ******NOTE MODIFIED NOT ALLOWED UNDER
 CONTRACTORS SCOPE OF WORK******
  
 2) PRODUCT APPROVAL FOR POLYGLASS
 MODIFIED PRODUCT THAT WAS CHOSEN HAS A
 DESIGN PRESSURE OF -45 PSF LIMITATION #9
 (SEE PG, 37 NOA) LIMITAION 9 DOES NOT
 ALLOW ENHANCED FASTENING FOR PERIMITER
 AND CONER ZONES THEREFORE THIS PRODUCT
 DOES NOT MEET THE PRESSURES REQUIRED
  
 3) THE SYSTEM ON PG. 42 MAY WORK AND THE
 LIMITATION IS #7 WHICH WOULD ALLOW FOR
 ENHANCED FASTENING BUT THEY WOULD BE
 REQUIRED TO BE CALCULATED BY AN
 ARCHITECT, ENGINEER OR ROOFING
 CONSULTANT
  
 BLDG PLAN REVIEW
 ADRIAN MORSE