Plan Review Details - Permit 06081714
Plan Review Stops For Permit 06081714
Review Stop E ELECTRICAL
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2006-09-10 00:00:00BILL, SEE ME IF THIS PROJECT DOES NOT
 GET TO ME BEFORE IT COMES BACK IN.
 PLEASE ALSO SEE NOTES I HAVE PLACED ON
 GENERATOR PERMIT #06082225

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-23 Cont ID  
Sent By btrobaug Date 2006-08-23 Time 18:15 Rev Time 0.50
Received By btrobaug Date 2006-08-23 Time 17:57 Sent To PC
Notes
2006-08-23 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2. FBC AS
 AMENDED. THIS ARTICLE ALSO IS AN
 EXTRACTION FROM THE EXEMPTION IN CHAPTER
 471 OF THE FLORIDA STATUTES , 471.003,
 ALLOWING THE CONTRACTOR TO DRAW THEIR
 OWN PLANS.
  
 2} PLEASE LOCATE ALL SERVICE EQUIPMENT
 ON A SITE PLAN, METER ENCLOSURE,
 DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225.31-39,
 230.70 AND 230.72 CAN BE REVIEWED.
  
 3} PROVIDE SPECIFICATIONS FOR THE
 TRANSFER SWITCH, INDICATING NUMBER OF
 POLES, AND HOW BOTH GENERATOR AND
 UTILITY POWER SOURCE CAN BE
 DISCONNECTED.
  
 4} INDICATE THE VOLTAGE OF THE SERVICE.
 NOTE: IF OVER 240 VOLTS, PLANS MUST BE
 ENGINEERED PER CHAPTER 471 FS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-23 Cont ID  
Sent By btrobaug Date 2006-08-23 Time 17:58 Rev Time 0.00
Received By btrobaug Date 2006-08-22 Time 16:16 Sent To E
Notes
2006-08-22 00:00:00TO "E" BOX